SECTION 01700 - PROJECT CLOSEOUT
General Definitions.:
The provisions of this 'section apply primarily to closeout of actual physical
work, not to administrative matters such as final payment and changeover of
It Specific requirements in other sect�,
ions have Precedence over
general requirements of this erection.
Procedures at substantial Completion*
Freres a ites: Comply with General Conditions and compl�.te the fallowing
before requesting Architect■s,/Engineer,'s inspeetian of the work. or
designated portion thereof, for substantial coxnpletivn0:
Submit executed warranties, workmanship bondsl maintenance agreements
inspect ion certificate, and similar required documentation far specific
units of work, enabling Owner's unrestricted occupancy and use ,
submit record dacumentat�i.on, maintenance manuals, tools, spare parts,
keys, and similar operational items,
Complete instructions of owner's operati
systems. ng personnel, and start-up of
Complete final cleaning, and remove temporary fac.111"ties and tools,
inspection Procedures: Upon receipt of Contractor ► s request,
Architect/ Engineer will wither proceed with inspection. or advise Contractor
of prerequisites not fulfilled. Following initial inspection,
Architect/ Eng ineer will either prepare Certificate of Substantial Complet-ion,
or advise Contractor of work which must be performed prior to issuance of
certificate; and repeat inspection when requested and assured that work has
been substantially completed. Results of completed inspection will farm
initial "Punch List!{ for final acceptance.
Procedures at Final Acceptance:
Rein�;ectian Procedures:Upon reeeiptaf Contracto�rs notice that work has
been completed, including punch list items resulting f rom earlier
inspections., and executing incomplete items delayed because of accep
table
circumstances, Architect/Engineer will reinspect word. Upon completion of
reinspection, Architect/Engineer will either recommend final acceptance and
final payment, or advise Contractor of work not completed or obligations not
fulfilled as required for final acceptance. If necessary, procedure will be
repeated.
Record Documentation.
SECTI9N QI?DO -" 1
4
Madison High School
Boiler Installation
Rexburg , Idaho
Record Drawin s: Maintain a complete set blue blackprints of contract
drawings and shop drawings for record during the course of the work to s
how
charges and actual installation conditions, sufficient to form a complete
record for Owner's purposes. Give particular attention to work which will be
congealed anddifficult to measure and record at a later dale, and work which
may require servicing or replacement duringI�fe of project. Require
entities marking prints to sign and date each mark-up.
Com ex S stems :
�.For this project with complex equipment and systems �
provide the following proDect finalization an start-up services.
Upon completinnc�f the equipment and systems installation and
connections, the Contractor shall assemble all E:qlllpmeiit and factory
representatives and subcontractors together for system start-up,
These people shall assist in start-Wup and check out their system and
remain at the site until the total system operations is acceptable and
understood by the Owner's representative. The factory representative
and system subcontractor shall also give instructions on operation and
maintenance of their equipment to the Owner's maintenance and/or
operation personnel. To prove acceptance of operatiQn and instruction
by the Owner's representative, the Contractor shall prepare a written
statement of acceptance, explaining lamer for h is signature. The
statement might read as f 011OWS:
"I , the Contractor , associated factory representatives and
subcontractors , have started each system and the total system, and
have proven their'nor'mal operation to the dwnerrs representative
and have instructed him in the operation and maintenance thereof
Owner's Representative
Signature
Date
This statement shall be
Oerator Instructions:
included
Con.tractor
Signature
Date
in the o & M Manuals .
Require each installer of systems requiring continued
operation/maintenance by Owner's operating personnel, to provide on -location
instruction to Owner°s personnelf11 # sufficient to ensure safe, secure
efficient, non -falling utilization and operation of systems. ,
SECTIC3N 01700 - 2
Madison High School
Boiler Installation
Rexburg , Idaho
Fina, Cleanin0
At closeout
Clasp il maintenance/ cleaning of
time, clean or reclean entire work for "first
building projects of a similar nature . Remove
non -permanent protect
ion and labels, dean exposed finishes, touch -uta minor
finish damage, clean or replace filters of mechanical systems, remove debris
and broom -clean non -occupied ,spaces, sweep and wash paved areas, police yards
and grounds, and perform similar cleanup operatian� needed to praduc� a
"clean" condition as judged. by Architect/ Engineer.
SECTION 01700 - 3
Madison High School
Bailer Installation
Rexburg , Idaho
SECTION 09250 - GYPSUM DRYWALL
PART 1 - GENERAL
RELATED DOCUMENTS0
Drawings and general provisions of, Contract, including General and
Su}aplementar�r Conditions and Divsion 1 Specification Sections ,
apply to work of this section.
SUMMARY:
Extent of each type of gypsum drywall construction. required is
indicated on Drawings
This SectIP ion includes the
constriction:
Gypsum board attached to
DEFINITIQNS:
following types
woad framing and
Gvpsum Beard Construction Terminolo
575 for definitions
otherwise defined in
UALITY ASSURANCE:
of terms for
this section
Of gypsum board
furring members.
0
Ref er to ASTM C 11 and GA
gypsum board construction not
or other referenced standards.
Fire -Resistance Ratingsy .Where indicated, provide materials and
constructions which are identical to those of assemblies whose fire
resistance rating his been determined per ASTM E 119 by a testing
and inspecting organization acceptable to authorhaving
1 les
Uri sd icti on 4
provide fire--resistance-rated assemblies, identical to those
indicated by reference to GA File Nos. in GA -6Q4 'IF re
Resistance Design Manua" or to design designations in U.L.
"Fire Resistance Directory" or in listing of other testing and
agencies acceptable to authorities having jur.�sdictivn.
5.ingle-Source des leach
related joint treatment materials from a
DELIVERY STORAGE, AND HANDLING:
type of gypsum board and.
single manufacturer.
Deliver materials in original packages, containers or bundles
bearing brand name and identification of manufacturer or supplier.
More materials inside under cover and deep them dry and protected
against damage from weather, direct sunlight, surface
contamination, corrasion, construction traffic and other causes.
Nealy stack gypsum boards flab to prevent sagging.
Handle qvnsum boards to prevent damage to edges, ends and surfaces.
GYPSUM DRYWALL SECTION 09250
- 1
Madison High School
Boiler Installation
Rexburg, Idaho
Do not bend or otherwise
PROJECT CflNDITIONS
damage metal corner beads and trim.
Environmental Conditions General: Establish and maintain
environmental conditions for application and finishing gypsum board
to comply with ASTM C Sia and with gypsum board manufacturer's
recommendations.
Minimum Room Temperatures: For nonadhesive attachment of gypsum
board to framing, maintain not less than 40°F (4°C) , For adhesive
attachment and finishing of gypsum board maintain not less than
SOOF (100C) for 48 hours prior to application and continuously
thereafter until drying iS complete,
Ventilate building spaces to remove water not required for drying
joint treatment materials. Avoid drifts during dry, hot weather to
prevent materials from drying too. rapidIy.
PART 2 - PRODUCTS
MANUFACTURERS
Available Manufactures: Subject to compliance with requirements,
manufacturers offering products which may be incorporated i n the
Work include, but are not limited to, the follow*i-ng:
Gypsum Boards and Related Products:
Georgia-Pacific Corp.
Gold Band wilding Products
United States Gypsum Co.
GYPS4 BOARD:
UI
Div., National Gypsum Co.
General: Provide gypsum board of hypes indicated in maximum
lengths available to minimize end-to-end joints,
Thickness: Provide gypsum board in thicknesses indicated, or
if not otherwise indicated, 5/8 inch thickness to comply with
ASTM C 840 for application system and support spacing
indicated.
Gypsum Wallboard.0
ASTM. C 36, and as, follows:
I -
Typed Types X for fire -resistance rated assemblies,
Ed es: Manufacturer's standard.
Thickness:
TRIM ACCESSORTE.S
Cornerbead and Ed
5/8.
Lm TrA for Inte for T t 1 1 t n 11
1.M— ao -...r 3 J& -W
Provide corner
GYPSUM DRYWALL SECTIQN 09250 - 2
Madison High School
Boiler Installation
Rexburg , Idaho
beads � edge tr�m and control � Dints which comply with ASTM C 1047
and requirements indicated below:
Material: Formed metal, cvmp�.ying with the follo��.nq
requirement:
Sheet steel zinc -coated by hot --dip process.
Edge trim shapes indicated below by reference to designations
of Fig. 1 in ASTM C 1047:
"LC" Bead, unless otherwise indicated.
Eck e trim complying with ASTM C 1047, formed from rolled zinc,
supe "LC" Bead per Fig, 1, unless otherwise indicated,.
GYPSUM BOARD JOLT TREATMENT MATERIALS16
General_:_ Provide materials complying with ASTM C 475, ASTM C 840F
and recommendations of manufacturer of bath gypsum board and joint
treatment materials f or the application indicated.
Joint Tawin:;.0 Paper reinforcing tape, unless otherwise indicated.
