RE: Building Renovations for
Dear Doug,
November
1994
Proposed Chinese Restaurant
P.O. sox Sao
12 NORTH CENTER STREET
RExBURG, InAl10 83440
PHONE (208) 359-3020
FAX (208) 359-3022
Reference 'is made to our visit to your building and the
discussions regarding the renovation workr bring it into
compliance with. the Uniform Building code requirements for a new
restaurant. The items discussed were as follows.
1# ENTRY WAY
Work needs to be done to the main front entrance of the building
to bring it into compliance with the "handicapped" r i f
the U.B.C. and the A.D.A. Thisi r iii' relat,ively
flat landing on el'ther side of the new door and encu.gh extra width
at the door to allow someone in a wheel chair to be able to -openthe r r. T '
j_ng ramp leading up to the door landing
should have no more than a 129.1 l desirably; however, a 1
lope is allowed on reconstruction work if suchr slope i
lute i s .r . See attached drawings depictiLng wheel
chair access requirements at doorways, access ramp handrail
requirements, etc.) To help wi this reconstruction the Cit
would ll e sidewalk to be removed and replaced to providea
higher "back -of -sidewalk" adie doorway entrance -P however, the
slope of the new sideway (sloping from
directions could not be greater than 300#16
2* RESTROOMS
Technically, there should be two
,xis. requirements. or the
rr mere & women)meeting
re could be two restrooms (men
not meet -1 -ng handicapped requ irementsu a unisex restroom
meeting a i - e requirements. As this is reconstruct ion work
where we have some latitude for campromi[.se, we have agreed
the men's restroom a "as is"; however, the women's restroom
wouldl arged and retrofitted to rneet all handicapped
requirement and sj-gned as both "" a"unisex "t
T restroom i*s really too small and crowded for the amount
of usage from a restaurant of th's type and, size, Ne hoPe that
the restaurant is successful and that you will be able to gra e
the men's restroom f ori too ion
g.
CEILING
We understand that the ceili'ngill be repaired and replastered
and that a lower false ceiling will be installed. Lights
lowered false ceiling need to he separatelyattached to the
permanent ceiling as shown on the enclosed drawing to minimize
light movement /breakage/ 1 ling Burin
g an earthquake event.
BASEMENT
The basement must be separated from the 1st floor din.'
ng
room/kitchen are "by not less than one hour
firmsresistive
construct ion" . More simply t t r this means that there needs to
be 2 layers f 1, gypsum board attached to the bottom
joists see attachedri for overlap rdetails)
separating the basement from the l t floor . The 3 pint: between
the gypsum boards need to be taped. This is the minimum
improvement necessary to provide for the safety f the people i
the restaurant the I t floor,
If the
basement P s
going
to
be used
in any manner, it would
also
need to
be brought
up to
the
present
life-safetv standards
T
meet toils standards, the basement would need, to have a fire
suppression inkier system and two separate exit one near
the north end and the other near the south n of the
basement
area)o The
i i t It width is 36 inches anda .need to be
larger n in upon occupant loads There are also stairway and
door requirements that have to be met. The existing door and
stairway t the southwest corner of the basement do not meet these
standards,
Tt is my understanding that you are goi.ng to
indicating i t you or the proposed restaurant o
basement area at present; and that you understand
brought up to safety standards before it is used,
Let me know if you
JAL/ jr„r
Enclosure
have any quest ions.
get the
plans t
it Will
City a letter
utilize the
have to be
Joseph A. Lairds �.
City Engineer Building off ic]lai
5
Slopes steeper than 1:20 shall beconsidered a ramp.
Ramps in new constructionsha
1:12, 30"
max. rise.,
11 be not steeper tha
Cross slope of ramp surfaces shall
than 1.,,48,
not be steeper
Handrails are required Whenthe rise ,exceeus:6"
(i50rnm)or ''run "'greater'' than '.7211.--"(1830
mm).
Table 4.8.2 - Allowable ramp dimensions for construction in
11
existing sites, buildings and facilities
Clear width of
ramps.
a 36"'"° (915 inimum.
Landings shall be at I
leading to it. Landin
minimumclean,
east as wide as the widest
length, shall be 601"
4a4 International Conference of Building Officals
ramp
1525mm)
Doors 'i
id
pull
n alcoves shall comply with the clearances for
e, push side and latch side front approaches.
Maneuver'iKng spaces shall be clear and have a slop
not steeper than 1 a48w
Doors to hospoltal bedroo s sha
latch side space
required
(1120mm) wide minimum.
be exe p
71Je
door
t from
IF
Is 44"
MANEUVERING CL A ANC S AT DOORS
ANSI 4.13.6.14, E15 & z1 6
International Conference of Building Officials s,3
Door closers shall be adjusted so that from an open
position of 90°, tie required. to move door to an
five
open position of -12° will be seconds minimum.
For other than fire doors the
required force for pushing open
V
or dulling open shall be.,
I. Interior hinged door*
5.0 pounds, maxunum
Z. Sliding/folding doer:
�-- - -- - 5.0 pounds, maximum
Handles, pu�.�.s, latches, locks and
other operable parts shall have a
shape easy to grasp with one hand
and does not require tight grasping,
tight pinching or twisting of wrist.
Thxesholds, if provided, shall
61
be Y2 ix�ch (13rnm} high maximum.
Exterior residential sliding
doors shall be 3/4 inch (19mxn)
high maximum.
4 Bottom 12 inches (3osmm} of all"
dovrs EXCEPT automatic doors,
power -assisted doors and sliding
doors shall have a smooth�:
.
umnterrupted surface.:,
1%
4 � _AJ
;1 -
f i
ANSI 49134101 011 1 & .14
46 International Conference of Building Officals
A
t•1'
48 min
4$ min
220
Space between two hinged or pivoted doors
in series shall be 4$" (1220mm) minimum plus
the width of any door swinging into the space.
ANSI 4.1 3.7
48 International Conference of Building Officals
13
t W ! ■
db ■ a
t..
■ i' i 1
i
i # i i
� # i
t
# f t
i ! i
i 7
f +it
t•1'
48 min
4$ min
220
Space between two hinged or pivoted doors
in series shall be 4$" (1220mm) minimum plus
the width of any door swinging into the space.
ANSI 4.1 3.7
48 International Conference of Building Officals
13
DOORS RON
PULL SIDE
•
1 18 min
455
V-��` x
PUSH SIDE
NOTE: x 12 in
(305) if the door'"
has both'a closer and a Latch.
ppboth
If door is equipped with closer
beyond latch side,
18" (455mm) min, beyond latch
side of door
60"(1525 mm) min.
r to. the doorway
perpendicula
4811
(1220mm) min.
perpendicular to the doorway
32" (815mm) min. width
(same width as do -or
opening)
d latch X = 12" (305mm} min.
MAN UV RING C-LEARAIINC S AT DOORS
ANSI 4.13
International Conference Of Building Offic&AGjS W %.F
i
?77
W
DOORS HING SID A OACH
PULL SIDE
PUSH SIDE
54 min
1370
dt
X = 36" (915mm} nun. beyond
latch side of door, if Y
�1S25mm) miLn.
to doorway,,
or
60er
icular
X = 42" (1065mm) min. beyond
latch side of door
Y 54„
it
perpendicula
(I 370ntm) min,,
r to doorway.
54" (1370xnrn) min.
doorway.
parallel to
Y 42"(1065mm)
perpendicular to doorway.,
e e_
It -1ach'and cls
's
er'
MAN UV RING CL ARANC S AT DOO S
50 International Conference of Building Officals
PULL SIDE
ORS
LATCH SID A
PROACH
24 min
C
E
co
NOTE: Y = 54 in (1 370 mm) minimum if the. door
has a closer.
X
24 min PUSH SIDE
NOSE; y = 48 i (1220 rni n i mu m i f the door
has a closer.
C
E Ito
N 8
WITH CLOSERS
X = 24" (610mm) min. beyond
latch side.
Y = 54" (1370LMM) min&
perpendicular to doorway.
WITHOUT CLOSERS
Y = 4811 (1220m -m) min.
perpendicular to doorway.
WITH CLOSERS
.0
X = 24" (610mm) min. parallel
to door beyond latch side.
Y = 48 " tl4
220mm) man.
pe.x,ve discular to doorway
W
WITHOUT CLOSERS
Y = 42" (1065rn-m) min*
perpendicular to doorway,,
MAN, UV RING CL EARANCES AT DO
0 R S--r
ANSI 4E13N6w7Y M8; U9 &.10
International Conference Of Building offi ,
ll
i
qr
GROUND AND FLOOR SURFACES
Ground and flooru1mmommfraces of. accessible routes, and
in accessible ro,ms and spaces shall be:
• Stable
•
Firm
• Slip resistant
Changes in level Shail comply with the folrrr lowing:
• 1/4 inch (6mm) high maximum shall be permitted
to be vertical, without edge treat ent.
• Between �nch (6 m) high mini
1/4 ium
inch (13mm) high maximum shall be beveled
with slo�Pe not steeper than 1:2.
and 1/2
• Greater
accompli
elevator.
[MMEW2.0
(a) Vert'cal Changes in Level
'/z i
by a
nch (13 m)
curb ramp
ANSI 4.5
64 International Conference of Building Officals
shall be
ramp or
1/4-1/2
6.13
2
r t t r i r r r r t•..
• f f r � t � a � � . � + i + } t � i
t i * ■ i 7 # a i f' � * * � � � #*i!t*}#tar*#
air}t+a**r4irt ;"M*�}.**#.*�#flit*i■'#t . r is * ■
t■+. f f t i t r t r t r t ..
