HomeMy WebLinkAboutHVAC PLANS - 21-00589 - Madison Armory Indoor Gun Range.pdfMADISON ARMORY
ZM001 INDEX PAGE
ZM002 HVAC GENERAL NOTES
ZM003 HVAC SPECIFICATIONS
ZM101.1 25YD & 50YD HVAC RANGE PLAN
ZM103.1 25YD & 50YD HVAC ROOF PLAN
ZM501 AIRFLOW SHEMATIC
ZM502 LOW VOLTAGE SCHEMATIC
ZM601 MECHANICAL SCHEDULES
ZM102.1 25YD & 50YD PENETRATION PLAN ZM602 MECHANICAL DETAILS
ZM301.1 50YD HVAC SECTION
ZM603 MECHANICAL DETAILS
SCALED FOR ORIGINAL DRAWING AT 22" X 34"
ZM001
MADISON ARMORY
100% SUBMITTAL
SAVED: 2021-08-24 16:44:06 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM001-003-21.038.00.dwg----
Project Manager:
Territory Manager:
Project Engineer:
Drawn By:
Approved By:
Origination Date:
ADAM ZIEGENFELDER
08/24/2021
WILLIAM LEWIS
SCOTT DESANTI
WILLIAM LEWIS
STEVE TIBBALS
REVISION DATENoBY
PROJECT STATUS
PROJECT NAMEP O Box 636, Provo UT, 84603Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.comThe use of these plans shall be restricted to the original project site for which they were prepared.Publications expressly limited to such use. Re-use, reproduction, or publication by any method in wholeor part is prohibited. drawings and designs remain the property of action target inc. without reservation.Action Target Inc. 2021 All Rights ReservedDRAWING NUMBER
SHEET NAME
SHEET NUMBER
SHEET INDEX
Signature:
Printed Name:
Date:
CUSTOMER APPROVAL:
NOTWITHSTANDING THE CONTRACT DOCUMENTS, APPROVAL OF THESE DRAWINGS SHALL ACT AS AN AMENDMENT
TO THE PARTIES' AGREEMENT AND SUPERSEDE ALL PREVIOUS DRAWINGS.
MECHANICAL ABBREVIATIONS INDEX
AP
MECHANICAL DUCT SYMBOLS
DESIGN CONTACTS
GENERAL NOTES:
1.EACH DRAWING HAS SPECIFIC KEYED AND GENERAL NOTES. THE NOTES ON
THIS DRAWING ARE GENERAL IN NATURE AND APPLY TO WORK DESCRIBED
IN ALL THE RANGE VENTILATION DRAWINGS AND SPECIFICATIONS.
2.THE RANGE VENTILATION DUCT ROUTING SHOWN IS APPROXIMATE AND
DIAGRAMMATIC AND IS NOT TO BE SCALED. MINOR ALTERATIONS ARE
ALLOWED TO AVOID LOCAL INTERFERENCES. WHERE FIELD CONDITIONS
REQUIRE SUBSTANTIAL CHANGES TO THE DUCT LAYOUT, CHANGES MUST BE
APPROVED BY ACTION TARGET.
3.THIS PROJECT AND ALL WORK SHALL CONFORM TO ALL LOCAL AND
NATIONAL CODES AND STANDARDS WHICH ARE APPLICABLE TO THIS TYPE
OF WORK, SOME OF WHICH ARE AS FOLLOWS: LOCAL AND NATIONAL
BUILDING AND MECHANICAL CODES, NFPA, ASHRAE, SMACNA AND OTHER
REGULATORY BODIES HAVING JURISDICTION OVER THIS TYPE OF WORK. ALL
SYSTEMS INCLUDING MATERIALS, EQUIPMENT AND WORKMANSHIP SHALL
CONFORM TO THE ASSOCIATED CODES AND REGULATIONS OF GOVERNING
BODIES, CODES AND REGULATIONS OF THE ASSOCIATED MUNICIPAL, STATE
AND FEDERAL AUTHORITIES.
4.THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, LICENSES, AND
UTILITY SERVICE AGREEMENTS RELATED TO THE INSTALLATION,
COMMISSIONING, TESTING AND BALANCING FOR THE COMPLETION OF THIS
WORK. THE CONTRACTOR SHALL ASSIST AND WORK WITH THE OWNER TO
OBTAIN OWNER SPECIFIC PERMITS, LICENSES AND AGREEMENTS.
5.THE CONTRACTOR SHALL COORDINATE THE RANGE VENTILATION WORK
WILL ALL BUILDING PLUMBING, ELECTRICAL, AND STRUCTURAL TRADES TO
PROVIDE ALL THE NECESSARY UTILITY CONNECTIONS FOR THE RANGE
VENTILATION EQUIPMENT. COORDINATE THIS WORK WITH ALL OTHER
TRADES IN ORDER TO RESOLVE ANY CONFLICTS THAT MIGHT ARISE DUE TO
THE INSTALLATION AND LOCATION OF DUCTWORK, PIPING, CONTROLS OR
EQUIPMENT THAT IS TO BE INSTALLED AS PART OF THIS PROJECT.
6.THE GENERAL CONTRACTOR OR OTHER DIVISIONS WILL INSURE THAT THE
RANGE ENVELOPE IS SEALED TIGHT TO MAINTAIN THE REQUIRED NEGATIVE
SPACE PRESSURE AS SPECIFIED ON THE DRAWINGS AND IN THE
SPECIFICATIONS.
7.ALL WALL AND ROOF PENETRATIONS FOR DUCTWORK AND OTHER RELATED
OPENINGS SHALL BE COMPLETED BY THE GENERAL CONTRACTOR OR BY
THE OWNER. PROVIDE ROOF CURBS FOR ALL ROOF DUCT PENETRATIONS
AND FLASH WATER TIGHT.
8.THE EQUIPMENT PADS AND STRUCTURAL SUPPORTS WILL BE FURNISHED
AND INSTALLED BY THE GENERAL CONTRACTOR OR BY THE OWNER.
9.DUCTWORK, PIPING, CONTROLS AND EQUIPMENT INCLUDING FILTER
HOUSING SHALL BE INSTALLED SUCH THAT THEY CAN BE SERVICED AND
REPAIRED OR REPLACED BY ANY PERSON ASSOCIATED WITH THIS PROJECT,
INCLUDING THE OWNER AND THE OWNERS REPRESENTATIVE.
10.ALL DUCTWORK, SUPPLY, EXHAUST AND RETURN SHALL BE SEALED AS
DESCRIBED IN THE DRAWINGS AND IN THE SPECIFICATIONS AND PER
SMACNA STANDARDS.
11.ALL DUCTWORK NEEDS TO BE RATED AT A MINIMUM OF 2” WC STATIC
PRESSURE. THE DUCTWORK CONNECTING TO THE RANGE EXHAUST FANS
AND THE FILTER HOUSING IS RATED AT A MINIMUM OF -8” WC STATIC
PRESSURE. SEE DRAWINGS AND SPECIFICATIONS AND SMACNA
STANDARDS FOR THE CONSTRUCTION AND INSTALLATION OF ALL
DUCTWORK.
12.ALL DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS. IF INSULATION
LINING IS NOTED THE DUCTWORK SHALL BE INCREASED IN SIZE TO ALLOW
FOR THE INSULATION.
13.ALL DUCTWORK ELBOWS SHALL BE RADIUS ELBOWS UNLESS NOTED
OTHERWISE. WHERE SQUARE ELBOWS ARE SHOWN THEY SHALL HAVE
SINGLE BLADE TURNING VANES. ROUTE ALL DUCTWORK AS HIGH AS
POSSIBLE ABOVE BALLISTIC BAFFLES. COORDINATE DUCT INSTALL WITH
CEILING SUPPORT SYSTEM. DUCTWORK SIZE CHANGES ARE ALLOWED AS
LONG AS THE FREE AREA IS NOT REDUCED. SUBMIT COORDINATED SHEET
METAL SHOP DRAWINGS FOR APPROVAL BEFORE FABRICATION OF
DUCTWORK SYSTEMS. SHOP DRAWINGS SHALL BE APPROVED BY ACTION
TARGET INC (ATI). ALL OFF- SETS, RISERS OR DROPS ARE TO BE INDICATED
ON THE SHOP DRAWINGS.