Setting--Ty_pe �7oint. Compounds Factvry-prepackaged, j vb--mixed,
chemical-hardening powder products formulated for Z.d.5e5 indicated,
For pref illincj0
gypsum board oints, use formulation
recommended by gypsum board manufacturer for this purpose.
Dryincx-Type products com
and intended
rM n_ F_ aI
Joint Com vunds : Factory --prepackaged vinyl --based
plying with the following requirements for formulation
use..
Factory-prernixed product.
All-purpose compound formulated for use as both taping and
topping campaund.
MISCELLANEOUS MATERIALS
General: Provide auxiliary materials far gypsum drywall
construction which comply with referenced standards and the
recommendations of the manufacturer of the gypsum board.
Gypsum. Board Screws: ASTM C 1002, Type W
PART 3 - EXECUTION
EXAMINATION:
Examine substrates to which drywall construction attaches or abuts
preset hollow metal frames, cash--in-anchors, and structural
framing, with Tnstaller presentI for compliance with requirements
SUMGYPDRYWALL SECTION 09250 - 3
Madison High School
Bailer Installation
Rexburg , Idaho
far installation tolerances and other
performance of drywall construction.
installation until satisfactory conditions
conditions affecting
Do not proceed with
have been corrected.
Gypsum Board Attachment Schedule. Gypsum board shall be
attached as per the following schedule:
Location
Single layer application
to walls
Single layer application
to ceiling
Double layer
to bottoms of
and ceilings
application
roof trusses
ADDlication /Attachment
Apply boards parallel or
perpendicular to framing,,
Stagger joints 2411 min.
each side of wall.
Attach with 1 1/211 tW
drywall screws at "l" c.c.
to all supports.
Apply boards
perpendicular to framing.
Stagger end joints one
half panel length in
adjacent rows. Attach
with 1 1/211 type W
drywall screws at 5" o.ce
to all supports.
Appy base layer
perpendicular to
framing
memers. Attach
with 1-
1/4" type S
drywall
screws at 24" a.c.
to all
supports. Apply face
layer perpendicular to
framing members.
Offset
prints 24' from base
layer joints.
Attach
with 1 7/811
type s
drywall screws at
9 '1 o. c.
to all supports,
-
and 1-
1/211
1I2" type G
drywall
screws placid 211
back on
either side of face layer
and
joints at 1211
o.c.
Note: Screw spacings specified in
fake precedence over screw spacirtgs
Gypsum Association assemblies.
APPLICATIaN AND FINISHING OF GYPSUM EiDARD, GENERAL:
Gypsum Board A ligation and Finishin Standard:
f inish gypsum board to comply with ASTM C 8
GYPSUM DRYWALL
this schedule
of ref ereneed
Install and
SECTIDN 09250 -- 4
madiSon High School-
11jailer Installaton
Rexburg , Idaho
Locate exposed end -butt Joints. as
ceilings
alternate
as possible, and
courses of boards
Install-ceilin
stagger
boards across
the number of end --butt joints
3MM
inches.
Instal wa111AartaLtion
of end -batt j,oints- or
far
from
center
of
walls
and
not
leis
than
24
inches
in
framing in the manner which minimizes
and which avoids end joints in the
niiAiiiiAu ■rel ���vi�n it 1nort 1�l
0
boards in manner which minimizes the number
avoids them entirely where possible. At
stairwells and similar high galls, install board horizontally with
end jaunts staggered over studs.
install exposed
sum
imperfect, damaged or
light contact at edges
space between boards..
board with face side out.
damp boards. Butt boards
and ends with not more than
Do. not force intim place.
Do not install
together f or a
1J 16 inch open
Locate either edge or end 'pints over supports except inn
horizontal applications or where intermediate supports or gypsum
board back --blocking is provided behind endjoi'nts. Position beards
so that line edges abut, tapered edges against tapered edges and
mill -cut or field -cut ends against mill --cut or field -cut tends. Do
not place tapered edges against mut edges or ends. Stagger
vertical joints over different studs on oppositesides of
part itions .
Attach,qypsum board to supplementary flaming and blocking. provided
for additional support at openings and cutout.
Spot grout hollow metal doter frames for solid care wood doors,
hollow metal doors and doors over 32 inches wide. Apply spot grout
at each jamb anchor clip just before inserting board into frame*
Form control 3oints and expansian joints at locations indicated,
with spaces between edges of boards., prepared to receive trim
accessories.
Tsolateperimeter, of
structural abutments,
with "U" bead edges tri -m,,
non -lead -bearing
drywall
partitions
at
Provide 1J4" to
1/211 spaces
and trite
edge
Seal joints with acoustical sealant.
METTIOnO OF GYPSUM nOARD APP�TCATTON-
single-Layer Application:_ Install gypsum wallboard as follows.
an ceilings apply gypsum board prior to wall /partition board
application to the greatest extent possible.
an partitions 1walls apply gypsum board vertica
framing}, unless otherwise indicated, and
lengths which will minimi c end join-ts.
11y (parallel to
provide sheet
GYPSUM DRYWALL SECTION 09250 5
Madison high School
Boiler Installation
Rexburg , Idaho
Double -Layer A
ligation: Install qvpsum backing board dor base
layer andgypsum wallboard for face layerd
on ceilings apply base lager prior to application of base
Layer on walls/partitions; apply face layers in same sequence.
Offset )oints between layers at least � 4 inches . Apply base
layers at right angles to supports unless otherwise indicated.
Sincfle-La
f 0 1 lows:
Fastening Methods : Apply gypsum boards to supports as
Fasten with screws., Fasten in accord with
File No. WP 3510 substituting Type W screws
with Gvnsum Board Attachment
Specification Section.
Gyspum Association
with nails, and in
Schedule
It this
Double -Layer
Fasten in
Methods :
Apply lase lager of gypsum board
and face
layer to base
layer as
follows:
Fasten both
base
layers
and
face
layers to
supports with
screws and
fasten
face
layer
to
base layer
with screws.
Fasten in accordance with Gypsum Association File No. GAS 5406,
substituting Type W screws for nails, and in accordance with
Gypsum Board Attachment Schedule in this Specifications
Section.
INSTALLATION OF DRYWALL TRIM ACCESSORIES:
General: Where feasible, use the same fasteners to anchor trim.
accessory flanges as required to fasten gypsum board to the
supports. otherwise, fasten f ranges to comply with manufacturer' s
recommendations.
Install corner beads
Install metal edge
otherwise
flange to
at external corners.
trim whenever edge
be ---exposed or semi ---exposed.
receive joint compound*
of gypsum board would
Provide type with face
Install "LC" bead where drywall construction
abutted to other construction and back flange can
to framing or supporting substrate.
Install control joinizo, at loczation� or if
at spacings and locations required by referenced
application and_fix�ish standard, and approved by the
visual effect.
FINISHING OF DRYWALL:
is tightly
be attached
not ,indicated
gypsum hoard
Architect for
General: Apply point treatment at gypsum board joints {both
directions) flanges of corner bead, edge trim and control joints;
penetrations; fastener heads, surface defects and elsewhere as
required to prepare work for decoration.
GYPSUM DRYWALL SECTION 09250 - 6
Madison High School
Boiler Installation
Rexburg, Idaho
Pref ill open 'Dints and rounded or beveled edged if any. using
setting -type joint -compound.
Apply joint take at j amts between gypsum boards, except where trim
accessories are indicated'.
Finish interior
compounds
rounded or
coat;
SUE
wallboard by
in 3 coats knot including
beveled edges), and sand
Embedding and First --- Coat:
or taping compound.
applying the fallowing joint
prefill of open joints and
between cots and after last
Ready -mix drying -type all-purpose
Fill (Second) Capt : Reader --mix
topping compound.
Finish (Third_) Coat
topping cornpaund.
drying -type
all-purpose
Ready-mjLx0
drying --types all-purpose
or
Partial Finishin Omit third coat and sanding on concealed
drywall work which is indicated for drywall finishing or whish
requires finishing to achieve fare-resistance rating, sound rating
or to apt as air or smoke barrier,
PROTECTION•
Provide final otection and maintain conditions,
suitable to installer, which ensures gypsum drywall
being without damage or deterioration at time of
Completion.
END OF SECTION 09250
in a manner
construction
Substantial
GYPSUM DRYWALL SECTION 09250- - 7
Madison High School
Boiler Installation
Rexburg, Idaho
1.01
1.02
SECTION 13300
FIRESTOPPING
RELATED DOCUMENTS
A. drawings
including
apply to
and general
General and
provisions of contract,
Supplementary Conditions,
work of this section.
DESCRIPTION OF WORK
A. P-roviLde firestvpping as indicated, and for the
following applications:
1. Penetrations through f ire -rated f loves,
ceiling, and walls. Seal holey accvmmodatincr
items such as pipes,
saying material for
ceiling.