IP .0
r** w t■ r�
t tt•a f oi*r®t#i+r* !�■•�a.ii+r*ty**r*t *+.*}* l4t #! *rt#■fa� + +t# t b i a*�k}*i�#�sr* f*}ar*ati#r*�lg*##*rt * f�,}a, r■atrtrir*af�
t t# trt' �*r��7*'a e}r*faf rr!gi:ir+r�,�t' * ++r � �t ■
a
ai • *#
*
tai 4 r * f ■tt�tt** #}+roti■F�*e t't*r�*i*4# #��r*T*rt}�r�t+t#r+r*4 #r*yi*■
***r*l
fir*k
•a +�i *f*+* • Fl !4 i�r..r.rt *t a t r� f■'� F+� ti f *i to#
+#'#t*tt#*##+�4israa.atarr#*r■i�fa #�#*♦tft*rt#t.r.i
t # t t # '1s # # * * ak t # i i f" t t i • ■ ■ # t # i t # 9 }
�"afi#a�t�trt*ttr ri■■+i t a *-#*Fs�tarr
r *,t * f • r� i�* t l* *
#*i*� •if r ■ # * ■# f ■ ■ # t * * r r t ■ t s # a #
-t f $ t t + *�a � � #*+fit#**it';�•�ll+�.■�r*i}*a■ri■r *i ���*torr 11.0% dl #
r�Y#�#tliF■rtr+i•ta'rt��°l�'�t�3yly#_*.�'_#_�_a_+_r_•_t t,i #,+� ■ r s+. # t fi r r i
(b) $eveIed Changes an Leve!
F
ACCESSIBLE ROU
X15
E
EC%
' FriT.4Ff+-+T+may Sri `i� f+iti r {:r a y iT �F aT• �. .
! a ► t
iT
R'r`y`y■)i`i}".R'rT, Tedi �. Fria`a T�`aia'r' =_T�Trlyi ::gyp*
C
(a) Width of Accessible Route for 9fl° Turn
1065 1 1065
OTE Dimensions shown aP J v whinx < 4S in (121-0 mmj.,
When
!1-
When turn's around an obstruction n[1 i -4z I
than 4811 (1220mm), the a
ccessinle route sha
pvc a minimum clear space of 4211 (1065mm
by 4811 (1220mm) minimum.
ANSI 4.3.3
Lj
International Conference of Building Offf0j;a1f; 67
i
•
Fiandrails shall be provided on both sides Of stairs
Al
and ramps- W/7 4e r e re�a�,�'��
EXCEPTION:
Aisle stairs
provided with
and aisle ramps
a handrail either at
the side or within the aisle width,
• V
Handrails shall be continuous within the full lg1.
of each stair flight and ramp run. �''`j � ` "`y
" � "' L"';
EXCEPTION. Handrails in aisles serving seating
Inside or doglegstairs on or
ramps shall be continuous between flights or runs.
EXCEPTION:
in Handra"Isi aisles seating
• Gripping surfaces shall be
interruption
by newel posts,
elements, or obstructions.
continuous, without
other construction
• Handrails and any surfaces adjacent shall
be free
of sharp or abrasive elements. Edges shall have
1/8 inch minimum
• 0
Handrai{s shall not rotate within their fittings.
ANSI 4.3.10
70 International of Building 0fficaConferences
NOTE: 1-114" mir, handrail does
not meet UBC 3306(i).
34" to 38"
865MM to 965mm
Handrails
�N.
6�
6�
with other
1-1/4 t 211
ozmm 1C
shapes shall be pe",rmitted
provided perimeter dimension of 4 inches minimum
(100mm) and 61/4 inches- (160mm1 mimum_
cross sect'ff
ion
maximum.
dimension
is 2'/4 incises
ANSI 4.3.10
Largest
.(57
International Co,nference of Building
Officials 71
� 70 TA.JA '&.I
1 .min
F T
itt r#.iT+#r.
*. }..7:a ail iiai ii"ri +Tt
. F i F 4..p r i i ri . b. a y a i. i F# .!.#
s � � � y + *.. { � .. ... • + r + �i !arra r i + #_ + t• . + i i t b a i . + . � • T T t i +'i
i.i.#•Fi.a •. tri•++a yart.r.#T di{{..•..i.i dta =•ti+ia+#.T7
bi++.7..*
ba. ...+-i-++. .+'.+F+•..zr=.i Yrrida.=.:+r,r4 *a..a
t : * • _ • • ,• •• ... i 7 . % • r # + .. F 4 1 i... i . i t :. + ..r . n
+al..+ii.ba•aati ti+a.+•ii+•'!.'*iii++##iiirl•T'l Ti+dl#+#•ir. t+i
12 min
•.+ry...+i i.
i. --bib 7.....iiibb. T T•
i a ..4 .. • • . r . r T + • • .
.*..:i. •#.a T+=+'.lilt
t # f f + i • b i• i #tri ... t + ...,. r.
s b.,.y�. i. a..T..ai7a.■i■bi
•.# T 4 fl a i l+% F i i � r = i s T . T T
}! T l y. a F. y i tai .■ ala r i NO F■ i
............
i!.T..bfi■ 7 4
. f f T •4 • b++ i F F i r F i t t J i .. i. i r i i. a r.
.•+■fit 4++.blit. J..i.... }il#.•lir. r.lr
sr t"r r ............ i.......... l.••4
tr ir•..i T+•.. T,•. y i...l Tf! •i#. i 4Tl l.7+
+'+. i•4.. -.i 41.4.�i.+.;.a.. T.4#rP• •?T4++1�
*i. b Lb a F0bi } }4 T ! .. l... a T bb !#fl}i Ti l4ri
.44.f+i 9%. it...
i.
b.i b bb i.i}*.r..ra •!.#..+ar+b F+laf.*r*•+t
a.+t.:.i.#..+..p+.+..4++++ :.44
4a+• r•#=+ Fdt t i t...i iu........•.....�•1. r.•
. + f .• i iii i tri . r. a ....... a . 4 .
l l . i '....
. y- . i.•. 7 J a. a 7 7. 7 4 4 4+ F f .. a ..-.. 4 *,
.+. all+T+##i Yii ii..#bi+i+a.-1i.la
.1. 4T T7.7#y 4+4+ P. TT T •.•lOrr
yiii.oi i1 +'ilr i..#-r.}r T■r 6{77 F0 rlr■.■'
'..7'#Pl+ati■abb■ai+r.t tiiiJ b... bbiir r.
* * + P + b i ■ .............................
YT Ta ri#++ii ei.. Toil...•.. l
kJ T•a••.#++Ftd+#drr lit t. ri .t. i..
+t:.r si..•T••ff .#�.T{+l+f!=4T+..•aa..
ar. aaT+.•. Fd i•+f i+a t..siiiti. .l i.
a 7�. *■-a#i#+iii+i#i++ii#aii•J b7+.�i i,
i.ia. r;�.. r T1pl■b. b F+7i irtri+iF+i7a'Ib -
! 7 a+#. a T. i i a bib i :iii Y aL .......... a i i i .. .
b..i..1 is. a=.. f++tr.a#tT b. a*i, r4•+t#t•
fF!#■r#7i"ira-bib bdA*,dLp *4por■ til.. lir**iia
(a) Elevation
................. i:i .........
y E4
+•• • • • • • • a.+ f i . + r i i
.............
12 min
b) Plan.
# up
12 min
rf l=T,. ay ti..4ati fi#+i Fia477l7#
+�rt#7 bi T#}i.a JYri#i.Fi F ii b+a■ay ibi
i b. r .. a .. w i 4,0 i F# .* r .. •'T i,b# a b b
•F.r•e'i-----'=.r :i+iiia-+.pail.#F
_.;i•ris4#7=+I.a.r7riT=Taa...a8-ia.v....ri.+#=`f##.....b
ib+i�T.ab+Yb+\Ai!}.ii#777T.iir#+i=•a.iiii F#fiN#:•• .ria+ibr
iii b o a r■.* .iia F i a. i• d.+4 + a r, -.4 40& .•:• r s .. r r .. i t i#
ir.iaa##77;...ili,�#.#s*T7.
...t#+T=. tit YziriT•T+•Viii .};; it+lit+T7=•••�•'
F'T.#..r.i004.!{}#iJ#■F7*1•-_•4 ------- 'r�r#ii#.=
i.'■.7 .'. *'til i {#T+4•• T'Mfi-+°�•• +i/ .=Jiiati r.7 a 91•ri4ia 4•F
raib b+.Tb•.•r�++�+a+.a .i.ir+r++ rl•i.'r #.d T. +Ta=iia.
'iia'F i'F'l.T T•iib}7a7.R•r.ta a.. r r.. r++=a=ori r.+ -t4 tyaa
iJ.i.�Fii.f.#....ai is..*i--
......+++........++:t+i++ + r.•ii
. a+. r i i b i t!■ **. i Y i r a 7!!} *.. .iii 7 4 7• s .. *al•: f■#+ f a•• . a _t + i i
i,i Fii9 d. 41 bi ..i a i l�7a•Y;ii+i }r.1t.i iibiib..;;.lT T .iaM+
a a.=. .... a+#.+ ..r s#i ri lFT •r ..i+•+*••��•'••'•iiii+ii.#
.*.•rr••'+#+"►.a•+,Tr..rit{{aT=••+iriii itlT •.ritiibii4b7i Tr7ila
7 of + • + • •'i # ti ■ t . 4 = . r i F r r 7 + + T ai ®i b i b F i i
AA i i7 a1717iriia+Fr-.A•r..Ir#!#l.. •' .�..#i=,p.a}.®.i*. ... +. ..i FF.F
.aa#b0DID&VAAii777MO. ••ii#.i#.. ...ba#1+•i.{{i.iiti#il+a
a) Elevation
(b) PID "
..}
ii
+Ti
t+
# .
•..
a+rbaaba.a
i-#bifl7 tai*a •'F b•F.i4 �
#+
Tr+t••bae{ .a;iii
.is, .!.r
++Ff++F.+i +r f..+i •+Ti f•4Fi .}+y..r .
TiT.t=.y...;i rtrat+iriii.iiii..a iii+t+ri i+. + + +a.a
.... + s...a•..} . ; i d.'
