PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: October 9, 2020 APPROVED: October 15, 2020
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Crapo Residence Remodel
STREET ADDRESS: 150 E. 2nd S. CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: Phoenix Fire Protection
4130 Airport Road
Nampa, ID 83687
IDAHO LICENSE: FPSC-108
CONTACT NAME: Teri Cruickshank
teri@phoenixfp.com
PHONE NO: (208) 468-9115
SYSTEM DESIGNED BY: Dennis Apple
dennis@phoenixfp.com
PHONE NO: (208) 346-2853
TYPE OF SYSTEM: NFPA 13R HEAD COUNT: 29
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: R-2
CONSTRUCTION TYPE: V-B AREA SQUARE FOOTAGE: 3,056
SCOPE OF WORK: This is going to be converted into a 4-plex.
PLAN REVIEW COMMENTS: Approved with the following comment:
1. Sprinklers shall be installed throughout the premises. (NFPA 13R 4.2 (1)
2. Means shall be provided for forward flow test. (NFPA 13R, 6.8.8)
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.