14.THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT AND WIRING
FROM THE POWER SOURCES TO THE EQUIPMENT DISCONNECT AND FROM
THE DISCONNECT SWITCHES TO STARTERS AND FROM STARTERS TO THE
EQUIPMENT.
15.ALL HIGH VOLTAGE CONDUITS AND WIRING SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR.
16.ALL LOW VOLTAGE CONDUITS AND WIRING SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR.
17.AUTOMATIC CONTROL DEVICES, SUCH AS TEMPERATURE SENSORS, RELAYS
AND PRESSURE SWITCHES WHICH ARE ASSOCIATED WITH THIS WORK AND
THESE SYSTEMS AND SHALL BE FURNISHED AND INSTALLED BY THIS
DIVISION.
18.ALL CONTROL WIRING SHALL BE RUN CONCEALED WHEN POSSIBLE. WIRING
IN WALLS SHALL BE IN CONDUIT. ALL CONTROL WIRING SHALL BE PLENUM
RATED. CONTROL WIRING IN EXPOSED AREAS SHALL BE RUN IN CONDUIT.
ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODES AND ANY OTHER LOCAL OR STATE CODES.
19.FIELD VERIFY LOCATIONS OF ALL RANGE MECHANICAL EQUIPMENT, ROOF
PENETRATIONS, AND DEVICES PRIOR TO FABRICATION OR STARTING NEW
WORK. MECHANICAL CONTRACTOR SHALL COORDINATE WITH OWNERS
GENERAL CONTRACTOR AND STRUCTURAL ENGINEER ALL SUPPORTING
STEEL FOR MECHANICAL EQUIPMENT. GENERAL CONTRACTOR TO FURNISH
AND INSTALL SUPPORT ANGLES AND SUPPORT BEAMS FOR MECHANICAL
EQUIPMENT.
20.THE CONTRACTOR SHALL INSTALL THE RANGE MECHANICAL EQUIPMENT IN
ACCORDANCE WITH MANUFACTURER'S INSTALLATION GUIDELINES AND
STANDARDS. MAINTAIN THE MANUFACTURER'S OPERATIONAL AND SERVICE
CLEARANCES AROUND EQUIPMENT.
21.ALL RANGE MECHANICAL SYSTEMS SHALL BE TESTED, COMMISSIONED AND
SHALL BE COMPLETE AND FUNCTIONAL AT THE COMPLETION OF THE
PROJECT. THE CONTRACTOR SHALL WARRANTY HIS WORK FOR A PERIOD
OF TWELVE (12) MONTHS FROM DATE OF FINAL ACCEPTANCE.
22.THIS WORK SHALL INCLUDE ALL THE PRODUCTS AND EQUIPMENT FOR
COMPLETE AND FUNCTIONAL SYSTEMS FOR THE AREAS INDICTED IN THESE
DOCUMENTS.
OWNER/CONTRACTOR TO PROVIDE
·
·
STRUCTURAL
·
·
·
·
ELECTRICAL
·
·
·
·
·
MECHANICAL
·
MISCELLANEOUS
·
·
·
·
·
·
·
·
·
ATTENTION:
REQUIRED INFORMATION:
THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE PROVIDED TO
SHOW GENERAL INTENT OF THE VENTILATION EQUIPMENT AND DUCT
LAYOUT.
ACTUAL EQUIPMENT AND DUCT SIZE WILL BE DETERMINED DURING
DETAILED DESIGN AND MAY VARY FROM THE SIZES SHOWN ON THESE
DRAWINGS.
ACTION TARGET'S DESIGNERS/ENGINEERS WILL NEED TO COORDINATE WITH
THE CUSTOMER'S STRUCTURAL ENGINEER, ARCHITECT, AND CONTRACTOR
THE LAYOUT OF THE VENTILATION SYSTEM AND SCOPE OF WORK.
PROVIDE ACTION TARGET WITH BUILDING DRAWINGS OF THE RANGE SPACE.
PLANS AND SECTION VIEWS IN AUTOCAD FORMAT. (PDF FILES OR HAND
SKETCHES ARE REQUIRED WHEN AUTOCAD FILES ARE NOT AVAILABLE.)
ACTION TARGET ROUTES VENTILATION DUCTING BETWEEN THE STEEL
BAFFLES AND THE BOTTOM OF THE RANGE CEILING STRUCTURE.
THE MINIMUM CLEAR DISTANCE FROM THE FLOOR TO THE BOTTOM OF THE
RANGE ROOF STRUCTURAL MEMBERS (TRUSSES, ETC.) IS 14'-0".
COMPLETE ACTION TARGET HVAC SURVEY WITH SALES ASSOCIATE AND/OR
PROJECT MANAGER.
ALL PERMITS AND LICENSES PERTAINING TO PROJECT.
STRUCTURAL SUPPORT OF MECHANICAL VENTILATION EQUIPMENT.
CONCRETE EQUIPMENT PADS FOR MECHANICAL VENTILATION EQUIPMENT,
IF APPLICABLE.
WALL PENETRATIONS FOR VENTILATION DUCTING
ROOF PENETRATIONS, PATCHING, AND ROOFING AROUND DUCT ROOF
CURBING AND EQUIPMENT SUPPORTS OF MECHANICAL EQUIPMENT. FLASH
AND WATER TIGHT SEAL.
MATERIAL AND INSTALL OF HIGH AND LOW VOLTAGE WIRE AND CONDUIT
FOR VENTILATION EQUIPMENT.
ELECTRICAL DISCONNECTS FOR MECHANICAL EQUIPMENT.
DEDICATED 120V CIRCUIT TO VENTILATION CONTROL PANEL.
INSTALLATION OF ATI PROVIDED VFD'S AND CONTROL/RANGE DISPLAY
PANELS.
INTERNET STATIC IP ADDRESS FOR REMOTE CONTROL ACCESS. CAT5 CABLE
TO RANGE CONTROL PANEL.
ALL GAS PIPE (SIZED FOR MECHANICAL EQUIPMENT), REGULATORS & FINAL
CONNECTIONS AND HOOKUPS FOR RANGE MECHANICAL EQUIPMENT
PROVIDE AN AIR TIGHT RANGE ENVELOPE. SEAL ALL HOLES, PENETRATIONS,
DOORWAYS, DOOR JAMS, AND OPENINGS IN RANGE WALLS, WALL TO ROOF
CONNECTIONS, AND ALL ROOF OPENINGS.
T-BAR CEILING BETWEEN SAFETY CEILING AND RANGE DIFFUSERS.
ANY FIRE/SMOKE DEVICES REQUIRED BY LOCAL JURISDICTION.
NOTE: THIS LIST IS PROVIDED TO IDENTIFY AND COORDINATE THE SCOPE OF
WORK FOR THE RANGE VENTILATION SYSTEM. A COMPLETE AND DETAILED LIST
WILL BE PROVIDED UPON CONTRACT.
MECHANICAL CALLOUTS
SCALED FOR ORIGINAL DRAWING AT 22" X 34"
ZM002
MADISON ARMORY
100% SUBMITTAL
SAVED: 2021-08-24 16:44:06 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM001-003-21.038.00.dwg----
Project Manager:
Territory Manager:
Project Engineer:
Drawn By:
Approved By:
Origination Date:
ADAM ZIEGENFELDER
08/24/2021
WILLIAM LEWIS
SCOTT DESANTI
WILLIAM LEWIS
STEVE TIBBALS
REVISION DATENoBY
PROJECT STATUS
PROJECT NAMEP O Box 636, Provo UT, 84603Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.comThe use of these plans shall be restricted to the original project site for which they were prepared.Publications expressly limited to such use. Re-use, reproduction, or publication by any method in wholeor part is prohibited. drawings and designs remain the property of action target inc. without reservation.Action Target Inc. 2021 All Rights ReservedDRAWING NUMBER
SHEET NAME
SHEET NUMBER
SYMBOLS,
ABBREVIATIONS, &
NOTES
· ALL DIMENSIONS SHOWN ARE IN FEET AND INCHES.
