Plan analysis based on
the 199. Uniform Building Code
Project Number: tay1chev Name: TAYLOR. CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE Date: June
Occupancy: Bl,B2,H4
Type of Con.ste. V-�Ihr
PP
NOTEe.The code items listed in
listing of all possi
selected sections of
this report
ale erode requirements
the code.
Report created using flan Analyst software
Portions of the material contained in this
Uniform Building Code ( X991 edition) with
Conference of Building officials.
DIRECTION BOUNDARY
SEPARATION
AREA INCREASE
NORTH Property line 130.0
EAST Property line 100.0
SOUTH Property line 120.0
WEST Public way 180.0
Area
it 100.00%, for open
Feet
Feet
Feet
Feet
area on
25, 1995
contractor: GENE PALMER CONST,
Designer: GENE PALMER
Engineer: NONE
Plans Examiner: JOE LAIRD
are not intended to be a complete
in the 1991 SBC. It is a guide to
by b w & a. (719) 599-5622
program are reproduced from
permission of Internationa�
FIRE PROTECTION
130. 0 Feet
100.0 Feet
120. 0 Feet
140.0 Feet
4 sides.
FL NAMEOCC MAX FLR AREA ALLOWED RATIO STATUS
�Mffl"� d== M!= �� ft� �� NEI* am
2 PARTS STORAGE S2 ok 1601 28000 0. 06 ok
2 LUNCH RM.FREC*STORAGE B2 ok 800 28000 0 . 03 ok
2 Locker Room B2 ok 480 28000 0.02 ok
TOTAL FOR FLOOR moo,
i Retail Sales Room
1 CAR SERVICE AREA
1 OFFICES
1 PARTS STORAGE
Z BODY SHOP
1 TRUCK SHOP
TOTAL FOR FLOOR
BUILDING TOTAL
B2
ok
coo 0.1
2800
GBUUU
280-00
U.lU
0.10
OK
ok
B1
ok
9450
28000
0.34
ok
B2
ok
630
28000
0.02
ok
B2
ok
2572
28000
0.09
ok
K4
ok
3575
17600
0.20
ok
H4
ok
3200
17600
0.18
ok
22227
23727
0.94
ok
25108
48299
0.52
ok
the
1,
Code review f or:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
The actual height of this building is 20. 0 feet.
The maximum height of the building is X0. 0 feet. -- Table 5---D
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 17-A & Table 5-A
Exterior wall ratings for Hawoccupancies are based on Table 9-C
NORTH
OCC BRG NON-BRG OPNG
WALL WALL PROT:
B1,
1hr
1hr
B2
1hr
1hr
H4
1hr
1hr
EAST
BRG NON-BRG OPNG
WALL WALL PROT
SOUTH
BRG NON-BRG OPNG
WALL WALL PROT
None
1hr
1hr
None
1hr
1hr
None
1hr
1hr
None
1hr
1hr
None
1hr
1hr
Nome
1hr
1hr
WEST
BRG NON-BRG OPNG
WALL WALL PROT
None
h
hr
Nene
None
1hr
1hr
Nonce
None
hr
1hr
None
The exterior walls may be of COMBUSTIBLE6eral. Sec.2201,
None -- No fireprr�tection requirements for Qpenings .
Prat -- Openings are to be protected with 3/4 hr fire assemblies.
area of the wall maximum. Seg, 50 4. (b) & Sec . 2 2 0 3 * & Table 5-A
Maximum single window size is 84 sq.ft with no dimension
greeter than 12 feet, --- Sec. 4306.(h)
50% of the
NOP -- Openings are not
perml4tted in this wall.
� -- These walls may be required to a have a, parapet wall 30 inches
above the roof ing. The parapet wall is required tv have the same
fire racing as the wail. See section 1710, for details and exceptions,
OTHER BUILDING ELEMENTS
ELEMENT
Interior Searing gall
Interior nonbrg wail
Structural Frame
Exterior Struct Frame
Shaft Enclosure
Floor/Ceii ing Assembly
Roof /Oiling Assembly
stairs
MATERIAL
Any
Any
Any
Any
Any
Any
Any
Any
Table 17-A
RATING
1
hr
1
hr
1
hr
1
hr
1
hr
1
hr
1
hr
None
NOTES
Sem Footnote #5
dee f ootnote #i
;4ree Footnote #9
NOTE.s See Sec, 170E.a} for Shat Enclosure ex�eptivns.
FOOTNOTES:
1) Elements in an exterior wall located where openings are not permuted �r
where prvtec�ion cif �apening� is required, shall be protected against
external fire exposure as required for exterior bearing galls or the
structural frame whichever is greater, -- Table 17a,&Ao footnote 1
5j Nonjoad-bearing walls within a tenant thatspace are not part of a
1hr �vrridar may �e of:
a) Noncombustible (nonrated) materials
b) Fire retardant~treated wood
c) One-hour construction (any materials ~_ Sec. 1705 a (b) 1.
9 ) In areas with vehicles or, airplanes, the floor surface shall be of
r�oricomb�astible f nonabsorbent materials , -- Sec. 702,( 2 . (b)
Page // 3
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
0
DRAFT STOPSO
I f there is combustible cvnstruc�ion in the floor/ceiling assembly, draft
stops shall be installed so khat the area of concealed spaces does not
emceed 1000 square feed and so that the horizontal dimension, between sops
domes not exceed 60 feet. -- Sec. 2516.(f)4,A,(ii1')
If there is combustible construction in the roof fcei 1 ing assembly, draft
stops shall be installed so that the area of concealed spare does not
exceed 300a square feet and so that the horizontal dimensiar� between stogy
does not exceed 60 feet. -- Sec. 251F.f)4,B.(ii�
OCCUPANCY SEPARATIONS
B1 -B2 1hr Offices
separation.