J
conduit, etc. Fire
wall cavities above
1. 03 QUALITY ASSURANCE
A. General: Provide f irestopp ing materials that
expand to fila cavities or provide adhesion to
substrates, and that will maintain seal under
normal, expected movements of substrates. Provide
firms safing, batt or blanket insulation that is
firms resistant as well as a smoke slap system,
B. UL Classification: Provide f irestopping materials
that are currently classified with UL as "Fill,
Void , or Cavity Materials", and "Through
Penetration Firestop Systems".
C. Fire '�ests; Provide firestopping materials that
have been tested in accordance with ASTM E 814
"Methods for Fire Tests of Through -Penetration Fire
Stops" ;and UL 1479 "Fire Test of Through-
Penetration
Firestops".
1.04
DELIVERY, STORAGE, AND HANDLING
A. Deliver firestopping materials to job site in
original, new, and unopened packages and containers
bearing manufacturer's name and a label identifying
contents.. -
Be Sore firestopping materials out of weather, at
temperatures below 900F (320 C) and as recommended
by manufacturer.
FIR.ESTOPPSNG SECTION 13300 - 1
Madison High School
Boiler Installation
Rexburg , Idaho
1.05 PROJECT CONDITIONS
A. Foam: Store unmixed liquid components in their
original� unopened containers at temperature of 650
t-0 8 0° F. - (180 to 270 C, } f or 12 hours minirnum
bef are use.
B a Use forced air ventilation when installing foam in
areas having less than two cubic feet of free air
for each pound of liquid mixture being foamed.
C. Store fire safing blankets in ariginal, unopened
packages.
PART 2 PRODUCTS
2 , 01 MANUFACTURER
A. provide the following f irestopping materials or
Engineer. approved equal:
1. Foams 3M fire protection products or equal by
Dow Corning.
2 . Sealant : 3M fire protection products or equal
by Dow Corning.
3, Fire Safing insulation: Thermaf iber 0
2.02 MATERIALS
A. Sealant: Provide ready -to -use fire protection
penetration seal that will stop passage of firer
smoke, and water through firs-rated wall and f loor
penetrations and will cure in the presence of
atmospheric moisture to produce durable and
flexible sear and will farm airtight and
watertight bonds with most common building
materials in any combination, including cement,
_ masonry, steel and aluminum.
B. composition.0
Provide one part, ready -to --use
material with consistency of soft caulk at
temperatures ranging from -350 to 160"F (-370 to
710 C) , and extension and compression properties of
+ or -40 o of original gap.
C. Primer: Provide Dow Corning 1200 RTV prime coat,
ifrequired..
D . masking Tapp:: Provide pressure-sensitive adhesive
tape as selected by installer.
FIRESTOPPING SECTION 13300 -- 2
Madison High School
Boiler Installatian
Rexburg, Idaha
E, Foam: Provide 14 to 18 lbsp /cu,ft. 'free foam"
density, two-part silicones elastomer� supplied in
liquid A and C components colored Flack and off
while, respectively, for each identificationh.
F. Mixing: Provide A and B components that, when
thoroughly mixed at rvvrn temperature in 1:1 ratio
by either weight or volumes, will expand and care to
a foamed elastomer in one to five minutes.
G. Dams: Provide alumina silicate fire -board, mineral
f iberboard
mineral f iber matting, mineral f fiber
putty, dict tape, gypsum wallboard type X, plywood
or particle }ward, as selected by installer.
PART 3 EXECUTION
3.01 INSTALLATION OF SEALANT
A. Applications,. Use sealant for simple fire rated
wall and floor penetrations, including conduit or
pipe through sleeves and firms rated expansion
joints.
B. Preparation: Inspect surfaces to be sealed to
establish that they are clan, dry, sound, and
frost--free.
1. Metal and Glass Surfaces. Clean w�.th cloth
saturated with non -alcohol solvent in
accordance with label i"nstructi, ons,
2. Priming: Test sealant adhesion to each
substrate material. Apply primer to any
surf ace showing poor adhesion.
3. Exposed Seals : Use masking tape to cover
finished substrate adjacent to sealant.
4. Support.
a. Where required, support sealant with any
common damning material, such as
cardboard., duct tapes, plastic foam, or
backer rod
-- b.- Where required, support sealant with 3-
inch thickness of mineral wool, inserted
and compressed into opening.
C. Installation: but sealant nozzle to desire size
and punctum inner fail seal.
FIRESTOPPING SECTION 13300 - 3
Madison High School
Bailer Installation
Rexburg, Idaho
1. 2 -Hour Rated Seal: Apply sealant bead to
depth of 1--1/Z" by pushing bead in front of
nozzle to fill void above support or, if
mineral wool support is used, to a depth of
1 / 2 11 thick*
2* Tool sealant immediately after application and
before skin forms., Immediately remove any
masking tape used. Protect seal from any
disturbance for 48 hours minimum.
3 . 02 'INSTALLATION OF FOAM
A . Applications : Use foam for complex fire -rated wall
and floor penetrations, including multiple cables
in trays, multiple conduit and pipes, and mixtures
of cables,, conduits, and pipes,
Bo Preparation: Remove combustible materials and
0
loose impediments from penetration openings and
adjacent surfaces.
i. Remove o i I and other free 1from
penetration openings.
C. Installation: Provide damming of penetration
0 inopen-ing accordance with manufacturerfs
instructons 0
1.0 Sealing:
Seal gaps and cracks left after
damming materials are in place,_
29 Mixing: Stir Parts A and B in their original
containers. Combine with 1:1 ratio of Parts A
and B. Stir resulting mixture thoroughly,
either by hand or with power mixer.
3 Foam Placement: Immediately after mixing,
pour or inject liquid foam into penetration
opening, not more than 1/3 full to compensate
for expansion during cure Follow
• manufacturer's instructions explicitly.
a. When dispensing continuously, do not
exceed measure snap time or 3 minutes,
whichever is less,,
be If opening is not filled when shot
reaches measured snap time or 3 -minute
maximum, stop application for at least 15
minutes to allow foam to set.
a
4* Dam . Leave dam in
place for 24 hours minimum
FIRESTOPPING SECTION 133 00 - 4
Madison High School
Boiler Installativn
Rexburg , Idaho
to allow foam to filly cure.
3.03 iNSTALLATION OF FIRE SAFZNG
A . Field cut blankets to fit wall cavities.
B. Secure blankets to framing with specially designed
safing impaling clips.
C. Field
cut
insulation a
minimum of 1/2v, wider than
cavity
to
be filled to
insure compression fit .
3.04 FIELD QUALITY CONTROL
A. Sealant:
adhesion,
Inspect seal
and seal and
after 48 hours for complete
correct any deficiencies.
B, FoamFollow manufacturer's installation
instruct ions precisely, including 4-point field
quality control checks which consist of foam colvr,
foam cell structure, snap time, and frame foam
density.
1. Inspect seal after 24 hours. Remove clamming
materials to inspect under site.
2. Correct any deficiencies by adding f oam or
sealant. Reinspect after 24 hours.
3. Reinstall damming materials which are required
to achieve fire rating.
3.05 ADJUSTINGAND CLEANING
A. Sealant: Clean excess cured sealant from nonporous
surfaces with commercial solvent such as naphtha
m-ineral salvents, fallowing instructions an
container label.
Be Foam: Clean spills of Pert A and Part B liquid
components with high -clash mineral spirit solvent,
fallowing instructions on container label. Trim
excess foam with sharp knife or blade.
C. gleaning: Remove equipment, materials and debris.
Leave area in undamaged, cleari condition.
END OF SECTION 13300
FIRESTQPPING SECTION 13300 - 5
Madison High School
Bailer Instal3ation
Rexburg, Idaho
DIV. 15 - SECTION 15000
GENERAL MECHANICAL REQUIREMENTS
ENOL
1. Requirements: The requirements listed under General
Conditions, Special Conditions and General Requirements are
applicable to this section and all subsequent sections of
Division 15 and form a part of the contrast.
2* Word to be Performe-d: Perform all work awarded to the crafts
of this Contractor by reason of labor agreements and
jurisdictions at no additional cost to the Owner.
6
MechanicalDi.vision Tndex
15000
15100
15400
15450
15700
15715
15900
General Mechanical Requirements
Basic Materials and Methods
51
Heating Equipment
Law Pressure Steam Bailers
Insulation
Water balance
Automatic Temperature
FEES., PERMITS AND REGULATIONS:
{Hot Water hailers} .1
Controls
3. The Contractor shall obtain and
the installation of this word,
Supplemental General conditions.
pay for permits required in
as defined by 3. 7 of the
2, Where specifications and drawings require higher standards
than applicably ordinances or statutes, specifications and
drawings shall take priority. Where specifications ani
drawings violate applicable ordinances or statutes the latter
shall take priority,
3. All work and materials shall be in full accordance with the
latest applicable State, City, County and local regulations
and ordinances. Nothing in these specifications or drawings
is to be construed to permit work not conforming to these
codes. The Contractor 'shall hold and save the owner and
Engineer free and harmless from liability of any natures or
kind arising frim his failure to complywith cedes and
ordinances.
4. Items which are not covered in Local and State cods shall be
installed per -the latest edition of the following codes.