. i . • `. 0.i �. *.p i . j i v '}
f * • p +.a + * 4 T F F i . i i } ..i i}Y . i %. 4 . i a %.%N
+. 1
■ ! "• . T . ■ p.:i'o * .�T-.. ■r. +. a Ts• .. �.. / *Fpi .Y irT ..r• ;n.ri i i
(b) Plan
International Conference. of Building Officals
4-NJ1-d
12 min
.. +
r liF
r. ....{..•.. r
+*tit++tf#f•T
br. b■# a r i l+. F .T . b+ F
• f+ +. T T +.a . i.`i i4 . i i i 4.4 a+ a b a i. "a r. t Y. a . b-&
A. t -. i : #F t d +F ra 4—.b + .-.p •i . i . _ . a a + . 1F..
.... r .i... 66 a +iii i ## # t b t F t #4* 4 b*#+ A! a## r++ f t !t b#
a) fevollorx
-i y y y i z y'.... i i .. i l r b i a i* +# i+ W* ................
i an 10 a i ad NJ b# I a i It r1 W11 r. r.! 7 *0 F f! t i T 1h, .0 '. i i ..t* R -
.ra
aa.a T4 TT T T T Tr .i raT 9a"?YT_�s..'7._T'_ _ -.. -----------
_ --._..._ - - - -
(b) Plan
9
12 min
Sign to nearest M.O.E.
3 EXITS REQUIRED BASED
PAID]
00111
,IQ Imph"L K,
• All required accessible spaces shall be pravided
with not less than one accessible means of egress
Ole
When two ormore exits are requiredfrom any
�`accessibleportion space, each of the
space shall be served by not less than two
�� accessible means of egress
• Maximum travel distance per Chapter 33
Accessi"ble eans of egress shall be continuouls;
M -
from each required.. ac,..cessli•
ri
ble occupiel. area to a
public shall 'include way
accessible routes
ramps
exit stairs
elevators
horizontal exits
smoke b
SECTION 31.
International Conference of Building Officials 73
U
Ir
I r -B m 1-1 [4 m . qw
i
150
WHEELCHAIRS
-1
EYE LEVEL
1065
54 International Conference of Building Officals
Zt
C
..
E
C
U
AC
ALL,OWA,NCESI
60 Inches (1 525mm)
turning space
r) i %, . !,
NOTE:
Dashed
lines indicate mini murn
length of clear space required on each arm of the
-shaped space
ire OrCler to CofnPl4ete the
tum.
0
40
M3
56 International Conference of Building Officals
60 min
1525
{u} 60-xn (1525 -mm), Diameter Space
T-shaped space
for 180° turns
N
tn
qp�
32 min i
36 min
915
Minimum clear
width for two
wheelchairs
Minimum clear width
for single wheelchair
ANSI 4.2.x , .2
International Conference of Building Officials 57
-
r
1
+. ,y --• .. _ br _. • _. w .-a`-'�aiarYsy-■ - � f- ,Ta ter, � ", _ r ,�..,. s � �•»>ay Y ` �. • ... �.
:
SPACE ALLOWANCES
woo
fo e
br
4900
b
T*moi a} '■ itai a raa= b. .4r
� � i}bi�Y ■ .}r .f.
■{ � o f f es!! r r b'
# ff � if i b aaaa f+.i • +
.-
f as +}
�*moi
s i i
b +' • J !'
i ■ si
+ T 4P • .ate+�ia
F
CO� "til { �+•
+F i dF
. b..b..■b
■ 1 a
. ;ice# }, ■•f;i
■ !1 !' r
# i +
sem+
0
■■■■s. T
i* T ■ # ! i f .■ ■'# it T f- i 6 !Y T' T dF i i• i.Y t } ■ �F i i
I ifs} +*##■�eF*i it �# f ##+ aria w���i�i a t ■ aft �*# f �4$ � t� yiit'a!,# �i�#`�lisf'e �,.
yy i • rt.i # ■■■.■ ■#tTf i'T#i�T�f+! al iR 'li��■#+ #��F ii.' ■■.
r 'i° t •s �1 f i i i i'F • ■ t ■ i i i ■, ,s ! f ■F �4 f # t i # ++ #' -i i ■■!
- f f i i• i+ # t f# i #i a i ■ _i_A ,i'_f i i• f f s
48
1220
ITEMS WITHIN
DASHED LINES ARE
WITHIN REACH
Z = X
OR GREATER
NOTE. x = Reach depth., v = Rcach height* z=
Clear knee space, z is the clear space below the <> s u n,
i
'hi h shall be at least as deep as the reach distance, X.
P
0
co
■eeeeeit �4-
ANSI 4.2.5
TABLE 4.2.5.2
60 International Conference of Building Officals
0
CLEAR FLOOR DR
GROUND SPACE
SHAD EXTEND A1C}
MORE THAN 25 in
(635 mm) UNDER
THE OBSTRUCTION
b a�
a f i 4 T
is+.faya+ar.*. arb
4. 9 -P
+ i +af yr
■ i ■ i � T
a e s � •_+_
- } .■- ■ * t ami r
. rt • . iaf
r a .r! i .ff,lar
a +ria{fib frb Y b ■ ■ b f S } ■ �Fa}`T '■i
i W i e i 4 i 7! 7q • Cr}i
,.ab ■a
a � +
•4 i . .
� f �
■ 4 T 'a
� ■• b i . f
� . t f +r ■
r b } + a f
.4 P b i r
r. ea}
r■ieeer ireeeeeP• fnee! +a■�e• �� � �� eeeeree■ �
�■■i
48
ANSI 4.2.5
TABLE 4.2.5.2
60 International Conference of Building Officals
0
CLEAR FLOOR DR
GROUND SPACE
SHAD EXTEND A1C}
MORE THAN 25 in
(635 mm) UNDER
THE OBSTRUCTION
b a�
a f i 4 T
SPACE ALLOWANCES
10 max
24
max
30
610
760
%V
:Xq
7 7
+
p q I I
+
M
1 4 a.
4ir 4 A
0*0 41
+.4 p
,p
0 A
+
IP III
+
+ . . .
I
-IF W -T
VIM40.4mv. on Mh # 0 q
_NT IF 4 D 4.4
w 4' 41 4p q, v
as 0 q I'
4h 41
Ill 0 *
10%
v IF a i#
i.
i 49
IL
YaY
a p 10 41
pI 2 A ib 41 4 - , 0
ANSI 4.2.6
internativn�l Conference of Building Officials 61
--Jj W
03 0
SEATING
AND
A
m
rn
CO
m cc
m
4
8
MINIMUM CL A ANCE
ANSI 4.31
62 International Conference of Building Officals
t
,_X �� _ .:- � ' -• ,� i+ ag +. fir,�,. .,,��' ; �.� a� � .,. ti;
_ p
_ i. 4 a �; 4..4i+�$,:+�d'3 $4.hrl
CA INETS AND MI RORS
0
38" (965m m) max
o bottom edge of mirror
ANSI 4.1 6.5
20mm) max
to usable shelf
International Conference of Building Officials 85
FACI I'Ty AC-CESSI 1LITY
0
42 min
1065
0 0 # # & * 0 A +fir i
41
� CLEAR
� FLOOR
� SPACE.,I h. 4-1 d
�� o
I �
e a
do
ko 'W
4J
�1* 0*�
's
1p
F ! 0 #
b l S�
► a�#�
Y
f 4w 1
M 46
0�
h0#�
41 -0 d5
46 415X
WA CLOSET
I
0
SECTION 3105(b)2., ANSI 4.17
86 International Conference of Building Off icals
I*
12 max
f3 0 -.- ,-4 n
FACILITY ACCESSIBILITY
X11
36 max
I I �.
%pw �
A -t>,A 0
12 min
305
455
Ln
t. 305
CO
j
f w
cof
455
s
Where r it ., extend grab bar on transfer .
ONE
TOILET PAPER
DISPENSER
WAT R CLOSETS
SECTION 3105(b) 2., ANSI 4,,17
International Conference of Building Officials 87
t. 305
f w
41 M
++
6 T
Ilk a t
is1
do
a�a �ti*a
T
F�
i � 4
a ■ � ��
i d1h #
A
#f+**
X0
A�
�0*
• a
dt #
9
a
#� +*
�# *�#
* 0 a
wf #� * ## doa .i i #a # # a 0 # #
*
46
# f�46
41
a
s
Where r it ., extend grab bar on transfer .
ONE
TOILET PAPER
DISPENSER
WAT R CLOSETS
SECTION 3105(b) 2., ANSI 4,,17
International Conference of Building Officials 87
g
AC1 ITY ACCESSIBILITY
J"WTV1
(b) End of Row
Ln
�
LO
It-
WALL-MOUNTED
t-
WALL-MOUNTED VV,C
(FLOOR -MOUNTED W
12 m a x
42 min 305
] 065
■ |
�
■��
1-7
ib
Ln
cn
F _-19
1065
of
T FACILITIESL
3 05.(b)2..,
ANSI 4zlbol
88, International Conference of Building O
. .faaa m •e�� ,flak �!sf.sL �.. r-��.��v,v���-�a��.�e
1
FACILITY ACCESSIBILITY
4 max
32 min
� MW Me* � ; .a wm .0'. .
ALTERNATE DOOR
LOCATION
42(1065)
LATCH APPROACH
ONLY, OTHER
APPROACHES 48
(1220) min
1 Y -,X i.{
LO
(WALL -MOUNTED W.C.)
FLOOR -MOUNTED W.C.)
TO.ILET FACILITIES
SECTION 3105(b)2., ANSI 4.18
International Conference of Building Officipals sq
URINALS
15"to 44"
380 to 1120mm
1 71-1 max
4K.�umfll - I
30" mJn
76Omm
Clear floor space to allow forward
approach.* 30" (760mm) x 4811 (1220mm)
ANSI 4m19
90 International Conference of Building Officals
17 min
.430 el)t
CLEAR
j FLOOR
I SPACE
a.
y
IL 1
i
i
L Mj
rMDWMIP 4ft� 1
19 marc
4$ min
1 220
LEG CLEARANCE
TOE CLEARANCE
FIXTURE DEPTH
OTE: Lashed ]-Inc. Indicares d imensj nable�ll'an�: �A t � � under nal under fixture r cj ,�t.t-, _
CLEARANCES
ANSI 4.20
Internatiomal Conference of Building Officials 01
Storage Shelves an,d Closet
SECTION 3105(d)
ANSI 4923
0
lnterna#zona! Conference of Building Officials 97
U*"t*j&-K
Accessi
ble emergency warning systems shall include
bosh audible,and visible signals.