B1 -H4 lhr
B2 -H4 1hr Offices
separation.
ADDITIONAL SEPARATIONS
-- Table 5-B
less than 25%
-- Sec. 503.(a)ex #2B
of majar use do not require a
less than 250 of major use do not require a
sw Sec. 51.%3• (a) ex #2B
FOR B 1 OCCUPANCY 4,
A 1hr occupancy separation is required around rooms containing a boiler
central heating unit greater than 4.00,,000 BTU input. -- Sec. 748.
Storage areas inexcess o� 30�� sc�, ft, are required to be ara., ed from
the retail area by a 1hr vccu.ancy separati4
on, -- Sic. 702,(b)2.
FOR B2 OCCUPANCY:
A 1hr occupancy separation is required around rooms containing a boiler
central heating unit greater than 400,000 BTU input. -- Sec, 708,
Storage meas in excess of 1000 sq. ft. are required to be separated from
the retail area by a 1hr occupancy separation. -- Sec. 7�2.(b�2.
FOR H 4 OCCUPANCY
A 2hr occupancy separation is reauired arr����,A ���}
-�� �.��,� ;
or
.� ..--- -� ..vis z.a.Lai.Ltly a IJOl lex' or
central heating unit. -- Sec. gig.
EXIT REQUIREMENTS:
FL NAME OCCUPANT NUMBER EXIT PANIC RATED DOOR NOTES
__________LOADREQUIRED WIDTH HDWR CORRIDOR SWING
_____ ___ MW _
2 *---------------
PARTS STORAGE
� 1 0.1 No No N/R
2 LUNCH RMrREC*STORAGE* 8 1 0,61 No No NIR
2 TOTAL Room * 10 1 0.02 No No N/R
23 2 0.6 No No NIR 7.
1 Retail Sales Room * 93 2 1.6 No Yes Out
1 CAR SERVICE AREA * 47 2 0.8 No Yes NIR
1 OFFICES * 6 1 0.1 No No NIR
1 PARTS STORAGE * 9 1 0.2 No No NIR
1 BODY SHOP * 18 2 0.3 No No Out 8
1 TRUCK SHOP * 16 2 0.3 No No Out 8
TOTAL 189 2 3. 2 No Yes Out
.,,
Gage review
Pro]' ect Id.:
Address: $71
for:
TAYLOR CHEVROLET EXPANSION
S0. YELLOWSTONE
*
NOTE: This area is being treated as an accessory far occupant loads.
--- Sec. 3302. ( exception
Rated corridors are to have 1hr fire protection on both sides of wally and
ce i 1 ing. -- sec . 3 3 0 5,9 ( Door apenings aye x`�?qui�'ed tv be p�'OteCt�?d ibwith 20 minute assemblies and window openings are required to him- -rn*g%e-s+- A
with labeled 3/,+ dour assemblies. --- Sec. 3305.(h)
Elevators opening into a raked corridor shall be OVI e�
lobby at each floor containing a rated corridor. --
Sec*
Walls and openings between the corridor and the elevator
required to be per sections 3 3 05,(g) and 3 3 05. (h) above.
W ith an elevator
33t15
lobby are
In areas where 2 exits are required, the minimum separation is
maximum diagonal vL the area or floor. -- Sec. 3303, (c)
Exit signs are required from all areas serving an occupant
�� Sec. 3314, (a)
Door swing is based an Sec. 3304.(b) except as noted,,
occupant load is based an Table 33-A.
Number of emits is based on Table 33---A except as Hated.
Emit width is in feet, and based on Sec. 3303.(b)+ Ji eq +- 0 5.
1/2 of the
V.Ae aiviaed approximately equally among exits .
Width shown for all areas is based on other exits. (0,,2)
Width shown for 1st floor is based on ather exits. (0.2)
Width shown for other floors & bas.ements is based an stairways
For the minimum width of doors,see Sec. 3304 s (fj �
For the minimum width of cvrridQrs, see Sec, 3305. (b)
For the minimum width of stairways , see Sec. 3306..(b)
FOOTNOTES:
1) The second f loor is required to
I
s 10 or more, -- Sec. 3303.(a)
8) The cumber of exits is based on
HANDICAPPED ACCESS:
5 a or more,
.ave 2 emits when the occupant load
Sec. 3319.
-Lj nd"uicappea access is required to at least
to this building. -- Sic. 31-03.(a) & (b)3.
2 } If a ramp is used for handicapped access,
1:1�. --- pec 3307. (C)
Hand icapped access may not be required
entry level. -ft- See. 3103(a) exc #2
Code review
Project Id.:
Address: 871
for:
TAYLOR CHEVROLET EXPANSION
SQ. YELLOWSTONE
one primary entrance
the max s1ope
1k �'�i
1ii
tO levels other than the primary
STAIR NOTES0
The maximum r�,se ci
-- See. 33[}x(c} f a stomp is 7 "Inches and the minimum run is 11 inches.
,
The minimum width of
is greater than 49.
Also See exit table
stairway is 36 inches, 44
--�
Sec. 3306.(b)
above to see i f n�inimum wi
inches if the occupant lead
dth is greater than 44 inches.