SECTION 15000 - 1
Madison High School
Boiler Installation
Rexburg, Idaho
a. uniform Mechanical Cady, published by the International
Association of Plumbing and Mechanical officials, latest
edition.
Ia. Uniform Plumbing Code, published by the International
Association of Plumbing and Mechanical ffici
Officials,als, latest
edition.
CO Sheet Metal and. Air -Conditioning contractors National
Association, Inc,, SMACNA,
d. National Electrical code published by National Fire
Protection Association, latest editian.
EXAMINATION OF SITE:
1. Examine the site and be informed of all cond'it ions under which
work is to be done before submitting proposal. No allowance
will be made for extra expenses on account of error.
2. Information shown relative to existing services is based upon
available records and data during preparation of drawings and
shah be regarded as approximate only. Make deviations found
necessary to conform with actual locations and conditions
without extra cost.
FIELD E, ASUREMEI TS
The Contractor shall verify the dim�nsians and conditions ga�verning
his work at the building. No extra compensation shall be claimed
or allowed on account of difference between actual dimensions and
0 kv those indicated an the drawings, He shall examine adjoining work,
on which his work is dependent for perfect efficiency and shall
report any work which must be corrected. No waiver of
responsibility for defective work shall be claimed or allowed due
to failure to report unfavorable conditions affecting his work.
ALTITUDE RATINGS:
Unless otherwise nested, all
an altitude of 4,850 feet
manufacturer's ratings must
specif ied equipment
above sea level,
be made aecardincrll
SUBI S TON OF MA'T'ERIAL LIST AND SHOP DRAWINGS
capacities are fay
adjustments to the
a&
0
1. Prior to the installation of any materiels and equipment and
within fifteen (l5) days of Contract awards the Contractor
shall submit to the Architect/Engineer for approval, five (5)
copies of the manufacturer's brochure containing complete
dimensional and performance characteristics, wir0
ing diagrams,
I
nstallation and operation instructions, etc., for the
SECTION 15000 - 2
Madison High School
Boiler Installation
Rexburg, Idaho
f ollowing equipment:
a. Controls and Sequences
b . Wiring Diagrams
c. Insulation
d. Domestic Hot Water Boiler
e. Piping Specialties
fo Pumps
g -e Hot Water Boilers
h. All items substituted under the "nor equal" clause
2. A material list shall be submitted stating whether the
materials proposed are as specified or are substitutions.
Contractor shall review and mark submittals prior to
submitt.�ng in order to makes sure that submittals comply with
specifications to his understanding. The submittals shall be
complete for the first submission andnot sent through in
piecemeal fashion, as far as practical.
SUBSTITUTIONS:
1. The materials and equipment described in the Bid Documents
establish the standards and quality to be mei by any proposed
substitution. The term 'nor approved equal" means that the
product shall fulfill the function of the specified item and
be approved by the' Architect/ Engineer.
2. Requests for approval on products not specified must be
submitted to the Architect/Engineer at least ten( -10) days
before the bid opening. Na substitution should be considered
by the Contractor prier to bidding unless a written request
for approval has been approved by the Architect/Engl"neerO
3. The request far prior approval shall be made for brand names
4.
in lieu of equipment specified. Equipment submitted mast be
equal or exceed all performance characteristics of specified
equipment and be aesthetically acceptable to the
Architect/ Engineer.
4. If the Architect/Engineer approves any proposed substitution
prior to receipt of aids, such approval will be set forth in
an Addendum. Bidders shall not rely upon approvals made in any
other manner.
5. Bidder shall base his bid only upon the materials or equipment
supplied by the manufacturers approved in the Bid Documents
or Addenda.
6e For a period of fifteen (15) days after the Contract Date, the
Architect/Engineer will consider written requester from the
SECTION 15000 - 3
Madison High School
Bailer Installation
Rexburg , Idaho
Contractor for substitution of products. The Contractor shall
submit a separate request for each product, support with
complete data, drawings and samples as appropriate,including:
a . Comparison of the qualities of the proposed substitution
with that specified.
b . Changes required in other elements of the work because of
the substitutions.
c. Effect on the construction schedule,
d. Cost data comparing the proposed substitution with
product specified.
e. Any required license fees or royalties,
f. Availability of maintenance service, and source of
replacement materials.
The Architect/Engineer shall be the judge of the
acceptability of the propose substitution.
7. The Architect/ Engineer will review requests for substitution
with reasonable promptness, and notify Contractor, in writing,
of the decision to accept ar red ect the requested
substitution. If the substitution has a higher cost, there
shall be made no additional cost to the Owner. If there is a
reduction in cost because of the substitution, a Change Order
may be written authorizing the substitution and thereby
passing the savings on to the Owner.
DRAWINGS0
1. Install work as indicated on drawings. Installation changes
necessary to coordinate with other work or to neet
architectural or structural conditions shall be made without
additional cost to the Owner.
2. For purposes of clarity and legibility, drawings are
essentially diagrammatic to the extent that mare offsets,
bonds, unions, special fittings and exact locations are not
indicated. Make use of all data in all Contract Documents and
verify information at site.
3. All dimensions and locations of equipment, doors, partitions,
fixtures, grilles, etc., are to be taken from the plans but
sha 11 be verified at the 3'ob site . Drawings are not to be
scaled.
DER2NITION OF PIPING:
SECTION 15000 - 4
Madison High School
11
Boiler Installation
Rexburg , Idaho
The term "piping" as used in these specifications or drawings mean
all pipe, fittings, nipples, valves, union. etc. , as required far
complete and. functional systems.
C00►PERATIC3IJ WITH OTHER TRADES :
1. The Contractor shill give full cooperation to other trades and
shall furnish in writing to the General Contractor, with
copies to the Architect/ Engineer, any information necessary to
permit the work of all trades to he installed satisfactorily
and with the least, possible interference or delay,
2. Where the work of the Contractor wi1l be installed in close
proximity to, or will interfere with work of other trades,
he shah assist in working out space conditions tv maks a
satisfactory adjustment. If so directed by the Engineer, the
Contractor shall prepare composite working drawings and
sections at a suitable scale not less than 1/4"-1'0"! clearly
showing how his work is to be installed in relation to the
work of other trades. If the Contractor installs his work
before coordinating with other trades., or so as to cause any
interference with work of other trades, he shall make the
necessary chances in his work to correct the condition without
extra charge.
3. The Contractor shall furnish to other trades, as required, all
necessary templates, patterns, setting plans,, and shop details
for the proper installation of work and for the purpose of
adjacent work.
INSPECTION=
1. Do not allow any work to be covered -up or enclosed
inspected, tested and approved by Architect/Engineer or
authorities having jurisdiction over the work.
2. Should any work be enclosed
inspection and test, Contractor
uncover work, and after it has
4r covered--ub before
until
other
such
shall at his awn expense
been inspected. tested and
approved, make all repairs necessary to restore all work
disturbed by him to its. original condition.
T YOR ceFINAL INSPECTION... 1!A -_ '-�.I■ I 1 ! - !l771�S��1 R r!!l�S�!! �R
All of the fallowing items must be
inspection. No excerptions will be made,
be made until all items are completed.
it Cleanin
completed prior to final
and final payment will not
of Equ ipnent and Premises;
SECTION 15000 - 5
Madison High School
Boiler Installation
Rexburg, Idaho
Thoroughly clear all parts of
Exposed parts which are to be
gleaned of cement, plaster and
and grease spats shall be
carefully wiped and all
Exposed metal work, shall be
brushes to remove rust and
clean. Trap elements shall
and flushing period, after
the apparatus and equipment.
painted shall be thoroughly
other materials, and all ail
removed. Such surfaces shall be
cracks and corners scraped out.
carefully brushed dawn with steel
other spots and left smooth and
. be removed during craning
which they shall be replaced.
2 operatinq Instructionsoperaand Service Manu .l
l.
The Contractor shad carefully prepare a full description
and Service Manual.for the entire Mechanical System. Femur (4)
copies of this Manual shall be submitted to the
Architect/ Engineer for approval at the most 14 days after
substantial completion of the. work. Failure to. submit for
approval will delay final inspection and acceptance of the
work by the Owner
A. The Service Manual shall be of the
covered, three {3} ring binder type,
following on the cover and spineIV
hard backed vinyl
imprinted with the
MECHANT CAL. MAINTENANCE OPERATING INSTRLTCTIUNS
PROJECT SAME:
MECHANICAL ENGINEER:
MECHANICAL CONTRACTOR:
B. The following items
pertinent data shall
sections separated by
catagories;
BOILER INSTALLATION
MADISON HIGH SCHOOL
REXBURG IDAHO
McClure Engineering
Superior Boiler
together with any other necessary
be included. At a minimum, provide
indexed dividers for the following
1. Hat water Boilers
2. Domestic Hot Water Bailer
3. Controls Items and Complete
4. water Balance Report
5, Piping Specialties
6. Pimps
This list complete
1 Section19 Draw incts .
Catagvries
separated
and is
Control Schematic
to be used as a guide.
of equipment Qr 5ybtem5 Miall be
9
by a divider with typewritten plastic
SECTION 15 0 0 0 - 6
Madison
Bailer
Rexburg
0
40
High School
Installatian
Idaho
protected index tab.