IT SHALL BE THE RESPONSIBILITY OF THE AWARDED
CONTRACTOR TO PROVIDE COMPLETE SHOP DRAWINGS OF
THE SYSTEMS OUTLINED WITHIN THESE BID SPEC DOCUMENTS.
SHOP DRAWINGS SHALL INCLUDE, BUT NOT LIMITED TO:
EQUIPMENT CUT SHEETS, MATERIALS CUT SHEETS,
EQUIPMENT LOCATIONS AND DIMENSIONS, DUCTWORK
ROUTING AND DIMENSIONS, HANGING/BRACING/MOUNTING
METHODS, CONTRACTOR CERTIFICATIONS, ETC.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS TO ENGINEER
FOR REVIEW AND APPROVAL PRIOR TO ACQUISITION AND
INSTALLATION OF ALL EQUIPMENT AND MATERIALS REQUIRED.
SPECIFICATIONS:
1.SECTION 23000 GENERAL REQUIREMENTS.
2.THIS WORK SHALL INCLUDE ALL LABOR, MATERIALS,
EQUIPMENT, FIXTURES, AND DEVICES FOR THE ENTIRE
MECHANICAL WORK AND A COMPLETE OPERATING AND
TESTED INSTALLATION AS REQUIRED FOR THIS
PROJECT.
3.ALL WORK SHALL BE EXECUTED IN ACCORDANCE WITH
ALL LOCAL AND STATE RULES AND REGULATIONS
APPLICABLE TO THE TRADE AFFECTED. AFTER
ENTERING INTO THIS CONTRACT, THE CONTRACTOR
WILL COMPLETE ALL WORK NECESSARY TO MEET THESE
REQUIREMENTS WITHOUT EXTRA EXPENSES TO THE
OWNER.
4.APPLICABLE CODES SHALL BE THE LATEST EDITION OF
IBC, IMC, IPC, AND IFC. INDUSTRY STANDARDS SHALL BE
AS FOLLOWS: ARI, ADC, AMCA, AGA, ANSI, ASHRAE,
ASME, ASTM, AWWA, ETL, IEEE, NFPA, NEC, NEMA, NESC
OSHA, SMACNA, AND UL.
5.THE CONTRACTOR SHALL OBTAIN THE NECESSARY
PERMITS TO PERFORM THIS WORK.
6.SHOP DRAWINGS AND COORDINATION DRAWING SHALL
BE SUBMITTED TO THE ARCHITECT AND ENGINEER AND
ATI FOR REVIEW AND MUST BE COORDINATE WITH ALL
OTHER TRADES. SHOP DRAWINGS SHALL INCLUDED
PLANS, ELEVATIONS, SECTIONS AND INDICATE
PRESSURE CLASS. DRAWINGS SHALL ALSO INCLUDE
FITTINGS, REINFORCING AND SPACING, SEAM AND JOINT
CONSTRUCTION DETAILS. PENETRATIONS THROUGH
PARTITIONS AND FIRE-RATE WALLS SHALL BE
INDICATED. HANGERS AND SUPPORTS WITH BUILDING
ATTACHMENT AS WELL AS VIBRATION ISOLATION SHALL
ALSO BE INCLUDED. SHEETMETAL SHOP DRAWINGS WILL
BE REQUIRED FOR ALL DUCTWORK IN THE ENTIRE
BUILDING. THESE DRAWINGS SHALL BE COORDINATED
WITH ALL PIPING, CONDUIT, VALVES, EQUIPMENT AND
DUCTWORK.
7.THE CONTRACT DRAWINGS SHOW THE GENERAL DESIGN
ARRANGEMENTS AND THE EXTENT OF THE SYSTEMS.
THE DRAWINGS MAY INCLUDE DETAILS THAT SHOW
MORE NEARLY EXACT LOCATIONS AND ARRANGEMENTS;
HOWEVER, THE LOCATIONS ARE SHOWN
DIAGRAMMATICALLY, AND ARE TO BE REGARDED AS
GENERAL. IT SHALL BE THE WORK OF THIS
CONTRACTOR TO MAKE SUCH SLIGHT ALTERATIONS AS
MAY BE NECESSARY TO MAKE COMPONENTS AND
SYSTEMS FIT. THE DRAWINGS SHALL NOT BE SCALED
FOR ROUGHING IN MEASUREMENTS NOR SHALL THEY BE
USED AS SHOP DRAWINGS.
8.EXISTING CONDITIONS SHALL BE CAREFULLY EXAMINED
BY THIS CONTRACTOR. THE CONTRACTOR SHALL
VERIFY LOCATIONS OF ALL EXISTING SERVICES AND
UNDERSTAND THE STRUCTURAL AND ELECTRICAL
DRAWINGS AND REQUIREMENTS NEEDED TO COMPLETE
THIS WORK.
9.THE EQUIPMENT CAPACITIES SHOWN FOR THE
EQUIPMENT IS THE MINIMUM ACCEPTABLE. ALL
EQUIPMENT SUBMITTALS SHALL GIVE THE SPECIFIED
CAPACITY AND PERFORMANCE AT THE GIVEN JOB-SITE
ELEVATION.
10.ALL EQUIPMENT SHALL BE FURNISHED AND INSTALLED
STRUCTURALLY ADEQUATE TO WITHSTAND THE SEISMIC
FORCES AS OUTLINED IN THE INTERNATIONATIONAL
BUILDING CODE AND THE SMACNA GUIDELINES FOR THE
AREA WHICH THIS PROJECT IS BEING CONSTRUCTED.
11.THE CONTRACTOR SHALL REFER TO OTHER DRAWINGS
AND PARTS OF THIS SPECIFICATION THAT COVER WORK
OF OTHER TRADES THAT IS CARRIED ON IN
CONJUNCTION WITH THE MECHANICAL WORK SUCH
THAT ALL WORK CAN PROCEED WITHOUT
INTERFERENCE RESULTING FORM LACK OF
COORDINATION. THE CEILING CAVITY MUST BE
CAREFULLY REVIEWED AND COORDINATED WITH ALL
TRADES. THIS CONTRACTOR SHALL INSURE THAT THE
INSTALLATION OF ALL DUCTWORK, PIPING AND
EQUIPMENT IS IN COMPLIANCE WITH ARTICLES 110-16
AND 384-4 OF THE NATIONAL ELECTRICAL CODE
RELATIVE TO PROPER CLEARANCES IN FRONT OF AND
OVER ALL ELECTRICAL PANELS AND EQUIPMENT. NO
PIPING OR DUCTWORK SHALL BE ALLOWED TO RUN
OVER ELECTRICAL PANELS.
12.THE CONTRACTOR IS RESPONSIBLE FOR THE
INSTALLATION OF A SATISFACTORY PIECE OF WORK IN
ACCORDANCE WITH THE TRUE INTENT OF THE
DRAWINGS AND SPECIFICATIONS. HE SHALL PROVIDE
AS A PART OF HIS WORK AND WITHOUT EXPENSE, ALL
INCIDENTAL ITEMS REQUIRED EVEN THOUGH THESE
ITEMS ARE NOT PARTICULARLY SPECIFIED OR
INDICATED. THE INSTALLATION SHALL BE MADE SO
THAT SEVERAL COMPONENT PARTS WILL FUNCTION
TOGETHER AS A WORKABLE SYSTEM AND SHALL BE
LEFT WITH ALL EQUIPMENT PROPERLY ADJUSTED AND IN
WORKING ORDER. THE CONTRACTOR SHALL
FAMILIARIZE THE OWNER’S REPRESENTATIVE WITH
MAINTENANCE AND LUBRICATION INSTRUCTIONS AS
PREPARED BY THE CONTRACTOR AND SHALL EXPLAIN
AND FULLY INSTRUCT HIM RELATIVE TO OPERATING,
SERVICING, AND MAINTENANCE OF EACH ITEM.
13.WORKMANSHIP SHALL BE THE BEST QUALITY OF ITS
KIND FOR THE RESPECTIVE INDUSTRIES, TRADE,
CRAFTS, AND PRACTICES, AND SHALL BE ACCEPTABLE IN
EVERY RESPECT TO THE OWNERS REPRESENTATIVE.