For roo s anil-*'i,
similar spaces not intended for
sleep,ing, visible signaling appliances shall be located
in accordance with Table 4.26.3.2(a).
Maximum morn One light Two lights One light
size opposite walls per watt
ft. cd cd cct
fit] x 20 15 — --
30 x 30 30 15
4{} x 40 60 30 15
50x54 95 eU 3�
60 x 60 135 95 30
70 x 70 185 110 8D
80 x 80 -- 140 80
90x90 -- 180 95
100 x 104 — — 95
1 1O x 110 - -- 135
120 x 120 -- — 160
130 x 130 — — 185
For corr*idors 20 feet (6m} wide axi u visible
a 0 V
signaling appliances shall be locat�d in accordance
with Table 4,,26.3.2 fib} .
Corridor length Minimum number of 75 cd
(20 it. Maximum Width) visible appliances tequi
Width)red
ft.
90 1
X30 -130 2
X130 - 230 3
>230 - 330 4
!�IMa - 430 5
>430 - 530 6
ANSI � 6 s TABLES 4.2.6,,3.
s r b
98 International Conference of Building Officals
TABLE 16=0
HORI,ZONTAL FORCJ
FACTOR, Cp
2. Nonstructural Components
6. Anchorage for suspended ceilings and 1i9htfiixtures
2-38
NEW FOOTNOTE 11 - Light fixtures installed in suspended
ceiling systems must be'independently supported from
structure ab, ove
•
U.B.C. Standard 25-2
Part III -Lateral Des'lgn Requirements
• Requires
IF fixture support for {fight fl*xtures
KNOWN EARTHQUAKE HAZARD,;
,v Structure above
i
W41
Of
filing
im
w,.
•ffa'i i i• 'del T �; -`-Fo _
�, . . - • •, -, : - '� �
•t'SLY'"S"'TEMS'�,:�Woov*-ODmFRAiMED'.
SYSTEM DESCRIPTION
GA FILE NOS' FG -5406
: I WOOD JOISTS, GYPSUM WALLBOARD
24" D.C. with 11/4" Type S drywall screws 24" c.c. F7C& layer 5/s" type ?C gypsum
wallboard or veneer base applied at right ang�es to joists through base layer with IN
Type S drywall screws 12" ox. at joints and intermediate fasts. Face layer faints offset
24" from base sayer joints, 11/2 11 Type G drywall screws played 2" hack on either side
of face layer end joints, 12" o.c. 112" plywood with exterior glue applied at right angles
to tap of joists with 8d naiis, CeiIing prov i des arse hoer #ire resistance protection for
wavcf framing.
GA FILE NO.- FC 5410
WOOD JOISTS, GYPSUM WALLBOARD
112" type X gypsum wallboard or veneer base applied at right angles to 2 x 10 wood
joists 16 " c.c. with 5d nails 15/j3" long., 0.099" shark, 1/4" heads, " o.c. supporting I"
nominal T & G wood sub and finish floor, or 1 q` plywood finished floorwith song edges
T & G and 15/32" interior plywood with exterior glue subfloor perpendicular to joists with
joints staggered. Nails l . d /4" from board, edge joints and 1/2" from board end joints,
GA FILE NO.'FC-5415.
PROPRIETARY*, -
WOOD JOISTS, GYPSUM WALLBOARD
/"# p rap ri t type Xgypsumwallboard r r basapplied t right angles to
r iBent furringchannels with I" Typedrywall screws 12" o.c. Wallboard end joints
located midway between continuous channels and attached to additsn I pieces of
charnel long with screws 8PIof . Resilient channels 1 ri .cF attached with 6d coated
nails 17/811 tops0.092 'F shank, 1/4" head to 2 x 10 wood IR F t 4" o,c. u orfsn 34'
nominal interior plywood with exterior glue T & G subfloor perpendicular to joists with
joints staggered. Underside of T & G joints covered between joist spaces with 61fx 221/21P
5/:B"' gypsum wallboard bitterns attached to flooring writh 16 gage, x I Va " segs x vz
crown staples spaced 71F o.c. along each edge.
PROPRIETARY GYPSUM BOARDS
The Blot Corporation - /8" Fl -SOK PL USTM
Donitar Gypsurn - -5/8" prod:R) Fireguard@
Georgia-Pacific - 5/81F Fir t p ', Type XXX
James HaTdie Gypsum - 51,,Pr H rdiro CR) Fire X, Type III
Pabco Gypsurn/8" FLAME CURBS Super 'C'
Temple -1 ni nd Forest Products - B" FIRE -RATED "T
Corporation
United States Gypsums Company _ 5/8,, SHEFTROCK101 Brand ui-n
Panels, FIRECODECRI C Core
68 *Contact the manufacturer for more detailed
information on proprietary products
SKETCH AND DESIGN DATA
HOUR o
r y 35"t",:;39 S..1
Approx. Ceiling Weight. 5 psf
Fire Test: FM FC 172t --7
Sound Test; Estimated
A-.'H0UR'.` ' 3 5#0 39 STG.<
Approx. Ceiling Weight: 2 p f
Fire Test: UL R1319-667 11-9-64P
Design L512
L R3501 -45a - - ,
Design L522
L R2717-387 6-10-65
Design L503
UL R3543-6 11 - 10-65
Design L519
ULC Design
Sound Testi NGC 402 4) 7-13-66
11
-1 -
li Testi- P) NGC 5037 7-19-66
i HOUR 35'to'*-,39*STC
Approx. Ceiling Weight: 21/2 pof
Fire Test: UL R -2� 5-25-73p
Design L51
Sound Test: Estimated
4.v7.3 Width. The minimum width of a curb ramp
shail be 36 in (915 mrn), exclusive of fared sides
4,7.4 Surface. Surfaces of curb ramps shall comply
with 4.5.
4.7.5 Sides of Curb Ram If a curb ram '
located where pedestrians must walk across the ramp,
or u,1here it '
is not protected �f r -
ral , then it shall have flared sides; the maximurn
slope of the flare shall b ]:10 i 12(a)). Curb
ramps Mth returned ctirbs may be us,,ed weirpedes-
trians r not normailly walk across the ram see
Fig. 12(b)).
4.7.6 B uilt-up Curb Ramps* BLii'pt-up curb ramps
shall be located so that they coo not project into
vehicular tr lanes (see Fig. 13),
Fig. 13
Built -Up Curb Ramp
4.7..7 Warning Textures. (Removed and resenject).
4.7.8 Obstnictions,Curb ramps shall be Iocated
rtecte-d to prevent their obstruction by parked
arils,
4.7.9 Location at Marked Crossings. Curb ram
ps
at marked crossings shall be wholly contained within
the markings, excluding any flared sides (see Fig. 1 ,
4.7* 10 Magonal Curb Ram if diagonal r
cor-
ner type) curb ramps have returned curbs or other
well-defined edges,, such edges shall be parallel to the
direction of pedestrian flow* The bottom diagonal
curb ramps shall have 48 in (1 220 mm) minirnum
larn Fig. 1 and . If is l
curb ramps are provided at marked crossings, the 48
in (1220 clear, space shad be within the markings
(see F'jg. 15(c) and (d)). If diagonal curb ramps have
flared sides, they -shall also have at least a 24 in 1
mm) long segment of straight curb located on each
side of the curb ramp and within the marked crossing
stile Hig. 15(c)).
.* 1 1 Islands Any raised islands in crossings s.
�iali
be cut through level with the street or have curb ramps
at bate sides and a level area at least 48 In (1 220 m
m)
long in the part of the island 'intersected by the
crossings (see Fig- 15(a) and .
Page 88 a App, E
D
Appendix IV
4•7. 1 2 Uncurbed intersections. (Rernoved and
reserved) -
11
.. 1 * General. Any part of an accessible route
a sloPe greater than 1:20 shall be considered a ram
and shall comply Mth 4.8.
4.8.2* Slope and 1. The least possible slope
shall be usedfor any ramp. The au slope of a
ramp in new construction shall be ] :1 . The maximum
rise for any run shall L>e 30 i mm) Fig; 16).
Curb ramps and ramps to be constructed on e-Asting
sites or *in em*sdng buildings or facilities may have
slopes and n'ses as shown in Table 2 if space
limitations prohibit the use of a 1 *-- 12 slope,r less (see
* 1 &6)q
4.8.3Clear Widft The minimum clear Width of a
ramp shall be 36 in 1 mm).
4.8.4 Landings Ramps shall have level landings at
the bottom and top of each run. Landings shall have
the folloMng features;
(1) The landing shall be at least as wide as the ram
run leading to rt
(2) The landing length sail be a minimum of 601n
(1525 clear{
(3) If ramps change direr n at landings, t .
minimum landing size shall be 60 in 1525
mm by 1 525 m,
(4) If a doorway 's located at a landing, then the area
in front of to doorway shall comply with 4.13.6.
4,98.5* Handrails. if a ramp run has a rise greater
than 6 In (250 rnm) or a hon"zontal projecdon greater
than 72 in (1830 mm), then.it shall have handrails on
both sides. Handrails are not required on curb riamps.
Handrails shall comply with 4.26 and shall have the
following features:
(1) Handrails shall be provided along both sides of
ramp Segment The inside handrail on smtchbackr
dogleg ramps shall alWaYS Lbe continuous,
(2) If handirails'are not contn, they shall extend
at least 12 in (305 the top and bottom of
the ramp segment and sha 1 i parallel with the floor
or eround surface.
(3) The clear space between the handrail and the
wolf shall be 1-1/2 in (38 mm).
(4) Gripping in surfaces shall be continuous~
{5} Tap of handrailgrinPirtg surfaces sha!l be
mounted hetuaeert 30 in and 34 in (76C] rrzm and $65
mm) wave ratnp surfaces.
(6) Ends of handrails sh,�11 be either rounded or
retLxmeCl srnoQ#h1y [o floor, walk or post.
August 1990
(7) Handrails sitald not rotate within ih.eir fittings.
ADA Compliance Guide
10
0
Appendix IV
Y.
I�
a�
r..