2 * Ma nu f a rf s Data;
a . Provide a lisp. of
manuf acturer and local
representative names, addresses and telephone
numbers in each category section noted above.
These will be fog use by the. owner to obtain
service and parts ,
b. Part numbers of all replaceable items.
C . Manufa.cturerI s cats and rating tables,
including brochures an all equipment fisted
under Approvals Required.
d. filing lubrication and greasing data..
e. Complete electrical load data. from operating
test.
f * Serial numbers of all principal pieces of
equipment.
g. Control diagram and operation sequence
together with labeling of control piping and
instruments to match diagrams.
h . Valve tagging chard indicating location and
function on job.
i. Written Guarantees.
System Test Run Reports*
a . Complete -water balance report,
As Built 9 lip
A complete set of blame line mechanical drawings will be
provided for the purpose of showing a complete picture of
the work as actually installed, These drawings shall
serve as work progress report shuts and the Contractor
shall make neat and legible notations daily as the work
proceeds, The drawings shall be available for inspection
at all times and shall be kept at a job location
designated by the Mechanical Engineer. At completion of
the work, these "As -Built" drawings shall be signed by
the Contractor, dated and returned to the Architect.
SECTION 15000
Madison High School
Boiler Installation
Rexburg, Idaho
Guarantee
All work under this section shall be guaranteed in
writing to be free of def ecti"ve work, materials, or parts
dor a period of one (1) year after f incl acceptance of
the work. Wotk required to repair or replace defective
workmanship materials or equipment shall be done at no
cost to the Owner. In addition, furnish all
refrigeration and emergency repairs, emergency service
and all refra.gerarit required during the one (1) year
operation. Contractor shall submit a letter including
items above and with blanks for date of acceptance and
date of expiration of Guarantee, as part_ of the final
inspection packet.
IN'STRUCTIQN OF OWNER'S PERSONNEL:
Prior to final 'inspection, the Contractor
instructional tour of the entire project.
by the Owner shall he instructed in:
shall conduct an on-site
The personnel designated
A. Operation of all Mechanical Systems
B. Elementary Trouble Shooting Procedures
C. Preventatives Maintenance Procedures
D. Uses of Operation and Maintenance Manuals
A letter from the Contractor acknowledging such has been done shall
be submitted to the Architect/Engineer with the final inspection
packet. The letter shall list the names of the owner's personnel
so instructed and endorsed by the owner to indicate completion of
this item.
MATERIALS:
I. All materials
installed
shall
be new, fall weighty of
the
best
quality with
the same
brand
or manufactures used
for
each
class of materials or equipment, such as valves, pumps.,
boilers, controls coils, air handling equipment and filters.
All rotating equipment shall operate in perfect dynamic
balance.
2. All materials and equipment shall be installed in a meat and
workmanlike manner by competent specialists for each sub -
trade. The installation of any material and. equipment not
meeting these standards may be condemn -ed by the
Architect/Engineer, and shall be removed andreinstalled at no
additional cast to the owner.
nELzVERY AND STORAGE
SECTION 15000 - 8
Madison High School
Boiler Installation
Rexburg, Idaho
i's Deliver materials in ampler quantities from time to time as
necessary for uninterrupted progress of the ward. Stere so as
to cause the least. obstruction to the premises and distribute
to prevent overloading to any portion of the structure.
2. Provide all temporary storage and shop areas that are required
at site for safe and proper storage of materials, tools and
other items used in the performance of the work. Construct
only in locations approved by the owner and do not interfere
with work of any other trade,.
3. Protect materials and equipment furnished under this section,
either stared or 'installed, until final acceptance of the
project as a whole,
4. Damage or defects
shall be made good
OVERTTME
developing bef ore acceptance of the work
at Contractor F s expense.
Contractor shall include overtime costs
TEMPORARY SERVICES:
in hits Bid for this work.
Provide temporary services when any
interrupted in connection with work of
period of time acceptable and approved by
FABRI CATION,
existing services are
this section beyond the
Owner .
1. All materials and equipment shall be identified by
manufacturer's name or nameplate data. Unidentifi6
ed materials
or equipment shall be removed from the site,
2. Equipment specified by manufacturer's number shall include all
accessories, controls, etc., listed in the catalog as standard
with the equipment. Optional or adda.tional accessories shall
be furnished as specified.
3. Where no specifies make of material or equipment is mentioned,
any 3firsi class product of a reputable manufactures may be
used provided it conforms to the requirements of the system
and meets with approval of Architect/Engineer.
4. Equipment and materials damaged during transportat-ion�
installation and operation shall be considered as "totally
damaged" and shall be replaced with new. Any variance from
this clause shall be made only with written approval of
Architect/ Engineer.
SECTION 15000 - 9
Madison High School
Bailer Installation
Rexburg , Idaho
ELECTRICAL 0
1.
0
General :
A. Provide equipment to suit available power; this
requirement supersedes the drawings and other portions of
specifications.
B. Provide and install electrical motors required dor
equipment specified in this Division of the
specif ications. Mawr disconnects . motor starters .
relays, push 'buttons and pilot lights, thermal overlaid
relays, connection of line and control conductors for
motors , etc. � not included in packaged mechanical
equipment shall be supplied installed and connected by
the electrical Contractor.
C. All power and control wiring and conduit is part, of the
Electrical section and/or Automatic Temperature Controls
section.
D. Pressure switches valves, flout switchest electrical
controls, etc.. not furnished bv the Contrnl -q Onntrantnr _
will be su
Contractor
connected
Contractor
pplied and installed bythe Mechanical �~ ~yi •
under this section of the specifications, and
bythe Electrical Contractor. The Mechanical
shall furnish the Electra cal C'nnt-rac-tnr wi i -I,
Lne necessary
connection of
submitted for
wiring diagrams required for electrical
this equipment. These diagrams shall be
approval with the material submittal,,
E. Equipment shall conform to National Electrical
Manufacturer"s Association Standards, Loyal Code
Requirements, and shall bear the Underwriters"
Laboratories'' label where applicable.
Fa ward openings giving access to "live" or rotating parts,
with screen, grilles, or structural parts to prevent
accidental contact with such parts,
MOTORS:
A, Provide motors for equipment of this division. Motors
shall be minimum size as indicated, but shall have
sufficient starting torque to start equipment.
... . I . -
B. Motor enclosures where not specified shall be drip -proof
for general use: totally enclosed fan cooled for wet,
dirty or exterior use.
SECTION 15000 -10
Madison High School
Boiler Installation
Rexburg, Idaho
C, Install motors far in-line
horizontal plane unless pumps
for vertical 'installation.
3. STARTERS:
circulating pumps in a
are speci f ica l ly des igned
A. Provide starters for packaged
are an integral part, or where
compatible with special motors.
and Specifications for special
equipment where
the design must
See Equipment
requirements.
starters
be
Schedule
8. Starters dor standard motors shad be furnished and
installed by the Electrical Contractor. Starters
furnished by the mechanical division shall be an integral
part of the mechanical equipment. Electrical connection
shall be by the Electrical Contractor, However, this
division shall coordinate wank to provide a completely
operative system.
Starters furnished under this section shall comply with
the following;
a. Enclosures :
NEMA. Standard far the locat ion
general purpose, NEMA Type 3 for
for watertight; NEMA Type 7 and
b,. Thermal Overload Devices:-
used;
NEMA Type 1 NEMAfor
raintight; NEA Type 4
I for explosion proof.
1 for single phase standard motors,
3 for three. phase standard motors.
1 far each ungrounded conductor for each, winding of
multi -winding or multi--speed motors.
Do Manual starters may be used dor motors up to 1/2 HP where
no interlycking is required. Provide pilot lights to
indicate the "ON" position.
E. Magnetic full -voltage starters for motors up to 30 HP.
F. Magnetic starters shah have 120 volt or lower control
circuits; HOA switch in the cover; auxiliary contacts for
necessary interlocking; integral disconnect switch or
circuit breakers for branch circuit, and short circuit
protection .
G, Short circuit interrupta..ng capacity of starters and
disconnects, shall be adequate fir the voltage +employed
and for current to be interrupted, This may require use
SECTION 15000 -11
Madison High School
Boiler Installativn
Rexburg, Idaho
of high interrupting capacity breakers or current
limiting fuses, If fuses are used, provide three (3)
spares for each disconnects.
CONTROLS.
Provide transient aver --voltage protection for all solid state
electronic devices. where protection is not incorporated within
control device, provide auxiliary over voltage suppressors selected
to protect the. equipment completely.
SCAFFOLDING, RIGGING HOISTING.
The Contractor shall furnish all scaffolding, rigga.ng, hoists,
cranes, and services necessary to erect and deliver to the premises
any equipment and apparatus furnished. Remove same from premises
when no longer required.
