Plan review based on
the 1991 Uniform Building Code
Name : MILLHOLL4W YOGURT RESTAURANT
Date: October 15,
Contractor: SILVERTREE
Designer : SILVERTREE
Engineer: NONE
Plans Examiner:
Report created using Flan Analyst software
Portions of the material contained in this
Uniform Building fade ( 1991 edition) with
Conferences of Building officials.
# SHEET IDENTIFICATION
1
K
Ki
2
5
by b w & a.
program are
permission
CORRECTION REQUIR.lmULi
PL1.0 PLOT PLAN NOT COMPLETE---
sdwk to front
parking stall
JOE
LAIRD
( 719) 5 9 9-56 2 2
reproduced from
of International
r
Provide a complete site plan showing
door, sidewalk wdtns , handicapped
and handicapped ramps,
ALL PLANS NOT SIGNED BY ARCH- All sheets
an architect or Engineer
to be0ped and sgned. by
registered in this state,
-- pec. 3U1.(b). WE HAVE NOT REQUIRED THESE
PLANS TO BE PREPARED BY A REG. ARCH; BUT WE DO STILL
EXPECT THEM TO BE AS COMPLETE AND THOROUGH AS IF
THEY HAD BEEN.
Al • 0 NO DOOR SCHEDULE PROVIDED WITH PLANS,` CONSEQUENTLY. WE DON'T KNOW
WHAT MATERIALS THEY ARE MADE OF IF THEY CaNT,AIN
WIDOWS, DR IF THEY ARE REQUIRED TO BE GLAZED W.12 MT
SAFETY MATERIAL. SEL SEC. 54D6.
A1 • ❑ NO WINDOW SCHEDULE-�-----�-- NORMALLY A W2NDoW SCHEDULE 2S PROVIDED
WIfiH CgMMERCIAL PLANS SHOWING SIZE, TYPEfBRAND NAME.
SAFETY GLAZING, E"S"C. NOTE ON PLANS SAYS TirlINDOWS IN
DINING ROOM WILL BE SAFETY GLAZED. WHAT ABOUT
OTHERS IN KITCHEN, BASEMENT, APT., ETC?
A-? NO ATTIC TIENT. SHOWN-____ Provide attic ventilation that
cQmpliEs with sect'
an 3205.
(c }
7
Required corrections f or:
Project Id: MILLHOLLOW YOGURT RESTALTRANT
Address: 1ST EAST ST.
# SHEET IDENTIFICATION CORRECTION REQUIRED
6 A -? NO ATTIC ACCESS SHOWN---- provide an attic access (22X30 min) to
each attic area.-- Sec. 3205.(a), THIS TO
INCLUDE BOTHE THE ATTIC OVER THE DINING ROOM AND
OVER THE APT.
7 A-1.1 INADEQUATE BS'MT EGRESS-- The basement area is required to have
an automatic sprinkler system unless it has adequate
egress wall openings. -- See Sec. 38,02, -- SEE
SUGGESTIONS ON PLANS FOR POSSIBILITIES OF GO1►�BINrNG
EGRESS OPENINGS Tn7ITH REQUIRED SND B ENT EXIT
$ A -? NO PLANS 2ND FLR APT----- This area requires glazed opening(s)
having an area equal to 10a or more of the floor
area. --� Sic. 1205 * (b)
9 A Na PLANS FOR 2ND. FLR APT-,-- This area requires operable exterior
opening (� � having an area equal tO 5% or more of the
floor area,, -- Sec. 1205 . (c)
10 A NO PLANS FOR 2ND FLS APT---- This area requires ars exterior o enin
for emergency escape or rescue with clear p �
area/dimensions specified. Sec. 1204,
11 A-? NO PLANS FOR 2ND FLR APT--- A smoke detector is required in this
location. NOTE: All detectors are to sound an alarm
in bedroom area. -- Sec. 1210.(a)4.
12 A '? NO DETAIL OF KITCHEN/2ND FLR APT FLR/CEILING ASSEMBLY.--- SHOW
1HRw FIRE SEPARATION MATERIAL ON BOTTOM OF JOIST AND
APT. FLOORING MATERIAL ON TOP OF JOIST. ALSO CALL
OUT HOW BOTH WILL BE CONNECTED TO JOISTS.
13 A-? NO DETAIL -OF BASEMENT CEI LING/1ST STORY FLOOR FIRE SEPARATION
ASSEMBLY. ---SHOW 1 HR FIRE SEPARTION MATERIAL
(2EA*5/811 GYpBOARD) ON BOTTOM OF JOIST AND IST STORY
FLOORING MATERIAL ON TOP OF JOIST. CALL OUT HOW
BOTH MATERIALS WILL BE CONNECTED TO JOISTS.
14 A-? NO DETAILS OF DUCTS, ETC* GOING THRU THE DIFFERENT 1 HR. FIRE
ASSEMBLIES . NO DETAILS OF HOW STRUCTURAL MEMBERS
(BEAMS) IN BASEMENT & KITCHEN WILL B .. GIVEN 1 HR.
FIRE PROTECTION. SEE SECS. 1704,1706,3309,4303
THRU 4308.
Page # 3
Required corrections for:
Project Id: MILLHOLLOW YOGURT RESTAURANT
Address: 15T EAST ST.
SHEET IDENTIFICATION CORRECTION REQUIRED
17
21
az
23
24
25
A1. I BS' MT NEEDS 2 EDITS--------- Provide 2 exit(s) from this area. Table 33-A & Sec. 3303.(x)
Al .0 1
A191
DIST. BTWN EXITS
equal
area.