THE CONTRACTOR SHALL COMPLY WITH ALL LOCAL, AND
OSHA SAFETY REQUIREMENTS IN PERFORMANCE WITH
THIS WORK.
14.THE ACCESS TO EQUIPMENT SHOWN ON THE DRAWINGS
IS THE MINIMUM ACCEPTABLE SPACE REQUIREMENTS.
ALL OPEN DUCT AND PIPE OPENINGS SHALL BE
ADEQUATELY COVERED AT ALL TIME TO PREVENT ITEMS
FROM ENTERING.
15.NO CUTTING OR DRILLING IN STRUCTURAL MEMBERS
SHALL BE DONE WITHOUT WRITTEN APPROVAL OF THE
ARCHITECT.
16.ALL FLOOR MOUNTED MECHANICAL EQUIPMENT SHALL
BE SET ON 6-INCH HIGH CONCRETE BASE, UNLESS
OTHERWISE NOTED OR SHOWN ON DRAWINGS. THE
UNISTRUT INSERT OF DUCTWORK AND PIPING SYSTEMS
SHALL INCLUDE ALL INSERTS, VERTICAL SUPPORTS,
HORIZONTAL SUPPORT MEMBERS, CLAMPS, HANGERS,
ROLLERS, BOLTS, NUTS AND ANY OTHER ACCESSORY
ITEMS FOR A COMPLETE SUPPORTING SYSTEM.
17.UPON COMPLETION OF THIS WORK REMOVE ALL
SURPLUS MATERIAL AND RUBBISH RESULTING FROM
THIS WORK AND LEAVE THE PREMISES IN A CLEAN AND
ORDERLY CONDITION.
18.THE ENTIRE MECHANICAL SYSTEM INCLUDING PLUMBING
AND HVAC SYSTEMS SHALL BE QUITE IN OPERATION.
THE CONTRACTOR SHALL MAKE PROMPTLY AND FREE
OF CHARGE, UPON NOTICE FROM THE OWNER, ANY
NECESSARY REPAIRS DUE TO DEFECTIVE
WORKMANSHIP OR MATERIALS THAT MAY OCCUR
DURING A PERIOD OF ONE YEAR FROM DATE OF
SUBSTANTIAL COMPLETION.
19.PRE FILTERS USED DURING CONSTRUCTION AND
TESTING SHALL BE REPLACED PRIOR TO TURNING THE
SYSTEM OVER TO THE OWNER.
20.SECTION 230100 OPERATION AND MAINTENANCE
MANUALS
21.THE CONTRACTOR SHALL TURN OVER TO THE OWNER
THE OPERATION AND MAINTENANCE MANUALS WITH THE
BALANCING REPORTS. THE MANUALS SHALL INCLUDE
AIR-BALANCING REPORTS, SYSTEM COMMISSIONING
PROCEDURES, START-UP TESTS AND REPORTS. ALSO
INCLUDED SHALL BE THE EQUIPMENT AND SYSTEM
PERFORMANCE TEST REPORTS AND WARRANTIES.
22.SECTION 233001 METAL DUCTS.
23.THIS SECTION INCLUDES RECTANGULAR AND ROUND
METAL DUCTWORK FOR VENTILATING, AIR
CONDITIONING SYSTEMS IN PRESSURE CLASSES FROM
MINUS 2 INCHES TO PLUS 10 INCHES WATER GAGE.
24.THE DUCT SYSTEM DESIGNS, AS INDICATED, HAVE BEEN
USED TO SELECT AND SIZE AIR MOVING AND
DISTRIBUTION EQUIPMENT AND OTHER COMPONENTS
OF THE HVAC AIR SYSTEM. CHANGES OR ALTERATIONS
TO THE LAYOUT OR CONFIGURATION OF THE DUCT
SYSTEM MUST BE SPECIFICALLY APPROVED IN WRITING.
APPROVED LAYOUT MODIFICATIONS PROPOSED MUST
BE WITHOUT INCREASING THE SYSTEM TOTAL STATIC
PRESSURE.
25.THE GENERAL FABRICATION REQUIREMENTS SHALL
ALSO COMPLY WITH ALL SMACNA’S HVAC DUCT
CONSTRUCTION STANDARDS. CONSTRUCTION SHALL BE
BASED ON STATIC PRESSURES INDICATED ON THE
SCHEDULES, DRAWINGS AND SPECIFICATIONS. TYPICAL
TOTAL STATIC PRESSURE OF THE SUPPLY FAN SYSTEMS
ARE IN THE 3.5” RANGE AND THE EXHAUST SYSTEMS
ARE TYPICALLY IN THE 7.5” RANGE, SEE SCHEDULES FOR
EXACT PRESSURES. COMPLIANCE OF THIS WORK SHALL
ALSO CONFORM TO NFPA STANDARD 90A.
26.TRANSVERSE JOINTS: SELECT JOINT TYPES AND
FABRICATE ACCORDING TO “SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,”
FIGURE 2-1, RECTANGULAR DUCT/TRANSVERSE JOINTS
FOR STATIC-PRESSURE CLASS AS REQUIRED FOR THIS
PROJECT, APPLICABLE SEALING REQUIREMENTS,
MATERIALS INVOLVED, DUCT SUPPORT INTERVALS, AND
OTHER PROVISIONS ARE TO BE PER THE SMACNA
STANDARDS.
27.LONGITUDINAL SEAMS: SELECT SEAM TYPES AND
FABRICATE ACCORDING TO SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,”
FIGURE 2-2, “RECTANGULAR DUCT/LONGITUDINAL
SEAMS,” FOR STATIC-PRESSURE CLASS FOR THIS
PROJECT, APPLICABLE SEALING REQUIREMENTS,
MATERIALS INVOLVED, DUCT-SUPPORT INTERVALS, AND
OTHER PROVISIONS ARE TO BE PER THE SMACNA
STANDARDS.
28.ELBOWS, TRANSITIONS, OFFSETS, BRANCH
CONNECTIONS, AND OTHER DUCT CONSTRUCTION:
SELECT TYPES AND FABRICATE ACCORDING TO
SMACNA’S “HVAC DUCT CONSTRUCTION STANDARDS -
METAL AND FLEXIBLE,” CHAPTER 4, “FITTINGS AND
OTHER CONSTRUCTION” FOR STATIC-PRESSURE CLASS
FOR THIS PROJECT, APPLICABLE SEALING
REQUIREMENTS, MATERIALS INVOLVED, DUCT-SUPPORT
INTERVALS, AND OTHER PROVISIONS ARE TO BE PER
SMACNA STANDARDS.
29.ROUND DUCTS AND FITTINGS, GENERAL FABRICATION
REQUIREMENTS: COMPLY WITH SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,”
CHAPTER 3, “ROUND, OVAL, AND FLEXIBLE DUCT” BASED
ON INDICATED STATIC-PRESSURE CLASS FOR THIS
PROJECT.
30.TRANSVERSE JOINTS: SELECT JOINT TYPES AND
FABRICATE ACCORDING TO SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,”
FIGURE 3-1, “ROUND DUCT TRANSVERSE JOINTS,” FOR
STATIC PRESSURE CLASS FOR THIS PROJECT,
APPLICABLE SEALING REQUIREMENTS, MATERIALS
INVOLVED, DUCT-SUPPORT INTERVALS, AND OTHER
PROVISIONS PER SMACNA STANDARDS.
31.LONGITUDINAL SEAMS: SELECT SEAM TYPES AND
FABRICATE ACCORDING TO SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE”,
FIGURE 3-2, “ROUND DUCT LONGITUDINAL SEAMS,” FOR
STATIC-PRESSURE CLASS FOR THIS PROJECT
APPLICABLE SEALING REQUIREMENTS, MATERIALS
INVOLVED DUCT-SUPPORT INTERVALS, AND OTHER
PROVISIONS AS PER SMACNA STANDARDS.