MANUFACTURER S DIRECTIC3NS
The Contractor, shah install all equipment an strict accordance
with all directions and recommendations furnished by the
manufacturer. Where such directions are in conflict with the glans
and specifications, the Contractor shall report such
conflicts to the Architect/ Enq ineer who shall make compromises as
he deems necessary and desirable.
LUBR T CATIONS0 0
The Contractor sell provide all ail for the. operation
equipment until acceptance. The Contractor shall be held
responsible for all damage to bearings while the equipment
operated by him up to the date of acceptance of the
11
-1 4 -
of all
is beim}
P_►«" • 1f1C LViIL,CdCLC]I- snail protect ail bearings and
during the installation with proper lubri'cation and
preventative coating .
ACCESSIBILI'T'Y:
shafts
rust
The Contractor shall locate all equipment which requires operations
or servicing in fully accessible positions. For example: Valves,
taps, gauges,clean-outs, motors, controllers, f iltersr switch--
gear, and drain points, If required for better accessibility,
furnish access doors for this purpose. Minor deviations from
drawings may be, made to allow for better accessibility, with the
Engineer's approval.
The Contractor shall provide the
locations of access panels for
damper, or other devices requiring
provided by the Contractor,
General Contractor with the exact
each concealed valve, control,
service. Access panels shall be
and installed by the General
SECTION 15000 -12
Madison High School
Boiler Installati,on
Rexburg , Idaho
Contractor. Locations of these panels shall be SUb](Ctltted, insufficient time to be installed in the normal course of work.
All cost incurred through Failure to perform this function as the
proper sequence of this work dictates, shall be borne by the
Contractor . Thi type, of access doors shall be as required by the
room f inish schedule. Acoust ical file access doors shall be equal
to Krueger type B, Style A for Acoustical plaster and Style C -fie
for sidewall, drywall or plaster construction. Where access doors
are installed in walls required to have a specific fire rating, the
access door installed shall be fire rated access door with U.L.
label, as manufactured by Nlilcor or approved equal. Access dater in
1 -hour construction shall be Class C and access doors in 2 --hour
construction shall be Glass B. Access doors shall be large enough
to easily perform the function for which the access door in
intended.
DIET OPERATION AND VIBRATION:
All work shall operate under normal conditions of load without any
sound or vibrations which is v�jectional in the opinion of the
Architect/ Engineer. Sound or vibration noticeable outside of the
roam in which it is located or annoyingly noticeable inside its own
room, will be considered objectionable, Sound or cribration
conditions considered abjectianable by the Architect/ Engineer shall
be corrected in an approved manner by the Contractor at his
expense. Vibration control shall be by means of approved vibration
eliminators in a manner as recommended by the manufacturer of the
eliminators,
MECHANICAL EQUIPMENT HANGERS:
The Contractor shall provide support far his work direct to the
building structure, and shall not hang equipment or piping from
ductwork or other piping, or other installed items.
FLASHTNG:
All pipes and ducts penetrating exterior walls or roofs shall be
flashed and counterf lashed watertight. Where other materials are
not specifically shown or specified, flashing and cvunterflashing
shall be 24 --gauge galvanized steel,
CUTTING AND PATCHING,
Mechanical work shall be laid out in advance of building
construction to permit building in pipe sleeves, inserts, anchors,
hangers, supports, fixture carriers etc., so as to eliminated
unnecessary cutting of structural members. Where cutting becomes
necessary, the Contractor shall employ the trade installing the
work originally to restore such cut work and close aper�ings
SECTION 15000 -13
Madison High School
Boiler Installation
Rexburg, Idaho
communicating from one compartment
member shall be cut without the
Architect/Engineer.
PAINTING
All mechanical
to. another. Na st t ral
written consent of the
Painting shall be by the General Contractor,
ABBREVTATTONS AND .SYMBOLS,
Schedule of abbreviations and symbols an
commonly used. Not all shown will appear
drawings show those most
on drawings and drawings
-MaY C:0nua-.n some hoz shown in schedule, obtain clarification from
Architect/Eng neer an any quest ionable item before submitting bid.
IDENTIFICATION:
PIPE IDENTIFICATION:
Tdentification of piping shall be done with Setmark pipe markers as
manufactured by Seton Name Plate Ciro. New Haven, Conn. 06505 or
approved equal. The calor coding shall comply with ANSI A13.1-
1981 Safety Color Coding regulations. The means of identification
shall be a talar coded band and ars identifying legend to indicate
the contents of the pipe and a direction of f low arrow,
The identifying coded color bands, legends, and directional arrows
on piping systems shall he located adjacent to each valve, at every
point of entry and exit where piping passes through a wall or
Ceiling, �on,each riser and junction, every 50 feet on long
continuous lines and adjacent to all special f ittings (regulating
valves, etc.)
Legends shall be. applied on the
pa -pe in a location that will
personnel from the floor area.
EQUIPMENT IDENTIFICATION:
color band on the perimeter of the
be easily visible to operating
Except for individual room heating units, and items furnished under
Temperature Control, X11 items of mechanicpment including
pans, pumps, boiler, and electrical switches and starters for
mechanical equipment and gauges shall be labeled.
Information on labels shall include the f ollowing:
1. Identification number and name.
and name shill be the same as that
or in these specifications.
2. If the item is a fan or pump, the
Generally phis number
shown on the drawings
flaw and head shall be
SECTION 15000 -14
Madison High School
0
Bailer Installation
Rexburg , Idaho
indicated,
3. If the item is
addition to its
it. is serving.
part of a unit the label shall
item numberr, the number of the
4. Valves shall be
normal operating
59 YYjlel'e the
only the
nameplate.
tagged with the
pas tions shall
mein unit serviced by
valve function needs
have,in
main item
area served and their
be indicated.
the valve is apparent,
to be included on the
The types of nameplates shall be as follows:
1. Valves tags shall be 1J2 -inch embussed tapes with
identification on one side for valves. Tags for magnetic
starters shad be screwed to the metal starter cover.
Tags shall be Addressograph No. 8--5300, or equal.
2a equipment nameplates shall be black faced formica with
white engraved lettering at least 3/16 -inch high, or
equal.
Valve tags shall be connected
chains. Screws shall be uses
installat'vri, the Contractor
complete list of all valves
identif ied.
END OF SECTIC?N 15000
to valve stems by steel r.ings or
I for equipment labels. Prior to
shall submit to the Engineer a
and each item of equipment to be
SECTION 15000 -15
Madison High School
Bailer Installation
Rexburg, Idaho
DIV. 15 - SECTION 15100
PIPING MATERIALS AND METHODS
GENERAL0 1.
1, Requirements: The requirements
listed under General
Conditions, Species -1
Conditions and
General
Requirements are
applicable to this section
and form
a part
of the contract.
2.o Work to be Performed:
Perform all work awarded to the crafts
of this Contractor
by reason of labor
agreements and
0 0
3urisdictions at no
additional cost
to the
Owner.
SCOPE -
'his section covers the materials
piping portion of this contract,
1. Hydropic piping
2. Domestic water
3. Boiler make-up
4 .
5.
7 .0
0
piping
mpi
Miscellaneous. vent
and methods used to complete the
including, but not limited to,
blowdown piping
and relief discharge
Install control valves.
Provide and install pumps.
miscelianous pip51
ing specialties.
ABBREVIATIONS:
0
piping
The abbreviations that fallow refer to standards or specifications
issued by the organizations identified below:
ANSI American rational Standard Institute, 1430 Broadway, New
York, New York 10018,
ASME American Society of Mechanical Engineers, 345 East 17th
Street, New York, New York 10017
ASPM American Society for Testi
ng and Materials, 1916 Race
Street, Philadelphia, Pennsylvania 191(]3.
IAPMO International Association of Plumbing and Mechanical
SECTION 151.00 - 1
Madison High School
Bailer Installation
Rexburg, Idaho
Officials,
California 90032,
MATERIALS:
5432 Alhambra Avenue, Los Angeles,
1. Black and Galvanized Steel: ASTM Specif ication A120 or ASTM
A53, Type E or S, Grade B .
2. Copper: ASTM Specif ication X88.
Pipe i i
Z ,
Screwed -black
32510, 150 lb.
far steel pipe
black to match
2. Solder: ANSI
and galvanized steel: ASTM Spec. A47, Grade
or 3 00 The , as required, banded malleable iron
2" dia.. and smaller. Galvanized or
pipe.
Standard B16.18 for cash bronze solder -joint
pressure f ittings. ANSI STANDARD B16,12 for wrought capper
and bronze solder-jointpressure fittings.
3. Welded: All weldingfittings used in the systems shall be
manufactured by Tube Turns , Inc . . Taylor Forge and Pipes Works,
Tube -Line or equal. Fittings shall match the pipe in which
they are installed. For black steel pipe 2" die. and larger,
use ASTM Slee. A234 standard weight steel butt welding
fittings, Na miters allowed.