4.9 Stairs
� h
u r fii co of Ramp
j Narizontai Projection or RuFz --- -
? , .imu m R15C MaxiniLm Horizontal ejection
slope in Inn f? rn
16-12 to < 1:16 30 760 30 9
Fig. 16
Camponents of a Single Ramp Run and Sample Ramp Dimensions
4.5,6 Crass Slope and Surfaces. The cross
slope of ramp surfaces shall be no greater than 1:50.
Ramp surfaces shall comply with 4.5.
4.8.7Edgy.ProtectiomRamps and landings wig
drop-offs shall have curbs, woes, railings, or praying
surfaces that prevent people ftom slippingoff the
ra _ Curbs shall be a minimum of 2 in (50 rnm)
high (see Fig. 17)*1
4,,8,8 Outdoor Conditions. Outdoor ramps and
their approaches shall be designed so that water wi11
not accumulate on waling surfaces.
4.,9 Stairs.
4.9.1 Minimum Number* Stairs r u to be
accessible'. shall couply with 4.9.
4,9.2 Treads and Risers On any elven flight of
stairs, all steps shall have uniform riser heights and
uniform Lead widths. Stair treads shall bo no less than
I I in (280 rnr wide, measured from riser to riser
(see Fig. 18(a)). Open risers are not permitted on
accessLble routes.,
4,9,3 N r _ ]Ti rsides of nosings shall not
e abriipt The radius of curvature at the leading edgia
f Lhe tread shall be no greater than 1 in (13 mrn).
Risers r shall he sloped or the underSiLde of the nosing
s,hall have an angle not less than 60 degr-=--es from the
horizontal. Nosings shall project no more than -1 in
'38 mm) (see Fig. 18)-
4.9.4-
4.9.4 Handrails* Stairways shall have handrails at
both sides of all stairs. Handrails shall compty with
4.26 and shall hithe folloWing features*
(1) Handrails shall be continuous slang both.51des of
stairs. The inside handrail on s)xitchback or doqleg
k stairs shall always be conflnuoussee Fig. t and
(b)).
(2) if handrails are not coma mous+ they shall extend
t least 12 in 305 beyond the top riser and. a t
least 12 in (305 mm) plus the of one traad
mond the bottom riser* At the top' the extension shall
be ,parallel tb the floor or ground surface. At the bot-
tom, the handrail shall continue to slope for a distance
f th of one tread from the bottom riser; the
remainder f the pension shall be b rr ont l see Fag.
1 and , Handrail pensions shall comply With,
*.
(3) The lcrar space between handraiis and wail shall
be 1-1/2 ire ,
(4) Gripping surfaces shall be uninterr-uptedb
newel posts, other trine l em.eats, or
t
(5) Top of handrail gipping swface shall be m -
led between 30 in and 3 in (760 mm and 665 nvn)
aboue stagy ..
(6) Ends of handradsshall be either rounded or
rump' smoothly to floor, Lvar post
(7) Handrails shall not rotate wiLhin their flttings.
4.9.5 Tactile Wamings at Stairs. (Removed
and Test.
4.9.6 Outdoor Conditions, Outdoor stairs and their
approaches shall be designed so that water Wil not
accumulate. on waWng surfaces.
Fuge 90 • Appy IV August 1990 ADA Cornpliance Guide
•
f' d
a:a
R'�i' if.7�'..
�M
e e
- 1, ..,•
,� - - 1. •'� - •,
P
a,
�: , ,
n i x IV
UFAS
e
L.
{ t
rt
1
ir. Y
_
SII-,
F
4•s
4v9 Sta*
Irs
+{
e {
1 ie
T
avMJon
I r3 ��-
wall
J
�� guard [al[
railing with extender! .
plai7om FIgo 17
txampIcs of Edge Protecdon an
(a)
Mush Ftiser
36mja
1 '}
it J Pia e. + r j.Odom 0400
+ �..y} � •� {'kl. •� � -
0?
0--- -P
IAO ® _ AiL o -
r,
2 m
305
36
m jn'
y '
• 2 L I e
- � .p a Ir r• - a a _ i + •� i. I e c a ",
i 1 p
' h . °.� , ..'r � Lr L •�� a :. e 1
.+�,. � F- d � } �i��l� �'7 �' i cif°�* 'a� I •� _
!
Handel ExtenslOns
7' '�J- j L 9 11
• a T ' . r..Y �., P{ ew.A I e
Usable Tread Width
Ton F'Ujjh'nGroup, Inc.
August 1990
J
' P J
App, IV Page 91
Z�
,� - - 1. •'� - •,
P
a,
�: , ,
UFAS
e
L.
' •
1
ir. Y
_
SII-,
1 ie
,.i r rA A
- ,w e':
y '.a ti•. ,. e a eiY •y�-Y:: er-
��.
y
,zr ,- ,. ,, �+a
- 'T' Pre`I '�• ale IF��',�1 �y .+-� �I,:Is.
Y ,
C
M.. :_I
f e6
1+
avMJon
I r3 ��-
wall
J
�� guard [al[
railing with extender! .
plai7om FIgo 17
txampIcs of Edge Protecdon an
(a)
Mush Ftiser
36mja
1 '}
it J Pia e. + r j.Odom 0400
+ �..y} � •� {'kl. •� � -
0?
0--- -P
IAO ® _ AiL o -
r,
2 m
305
36
m jn'
y '
• 2 L I e
- � .p a Ir r• - a a _ i + •� i. I e c a ",
i 1 p
' h . °.� , ..'r � Lr L •�� a :. e 1
.+�,. � F- d � } �i��l� �'7 �' i cif°�* 'a� I •� _
!
Handel ExtenslOns
7' '�J- j L 9 11
• a T ' . r..Y �., P{ ew.A I e
Usable Tread Width
Ton F'Ujjh'nGroup, Inc.
August 1990
J
' P J
App, IV Page 91
Z�
vs
Extension at(C)
Bottom of ,Run
lY[7TE
.K Is the 12 [n MLrilmurn handraIi ,e;tens[art requlted
al each top riser,
Y is faze mfiamurrt hanciraI1 extensionof 12 in plus Me
width of one triad that Is rlequlred at each bottom rfser
Page 92 1 App. 1
Fig. 19
Stair Handraffis
Augustiggo
Appendix IV
4.9 Stairs
Elevation Of (b)
Center Handrail
IL#
(d)
Extension at Torr of Run
ADA Clina Cie
HANDRAILS
Mwn
• Handrails shall beprc�videds on both 'Ides of stairs
and ramps: a=l`li e) r e req 16166- a, �'�..�Lfl
EXCEPTION. Aisle stairsand aisle ramps
provided with a handrail either at
the side or within the aisle width, �_
• fullHand-rails shall be continuous within the length
of each stair fli tgh and ramp run., �'`` �' ` �`' `'°"'{"""' � 4 L
41
r
EXCEPTION: Handrails in aisles serving seating
• In�i-sde handrails on switchbackordogleg stairs or
ramps shall ,be continuous between flights or runs, �.
EXCEPTION: Handrails inn aisles serving seating r
�.._.LWL
le Gripping surfaces shall be continuous, without
interrupt"
ion icy newel posts, other construction
elements, or obstructions. �,.
ti
• Handrails and any surfaces adjacent shall be free �-
of sharp o'c'abrasive elements. Edges shall have
im
1 /8 inch miniradius.
L
•
hiandrails shall not rotate within their fittings. � -•
ANSI 4.3.10
70 International Conference of Building Officals
� S Aji
ACCEPTABLE HANDRAIL
[Section 3306(i)]
-1 - -f I n rp
NOTE:
QTHEF1 SHAPP-q neev o
DETAIL.
IF THEY PROVIDE AN 0C ACCEPTABLE
EQUIVALENT GRIPPING SERVICE.
SEE THIRD PARAGRAPH OF
SECTION,3,30(3(i)
0
�-- HANDRAIL
1 1/2"Minimum
2" maximum, or
equivalent gripping
sUrface
NOT
ACCEPTABLE
NOTE: 1-1/4" min handrail does
not meet UBC 3306(1).
x
0
34" to 38"
865mm to 965mm
1-112#0 2'.
32 mm to M� "
Handrails with other shapes sha
provided perimeter dimension of 14
be per *itted
inches ini um
(10( m) and 6'/4 inchesk4i 60 M) maximum.
cross section dimension is 2'/4 inches
maximum.
-T 2- b I -fl- �2, &5- U
r_r � T • I� �R�� 4L
International Conference of Building Offlc*fibls 71
t
Ir
JA Accessibility Guidelines
(a)
Handrail
Appendix 1V
4.26 11 draiU,, G=b BArs, 4 Tub md ..
er S,atA
(b)
Hxindrat'!
(C) (e)
Handrail Garb fear
Fid, 39
Saxe and Spacing of Handralls and Crab Bars
4'2 $' 4 E -- I nating HaxZardS. ,A handrall or
grafi bar and any wad or other surface adjacent
to It shad bc frce of any sharp or ahrastve ele-
ments. Edges shall have, a Minimum radius of
1/8 In (3.2 mm).
Page 228 * Appy I
NW. -I
Controls and Operating
Mechanisms,
.2 7. Gene , . Controls and operating
mechaaiisms requfred tv be accessible by 4.1
shall rompty with 4.27.
August 1991
ADA Compliance Guide
12 min
12 min
- to 4r+wRl.•+. ai*ai•i d.#
m. .i. L -7m F rb ii+iriF-1
- .. #.. r. s...x..:..ia. x•..t-+,lksrii 4i#a
•..... i i i .+ l i d ...
r-.-ix-at•yi,i tlik iarr}arft aW �i �f i+4 4 1-1 4. T F +i...i.iiiFrr+T Fi•.i+i•r r�i+• #*teTta•r+a+i.+T
.ra1. •+
bi*F+i #aPb . .dr ri*•+d t
._a .+. *--
...........
•
12, min
mi
C
+di, h.....
• +
a. r. i..
•! t F. r r i.. k 7 i i■ i i T� 4# F d a r y.
byiFi i#...a�..{}Fi.Rf+•biilF .f.
F...T F7 7 dd. i Lij{+T
F••. b F F i i i. i T 7 4 T T 4 i*** f 7 b
rii-ti*.T+T ■iii9.i.i0TFb.i .}a a
� M
+{ i r+
i+t.. a.. ■}bbii.a arTki-:aiTa'#T•?++x+-
i q, F w r F 0 F F d.