Provide handrails on bath. sides of a stairway 34 to 38 it above the nosin
(Mai be on one side if less than 4�4 inches wider __ Sec. 33,060(fl ��
Provide a guard rai�, where drop tiff is grit a eater than 30 nch��, Minimum height
42 inches, maximum opening size = 4 inches. -�- pec. 1712 .(��
The minimum headroom is C f t . -- S inches . -- Sec. 3306. {
Enclosed usable spare under the stairs is required to be protected as required
for 1hr f ire-resistive construct ion . -�- Sec . 3 3 0 6
Provide a landing within 1 inch (l/2 inch at
access* 9 ) of the threshold. -- Sec. 3304.{i�
doors used fog handicapped.
„X ►V1 " 1* game as aoQr width and the mini
-- Sec. 3344. j) mum length is 44 inches.
The maximum travel distances in this building is 150 f eet.
--_ Sec. 3 303. (d)
ROOFING REQUIREMENTS:
1 The roofing on this bu*ld*
Table 32-A ng is required to be Class B or better.
--
2) See section 3204. and 1CB0 research reports for requirements.
AUTOMATIC SPRINKLER SYSTEMS.
If openings are not provided in each 50 feet of exterior wall or there is
floor area more than 75 feet from an exterior c�p�ning, an autamatic
sprinkler system is required, -- Sec. 3802. (b)
An automatic sprinkler system is required in retail sales rooms with a
f loor area greater than 12 000 sq.ft. --- Sic. 38��. (d)An automat c sprinkler system 3s required in an H4 occupant mare th
30-00 square feed.. -- Sec. 38.02.(f)2, � a�
If there are l00 or more sprinklers, the autvmatic sprinkler sstem shal
supervised by an approved central Y 1 be
or a local alarm wY�ich wigill•Ar°pr et�ry� yr remote statian service
ve an audible Signal at at � constantly
attended 1ocation. �� pec. 3803.
STANDPIPE REQUIREMENTS:
,A class II standpipe
A hose is xequ�.red.
FOOTNOTES:
1) The locat
A
s required. -- Table 3 8-A
-- Table 38--A
ion is to be per Sec 3805. (c). (d) p and/or (e)
Code nevi ew for ; Page # 6
Project Id. : TAYLOR CHEVROLET EX .0N
Address : 871 5YELLOWSTONE
WALL AND CEIL1NG FINISH.0
l) Wadi and ceiling finish materiels are required to Damply with
Sic. 4204. (a) and Table 42--8.
2) Carpeting on the ceiling is required to have a Claims I flame
spread rating. -- Sec. 4 2 0 4. (b)
3) Textile wall coverings shall have Class I flame spread rating.,
and shall be protected, by automatic sprinklers or meet the
acceptance criteria of U.B.C. Standard No. 42-2 -- sec. 4205.
INSULATION NOTES
:
1) All insulation material including facings are required to have a flame-
spread rating of 25 or less and a maximum smoke density of 450 unless
it is in a concealed space and the facing is in contact with a wall or
ceiling. -- Sec. 1714.(c) exc.#2
2-) Foam plastic insulations are required to be p 3,
GLAZING REQUIREMENTS:
All glazing in hazardous
glazing material. -- Sec.
ADDITIONAL REQUIREMENTS:
locations is required to be of safety
5406 o (d)
For B1 occupancy
Devices generating a glow or flame are required to be 18 anches above
the floor,, Sem. 708m
The minimum clear height is required to be 7 feet, -- S(C) 10
Parking garages require a ventilation system that exhausts 1.5 cfm
per sq.ft. of floor area. -- Sec. 705.(b) 2.
For B2 occupancy
In all aromas customarily occupied by humins, provide natural or
artificial light and ventilation, -- Sic. 705,(a)&(b)
For H4 occupancy
If required by the Fire Code, spill control, drainage. & containment
shall be provided. --- Seca 902*(c), (d), & (e)
Smoke and heat venting shall be provided as set f
0" in he Fire
Code. -- Sec. 902.(f)
Devices generating a glow or flame are required to be 18 inches above
the f 1 oor Sec.. 908.
A ventilation system that exhausts 1,0 cfm per sq.ft,, of floor area.
An exhaust pipe is also rewired at each stall. -�- Sem,
9050 (C)
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
HANDICAPPED REQUIREMENTS:
NOTE: Section numbers 11' S
ted below are from ANSI A117.1 �- 198E
ruuNTAlNS
13 One must have a sPout within 36 inches of the floor. did= 4=W Sec. 4.15.E
2 ) Spaut must be at the front of t�.e unit. --- Sec, 4.15.3
3} Controls must be at or near the front of the unit. Sec. 4.1.5.4 & 4.25.4
4) A cantilevered unit is rewired to provide a clear area under the unit of
27 inches high, 30 inches wide, and 17 inches deep. --- Sec, 4,15.5 (1)
5) A clear area of 30 X 48 inches is required at the fountain. The cleararea is required to provide for a forward approach with a cantilevered
unit and for a side approach. otherwise. --� Sec. x.15.5 & Fig.27 bjrcfd
TOII3ET FACILITIESJ6:
1) A 5' diameter unobstructed turning spare is required in the toilet room,
Sec, 4.2.3 & Fig. 3(a)
2 ) When water closet is not in a compartment, the clear required is
a} 48 inches wide by 5G inches deep Witha side approach.
-,j
�- Seca.. 4. 16. 2 & Fig. 28
X33 48 lI'IChe$ wide by Ufa lIlChE.'S deep in71'�h �. f.10I'1'� c3ZJp�'O�.C�'1 r
__ Sec. 4.1 .2 & Fick. 28
c) 60 inches wide by 56 inches deep with both aPProaches.