4. Branch Connections Welded.* Connections made to mains shall
be made with Schedule 40 welding fittings when the branch size
is equal to, or one size smaller than, the main. when the
branch size is two or more pipe sues smaller than the amain,
"Weld -0 -Let" or "Thread--p-Let's fittings may be used. "Weld -0-
Let" and " Thread -t? -Let" type fittings shill be manufactured. by
Bonney Forge, Tool Works, Phoenix Forging Company, or equal.
Fittings shall match the pipe in which they are installed,
5e Flanges toFlangedjoints in steel pipe shall conform to the
American standard fir cast .iron flanged pipe fittings, Class
125 (B16-1-1948) and ASTM A126, Class B. For 150 1b, yr 300
1b, carbon steel flanges, conform to ASTM A181, Grade i.
6, unions: Piping 2-1/2" and larger shall have bolted flange
0 6
connections. For piping 2" and smaller, furnish 300 lb.,
ground joint, malleable iron, screwed unions, galvanized or
black to match the pipe., Dielectric, Epco, or equal
insulating fittings shall be used to connect dissimilar pipe
materials to prevent eleGtralytic action.
SECTION 15100 - 2
Madison High school
Boiler Installation
Rexburg , Idaho
PIPE JOINTS:
1. Threaded Joints: Threads on iron pipe sire pipe shall be
standard taper pipes threads. When a pipe joint material is
used it shall be' applied only on male threads and such
materials shall be approved types, insoluble in water and non-
toxic. Cleanout 'Plugs and caps shall be lubricated with
water- insoluble, non --hardening material or tapes.
2• Welded. Use gas or electric -arc welding in accordance with
ASME Code for pressure piping.
3. Flanged Steel; Use factory cuto, asbestos -free, compressed
sheet ring gaskets, or equal. All flange fasteners shall be
zinc plated or galvanized. Coat gaskets with fluid--compatible
lubricant before installation.
4. Solder Joints: Tubing shall be cut square and burrs removed.
Both sidesof fittings end outside �f tubing shall be well
cleaned before sweating. Care shall be taken to prevent
annealing of fittings and hard drawn tubing when making
connections. Joints for sweated fittings shall be made with
a non-corrosiue past flux and solid 50/50 tin -lead or 95/5
din -antimony wire solder. Cared solder will not be ermitted,
SERVICE
Domestic Water
Make --Up Water
.Alm
PIPING SYSTEM MATERIALS
(Hot and Cold)
SYSTEM CONSTRUCTION
Schedule 40 galvanized A120 or
better with 150 1b. malleable
iron fittings to match.
4r piping shall be Type L hard
drawn popper tubing with solder
type wrought copper f ittings.
Connections made with factory
made 'Tee Drillrequipment will
be pern lotted .
Schedule 40 black A53 wieth
forged steel, welding fittings,
9 0
Piping 2" and smaller may use
300 lb. malleable iron threaded
fittings.
Or piping shall be Type L hard
SECTION 15100 - 3
Madison High School
Boiler Installation
Rexburg ,
Blowdown
Idaho
Relief Valve Discharge
and Drains
Hydropic System
GENERAL PIPE REQUIREMENTS:
1.
Provide and erect,in
best practices of the
I.
complete installation t
the drawings shall be
may not show all items
2 Size any section
same i the
are nominal
copper tubing with solder type
wrought copper f ittings.
Connections made with f actory
made `Tee Drill' equipment will
be permitted.
Schedule 8 0 black Al2 0 or
better with 300 lb. malleable
iron threaded fittings.
Schedule 40 black steel pipe
with 150 lb. malleable iron
threaded fittings and approved
pipe daps .
Piping shall be Schedule 40
black steel pipe with nasi iron
screwed (fittings, or forged
steel welding fittings. P �.ping
211 and smaller may b.e schedule
40 black steel pipe with
screwed malleable - iron
fittings. Victaulic coupling
with schedule 40 pipe
acceptable with hydronic piping
2 1/2" diameter and above.
Victaulic valves are also
approved.
i workmanlike manner, according to the
trades, all piping required for the
)f these systemsi. The piping shown on
considered as diagrammatic and may or
in their correct positions.
of pipe,
for
which size
is not
indicated, the
largest
pipe
connecting
to it.
Sizes fished
3. Piping shall be arranged to maintain head
room and keen
passageways clear, and where necessary, shad
maintain the required clearances and conform
structural features of the building. All piping
run parallel and straight with adjacent walls or
shall present a uniform appearance, and shall be
together in long runs. All hanger rods shall be
4. The piping mai have to he
offset to
with the
shall be
ceilings,
grouped
vertical.
offset, lowered, or raised as
SECTION 15100 - 4
Madison High School
Bailer Tnstallation
Rexburg, Idaho
required, or as directed at the site. This does not relieve
the Contractor from responsibility for the proper erection of
systems or piping as described in the specifications and
approved by the, Engineer. All pi
ping shall be cud
accurately for the fabrication, to measurements established at
the canstruction site, Pipe shall be worked into place
without springing and/ter forcing, properly clearing all
windows, doors! and other openings and equipment. Cutting or
other weakening of the building structure to facilitate
installation will not be permitted,
5. Make changes of sizes or
Street ells, bushings,
fending of pipe are not
direction with manufactured fittings.
reducing flanges, close nipples and
allowed, unless specifically called
auz. wnerever changes in sizes of pipes occur the changes
shall be made with reducing fittings.. All pipes shall have
burrs and/or cutting slag removed by"reaming or other cleaning
methads.
f. All open ends of pipes and equipment shall be properly capped
or plugged to keep dirt and other foreign materials out of the
system. Plugs of rags, wooly cotton waste or similar
materials may not be used in plugging.
7. Provide unions at connections to equipment, on service side of
valves, and elsewhere as required to facilitate maintenance.
Flanges or unions,, as applicable for the type of piping
installed, shall be provided for connection to all items of
equipment.
s, Run full pipe size through shutoff valves, gas cocks ,
balancing valves etc. Change pipe sizes within three pipes
size diameters of final connection to temperature control
valves, furnaces, pumps, boilers, fixtures, cvils, and other
equipment.
9. Provide dielectric connectians between copier and dissimilar
metals. In copper systems threaded piping including
connections to equipment. shall be brass pipe ani fittings.,
lo. All piping shall be sv installed to insure noiseless
circulation.. All valves and specialties shall be so placed. to
permit easy operation and access. All valves shall be
regulated, packed and adjusted at the completion of the work!
before final acceptance. All piping shall be erected to
insure proper draining. Steam mains shall be pitched down in
the direction of flow, a minimum of 1 inch per 40 feet.
Condensate return mains shall be pitched down in the direction
of flow a minimum of 1 inch per 20 feet. Water piping may be
run level, but shill be free from traps.
SECTIa►N 15100 - 5
Madison Nigh School
Boiler Installation
Rexburg , Idaho
I1, All pipes Piercing waterproof membranes shall he flashed
watertight.
EXPANSION ANIS CONTRACTION:
The Contractor
and contraction
as required to
shall make all necessary
of piping, with offsets,
prevent undue strain,
PIPE HANGERS AND SUPPORTS:
19 General:
provisions for expansion
loops, anchors and guides,
A. Use ITT Grinnell, Fee & Mason, Kin --Line or equal.
B. All support components shall conform to Manufacturer's
Standardization Society Specification SF -58.
C. Use zinc plated or galvanized hanqers attachments, moods,
nubsbolts, and other accessories in boiler rooms and
other high humidify areas, or where exposed to the
weather.
2. Horizontal Piping:
A. All piping shall be rigidly supported from the building
structure by mans of adjustable type hangers. Where
pips run side by side, support on rod and anile iron
trapeze hangers. Minimum hanger spicing shall be as
scheduled to prevent sagging, However, were structural
members are on centers at odds with the schedule, the
shorter centers of the structure shall determiLne the
hanger spacing. In any case, the hanger spng shall be
sufficient to- support the weight of the pipe.
B. Flexible connectors shall be supported on both SldeS.,
within 2 feet of the connector.
C. Hanger Spacing'.
STEEL PIPS
,PIPE DIAMETER MAXIMUM SPACING
COPPER TUBE
MAXIMUM SPACING
1%211
5 r_011
5f
_011
3/411 - -
61-011
Jcr
-Olt
111 to 1,1/411
7
-011
5f
�011
1-1/211
9
.0 If
211
lor-011
8 r
.011
2-1/211
11r__011
9 r
�01'1
311
12/-011
JL01�011
SECTION 15100 - 6
V
Madison High School
Baler Installation
Rexburg Idaho
41r 14 '--Q 12 ► _0r1
511 161F -011
8"
191�011
D. Support Rad Dimensions:
1 /2 It t0 2'r pipe 3 /8 It rod
2-1/211 to 311 pipe 1 2 It rad
411 to 511 pipe 5 / g rod
611 pipes 3 4 rod
8" pipe 7/811 rod
3, Structural Attachments;
A. Attachments to solid concrete shall use Grinnell Fig. 285
light weight concrete inserts for loads up to Opp lbs,,
or Grinnell. �'ig. 282 1�� universal concrete insert, for
loads up to I,140 lbs.