---�-------- The distance between the exits must be
to or greater than 1/2 of the diagonal of the
-�-� Sec. 3303 (c) .
LANDINGS NST DEFINED ----- Provide a landing on both siders of
door'. Nate: The step & size requirements. -�� Section
33049 & (�}
BSMT LANDING NOT CORRECT- Provide a
door. Note:
3304. (1) &
The step &
( 7 )
lanc"ting on both sides of
size requirements. -- lection
Sle2 BSMT STARS NST CORRECT The maximum rise of a step is 7 inches
and the minimum tread is 11 inches. -.- Sic. 3306.fc)
S1 . 2 1 HR CONST UNDER STARS - d- The enclosed usable space under the
stairs is required to be protected by 3hr
fire -resistive constructian. -- 3306,(I)
PLlsO HANDI. ACCESS NOT SHWN -- Provide handicap access to the
building. -- Chapter 31
A-?
A-?
LAV. CLR HT NOT SHOWN --- Provide the required 29 inch height,
30 inch, clear width, & 17 inch clear depth under at
least one lavatory. -- AN'SI A117.1 Sec. 4.19.E &
Fig. 31
MIRROR HT NOT SHOWN -----
bottom within
Sec. 4,19,,,6
Provide at least one mirror with the
40 inches of the floor. --� ANSI A117.1
A-? GRAB BARS NOT SHOWN ------
plans that
4,17.6, & 4.24
drab bars need to be shown an
comply with ANSI ,117.1 See. 4.15.4,
the
F1. 0 COLUMN SIDES NEED
T0 BE
SHt3TrVN ON PLANS FOR COLUMNS ON
FOOTINGS
F2 &
THESE
F3. THE SIZE{S} OF THE BEAMS RESTING
COLUMNS ALSO NEEDS TO BE CLARIFIED.
ON
Reguir�d corrections for: Page # 4
Project Id.* MILLHOLLOW YOGURT RESTAURANT
Address.* 1ST EAST ST.
# SHEET IDENTIFICATION CORRECTION REQUIRED
-----------------------------------------------------------
26 F1. 0 NEED COPY OF 'YOUR CALCULA TIONS SHOWING HOW YOU ARRIVED AT THE
SIZES OF AND REBAR IN FOOTINGS F2 & F3; THE SIZES OF
THE COLUMNS ON THESE FOOTINGS; AND THE SIZE OF THE
BEAMS ON THESE COLUMNS.
27 NA NO SOILS REPORT INCLUDED- -- WHEN YOU GET THE GROUND FOR THE
FOOTINGS EXPOSED, WE WILL NEED TO GET WITH YOU TO
SEE IF IT HAS THE DESIGN BEARING STRENGTH OF
0 D OPSF . GRAVEL PROBABLY WILL; HOWEVER SILT WILL
BE MORE IN THE 1000 TO 1500 PSF VALUES.
28 51.0 WEST BRNG WALL----------- DOES THIS BEARING WALL GO FROM
BASEMENT FLOOR TO THE ROOF? ARE THERE ROOF LOADS
ON IT? ARE YOUR METAL 2X4 1 S & 2x6 I s THS SAME
STRENGTH AS WOOD MEMBERS? SEE SEC. 2517 (g) &
TABLE 25R-3. THIS TABLE INDICATES THE NEED FOR
2X6's ON 16" CENTERS.
29 51.0 WALL SUPPORTS OVER WINDOW S. -- IF 3"X6"X3/16" COLUMNS & WF10-30
HEADER BEAMS ARE NEEDED AT THE 2 LOCATIONS SHOWN,
WHY ARE THEY NOT NEEDED AT THE OTHER 4 SIMILAR
LOCATIONS?
30 S1.0 NEED COPY OF YOUR CALCULATIONS DETERMINING THE SIZE OF THE
WF10-30 BEAMS SUPPORTING THE KITCHEN CEILING & THE
3"X61IX3/161" COLUMNS SUPPORTING THEM. ALSO DETAIL OF
CONNECTIONS OF COLUMNS, BEAMS & JOISTS. ALSO A
DETAIL OF CONNECTION BETWEEN JOISTS & WEST BEARING
WALL.
31 51. 1 CORRECT TYPICAL EVE DETAI L SO IT SHOWS THE CORRECT ROOFING
(CEDAR SHAKES) AND CORRECT SIDING (CEDAR). WHAT
ABOUT DETAIL OF HANGING CEILINGS OR LISTS OF WALL &
FLOOR FINISHES FOR DIFFERENT ROOMS, T.E. KITCHEN,
DINING ROOM, REST ROOMS, BASEMENT, APT., ETC.
32 EMPIvO ELECTRICAL, MECHANICAL & PLUMBING PLANS NOT COMPLETE. PLAN
SHOWN ONLY COVERS ELECT. SEE ATTACHED EXAMPLES OF
TYPICAL PLANS FOR THESE ITEMS. SPRINKLING SYSTEM
PLANS ALSO NEED TO BE REVIEWED BY PLUMBING INSPT.
ALSO NEED AGRMT WITH CITY TO COVER LANDSCAPING ON
CITY PROPERTY.
33 51.3 STRUCTURAL DETAILS------- HOW WERE THE SIZES OF STRUCTURAL
ELEMENTS DERIVED? SEE OTHER COMMENTS REGARDING
DETAILS SOWN ON THE PLANS RETURNED HEREWITH.