-- Sec. 4.1fi.2 & Figs, 28
d) Sade bar is required to stark within 12 inch -es of the back wall and
extend. t0 54 inches from the back wall.6-1 & gig. 29
The rear bar is required to be 36 inches lvx�g. -- Fig. 29
33 When mater closet is in a campartment, the area reauzrecl
a) 56 inches deep by 60 inches wide with a
at the side. Door is at front or side,
b) 65 inches deep by 36 or 48 Inches wide w
and door at front. -4 Fig. 3O(b)
d) If a f Ivor mounted water closet is used
shown above must be 'increased 3 inchesQ *A e% t-41 III.
4)
grab far at the back
--
Fig . 3 0 (a) or
ith drab bays on bath
�. ,� •,.x.•,,« ,.1ca1. iz> u.L t"a r t:qu-Lreu -co 'SLaTz W1thiI1 12
extend to 54 inches from the Yuck wall.
The rear bar is required to start within
and be 36 inches long. -- rig. 3 0 (a)
m I1 G ]'1 _ w r { r _
the depth dimension
and one
sides
.may . ,>vkaj a kij)
inches of the back wall and
f 'inches of the side wall
;sem ��� II ��- t-.:id�-� �� � -� -co.� � inches above the floor,, F
5} The tip of the seat on the water closet is required to be 17
above t -hs floor. -- Fig. 29(b) & Fig. 30(d)
6) Urinals are required to be stall type or have an
7)
10)
wiLnin 1-i inches of the floor, -- Sec,, 4.18,�
A clear area of 30 X 48 inches is required in
-- sec. 4,18.3
29(a),(b) &
to 19 inches
elangated rim and, be
ig, 29(c)
front of the urinal.
prvvjLae a c�t�ar area. under the lavatory of
29 inches. --� SecA. .1 9. 2. 1 & F4.g , 3 1
A clear area of 30 X 48 inches is required in
--ft- Sec. 4.19.3 & Fig. 32
IF
The bottom of mirror is required to be within
-- Sem. 4.1-9.6 & Fig. 31
front of
40 inches
the lavatory.
of the Boar.
E
City of Rexburg
Engineering Department
12 North Center/P.O. Box 280
Rexburg, Idaho 83440
(208) 359-3020
Plan analysis based on
the 1991 Uniform Building Code
Project Number: tay1chev Name: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE Date: June
Occupancy: BI,B2,H4
Type of Const: V -N
NOTE a. The code items listed in this report
listing of all possible erode requirements
selected sections of the erode.
Report created using
Portions of the mater
Uniform Building Cede
Plan
41
ial
Analyst software
eontained in
( 1991 edition l
conference of Bu1lding Of f vials
DIRECTION BOUNDARY
NORTH Property line
EAST Property line
SOUTH Property line
WEST Public way
Area increased 100.00%
Rai as 0 ZVI 0
.W��WqNk
130.0
0.10
100.0
ok
120.Q
0.05
180-80
ok
for open
a
Feet
Feet.
Feet
Feet
area
this
with
25, 1995
contractor: GENE PALMER CONST.
Designer: GENE PALMER
Engineer: NONE
Plans Examiner : JOE LAIRD
are not intended to be a complete
in the 1991 UBC. It is a guide to
by b w & a.
program are
permission
(719) 599-5622
reproduced from the
v� international
FIRE PROTECTION
130.0 Feet
100. 0 Feet
120.0 Feet
14 0. 0 Feet
on 4 sides.
FLNAME ___OCC MAX FLR AREA ALLOWED RATIO STATUS
2 PARTS STORAGE g2
2 LUNCH RMIRECeSTORAGE B2
2 Locker Room g2
TOTAL FOR FLOOR
1 Retail Sales Room
1 CAR SERVICE AREA
1 OFFICES
1 PARTS STORAGE
1 BODY SHOP
1 'TRUCK SHOP
TOTAL FOR FLOOR
WARNING -- This floor is over the
BUILDING TOTAL
ok
ok
ok
ok
ok
ok
ok
ok
ok
630
2572
3575
3200
22227
allowed area.
25108
16000
0.10
ok
16000
0.05
ok
16000
0.03
ok
16000
0.18
ok
16000
0.17
OVER
16000
0.59
OVER
16000
0.04
OVER
16000
0.16
OVER
10200
0.35
OVER
10200
0.31
OVER
13636
1.63
OVER
X7743 f]0 0
k
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
The actual height of this building is
The maxi mZ�-�r! hc; f`�t�,t r,� 'I--H�. 1-,,, 4
20.0
feet.
---- --------_-••
"I X= X= is 4u.0 feet. -- Table 5 - b
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 17---A & Table 5-A
Exterior wall ratings for H-Occupancies are based on Table 9-C
NORTH EAST SOUTH WEST
OCC BRG NON-BRG OPNG BRG NON--k-BRG OPNG BRG NON-BRG OPNG BRG NON-BRG OPNG
WALL WALL PROT WALL WALL PROT WALL W'1111111LL PROT WALL WALL PROT
B1 Ohr Ohr None Ohr Ohr None Ohr Ohr None Ohr Ohr None
B2 Ohr Ohr None Ohr Ohr None ohr Ohr None Ohr Ohr None
H4 Ohr Ohr None Ohr Ohr None Ohr Ohr None Ohr Ohr None
The exterior walls may be of CDMBUSTIBLE material. Sec.2201,
bane -- No fire protection requirements for open ings,.