32.TEES AND LATERALS: SELECT TYPES AND FABRICATE
ACCORDING TO SMACNA’S “HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE,” FIGURE 3-5, “90
DEGREE TEES AND LATERALS,” AND FIGURE 3-6
“CONICAL TEES,” FOR STATIC-PRESSURE CLASS PER
THIS PROJECT, APPLICABLE SEALING REQUIREMENTS,
MATERIALS INVOLVED, DUCT-SUPPORT INTERVALS, AND
OTHER PROVISIONS PER SMACNA STANDARDS.
33.SHEET METAL MATERIALS, GENERAL MATERIAL
REQUIREMENTS: COMPLY WITH SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE”
FOR ACCEPTABLE MATERIALS, MATERIAL THICKNESS,
AND DUCT CONSTRUCTION METHODS UNLESS
OTHERWISE INDICATED. SHEET METAL MATERIALS
SHALL NEW PRODUCT WITHOUT IMPERFECTIONS.
GALVANIZED SHEET STEEL: COMPLY WITH ASTM A 653.
GALVANIZED COATING DESIGNATION: G60.
REINFORCEMENT SHAPES AND PLATES: COMPLY WITH
ASTM A 36, STEEL PLATES, SHAPES, AND BARS: BLACK
AND GALVANIZED. TIE RODS: GALVANIZED STEEL,
¼-INCH MINIMUM DIAMETER FOR LENGTHS 36 INCHES OR
LESS; ⅜-INCH MINIMUM DIAMETER FOR LENGTHS
LONGER THAN 36 INCHES.
34.SEALANT AND GASKETS, GENERAL SEALANT AND
GASKET REQUIREMENTS: SURFACE-BURNING
CHARACTERISTICS FOR SEALANTS AND GASKETS SHALL
HAVE A MINIMUM FLAME-SPREAD INDEX OF 25 AND A
MAXIMUM SMOKE DEVELOPED INDEX OF 50 WHEN
TESTED ACCORDING TO UL723; CERTIFIED BY AN NRTL.
USE A TWO PART TAPE SEALING SYSTEM OR A WATER
BASED JOINT AND SEAM SEALANT. FLANGED JOINT
SEALANT SHALL COMPLY WITH ASTM C 920.
35.HANGERS AND SUPPORTS, HANGER RODS:
CADMIUM-PLATED STEEL RODS AND NUTS. STRAP AND
ROD SIZES: COMPLY WITH SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,”
TABLE 5-1, “RECTANGULAR DUCT HANGERS MINIMUM
SIZE,” AND TABLE 5-2, “MINIMUM HANGER SIZES FOR
ROUND DUCT.”
36.STEEL CABLES FOR GALVANIZED-STEEL DUCTS:
GALVANIZED STEEL COMPLYING WITH ASTM A 603.STEEL
CABLE END CONNECTIONS: CADMIUM-PLATED STEEL
ASSEMBLIES WITH BRACKETS, SWIVEL, AND BOLTS
DESIGNED FOR DUCT HANGER SERVICE: WITH AN
AUTOMATIC-LOCKING AND CLAMPING DEVICE.DUCT
ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS,
OR SELF-TAPPING METAL SCREWS: COMPATIBLE WITH
DUCT MATERIALS.
37.TRAPEZE AND RISER SUPPORTS FOR
GALVANIZED-STEEL DUCTS SHALL BE USED AS NEED
AND ARE TO BE GALVANIZED - STEEL SHAPES AND
PLATES. WIRE HANGERS ARE NOT ALLOWED. USE
THREADED ROD TO STEEL JOIST WITH ANVIL STEEL
WASHERS AND DOUBLE NUT CONNECTION. ONE INCH 18
GA GALVANIZED STEEL STRAPS ARE ALLOWED FOR
SMALLER SINGLE RUN DUCTWORK.
38.INSTALL DUCTS ACCORDING TO SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE”
UNLESS OTHERWISE INDICATED. DUCTWORK IS TO BE
INSTALLED WITH FEWEST JOINTS AS POSSIBLE. SHOP
AND PRE FABRICATED THE FITTINGS WHENEVER
POSSIBLE. PREFABRICATED FITTINGS ARE TO BE USED
FOR CHANGES IN DIRECTIONS AND BRANCH
CONNECTIONS. UNLESS OTHERWISE INDICATED,
INSTALL DUCTS VERTICALLY AND HORIZONTALLY, AND
PARALLEL AND PERPENDICULAR TO BUILDING LINES
AND WALLS. INSTALL DUCTS WITH A CLEARANCE AT
LEAST 1 INCH, PLUS ALLOWANCE FOR INSULATION
THICKNESS WHEN NOTE IN THE SPECIFICATIONS OR
DRAWINGS. WHERE DUCTS PASS THROUGH EXTERIOR
WALLS AND ARE EXPOSED TO THE OUTSIDE OR VIEW,
COVER THE OPENING BETWEEN THE WALL AND DUCT OR
DUCT INSULATION WITH SHEET METAL FLANGES OF
SAME METAL THICKNESS AS THE DUCT. OVERLAP
OPENINGS ON FOUR SIDES BY AT LEAST 1-½ INCHES.
DURING CONSTRUCTION PROTECT DUCT INTERIORS
FROM MOISTURE, CONSTRUCTION DEBRIS AND DUST,
AND OTHER FOREIGN MATERIALS AT ALL TIMES.
39.DUCT SEALING SHALL BE FOR THE DUCT STATIC
PRESSURES, SEAL CLASSES, AND LEAKAGE CLASSES
SPECIFIED IN “DUCT CONSTRUCTION SCHEDULE”
ACCORDING TO SMACNA’S “HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE.” THE CONTRACTOR
SHALL COMPLY WITH SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,”
CHAPTER 5, “HANGERS AND SUPPORTS.”
40.THIS CONTRACTOR NEEDS TO GET APPROVAL FROM
THE STRUCTURAL ENGINEER ON ATTACHMENT
SELECTION AND SPACING OF THE SYSTEMS HE WANTS
TO INSTALL AND THE SUPPORTING OF THE DUCTWORK
FROM THE STRUCTURE. BUILDING ATTACHMENTS SHALL
BE CONCRETE INSERTS, POWDER-ACTUATED
FASTENERS, OR STRUCTURAL-STEEL FASTENERS
APPROPRIATE FOR CONSTRUCTION MATERIALS TO
WHICH HANGERS ARE BEING ATTACHED. IF
CONSTRUCTION PHASING ALLOWS INSTALL CONCRETE
INSERTS BEFORE PLACING CONCRETE IT IS PREFERRED.
POWDER-ACTUATED CONCRETE FASTENERS ARE TO BE
INSTALLED AFTER CONCRETE IS PLACED AND
COMPLETELY CURED. ONLY USE POWDER-ACTUATED
CONCRETE FASTENERS FOR STANDARD-WEIGHT
AGGREGATE CONCRETE OR FOR SLABS MORE WHICH
HAVE A THICKNESS GREATER THAN 4 INCHES.
POWDER-ACTUATED CONCRETE FASTENERS ARE NOT
TO BE USED FOR LIGHTWEIGHT-AGGREGATE
CONCRETES OR FOR SLABS LESS THAN 4 INCHES THICK.
41.HANGER SPACING: COMPLY WITH SMACNA’S “HVAC
DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE,” TABLE 5-1, “RECTANGULAR DUCT HANGERS
MINIMUM SIZE,” AND TABLE 5-2, “MINIMUM HANGER SIZES
FOR ROUND DUCT,” FOR MAXIMUM HANGER SPACING;
INSTALL HANGERS AND SUPPORTS WITHIN 24 INCHES OF
EACH ELBOW AND WITHIN 48 INCHES OF EACH BRANCH
INTERSECTION. IF THE HANGERS ARE EXPOSED TO VIEW
THEY SHALL BE THREADED ROD AND ANGLE OR
CHANNEL SUPPORTS. INSTALL UPPER ATTACHMENTS TO
STRUCTURES. SELECT AND SIZE UPPER ATTACHMENTS
WITH PULL-OUT, TENSION, AND SHEAR CAPACITIES
APPROPRIATE FOR SUPPORTED LOADS AND BUILDING
MATERIALS WHERE USED.