Fi++x. +f til ...yi a.+!•+rt+i.. r}++
*iix.*x... F+Fri. .r..++i x lit x.a+a•.*{{#ii,
� bir F .. T i i i+ i i e•i y F+ i b i. r. a.
■iii+i... - •T4�biYYr•.a
• i i w ■i rib + t+ r l. . e a{ y a{ f i d -d
}a.. a;ax a.. +FaIbFt11*ir
T+++irsix. R T!{b F.. iaT6'bisfi. ri*........
+TT•'i{F+...+T•F Fi*+#r..Fiil ,I i*. W. Ty +f.
r•+a! •a ■ o. 4. i=a.•.F f•i^! F+x*. + .. ml
bpi++r . yad.#+i #...
{ i t* r . aA +,
-
+x TT r•e r..fiTw ■+.i . +d
Simi 'TT.f+titids #+ii
T. f 6+ ... #+ i r i* i s ra • T T id d b. -. i x -i
•+ i r .+ i t r.� : i r rT i' R# x d i a i. rib . �
T r.
4.
T d k l &1.- •# v i i i- e 4 T T T k i b+
d, •{# + l i i. a F{ i b. - 1 T T i 0 +i i f k i.
y r T 4 h 1h. d. 1h s.{F+bir .h..Tf+Ft F-
.saaa+:x•.. elT•F+#i.....f•4.i*F... . .
_rF4
abir #i.. ib F+.i.. —4 a{alai a;}.a.a f#.i..
■c4T TT i.i*.{TTFr. ..#+ .ilii ra. lT�f T+. .•d
r a 1pa!•TFF l...af 7d.#r.abi+i Fi.•.. a,sa +{T.
+rf.e Ra�lFi.+.bef 4Fi. a.i a. t•#FT+4dF.FalaT .+t
(a Elevation
sTbarb i r.T'Fi�# F+i.YT T F+i.s.a . a#i' Fi+•x .. T
■ i tt i F*T.f Fi'. .. afY ri a. ...++##
.kW** &&
kW**ik r,
!�
•#••ap dx aab Fir ii.. f•T -•Fix .`ia.
axy ri
]4
1 � 1
12 min
:10
.
rdPibitb+Tlw T; a. t:y.�-er.�i#•rtT F.+Tb a•riit;rri'f+++�
b F a! F+ r+ 1. 4 T a T# c r i i i i■ i i T i T b T .} _. T a s e .. a° . T• a. a .. . x.
. Taa..T..ar i•WT bi ti{ia Ta.. sy. T...a T.a.
!++lr lTt'F•Tta+ xi.i rii+r {.ay+,a.y .ay.ba T•e a.TTtR
iid.ritii•litlribriiTla ay �...axaa.r.a:iii+•i Fii#ib ri Tii NO,
Fi+rh 044-0
iai•l+i*+i F++:f r;lRb..=aa�i. a. rd .�....l *#T!!IF#i FRiiand ii#iFii!
a.. . ....• . +-arra.- -=a..a=..-a.a.='a.
. af. ....iiri.i..d}i�+l}+•.aa..larahtivid@ltYlif4itirill•rt•aF}ar
b b-6 -h-i i-.- .. i h. x e{ i+. %.q 9-N. y .... a.
i F•1+i}{T.:..}a. ..a. w...W* .-ft{{yif T{f*+i7Y4il+i'i{i
a Ta -a. a. a. .}a.a a.'aiT-,.+i��x•i i�x•s xt+f*+
.Y+.x•x-ia•x i4ri.rf isi9�{aa}..+.ir.aa.xr.i ax!rit.s#iiii.•. it ri.
d d.d i .# i i i fb i r + i i •k i l } d r + T e 4 T = T ! .. + . • .'. • .. • a ... + . ar . • '• a • r y'
+F{e•F{+++.F.aaa.aa. ..ii.+.®. t..r#i*i.. i+b.}*6+++d+
rt#�i+ii+-++a•{+.a ri.•{ar. xixr
ii*i*tir444TbT b.RTa•+•"a +'a.•'ir .rx**x•t+i i... a r r s a tib s.•.
(a. Elena tion
jFA a n
+ + i
* M
a fa
d # i
T b i F k e i d. i.
rir.*r.dF.a.�
i•+•i it
:y
.ter ...y+arF
...........
t
�l+lair. -.Karr -
d
*. rrl. bf+f+bi bi ktiai. al trT i.rir. aff}.
•{i4.�.ss•.i.•r•b+9•-FiY4ir rr ... T+,•.i+daiii+.a Y..•
iii+i!{IFT b•k4litFF.T=ab+!■lli�ili ri..#r*•T#FTT•Tr F+
a) Eleva ti rz
• • •blx x.i.T ••T T•.}T■!•ii lirFr r.. l+Tb F+lii
b y y b T 7 h i F i 4• r� 9+� 4�T li F i =! ■ r*+ i+ b h+ br i+. i
hlr. +af Ti T+bxtk.. ....f f ifi'rt....T•
• e# f Fl itx r ray- ... f _. a+,
Plan
ANSI w3x! 1
72 International Conference of Building Officals
I I
12 min
ixdr*
• i { i .
i b++i... FTi'i Tr .
A i Y•... l+f.+-`Farr r.
T=+. r i y F
Yf ix-F*+*+,hr...a -.'•lLbk'W'.T .x bTT■F!•
a' b�F•b rilFbt••+•fi•*!T•■ltr r4.r rTTr
t d. 4'$ lib b+r dbid6ii** b p1mp*+b r■ lFrrdbr+•MpT+ii+k i.i..r.
a) Elevation
*. a,•+# -1 b i —d- T 4 R r T s 1 revs m b b* T r soon r$ i i f d q} r
66 i b r r z# i -4 ■ 1 SO r i#+. a l d .. r .... p. +#
i d i. i .. i.•'a T r T b}. r* i r r i &.--. 4= a=+{ R f i k d- #.
FaT+ab+bk FFiT`k..a*+.b li h++i Fi#. ra.f.. d. .i :r.
a • + r • r d .. i i .. + �i # k + # + x + d . i ..... a ... �. a a a
) Plan
12 min
305
T
shall
13oor closers
0
pos,
IM 0 a a z M
open position of 12 W1.11 be five seconds mini u
For other than fire doors the
required force for gusg v��en
o�u�.�.�g vpe� sha�1 fie:
r
1. Inten'or hi-ncrbed, door:
5--0 pounds, maximum
2. Sliding/folding doer:
5.0 pounds, maximum
Handles,, pulls, latches,, locks and
after operable parts shall have a
shape ea.�y to grasp with one hand
and does not require fight grasping,
tight pinching or twisting of wrist*
thresholds, ff proviLded, shall
be 3/2 inch (13mm) high maximum.
Exten"or residential sliding
doors shall be 3/4 arch (19mm)
high maximum.
Bottom 12 inches (305mm) of all
doors EXCEPT automatic doors,
power -assisted doors and sliding
doors shall have a smooth
uninterrupted surface.
ANSI4.13.10, .11,
46 International Conference of Building Officals
411
0
� 1
+ www.
SPACE A LO AN Q
W CENNO
f
# i
i •* t
F . . t ■ F
T F
t t .i . Stu. •■ �• .w}`
�� • f T f a F Y '� 9 F#
f �
.ice+t F •+N _
a ■ .■. .mow
+y
i ■ a ra
s �y
i
# 4 _
Cx * + +
c • / ■a#
# i
��+�,. "i �`�■ ..................... 4 i` ti■#iia •a*w:�■,** *iai+e*r �i.�'*iiia � a wF�a ���t; ■ t } � # i'•
'�'- '■,'■ �2f �i!`�t � �� #■� � � s~a �*e at4�+fay �4 � � i■� �'!�!■'� #'�fii+ }Ti *;+'E
i� i f i ► b i ■ t+ ` s*i i tib*■'�}iiia+`fes f
510-635
X = 0-20
ITEMS WITHIN
DASHED LINES ARE
WITHIN REACH
OR EATER
NOTE: x - Reach depth, y = Reach height-,.,
Clear knee space, z is the clear space below the
which shall be at lemst as deep as the each disks, X.
ANSI 4.2.5
TABLE
60 International Conference of Suildj*ng Officals
CLEAR FLOOR OR
GROUND SPACE
SHALL EXTEND NO
MORE THAN 25 in
(635 rrtm) UNDER
THE OBSTRUCTION
�YJY�
4�4
S
Jk�r
V4.
Em
F #
,t• } }
t + • +•w . T
•F
#
F # w w # + F }
+
�
•�
+ f w
wi
� T t
+iF
w #
■ F a
'�� �� �* �� � ■fes �� �� �4
�
48
CLEAR FLOOR OR
GROUND SPACE
SHALL EXTEND NO
MORE THAN 25 in
(635 rrtm) UNDER
THE OBSTRUCTION
�YJY�
4�4
S
Jk�r
V4.
Em
SPACE ALLOWANCE.S
10 max
asn", 4mk
0
o-�n
INK
International Conlerence of SuMing Officials 61
Appendix 1V
4*26 H dxalls,
.. #Tub and ShDwer
Seats
(a) Shelves
#*.24 ' Hzmdx&Us . GrabRaxs
d Shower Seats,,
0
rQ
ADA Access"ibil'ity Guidelines
Fig. 38 (b) Closers
Storage Sheives and Closets
*2 6. IL * G -en cral. AE h and ra grab bars-,
d tub and shower seats requtred to be acces-
sible by 4,11
c -
11 4.8., 4.90 4.16. 4.3 7.0 4.20 or 4.21
hall comply with 4,26.
4.26,2* Size and Spacing of Grab Bari
and HsndralIs. The diameter or width of the
grippes surfaces of a handrail or grab bar
shall be 1- 1/4 in to 1- 1 /2 in (32 mm to 38 m3n) .
or the shape shall provide an equivalent grip.
ping
surface. If handrails or grab bars are
mounted adjacent to a wall, the space between
the wall and the grab bar shall be 1- 1 f2 in
(38 rxirr}) (see Fig. 39(a). (b), (c). and (e)). Hand-
rails may be located In a recess if the recess is
a rna)dxnum of 3 in (75 mm) deep and extends
at least 18 in (455 mxxi) above the top of the rail
(seg Fig. 39{d)).