Prot -- Openings are to be protested with 3/4 hr fire assemblies. 5a of the
area of the wall maximum. Sec. 504.(b) & Sec.2203. & Table 5-A0
Maximum single window size is 84 sq.ft with no dimension
greater than 12 feet. -- Sec. 4306.(h)
NOP -- openings are not permitted in this wall.
These walls may be required to have a,parapet wall 30 inches
above the roofing. is
The parapet wall required to have the same
fire rating as the wall. See section 1710, for details and eccetior►s.
F
OTHER BUILDING ELEMENTS Table 1711111111111111111111111A
ELEMENT MATERIAL MATING NOTES
Interior Bearing wall Any p hr
Interior nonbrg wail Any o hr
Structural Frame Any o hr
Exterior Struct Frame Any a hr See footnote #1
Shaft Enclosure Any T hr
Floor/Ceiling Assembly Any 0 hr See Footnote #9
Roof/Ceil'OL ng Assembly Any 0 hr
Stairs Any None
NOTE!. See Sec , 17 0 6 . (a) for Shaft Enclosure gxceptions .
FOOTNOTES:
lj Elements in an exterior wall locateda 6 ripenings are not permitted
where protect'III`on of openings is required. shall be protected against
external fire exposure as rewired for exterior bearing walls or the
structural frame, whichever is greater. -- Table la -Al footnote 1
9) In areas with vehicles or airplanes, the floor surface shall be of
noncombustible, nonabsorbent materials. --- Sec. 702.(c) & 902-a(b)
or
F6
Cade review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 8 71 S0. YELLOWSTONE
DRAFT STOPS:
If there is combustible construction in the floor/oiling assembly, draft
stops shall be installed so that the area of concealed space does not
exceed l000 square feet and so that the horizontal dzmensivn betweendoes not exceed Ca feet. ---- Sec. 251 0 .. � st�pS
If there is cambustibl� construction in the
o
stops shall be installed so that the area of concealed space assembly' draft
exceed 3000 squamae feet and so that the horizontal dimension betwe�� ���does not exceed 60 feet. -- Sem. 2516.(f)4.B.(iii) en s
OCCUPANCY SEPARATIONS -- Table 5-B
B1 --B2 1hr Offices less than 25% of major use do not require a
separation. --
Sec,.B1-H4 1hr 503 a (a) ex #2B
B2 -H4 1hr Of f ices legis than 25% of major use do not require a
separation. -- Sec. 503.(x) ex #2B
ADDI'I'IONAL SEPARATIONS
FSR B 1
OCCUPANCY:
A 1hr occupancy separation is required
central heating unit greater than
Storage areas in excess of l000 sq. ft.
the retail area by a 1hr occupancy
FDR B 2 OCCU�ANCy:
A 1hr vccupan�y s�paration is required
central heating unit greater than
Storage areas in excess of 1000 sq . ft .
the retail area by a 1hr occupancy
FOR x4 OCCUPANCY
A 2hr occt�rzanr*v carr-.�,.-��-; ..,.. _ � --- ---ML
-
tamps
around rooms containing a boilr ar
400,000 BTU input.., --- Sec. 7os.,
are required to be separated.from
separation. -- Sec, 702, (b) 2,
around rooms containing a boiler or
400,000 BTU input. --� Sec. 708,
are required to be separated from
separation. -- Sec. 702.(b)2,
- - --�--T4--J �4r��-� �-�-Wi� -L :5 requl�'et� around rooms containing a. boiler or
central heating unit. -- Sec. 9p$.
EXIT REQUIREMENTS:
FL NAME OCCUPANT NUMBER EXIT PANIC RAVED DOOR NOTES
MWW ________LOAD_ REQUIRED WIDTH HDWR CORRIDOR SWING
-------------No No
2 PARTS STORAGE * vim ------------ -
-----N/R
---
---------
5 1 0.1 No No N/R
2 LUNCH RM, REC. STORAGE* 0.1
2 Locker Room * 10 1 0.2 NoNIR
23 2 006
TOTAL No
1 Retail Sales Room * 93 2 1.06 No No Yes OutN/R
1 CAR SERVICE AREA
1 OFFICES ,t 46 i 0'8 NO YeS NIR
1 PARTS STORAGE * 1 0.2 No 0.01 No No N/R
1 BODY SHOP * 18 2 0.3 NO No NIR
1 TRUCK SHOP * 16 2 No Out 8
TOTAL 0.3 No No Out $
189 2 3.2 No Yes Out
Code review
Project Id.:
Address: 871
for:
TAYLOR CHEVROLET EXPANSION
SO. YELLOWSTONE
* NOTE: This area is being treated as an accessory for occupant loads,.
--- Sec. 3302.(a) exception
Ratted corridors are to have Thr fire protection on both sides of walls and
'ling, _.. Sec.3305.(g) � .ceDior openings are require. to be protected.
with 20 mi�.ute assemb�.ies and window openings are required to be protected
with labeled 3f4 homer assentblies. -- Sec. 3305. (h)
Elevators opening into a rated corridor shall be provided with an elevator
3obby at each f i oor conta fining a rated corridor . -- Sec- . 3 3 a 5 . ( j )
Walls and openings between the corridor and the elevator lobby are
required to be per sections 3305.(q): and 3305.(h) above.
In areas where 2 exits are required, the minimum �eparat,ion is 1/2 of tie
maximum diagonal of the area or floor. -- Sec. 3 30 3, (c)
Exit signs are required from all areas serving an occupant load of 50 or more.