42.COORDINATE DUCT INSTALLATIONS AND SPECIALTY
ARRANGEMENTS WITH DRAWINGS. MAKE DUCTWORK
CONNECTIONS TO EQUIPMENT WITH FLEXIBLE
CONNECTORS FOR THE RATED PRESSURE AND USE
INDOOR OR OUTDOOR. COMPLY WITH SMACNA’S “HVAC
DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE” FOR BRANCH, OUTLET AND INLET, AND FAN
OR UNIT CONNECTIONS.
43.FABRICATE DUCTS WITH GALVANIZED SHEET STEEL
EXCEPT AS OTHERWISE INDICATED AND AS FOLLOWS:
ELBOW CONFIGURATION - RECTANGULAR DUCT:
COMPLY WITH SMACNA’S “HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE,” FIGURE 4-2
“RECTANGULAR ELBOWS.” BRANCH CONFIGURATION -
RECTANGULAR DUCT: COMPLY WITH SMACNA’S “HVAC
DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE,” FIGURE 4-6, “BRANCH CONNECTIONS.”
RECTANGULAR MAIN TO RECTANGULAR BRANCH:
45-DEGREE ENTRY.RECTANGULAR MAIN TO ROUND
BRANCH PROVIDE A 45 DEGREE TYPE TAKE-OFF.
44.SECTION 233300 AIR DUCT ACCESSORIES.
45.GENERAL, COMPLY WITH NFPA 90A, “INSTALLATION OF
AIR CONDITIONING AND VENTILATING SYSTEMS,” AND
WITH NFPA 90B, “INSTALLATION OF WARM AIR HEATING
AND AIR CONDITIONING SYSTEMS.” COMPLY WITH
SMACNA’S “HVAC DUCT CONSTRUCTION STANDARDS -
METAL AND FLEXIBLE”FOR ACCEPTABLE MATERIALS,
MATERIAL THICKNESSES, AND DUCT CONSTRUCTION
METHODS UNLESS OTHERWISE INDICATED. SHEET
METAL MATERIALS SHALL BE FREE OF PITTING, SEAM
MARKS, STAINS, DISCOLORATIONS, AND OTHER
IMPERFECTIONS. MATERIALS, GALVANIZED SHEET
STEEL: COMPLY WITH ASTM A 653, GALVANIZED
COATING DESIGNATION G60. REINFORCEMENT SHAPES
AND PLATES: GALVANIZED - STEEL REINFORCEMENT
WHERE INSTALLED ON GALVANIZED SHEET METAL
DUCTS: TIE RODS SHALL BE GALVANIZED STEEL, ¼-INCH
MINIMUM DIAMETER FOR LENGTHS 36 INCHES OR LESS;
⅜-INCH MINIMUM DIAMETER FOR LENGTHS LONGER
THAN 36 INCHES.
46.MANUAL VOLUME DAMPERS, STANDARD, STEEL, MANUAL
VOLUME DAMPERS: STANDARD LEAKAGE RATING WITH
LINKAGE OUTSIDE AIRSTREAM, SUITABLE FOR
HORIZONTAL OR VERTICAL APPLICATIONS. FRAMES
SHALL BE A HAT-SHAPED TYPE, GALVANIZED SHEET
STEEL, MITERED AND WELDED CORNERS WITH FLANGES
FOR ATTACHING TO WALLS. PROVIDE FRAMES FOR
INSTALLING IN DUCTS. THE BLADES ARE TO BE MULTIPLE
OR SINGLE BLADE OR PARALLEL THE BLADE AXLES
SHALL BE GALVANIZED STEEL, DAMPERS IN DUCTS WITH
PRESSURE CLASSES OF 3-INCH WG OR LESS SHALL
HAVE AXLES FULL LENGTH OF DAMPER BLADES AND
BEARINGS AT BOTH ENDS OF OPERATING SHAFT. 2.10.4
MANUAL BALANCING DAMPERS.
47.CONTROL DAMPERS, GENERAL REQUIREMENTS: USE
PARALLEL BLADE CONFIGURATION FOR TWO-POSITION
CONTROL. SEE DRAWINGS FOR SIZES.
48.CONSTRUCTION SHALL BE STANDARD STEEL. PROVIDE
STANDARD LEAKAGE RATING WITH LINKAGE OUTSIDE
AIRSTREAM, SUITABLE FOR HORIZONTAL OR VERTICAL
APPLICATIONS. THE FRAMES SHALL BE HAT-SHAPED
CHANNEL WITH INTEGRAL FLANGES. THE BLADES SHALL
BE AIRFOIL, GALVANIZED STEEL WITH A PARALLEL BLADE
CONFIGURATION. MATERIAL SHALL BE ASTM A 653
GALVANIZED STEEL. THE BLADE SEALS SHALL BE
REPLACEABLE AND ARE TO BE MECHANICALLY
ATTACHED EXTRUDED SILICONE, VINYL, OR PLASTIC
COMPOSITE. THE JAMB SEALS ARE TO BE STAINLESS
STEEL, OR COMPRESSION TYPE. THE AXLES SHALL BE
MECHANICALLY ATTACHED TO BLADES. BEARINGS ARE
TO BE STAINLESS STEEL MOUNTED IN THE FRAME.
WHERE BLADE AXLES ARE INSTALLED IN VERTICAL
POSITION, PROVIDE THRUST BEARINGS. THE LINKAGE
SHALL BE CONCEALED IN FRAME AND CONSTRUCTED OF
ALUMINUM AND PLATED OR STAINLESS STEEL WITH
STAINLESS STEEL HARDWARE. THE DAMPERS AND
ACTUATORS SHALL BE ACCESSIBLE FOR VISUAL
INSPECTION AND SERVICE. DAMPER ACTUATORS SHALL
OPERATE WITH DAMPERS WITH SUFFICIENT RESERVE
POWER TO PROVIDE SMOOTH MODULATING ACTION OR
TWO-POSITION ACTION AND PROPER SPEED OF
RESPONSE AT VELOCITY AND PRESSURE CONDITIONS
TO WHICH THE DAMPER IS SUBJECT TO. ACTUATORS
SHALL PRODUCE SUFFICIENT POWER AND TORQUE TO
CLOSE OFF AGAINST THE MAXIMUM SYSTEM
PRESSURES ENCOUNTERED. ACTUATORS SHALL BE
SIZED TO CLOSE OFF AGAINST THE FAN SHUTOFF
PRESSURE AS A MINIMUM REQUIREMENT. PROVIDE ONE
ACTUATOR FOR EACH DAMPER ASSEMBLY. MULTIPLE
ACTUATORS REQUIRED TO DRIVE A SINGLE DAMPER
ASSEMBLY SHALL OPERATE IN UNISON IF NEEDED.
49.FLANGE CONNECTIONS SHALL BE ADD-ON OR
ROLL-FORMED, FACTORY-FABRICATED, SLIDE-ON
TRANSVERSE FLANGE CONNECTORS, GASKETS, AND
COMPONENTS, GALVANIZED STEEL, GAGE AND SHAPE
TO MATCH CONNECTING DUCTWORK.
50.TURNING VANES SHALL COMPLY WITH SMACNA’S “HVAC
DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE”; FIGURES 4-3, “VANES AND VANE RUNNERS,”
AND 4-4, “VANE SUPPORT IN ELBOWS.” VANE
CONSTRUCTION SHALL BE SINGLE OR DOUBLE WALL.
51.DUCT-MOUNTED ACCESS DOORS PROVIDE IN
ACCORDANCE WITH SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE”;
FIGURES 7-2, “DUCT ACCESS DOORS AND PANELS.”
DOOR: DOUBLE WALL, RECTANGULAR. GALVANIZED
SHEET METAL WITH INSULATION FILL AND THICKNESS AS
INDICATED FOR DUCT PRESSURE CLASS. HINGES AND
LATCHES: 1-BY-1-INCH BUTT OR PIANO HINGE AND CAM
LATCHES. FABRICATE DOORS AIRTIGHT AND SUITABLE
FOR DUCT PRESSURE CLASS. FRAME SHALL BE
GALVANIZED SHEET STEEL WITH BEND-OVER TABS AND
FOAM GASKETS.