4.26.3 Structural Stre a The structural
strength of grab bars, tub and shower seats,
fasteners, and mountirV devices shall meet
the fallowing speciftcat#on:
(11 Bending stress [n a grab tsar or seat
induced by the maximum bending moment
from the appllcaUon of 250 1bf (i I I2N) shall
Thompson Publishing Gra-yap, Inc.
be less than the allowable stress for the
material of the grab baror seat.
(Z) Shear stress induced in a grab -bar.or
seat by the application of 250 Ibf (I 112N) shall
be less than the allowable shear stress for the
material of the grafi bar or Neat. If the con-
nection between the drab bar or seat and Its
mounting bracket or other support is consid-
ered to be fully restrad.ned, then direct and
torsional shear stresses shall be totaled for the
combined shear stress, which shall not exceed
the allowable shear sues$.
(3) Shear force induced in a fastener or
mounting device from the application of 250 lbf
(11 12N) shah be less than the allowable lateral
load of either the fastener or mounting device
or the supporting structure, whichever is the
smaller allowable load.
(4) Tensile, force induced in a fastener by a
direct tension force of 250 Ibf (1 i I2N) pias the
Max-imum moment from the application of
250 lbf (1 112N) shall be Less than the allowable
withdrawal load between the fastener and the
supporting structure.
(5) Gran bars shall not rotate within their
fittings.
August 1i
App. I * Page 227
0
:E
CO
JJ
%%&& !
E.
ry
4M
1
e
C
#*.24 ' Hzmdx&Us . GrabRaxs
d Shower Seats,,
0
rQ
ADA Access"ibil'ity Guidelines
Fig. 38 (b) Closers
Storage Sheives and Closets
*2 6. IL * G -en cral. AE h and ra grab bars-,
d tub and shower seats requtred to be acces-
sible by 4,11
c -
11 4.8., 4.90 4.16. 4.3 7.0 4.20 or 4.21
hall comply with 4,26.
4.26,2* Size and Spacing of Grab Bari
and HsndralIs. The diameter or width of the
grippes surfaces of a handrail or grab bar
shall be 1- 1/4 in to 1- 1 /2 in (32 mm to 38 m3n) .
or the shape shall provide an equivalent grip.
ping
surface. If handrails or grab bars are
mounted adjacent to a wall, the space between
the wall and the grab bar shall be 1- 1 f2 in
(38 rxirr}) (see Fig. 39(a). (b), (c). and (e)). Hand-
rails may be located In a recess if the recess is
a rna)dxnum of 3 in (75 mm) deep and extends
at least 18 in (455 mxxi) above the top of the rail
(seg Fig. 39{d)).
4.26.3 Structural Stre a The structural
strength of grab bars, tub and shower seats,
fasteners, and mountirV devices shall meet
the fallowing speciftcat#on:
(11 Bending stress [n a grab tsar or seat
induced by the maximum bending moment
from the appllcaUon of 250 1bf (i I I2N) shall
Thompson Publishing Gra-yap, Inc.
be less than the allowable stress for the
material of the grab baror seat.
(Z) Shear stress induced in a grab -bar.or
seat by the application of 250 Ibf (I 112N) shall
be less than the allowable shear stress for the
material of the grafi bar or Neat. If the con-
nection between the drab bar or seat and Its
mounting bracket or other support is consid-
ered to be fully restrad.ned, then direct and
torsional shear stresses shall be totaled for the
combined shear stress, which shall not exceed
the allowable shear sues$.
(3) Shear force induced in a fastener or
mounting device from the application of 250 lbf
(11 12N) shah be less than the allowable lateral
load of either the fastener or mounting device
or the supporting structure, whichever is the
smaller allowable load.
(4) Tensile, force induced in a fastener by a
direct tension force of 250 Ibf (1 i I2N) pias the
Max-imum moment from the application of
250 lbf (1 112N) shall be Less than the allowable
withdrawal load between the fastener and the
supporting structure.
(5) Gran bars shall not rotate within their
fittings.
August 1i
App. I * Page 227
Appendix IV
4.3 Accessible Route
255
(a)
Clear Fovr Space
30
760
Parallel Approach
NC
(b)
High and Low
(C)
Maxirnurrz Side Ruch over Obstruction
Fig. 6
Side Reach
4.2.6* Side Reach.. if the clear floor space allows
parallel approach by a person in a wheelchair, the
maximum high side reach allowed shall be 54 in
(1370 r.) and the low side reach shall be no less
than 9 i (230 above Lhe floor F* a and i
Side Reach UmIts
UFAS
Q
AJ �
ALJA ACcessibility Guidelines
4-o213 Detectable WanUngs.,,
4.�9.1 Geneml. Detectabio warnings redu[r-ed
by 4. .I and 4_7 shah comply with 4.2 9.
4.29.2* DetectabIe Wanaings vn Walking
Sur&ccs-t Detectable warnings shall consist
Of raused truncated domes with cx d(czrneter of
nomqzcV J. 9 art 12,3 nuN. a he%ht Of nominal
0.2 trz (5 mixt and a center- to- center spacvig of
nomiruxi 2.35 ire (60 rTtrrO and Shad caritrast
uisucxity with adjoining surfaces, either light -on -
dark, or dark-on-Iigltt.
7�te rrurterial used to provide coRCl-ast ShCc.tl be
an 'ittte-gx-aI ,ptxr-i v. f' the umikrng s ur_ fuce..De[ect-
Qb�e wc.�rnings users on interior surfaces shalt
d 'er.frorn aeJavxLr-g walking surfaces to res at-
tency or.saund-on-cane contact.
4.29.3 Detectable Wan:llngs on Doors
To Hazardous Areas. (Reservedjl
4.29.4 Detcctle WsLrnings at Stairs,,
(Re-seruedi.
4.29.5 Detectable Wamings at
us VehiculayAreas
!k}.
i � �{. wak
CMSSes or Rdjoins a vehicular way,, and the
walk'ng r17 -c
.rffirl9, or ether elernenLs
i '
nan Oas and vehicular
belween the ae boundary
tinuous .-rera!s shall be fined con-
�lPl M
bice 6 I
(915 ) l-cl , COMwith 4.29,2,
4.29-.6 Dete.abW
arnlngq at
ReflecUng pouts. The
P 0 0 1 S s n;--i'edges Of reflecting
-Drot-ectedslings., ] l l
OF rt-electabte wamiligs coniplying
with 4.2+2.
4.29,7 Stain ida t-.. (Re,-,serocd).
4.b3O Sigilage;
4.3 0, 1 e ral ig -1--cl e req I
access� (e .1 Shall comply l
,phr u�� . }
4.30.62* Character PraDortion, Letters and
numbeirs on signsall hivea wfdLh-to�hefght
ratio between 3:5 and 1: 1 and a strOke-width.
-*t ratio between 1:
age 230 * App. I
Appendix IV
4-v29 Detectable. Warnl,ngs
x.30.3 Charo[��Qr .�`�eigtt�. Characters cu -td
numbers on sirens s�taI[ be sized accard%rW t,0
tttc viewtrcg distQrueJrom which they are to
be react. The rnirlimccrn hefgh[ is measur-ed ustrlg
an uPper ccxse X. Lvu)er ease clzczracters. trre
p.er-mittect.,
Hel*ght eve Nimmum
Finished .door Character H
e�ght
'Suspended or Projected
OvCrhead In 3 in. (75 rnrW
mtntmurn
cOmP'Lance wfth 4.4.2
4.30.4* Raised and Brain ers
and Pctoriuz synboz si
axzs
(P'ietvgraxrLs). Leiters and nurnerais shad be
raised 1/32 in (0.8 nzm) minimum, Upper case.
sins sent' or strrrple sertJtype and shall be
aecornpanfed uJi[Pt Grade 2 Brasile, Raised
characters shall be at least 5/8 iii (16 mm)
high, but no higher than 2 in (50 mm). picto-
grams shall be ticcorrtpanied by the equivalent
verbal description p?aced d�recjlj below the
P tcio
�x��r.7Zrnension of the picto-
gram shat be fi to (252 mrro rnzn-
UrIUrrt in heigfit.
4.30,5* PinLsh and ContrcLst..'The chiarac-
ters and back -ground of s
gns shall be eggshell,
Matte. or Other non-glarefinish. Characters and
symbols shall contrast with their
either lighL characte-r!3 on a dark background
r d -ark cheziracters on a light background..
4.30 Mountie ton
and Hi#
�Wtcre- Permanent iderffijicatioll L; provUed ror
terns and.c',S *�
shall be fled on
%mr -
Lhewall ut he l t f
�
z there i f space , he door-.
doubleOJ the door,, tricludin to Lhe Icitch side
9 Ut leaf doors,
f - ill be placed oT2 the nearest
Lvc111. -"OUT-Iting height shall be 60 irl (1525 miro
aDOV e) tr ds ; r to the Ce111erT;17
. .
be sO thctt a nerson may czpp-oach udUhin 3 in
(76 rnrro o "
szarlctge Iviffin. lit
encountenng piro-
trudi-Tigre 1- sir ig witl i7 Z ttle SLv ing
of a oor.
*30.7* SY-Mbols Of Accessibility*
(1) il
idenIff..Les aTId efL>Ments
u'
led as accessibie by 4.1 S'hall use the
International b 1 Of accessibility.
February 1992
ADA COMPfianC6 Guide
Appendix IV
(a)
Proportions
International Symbol of Accessibility
Display Conditiolls
International Symbol of PAA,
&�
(C)
Internaflonal TDD Symbol
(d)
International Symbol of Access for Hearing Loss
Fig. 43
International js
Tho-r'npson Publishing Group, Inc.