-- sec. 3314.(a)
Door swing is bayed on Sec. 3304.(b) except as noted.
Occupant load is based on Table 33-A.
Number cif ets is based on Table 33-A except as noted,.
Exit width is in feet and bayed on Sic. 3303.(b).
Exi t width is to be divided approximately equally
Width shown for all areas is based on other exits.
Width shown for est floor is based on other exits.
Width shown for other f loors & basements is based
For the minimum width of doors, see Sec. 3304.(f)
wr.: i ti.... ... .- _ t - - - - it
sec.
among exits(On2)
( 0 * 2 )
vn stairwa�rs .
%.$.L.4.11G =�E.L11����.�irt w��.�n yr cvrriaors, see 3305. (b)
For the minimum width of stairways, see Sec. 3306,(b)
FOOTNOTES:
1 The second floor is required to have 2 exits when the
is 70 or more. -- Sec. 3 303. (a)
S} The number of exits is based on pec. 3319.
HANDICAPPED ACCESS:
1) Handicapped access is required to
to this building. -- Sec. 3103. (a)
2) If a ramp is used For handicapped
Sec 3307.(c)
Handicapped access may not be
entry level. -- Sec. 3103(a)
at least
& (b) 3.
acce�s,
occupant load
one primary
the max slopeis
required to levels other than the primary
enc # z
Code review tor:
Project Id.: TAYLOR CHEVROLET EXPANSION
Ad -dress : 871 SO. YELLOWSTONE
STAIR NOTESmi�% .91 OL:
illct��.![{y,lfl rise or a step is '� inches and the minimum run is ll inches .
_�- pec. 33U5. (cj
The minimum width of a stairway is 36
is greater than 49. -- Sec. 3306.(b)
Also see exit table above to see if
Provide handrails on both sides of a s
(May be on one side if less than 44
Provide a guard rail where drop aff is
inches, 44 inches if the occupant lead
minimum width
tairway 34 to
inches widej
greater than
is greater than 44
38 inches above the
-- sec. 3306,(R)
30 inches, Minimum
inches.
eosin .
heig
ht
W
= 42 nchesf maximum openingsize = 4
The minimum headroom is 6 f to WAft 8 inches
Enclosed usable space under the stairs
for 1hr fire-resistive construct ion.
Provide a landing within l
access) of the threshold
0 a
inches. -- Sec. 1712.(a)
. -- Sec. 3306.(0)
is required to be protected as required
-- Sec. 3306.(1)
inch (1/2 inch at doors used for handicapped
-- Sec. 3304. (i)
'kae minimum Wlatn 3S Sime as ann-r wi ai-H mnA +-Ha
�- Sec. 3304.(j)
The maximum travel
-�� Sec. 3303. (d)
Nw-
distance in this building is
minimum length is. 44
150 feet.,
inches.
ROOFING REQU'IREMENTS
1} The roofing on this building is required to be Class C -- Table 32 --*A
2 See section 32�� , and ICBD research reports for rec��xirements .
AUTOMATIC SPRINKLER SYSTEMS;
If openings are not provided in each 5D feet of �xterivr wail or there is
floor area more than 75 feed. from an exterior opening, an automatic
sprinkler system is required.--- Sem. 3502.(b)
An automatic sprinkler system, is required in retail males rooms with a
floor area greater than 12,000 sq.ft.�--in
Sec. 3802.(d)
An automatic sprinkler system is requiI. red an H4 occupancy more than
3000 square feet. -- Sic. 38U2. (f ) 2.
If therms are 1p0 or more sprinklers, the automatic sprinkler system shall be
supervised by an approved c�ntral, proprietary, or remote station service
or a local alarm which will gives an audible signal at a constantly
attended location,, -� Sec. 3843.
STANDPIPE REQUIREMENTS:
A class II standpipe is required. -- Table 38-A
A hose is required. -- Table 38-A
FOOTNOTES:
1) The location is to be per Sec. 3805e(C)j(d)rand/or(e)
Code review for,
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
WALL AND CEILING FINISH.,
1) Wall and Ceiling finish materials are required to comply with
Sec. 4204.(a) and Table 42-8.
2 Carpeting an the ceiling is required to have a Class I flame
spread rating. --- Sec.. 404, (b)
3} Textile wall coverings shall have Class I flame spread rating.
and shad be protected by automatic sprinklers or meet the
acceptance criteria of U*BoC* Standard No;. 42-2 -- pec . 4205.
zNsuzATroN uoTIEsIs
1} All insulation material including facings are required to have a flame-
spread rating of 25 or less and a maximum smoke density of 450 unless
it is in a concealed spaces and the facing is ,in contact with a wall
orcei3inq --�Sec. 1714.(��
exC.#2
2) Foam plastic insulations are requi-red to be protected. -- Sec. 1713.
GLAZING REQUIREMENTS:
All glazing in hazardous locations is required to be of safety
glazing material. -- Sec. 5406.(d)
ADDITIONAL REQUIREMENTS s
For B1 occupancy
Devices generating a glow or f lame are required to be 18 inches above
the floor., -- Seg. 708,
The minimum clear height is required to be ? feet. Sec, ?'09.(c)5.