52.FLEXIBLE CONNECTORS SHALL BE FLAME-RETARDANT
OR NONCOMBUSTIBLE FABRICS COMPLY WITH UL 181,
CLASS 1. THE OUTDOOR SYSTEM, FLEXIBLE
CONNECTORS SHALL BE FABRIC GLASS FABRIC DOUBLE
COATED WITH WEATHERPROOF, SYNTHETIC RUBBER
RESISTANT TO UV RAYS AND OZONE.
53.DUCT ACCESSORY INSTALLATION SHALL BE ACCORDING
TO APPLICABLE DETAILS IN SMACNA’S “HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE”
FOR METAL DUCTS. USE GALVANIZED-STEEL
ACCESSORIES IN GALVANIZED STEEL. INSTALL VOLUME
DAMPERS AT POINTS ON SUPPLY, RETURN, AND
EXHAUST SYSTEMS WHERE BRANCHES EXTEND FROM
LARGER DUCTS. WHERE DAMPERS ARE INSTALLED IN
DUCTS HAVING DUCT LINER, INSTALL DAMPERS WITH
HAT CHANNELS OF SAME DEPTH AS LINER, AND
TERMINATE LINER WITH NOSING AT HAT CHANNEL. SEE
DRAWINGS FOR SOME OF THE DAMPER LOCATIONS.
HOWEVER DAMPERS WILL NEED TO BE PROVIDED AS
REQUIRED IN THE SYSTEM TO BALANCE THE SYSTEM
ADEQUATELY. DAMPERS ARE TO BE SET AT A FULLY
OPEN POSITION BEFORE TESTING, ADJUSTING, AND
BALANCING. INSTALL TEST HOLES AT FAN INLETS AND
OUTLETS AND ELSEWHERE AS NEEDED FOR BALANCING.
INSTALL DUCT ACCESS DOORS ON SIDES OF DUCTS TO
ALLOW FOR INSPECTING, ADJUSTING, AND MAINTAINING
ACCESSORIES AND EQUIPMENT AT THE FOLLOWING
LOCATIONS: FIRE AND SMOKE DAMPERS LOCATIONS IF
JOB REQUIRED! AS WELL AS CONTROL DAMPERS AREAS.
DOORS ARE TO BE INSTALLED WITH SWING AGAINST
DUCT STATIC PRESSURES.
54.INSTALL FLEXIBLE CONNECTORS TO CONNECT DUCTS
TO EQUIPMENT. INSTALL DUCT TEST HOLES WHERE
REQUIRED FOR TESTING AND BALANCING PURPOSES.
SCALED FOR ORIGINAL DRAWING AT 22" X 34"
ZM003
MADISON ARMORY
100% SUBMITTAL
SAVED: 2021-08-24 16:44:06 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM001-003-21.038.00.dwg----
Project Manager:
Territory Manager:
Project Engineer:
Drawn By:
Approved By:
Origination Date:
ADAM ZIEGENFELDER
08/24/2021
WILLIAM LEWIS
SCOTT DESANTI
WILLIAM LEWIS
STEVE TIBBALS
REVISION DATENoBY
PROJECT STATUS
PROJECT NAMEP O Box 636, Provo UT, 84603Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.comThe use of these plans shall be restricted to the original project site for which they were prepared.Publications expressly limited to such use. Re-use, reproduction, or publication by any method in wholeor part is prohibited. drawings and designs remain the property of action target inc. without reservation.Action Target Inc. 2021 All Rights ReservedDRAWING NUMBER
SHEET NAME
SHEET NUMBER
HVAC
SPECIFICATIONS
KEYED NOTES (SHEET ZM101.1)•• GENERAL NOTES (SHEET ZM101.1)SHEET NAMESHEET NUMBERSCALED FOR ORIGINAL DRAWING AT 22" X 34"ZM101.1MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 16:20:42 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM101.1-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedHVAC 25YD & 50YDRANGE PLANSCALE: 1/8" = 1'-0"HVAC - 25YD & 50YD RANGE PLAN
KEYED NOTES (SHEET ZM102.1) GENERAL NOTES (SHEET ZM102.1)SHEET NAMESHEET NUMBERSCALED FOR ORIGINAL DRAWING AT 22" X 34"ZM102.1MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 13:59:25 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM102.1-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedHVAC 25YD & 50YDPENETRATIONPLANSCALE: 1/8" = 1'-0"HVAC - 25YD & 50YD PENETRATION PLAN
KEYED NOTES (SHEET ZM103.1)•• GENERAL NOTES (SHEET ZM103.1)SHEET NAMESHEET NUMBERSCALED FOR ORIGINAL DRAWING AT 22" X 34"ZM103.1MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 14:51:27 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM103.1-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedHVAC 25YD & 50YDROOF PLANSCALE: 1/8" = 1'-0"HVAC - 25YD & 50YD ROOF PLAN
KEYED NOTES (SHEET ZM301.1)••• GENERAL NOTES (SHEET ZM301.1)SHEET NAMESHEET NUMBERSCALED FOR ORIGINAL DRAWING AT 22" X 34"ZM301.1MADISON ARMORY100% SUBMITTALSAVED: 2021-08-25 10:58:11 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM301.1-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedHVAC 50YDRANGE SECTIONSCALE: 1/8" = 1'-0"HVAC - 50YD RANGE SECTION
SCALED FOR ORIGINAL DRAWING AT 22" X 34"SHEET NUMBERSHEET NAMEZM501MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 14:54:46 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM501-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedAIRFLOWSCHEMATICPURGE SYSTEMAIR FLOW SCHEMATIC - 25YD & 50YD RANGES NOT TO SCALE1ZM501MAICTVFDAOBODPAISBIBUILDING DIFFERENTIAL PRESSUREDOOR STATUSTAIOUTDOOR TEMPERATUREPAIRANGE PRESSUREAORANGE PRESSURE SETPOINTMAICTVFDAOBOGAS HEAT HLAIE.A. 34,320 CFMEXHAUST FA(EF-1)17,160 CFMS.A.31,200 CFMSUPPLY FAN(MAU-1)31,200 CFMO.A. 31,200 CFMMBO(FB-1)DPHEPAFILTERDPBAG TYPEFILTERMERV 14AIAIAIANALOG INPUTESEND SWITCHHLHIGH LIMIT SWITCHVARIABLE FREQUENCY DRIVECTCURRENT TRANSFORMERBOBINARY OUTPUTVFDMMOTORIZED DAMPERDSPDUCT STATIC PRESSUREMAKE-UP AIR SCHEMATIC - RANGE BAYSEXHAUST AIR SCHEMATIC - RANGE BAYSAIBIBIBIBIESTAIPAIE.A. 34,320 CFM