Bo Attachments to steel beams where pipe is 211 or less shall
use Grinnell Flog, 87 malleable iron C-clamp with
retaining clip, or equal. Where pipe is 2-1/2" or
larger, use Grinned Fig. 229 malleable iron beam clamp
with exterision piece.
4. Intermediate Attachments:
Continuous threaded rods may be used where necessary. Na
hooks, chains, wire or perforated straps may be used.
5. PiPe attachments:
A. For steel pipe or insulated pipe with
protection shields, use Grinnell Fig,, 260
clevis hangers or Grinnell Fig. 70 adjustable
hangers, or equal.
B. When thermalin excess of 1/2"
anticipated. use Grinnell Fig. 174 adjustable
roll, or Grinnell Fig, 271 PjLpe.roll stand.
Where pipe is insulated, use a pipe covering
saddle in conjunction with the roll device.,
6,6 Spring Hangers:
A. For wipe sizes 2" and less,
to 3/411 are expected, use
spring hanger, or equal,
insulation
adjustably
swivel ring
axially iS
swivel pipe
or equa 1.
protection
where vertical movements up
Grinnell Fig. 247 light duty
SECTION 15100 - 7
Madison High School
Baler Installation
Rexburg , Idaho
B. For pipe sizes larger than z'{, use Grinnell Fig. 268
spring hanger, or equal.
TESTS.
I. General:
A, The piping shall be entirely free of sir when Perf orming
the hydrostatic tests,
B. The Contractor shall coordinate the dime of hydrostatic
test (s) by ratifying the Engineer at least 48 hours in
advance of the proposed test(s),
C. Any piping which is to he insulated,. placed with the
construction, - or otherwise concealed, shall be carefully
tested before being insulated or permanently enclosed.
D. Instruments required for making the tests shall be
provided by this Contractor. Relief salves set tv avoid
excessive pressure during testing shall also be provided.
E. New pipe -lines which are to be connected too existing pipe
lines shall be tested by isolating the new pP.
ipe with
spectacle blinds, blind flanges or other suitable mans.
F. Before f inal acceptance of the piping system as a whole ,
the Contractor shall make all required adjustments
including controls, valves, etc. , and shill place the
entire piping system in perfect operating condition. At
the completion of the work, this Contractor shall furnish
the Engineer with all certifications of inspec�ifln.
G. If inspectian or tests show defects, such defective worl�
or material shall be corrected or replaced and inspection
and tests shall be repealed. All repairs to piping shall
be made with new materials. Na caulking of screwed
joints or hales will be acceptable. All defects in
materials and workmanship which appear
during the tests shall be promptly remedied and the test
small be reapplied.
2. Wader Lines: (Including make --gyp, cold, blowdown)
All water limes shall be tested hydrostatically at 125 psi and
shall show no pressure loss in a one hour eriod.
3. Hydropic System:
Piping shall be tested
with
a 125-1b,
hydrostatic test.
SECTION 15100 - 8
Madison High School
Bailer Installation
Rexburg, Idaho
Valves shall be installed as necessary to
pressure shall remain on all parts
0 a 0
isolate system. The
of the system fir
cul L 1U1U11 L Llme za permit a complete examinatiron.
FLUSHING DRAINING, AND -CLEANING PIPE SYSTEM:
The Contractor shall flush out all water piping systems with water
before placing them in, operation. Air lines shall be cleaned bY
blowing them out with air. After systems are in operation and
during the test period, all strainer screens shall be removed and
thoroughly cleaned.
LVE
1 . General:
A. All valves shall be installed in locations which allow
ease of operation and maintenance.
B . Provide valves, cocks and strainers at nominal pipe size
unless otherwise indicated..
C. Wherever passible, install valves with stems in a
vertical position. Da not install with stem below a
horizontal position unless approved by the Engineer.
2. Specifications and Approved Manufacturers:
A.
C.
Q
Gate Valves:
1. Valves 2" and smaller shall be Crane No. 428 or
equal, bronze, screwed, 125 psi steam rating with
rising stem.
2. Valves 2--1/2" and larger shall }3e crane No. 4b5 -1J2
or equal, Clasp 125 flanged iron body, bronze trim
and rising stem.
Ball Valves,,
Valves shall be Jamesbury Type 1000 or equal, bronze
screwed body with bronze trim, TFE seats and seals.
Swing Check Valves:
1. Valves 2" and smaller shall be
equal, bronze, screwed, 200
regrindable seats.
Boiler Pressure Relief Valves:
Cram Na. 3 6, or
lea. rating, with
SECTION 15100 - 9
Madison High School
Boiler Installation
Rexburg , Idaho
E.
Boiler pressure rel0
ief valve
of the boiler.
manufacturer,
BTUH capacitor
sit by boiler
Manual
Air Vents
and
gauge
Provide
Crane'Nv.
88
bronze
Flow Control
Furnish
Furnish
equal,
SPECIALTIES:
19 General:
to be ASME rated far full
halve to be furnished and
Valves:
needle valve or equal.
Balancing Valves:
single component circuit balancing valves.
Armstrong CBV1 series, ge11 & Gosset, or approved
A. Each pressure gauge shall be repairable, with
construction materials, graduations and range suitable
for the application . Gauges shall lae provided-with
isolating valves .10 subject to vibration or shock
loads provides snubber or liquid -f illed gauge.
Be Each thermometer shall have a field adjustable scale for
calibratian. Provide thermometers suitable dor
environmental and operating conditions. All thermometers
shall be installed in matching thermowells.. Where.
installed an, insulated piping or equipment, use extended,
neck thermowelis to place the thermometer outside the
insulation. Each thermometer shall be calibrated at mid,
scale before project completion,
CO Provide fall or globe valves for strainer blowoff.
Direct blowoff to prevent personnel or equipment damage.
Valve shall be the same size as the nominal blowoff
Connection.
D. Install all piping connection without strain to pump or
equipment connection points. The Contractor may be
required to disconnect piping to demonstrate strain -free
connectians.
2. Specifications and Approved Manufacturers:
A. Pressure gauges shall
Ashcr-oft, "Duragagel' or
equal. Dials shall be
Provide Crane No. 88 or
E'_aCh gauge s
be Marshalltown "Premagage'fr
Trerilce No. 50OX, or approved
4-1/2" unless otherwise noted.
approved equal needle valve for
SECTION 15100 -10
Madison High School
Bailer Installation
Rexburg , Idaho
g. Thermometers shall be lens front, red reading 911 mercury
type; straight, back, side or adjustable angle mounting
to suit -installation. Weksler Industrial Thermometer or
equa1,,
C• Saf ety valve discharge elbows shall be Grinnell Figure
1538 or equal, cast iron, threaded inlets. Install at
the point of discharge for alb new relief valves.
D. Backf low'prev'entor shall threaded bronze construction,
reduced pressure-type, with corrosion resistant seats,
springs, shafts and fasteners.. Furnish with ball valve
test cock. Unit shall be approved for high hazard
crass -connect applications by IAPMO and local authority
having jurisdiction. Furnish Watts #909, equal by Febco
or approved equal. Pipe drain connection to floor.
E. Flexible connectors shall have a corrugated inner tubing
of tin bronzes (98* -3/4% cu, 1-1/4% tin} or stainless
steed.. Outer shield shall be wire braid of same alloy.
Flanges shall be ASS 1.50 Th, standard flanges.
Connectors shall be rated dor 150 psi working pressures
with a 4: 1 safety factor, Metraf lex ML, Flexonics. or
equal.
F . Hydronic S
Bell
& Gossett,
1, Con
rens ion
Taco.,
Tank:
Provide equipment listed below by
Armstrong, or other approved equal.
Welded steel, 150 PSI,
tank. Provide with air
glass. Furnish Bell &
Airtrol, Armstrong, or
2. Air Separatore.-
Separator
Separator
strainer.
Armstrong,
horizontal, ASME
control f itting
Fossett Model No
approved equal.
to be ASME rated
to be rued for 3 4 6
Furnish Bell &
or approved equal.
. l"oma Pum -1;
rated, 15 gallon
and sight gauge
15 with ATF -m-12,
of steel construct ion.
GPM and have. a re -movable
Gossett Rolairtrol R-5,
Furnish and install base mounted circulating pumps with
iron body, bronze fitted with mechanical seal, and
rubber -mounted motor, and suction diffusers,, at locations
and capacities as shown on mechanical drawings. Furn0
ish
Bell & Gossett, Armstrong, or approved equal,
SECTION 15100 -11
Madison High School
Boiler Installation
Rexburg , Idaho
3
x ;
Installatian:
A • All specialties shall be installed in accordance with the
best standard practices and as recommended by the
manufacturer,
B . Where thermometers or fest fittings, occur in insulated
piping systems or in insulated equipment, extension necks
shall be provided to extend beyond the insulation.
C. Manual air vents shall be installed at the high paints in
the piping system, and at each new hot water convector.
END OF SECTION -15100