Parking garages, require a ventilation system that exhausts 1.5 Gfm
per sq.ft. of floor area. -- Sece ?05.(b) 210
For B2 occupancy
In all areas customarily occupied by humans,, provide natural or
artificial light and ventilation. -- pec. 705.(a)&(b)
For H4 occupancy
If required by the Firms Code, spill control, drainage, & containment
shall be provided. -� Sec-, 902.(c), (d), & (e)
Smoke and head venting shall be Provided as set forth in the Fire
Code . --- Sec. 902.(f)
Devices %-jent::rating a yiuw or fame are requirea to be 18 inches move
the fluor. -- Sic. 908.
A ventilation system that exhausts 1. t? efm per sq.ft. of floor area.
An exhaust pipe is also required at each still. �4- Sec.
905 . (c)
Page # 7
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 8.71 SO. YELLOWSTONE
HANDICAPPED REQUIREMENTS:
NOTE: Section nursers listed bylaw are frim ANSI A117 a I - 198+6
WATER FOUNTAINS
1 ) One must have a spout within 36 inches of the floor. -- Sec. 4.15*2
2) Sport must be at the front of the unit. -� Sec. 4ol593
3.) controls must be at or near the front of the unit. --- Seg. 4,15.4 & 4a25 -a4
4') A cantilevered unit is required to provide a clear area under the unit of
27 inches high, 30 inches wide, and 1? inches deep. --- Sec.
5 ) A dear area of 34 X X48 inches .is required at the fountain. The clear
area is required to provide for a forward approach with a cantilevered
unit and for a side approach otherwise. -- Sec. 4.15.5 & Fig.27 bfcfd
TOILET FACILITIES
3 A 5' diameter unobstructed turning space is required in the toilet room,
-�! Sec. 4.2.3 & Fig. 3 (a)
2) When water closet is not in a compartment, the clear area required is;
a) 48 inches Wide by 56 inches deep with a gide approach.
-- Sec. 4.16.E & Fig. 28
b) 48 inches wide by 66 inches deep with a f ront approach.
Sec. 4.16.2 & Fig. 28
c) 60 inches wide by 56 inches deep with both approaches,
City of Rexburg
Engineering Department
12 North Center/P.O. Box 280
Rexburg, Idaho 83440
(208) 359,P-3020
Plan analysis basted on
the 1991 Uri form Building Code
Project Number: taxIlchev Nam ---e:
Address: 871 S4. YELLOWSTONE
Occupancy: B1,B2,H4
Type of Const Jjj-N
TAYLOR CHEVROLET EXPANSIQN
Date: June
NOTE .The code items 1isted in this report
listing of allpossible code requirements
selected sections of the code.
Report created using Plan Analyst software
Portions of the material containedin this
Uniform Building Cade ( X991 edition} with
Conference of Buildinct tiff ficial s _
DIRECTION BOUNDARY SEPARATION
AREA INCREASE
NORTH Property line 13 0. 0
EAST Property line 100.0
SOUTH Property line 120.0
WEST Public way 18Q.0
Area increased 100.00% for open
Contractor:
Designer
9
25, 1995
GENE PALMER CONST.
GENE PALMER
Lnglneer: NONE
Plans Exami*ner.w JOE LAIRD
are not intended. to be a completes
in the 1991 UBC. It is a guides to
by b w & a. (719) 599-5622
program are reproduced from
permission of International
FIRE PROTECTION
130.0 Feet
100.0 Feet
120. 0 Feet
140.0 Feet
on 4 Sides,
FL NAME OCC MAX FLR AREA ALLOWED RATIO STATUS
- -
----------------
-------------------------- ------
2 PARTS STORAGEB2 ok 1601 24000 0.07 ok
2 LUNCH RMrRECeSTORAGE B2 ok 800 24000 O.o3 ok
2 Locker Room B2 ok 480 24000 0.02 ok
TOTAL FOR FLOOR
1 Retail Sales Room
1 CAR SERVICE AREA
1 OFFICES
1 PARTS STORAGE
1 BODY SHOP
1 TRUCK SHOP
TOTAL FOR FLOOR
WARNING --This
BUILDING TOTAL
0
ok
ok
ok
ok
ok
ok
9450
630
2572
3575
3200
Hoar is over the aZlowed.22227
area.
25108
41312
Oa12
Oal,2
0.39
0.03
0.011
0.24
0.21
1.10
0.61
OVER
OVER
ok
the
Code review
Project Id.
Address: 871
for:
TAYLOR CHEVROLET EXPANSION
SO. YELLOWSTONE
The actual height of
this
building i"S
20.0- feet.
The maximum height of
the
building is
55. 0 feet. -- Table 5-D
EKTERIOR WALL
FIRE RATINGS AND
OPENING
PROTECTION
Table 17-A &
Sec.
2003. (a)
Exterior wall ratings
for
H -occupancies
are based on Table 9-C
NORTH EAST SOUTH
OCC BRG NON-BRG OPNG
WALL WALL PROT
B1 2hr Ohr None
B2 2hr Ohr None
H4 4hr Ohr. None
BRG NON-BRG OPNG
WALL WALL PROT
2hr
2hr
4hr
Ohr
Ohr
Ohr
Nome
Nome
Nene
BRG NON-BRG OPNG
WALL WALL PROT
Thr
Ohr
None
2hr
Ohr
None
4hr
Thr
None
WEST
BRG NON-BRG OPNG
WALL WALL PROT
2hr Ohr None
2hr Ohr None
4hr Ohr None
The exterior walls are required to be of NONCOMBUSTIBLE material. Sec4, 2003 . (a)
'one NQ dire protection requirements for openings.
Prat -- openings ars to be protected with 3/4 hr fire assemblies. 50%- of the
area of
the wall maximum.