SCALED FOR ORIGINAL DRAWING AT 22" X 34"SHEET NUMBERSHEET NAMEZM502MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 14:54:46 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM501-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedLOW VOLTAGESCHEMATICPURGE SYSTEMCONTROL WIRING SCHEMATIC - PURGE SYSTEMEQUIPMENT LEGEND - BY ACTION TARGETITEMQTYDESCRIPTIONJB41WATERPROOF JUNCTION BOX - CONTAINS PRESSURE SENSORSS4DOOR PRESSURE SENSORTH1TEMPERATURE/HUMIDITY SENSORDP1DIFFERENTIAL PRESSURE UNITRCP1RANGE VENTILATION CONTROL PANEL CONNECTED TO MASTERCONTROL SCREENMCS1MASTER CONTROL SCREEN (W/ SMART ACCESS)MAU-VFD1VARIABLE FREQUENCY UNIT FOR THE MAKEUP AIR UNITEF-VFD1VARIABLE FREQUENCY UNIT FOR THE EXHAUST FANP1DUCT PRESSURE SENSOR KEYED NOTES (SHEET ZM502)RANGE ENTRANCE DOOR - SSIDE ENTRANCE DOOR - SSUPPLY TEMP - THSUPPLY DUCT PRESSURE - PMAU OUSIDE AIR TEMPOUSIDE AIR FILTEREVAP ENABLEOUTSIDE AIR DAMPERMAU HEAT CONTROL/ENABLE120V 15A INPUTFILTER RETURN BANK - DPSUPPLY VFD - MAUEXHAUST VFD - EFADJUSTABLE FREQUENCY DRIVE PROVIDEDBY ATI AND LOCATED INDOORS. VFD SHALL BEIN A TEMPERATURE CONTROLLED ANDACCESSIBLE LOCATIONADJUSTABLE FREQUENCY DRIVE PROVIDEDBY ATI AND LOCATED INDOORS. VFD SHALL BEIN A TEMPERATURE CONTROLLED ANDACCESSIBLE LOCATIONHVAC MASTER PANELPURGE VENTILATIONRCP10x10J-BOX10x10J-BOXATI SUPPLIEDJ-BOX (JB-4)4x4J-BOXDUCT MOUNTED1-18/41-18/42-18/42-18/63-18/44-18/42-18/63-18/41-18/62-18/41-18/61-18/42-RS-4851-CAT5E1-18/42-RS-4851-CAT5ESMOKE DETECTOR(BY OTHERS)1-18/4INTERNET IN from SMART RANGE AXIS (SRA)1-CAT5ETYP.TYP.PNEUMATIC TUBE TO SPACEADJACENT TO RANGE1/4"1/4"PNUEMATIC TUBE
SCALED FOR ORIGINAL DRAWING AT 22" X 34"SHEET NUMBERSHEET NAMEZM601MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 16:43:50 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM601-603-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedMECHANICAL HVACSCHEDULES
SCALED FOR ORIGINAL DRAWING AT 22" X 34"SHEET NUMBERSHEET NAMEZM602MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 16:43:50 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM601-603-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedMECHANICALDETAILSMANUAL BALANCING DAMPER ROUND6 38 IN. MAX.18 IN. DIAMETER20 GA.FRAMEAND BLADETHICKNESSNOTE:BASIS OF DESIGN: GREENHECK MBDR-50PRESSURE: UP TO 4 IN W.G.38 IN. SQ. LOCKINGMANUAL QUADRANTGALVANIZEDSTEELSYNTHETICSLEEVEAXLE BEARINGTYPICAL DUCTWORK45 DEGREE TAKE-OFFAIR FLOWAIR FLOWDUCT/PIPE ROOF CURB DETAILWITH RIDGE PEAK FOR WATER SHEDTYPICAL ROOF DUCT SUPPORTTYPICAL DUCT STRAP HANGERDUCT CONSTRUCTIONTYPICAL ROOF CURBTRAPEZE HANGER DETAILRADIAL DIFFUSER DETAIL (TYP.)FRONT VIEW4"18"4"24"28"24"18"24"24"48"12"TOP VIEW0.375"Ø MOUNTING HOLE(TYP-5)SIDE VIEWRIGHT18"Ø2"18"ØFILTER BANK INSTALLATION DETAIL (TYP.)25"36"DUCT TRANSITIONFROM RANGEDUCT TRANSITIONEXHAUST FAN SIDEMEDIUM EFFICIENCYFILTER SECTIONMERV 14HEPA FILTERSECTIONMERV 17DUCTWORKCONNECTINGTHE FILTER BANKTO THE EXHAUSTFAN SHALL BERATED AT AMINIMUM OF 8"WCSTATIC PRESSURE.CONCRETEPAD OR ROOF(BY OTHERS)EQUIPMENT RAILL/ARDEN MODEL SER-POR EQUIVALENT (TYP)CEILING REQUIREMENTS DETAIL8'-0"CONSTANT SLOPE CEILING ONLY (NO STEPS)SLOPE AS NEEDED DOWN TO STATIC FIRING LINE.INSTALL ALL RADIAL DIFFUSERSAT THE SAME HEIGHT. INSTALLJUST ABOVE DOOR JAMS ANDWINDOW JAMS. DO NOTINSTALL HIGHER THAN NEEDED.TYPICALLY 7'-0" MINIMUM.SAFETY CEILINGHEIGHT1'-6"7'-0"ACTION TARGETBALLISTIC SAFETYCEILING
SCALED FOR ORIGINAL DRAWING AT 22" X 34"SHEET NUMBERSHEET NAMEZM603MADISON ARMORY100% SUBMITTALSAVED: 2021-08-24 16:43:50 BY: BILLY.LEWIS AT: Z:\_Projects\2021\21.038.00 - Madison Armory GR\Mechanical\ATI-ZM601-603-21.038.00.dwg
DRAWING NUMBER----Project Manager:Territory Manager:Project Engineer:Drawn By:Approved By:Origination Date:ADAM ZIEGENFELDER08/24/2021WILLIAM LEWISSCOTT DESANTIWILLIAM LEWISSTEVE TIBBALSREVISIONDATENoBYPROJECT STATUSPROJECT NAMEP O Box 636, Provo UT, 84603
Office: (801) 377-8033 | Fax: (801) 377-8096 | www.ActionTarget.com
The use of these plans shall be restricted to the original project site for which they were prepared.
Publications expressly limited to such use. Re-use, reproduction, or publication by any method in whole
or part is prohibited. drawings and designs remain the property of action target inc. without reservation.
Action Target Inc. 2021 All Rights ReservedMECHANICALDETAILSPIPE HANGERSROOF PIPE SUPPORT - POLYMER BASETYPICAL GAS PIPING LB. TO OZ. CONNECTIONRCP PANEL DETAILDISPLAYRCPCOORDINATE LOCATIONWITH BUILDING OWNER.MUST BE LOCATED WITHIN300' OF RCP.RANGE VENTILATIONCONTROL PANEL. INSTALL INCONDITIONED SPACE WITHIN300' OF EQUIPMENT DISPLAY.FINISHED FLOORVENTILATION CONTROLPANEL (VCP).BY ACTION TARGET.24Hx20Wx8DTYPICAL PANELSIZE.(DETAIL 5)RCPPANELTROUGHCONDUIT & TROUGHBY ELECTRICALCONTRACTOR.CONTROLS120VVARIABLE FREQUENCY DRIVE DETAILMOUNT VFD TO WALLUSING HOLLOW WALLOR MASONRY ANCHORSTHE LOCATIONS OF THE VFD'S,RANGE VENTILATION CONTROLBOX AND RANGE VENTILATIONDISPLAY ARE TO BE DETERMINEDBY THE CUSTOMER OR GENERALCONTRACTOR.IT IS RECOMMENDED THAT THEVFD'S AND THE RANGEVENTILATION CONTROL BOX BEINSTALLED IN AN ELECTRICALROOM AND THE RANGEVENTILATION DISPLAY IN ANADJACENT RETAIL SPACE WHEREIT CAN BE EASILY SEEN ANDREADILY ACCESSIBLE.ACS-CP-AFINISHED FLOORMOUNT VFD ON WALLWHERE DIRECTED BYOWNER IN ACONDITIONED SPACEVARIABLE FREQUENCY DRIVE (VFD) DETAILVRD = VARIABLE FREQUENCY DRIVEE.C. = ELECTRICAL CONTRACTORSUPPLY ANDEXHAUST FAN VFDBY ACTION TARGETCONDUIT ROUTEDTO RANGE CONTROLPANEL (RCP). E.C.30.5H x 13.4W x15.7D DIMENSIONSARE FOR ONE OFTHE LARGESTDRIVE SIZES. SIZETBD.(DETAIL 3)NOTE:EACH VENTILATIONSYSTEM REQUIRESA VFD FOR THESUPPLY ANDEXHAUST FANS.HIGH VOLTAGE CONDUITAND TROUGH. BY E.C..FINISHED FLOORSUPPLYFANVFD4x4 J-BOXTYP.HIGH VOLTAGE TROUGH B.O.EXHAUSTFANVFDR-CER TYPEEQUIPMENT STAND DETAILROOF MOUNTED - R-CER TYPE EQUIP. STANDSUTILITY TYPE EXHAUST FAN DETAILFLEXIBLECONNECTIONTRANSITIONEXHAUSTDUCTGRAVITYBACKDRAFTDAMPERWEATHER-PROOFENCLOSURE OVERMOTOR SECTIONDUCT SUPPORTSAS NEEDEDMOUNT ON SEISMICALLYCAGED SPRINGVIBRATIONISOLATORSR-CER TYPEEQUIPMENT STAND(TYP.)MAKE-UP AIR UNIT CURB DIAGRAM