ADA Access ibil ity Guidelines
symbol shall be dSsplayed as shown in
Fig. 43(c) and (b)lt
(2) Vokane COntrol Tel6phones.. Tetephorws
requil-ed tO have a L*I=e cOnftvl by 4J.3(17)jb)
ShaU be WRntffLed by a sign contaOlng a deptc-
t0n of a telephorte handset Lvith radfattig sound
xaves,
(3) Text Telephones. Text telephones utr-ed
bytdmty7ed by the
ttOOal TDD sYMbOl ft 43(c)). in axldoDrL a
facility has a public wxt tetephorle., dtreCttonal
-s4nage kufka"ng the kxatton ofthe nearest
text telephDne shall be placed adjacent to aR
bclnk'5 Of telePhonesr which do rwt contain a text
telephOne. Such directkrLal s,jg� shaU inc,
the 'r���tOnal TDD Sg�_ If afacUlty has
banks of teLePhones,, b4e directiOnal s9nage
Shafl be PrOvfiAld at the entrunce te,g., in a
buMing directory)d
(4) AssistiMUsten[nn S Y S t�.s. In cxssembty
areas w here PermanentlysIs ffn7l
Usten ing ys d assisave
tl-� arle required by 4.1,3091(b)
the amaczbilay of such systerns,shaU b, identi-
fied with stgu,�e that incLtd-es tt�e ftitemational
syn'h01 of accessfOr hear&W los-S ft 43(d)1MY
4*30.8* Illumination Leve Ls. (aeser'vecU.
4.31 Telephones,
4.31.1 Gener8l. Public telephones required
to be arcessiNe by 4. 1 shall comply with 4.3 1
4.3 1a2 Clear Floor or
dear d 8 floor or ground space, at least 30 in by
48 In (760 =n by 1220 mm) that allows
either a forward Or parallel approach by a
person using a wheelchair shall be P-Mvided
at telephones (See Fig, 44). The clear floor or
ground space shall COMPlY with. 4.2-A. Bass -.p
enclOsures., and fixed seats sh not Impede
approaches to telephones by People who use
wheelchairs.,
4.31.3* Mount'U9 ]Ele4ghta T11e highest
Operable Part Of the telephone shall be withtn
the reach ranges sPecifted in 4. 2.5 or 4.2.6.,
4.31.4 Protruding oibjects. 7%
h 0
shaU cOmplY with 4.4. tep , nel
August 1991
App- IV -P Page 231
MEDICI
k
rAE31
w
NETS AND MIRR.OR
ANSI 4.'16.5
International Conference of Building Officials 85
i.
ACILITY ACC SSI ILIP4,
i
� CL
� FLS
� SP
4� min
F
MEMO-RoMF i
1 525
455
WATE;;
n C 0 S TS
SECTION 3105
(b)2.., ANSI 4.17
86 International Conference.9uding p�icas
Aid
pis
I u
y
Qr- d -.a_.. 4:.4, wr'
FACILITY ACCESS'l ILITY
12 max
305
�4 min
Wheve SpaCe perMitS., extend arab bar on tran.sfer side.
'I-,'
TOILET PAPER
N
■
10 4b W
Lit
A.
OD
12
m't n
12 min
305r
'.305
mit..
I
*• *�
• i #
i
�i*
#i#00
!##si#
dp f i
M +�1h
�
+ i
i i i # # #i9�2
i * �
Rk 40
0
■
i
*#* #i#
!
i4�
t #
0i
IL
i
�X-*#
i#i
##�
12 max
305
�4 min
Wheve SpaCe perMitS., extend arab bar on tran.sfer side.
'I-,'
TOILET PAPER
DISPENSER
WAT R C OS TS
SECTION 3105(b)2., ANSI 4.17
International Conference of Building Officials 87
1\I
N
OD
DISPENSER
WAT R C OS TS
SECTION 3105(b)2., ANSI 4.17
International Conference of Building Officials 87
1\I
E
k
0
17 mit
430
I CLEAR
�4�d1
i # F e o
I FLOOR
I SPACE
t ;
�z A
0
LEG C
11 min
LEARANCE ..,.,.
w%W
.,
TOE
CLEARANCE
114. 7 min FIXTURE DEPTH
MMINOWI&WA
TE: Dashed ling indicate;i dis- nsi nal clearance t` opiional under fixture losure.
International Conference of Building Officials 91
s � ■
max
�z A
0
LEG C
11 min
LEARANCE ..,.,.
w%W
.,
TOE
CLEARANCE
114. 7 min FIXTURE DEPTH
MMINOWI&WA
TE: Dashed ling indicate;i dis- nsi nal clearance t` opiional under fixture losure.
International Conference of Building Officials 91
W
Appendix {V
A4.15 Drinking Fountains and Water Coolers
A4.15 Drinking Fountains and Water
Cool.er&
A4. 15,2 Drinking fountains with tz.,�o sporiLs can
assist both handicapped people and those people
who find it difficult to bend oder.
A4.16 Water Closets.
A4.16.3 Height Preferences for toilet sat heights
vary consideramong disable people- Higher seat
heights may be an advantage to some ambulatory
disabled maple but a disadvantage for wheelchair
W02C.141
UP
455
E1
Fakes transfer position, swings
footrest out of the gray* sets
brakes.
Removes a rm re4 transfers.
Takes transfer posit it o n, removes
armrest, brake&
Thompson Publishing roup, Inc.
UFAS
users and others. Toilet seats 18 i (455 high
serer t . be a reasonable compromise. Thick seats and
filler rings are available to adapt standard lures t
these requirements.
A4. 16.4 Grab Bars. Fig. A5(a) and (b) show the
diagonal and side approaches most cornmon� used to
transfer from a wheelchair to a water closet Some
wheelchair users can transfer from tr:e frost of the
toiled while others use a 90 -degree approach. Most
people who use the two additional approaches can
also use either the diagonal approach or the side
approach.
Moves wheelchair out of the
way, changes position some
people fold chair or pivot it
90" to the toiled.
(a)
Diagoilad Approach
Transfers.
(b)
Slde Approach
Fig. AS
Wheelchair Transfers
August 1990
P � r toiled releases
brae.
'setons on toilet
App. I * Page 127
ASA Accessibility Guidelines
6. 2 Ent,iCeC, At least one accessible
entrance that complies with 4.14 shall be
protected from the weather by canopy or
roof overhang. Such entrances snail Incorpo-
rate apassenger loading zone that complies
With 4.6.€7,
$.3 Patient Bectrooms, Pmvide accessible
patient bedrooms in compliance with 4.1
through 4.35. Accessible patient bedrooms
shah campy with the fallowing:
(1) Each bedroom shall have a dear that
complies with 4.13.,
EXCEFiiON: Entry doors to acute care hospi-
tal bedroorns for in -patients shall be exempted
cram the requirement in 4. I3.& for maneuver-
ing space at the latch side of the door if the
door is at least 44 in (1120 mm) wide.
(2) Each bedroom shall have adequate space
to provide a maneuverl.ng space that complies
with 4.2.3. In rooms with 2 beds, it is prefer-
able that this spare be located between beds.
(3) Each bedroom shall have adequate
space to provide a rrrintmum clear floor spare
of 36 in (915 mm) along each side of the bed
and to provide an accessible route complying
with 4.3.3 to each side of each bed.
6.4 Patient ToUet Roo 9,, Where toilet/
bath rooms are provided as a part of a patient
bedroom, each patient bedroom that is required
to be accessible shall have an accessible toilet/
bath room that complies with 4.22. or 4.23 and
shall be an an accessible mute.
f44A�*-Z-1-if-A ZVI. V I -it -0
7a, I. General,, In addition to the requirements
of 4.1 to 4.35, the design of all areas used for
business trazisactions with the public sha31
comply with ?.
Page 238 - App, IV
Appendix IV
7.2 Sales mad Service Coters,
Teller Windo Wfor-ic, an
Co ters .
(1) in department stores and miscellaneous
rets stares where counters have cash registers
and are provided for sales or distribution of
goods or services to the public, at feast one of
each type shah have a portion of the counter
which is at least 36 in (915 nun) in length with
a maxiinum height of 36 in (915 mm) above the
finish floor. It shall he on an accessible rout
complying with 4,3. The accessible counters
must be dispersed throughout the bufidi.ng or
facittty. In alterations where it is technfcalIy
infeasible to provide an accessible caunter, an
auxiliary counter meeting these requirements
may be provided.
(2) At ticketing counters, teller stations in
a hank, registration countess In hotels and
maiels, box office ticket counters, and other
counters that may not have a cash register
but at which goods or services are sold or
distributed, either;
L0 a portion of the mafn counter which
is a rrLnimum of 36 Ln (SIS mm) in length
shad be provided with a maximum height of
36 in (915 mm); or
(ii) an amciiiary counter with a maximum
height of 36 In (915 rnm) in close proximity to
the main counter shall be provided; or
viii.) equivalent facilitation shall, be pro-
vided e.g., at a hotel registration counter,
equivalent faclitation might consist of:
( l.) provision of a folding shelf attached to the
main counter on which an individual with
disabilities can write, and (2) use of the spare
on the side of the counter or at the concierge
disk, for handing rnateria3s bask and forth).
All accessible saes and service coun-
ters shall be on an accessible mute cvmpbYi-rig
with 4_3.
August 199, 1
(31* Assistive, Listening Dices. (Reserved)
ADA Compliance u ids,.
T�,SLW 16-U
2-38
HO€�IZ0�ITAL FORCE- FACTOR,Cp
2. Nonstructural Components
6. Anchorage for suspended ceilings and light fixtures
NEW FOOTNOTE 11 -Light fixtures installed in suspender
S�illll��iiiijlil)�Ill�IIIIIIIIIIIIIIIIII12k, 01111111111ceiling systems must be u
structure above
U.B.C.•
Part Ill-
Standard
25-2
Lateral Design Requirements
• Requires independent fixture support for light fixtures
• KNOWN EARTHQUAKE HAZARD!
Structure above
M
Suspended ce
fling
US C page 1-337 & 3-781i.o•
Adds UBC Standard 25-2 and deletes recog,nized
Standards ASTM C635 and C636.
U
•UBC Standard 25-2 is similar to UBC Standard No. 47-18
from the 198.8 code.
• Part 111 of the Standard contains provisions regarding
lateral restraint and independent wire support flight
fixtures which are unique to the UBC and not contained
in the recognized standards,