Sec.
504.(h)
the
& Sec.
Maximum
mingle
window size
is $4
sq.
ft
with no
greater than 12 fejt. -- Sem. 4306.(h)
NDP -- openings are not permitted in this
* -- These walls may be required to have
2003 . (b)
dimension
wall.
a parapet
wall 30
an-ove tne rooting.
The
parapet wall
is required to have
the
firms rating as the
walk.*
See section
1710,. for details
and
inches
same
exceptions.
OTHER BUILDING ELEMENTS Table 17-A
ELEMENT MATERIAL RATING NOTES
Interior Bearing wall Any o hr
Interior nvnhrg wall Any 0 hr
Structural Frame ,Any p hr
Exterior Struct Frame Any 0 hr See footnote #1
Shaft Enclosure Any 1 hr
Floor/Ceiling Assembly Argy p hr See aatnae #g
Roof /Ceiling Assembler Any 0 hr
Stairs Any None
NOTE: See Sem. 1706.(a) for Shat Enclosure exceptions.
FOOTNOTES
1} Elements in an exterior wall located where openings are not permitted
where protection. of openings is required, shah. �e prat�cte�. against
external firms exposure as required for exterior bearing wally or the
structural frame, whichever is greater, -- Table 17-A, footnote 1
9 ) In areas with vehicles or airplanes, the floor surface shall be of
noncombustible, nonabsorbent materials. --- Sec. 7c32.�c) & 9�2.(b)
3)
Gll
5}
6)
7)
9)
10)
_- Sec. 4.16.2 & Figs 28
.0
a) 5icxe jDar is requI*
ired to stmt within 12 inches of the back wall and
extend to 54 inches from the back wall. -W- Sec,, 4.1G.4 & Fig. 29
0
-rne rear mar is required to be 36 inches lona. �- Fig. 29
�vnen water closet
is in
a. compa�t�nent, the
a) 56
inches deep
by .60
inches wide r�ith a
at
the side.
Door is
at front or side.
bj 66
inches deep
by 36
or 4$ inches wide
and
door at front
. --
Fia. 3 n ( t�
area required�is 0
drab bar at the back
�ftaw Fi e 30 (
with grab hors on bath
d) If a floor mounted water closet is used,
shown above must be increased 3 _inches,
thedepth dimensi
on
... ,l� it i rrr '} rt
R-.! j O.Lue! "Urs are requirea to start within. 12
extend to 54 inches from the back wall.
The rear bay is required to stat within
and be 36 inches long. -~ Fig. 30(a)
The bars are to be 3 3 to 3 6 inches above the
Fig., 30(c).(d)
and one
sides
may. a�
inches of the back wall and
0
-- rig. f.bBa & 7.56b
6 inches of the side wall
floor. -- Fig. 29(a),(b) &
Tne zap or Lne seat on the water closet is required
above the floor. -- Fig. 29(b) & Fig. 30(d)
Urinals are required to be stall type or have
within 17 inches of the floor.. -� Sec. 4.18.2
A clear area of 30 X 48 inches is required in
»..
Sec. 4,18.3
�I I�P'f LSCC y 1,% -z
to be 17 to 19 inches
an elongated ring and be
& Fig. 29(c.)
front of the ur�nal.
������ Proviae a clear area under the lavatory of
2 9 inches. Fig. 31
A clear area of 30 X 48 inches is required in
�-- Seco 4al9e3 & Figs 32
The bottom of mirror is required to be within
�- Sec. 4.19.6 & Fig. 31
front of
40 inches
the lavatory.
of the floor,
1%
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address,: 871 S0. YELLOWSTONE
DRAFT STOPS ea
If there is combustible construction
in the f loor/ceilinq assembly . draft
stops snall be installed so that the area of concealed �space doe9
s not^T
exceed 1000 square feet and so that the horizontal dimension between stops
does not exceed 60 deet. -- Sic. 2516e(f)4*Ao(111)
If there is combustibly construction in the roof /ceilina assernbly_ car -Aft
stops shall be installed so
exceed 3Q00 square feet and
does not emceed 6 0 feet . --
OCCUPANCY SEPARATIONS
B1 -B2 1hr Offices
separation.
Bl -H4 1 -hr
B2 -H4 1hr Off
.ices
separation.
ADDITIONAL SEPARATIONS
FOR B 1 OCCUPANCY:
I
that the area of Concealed space domes not
so that the horizontal dimension between stops
Sec. 2516.(f)4,B.(ii1M)
-- Table 5---B
less than 25%
-- Sec. 503.(a)
of ma � or use do not require a
ex # 2B
less than 25% of major use do not require a
-_ Sec. 503. (a) ex #2B
ii, -Lnr- occupancy separazion
is requirea
around rooms
containing a
boiler or
central heating unit
greater than
400,000 BTU
input. -- Sic.
708.
Storage areas in excess of 100D sq. ft. are required to be separated from
the retail area by a 1hr occupancy separation. --- Sic. 742.(b)2.
FOR B 2 OCCUPANCY;
�, .Li�L u�;�:u,�a�dc:y 5epdr�a-civn
is �-equirea
around rooms
containing a
boiler or
central heating unit
greater than
400,000 BTU'
input. -- Sec.
7081,
Storage areas in excess of 11000 sq.ft, are required to be separated from
the retail area by a 1hr occupancy separation. -- Sec. 702.(b)2,
FOR H4 OCCUPANCY ;
A 2hr occupancy separation
central heating unit.
is required around reams containing a bailer or
r w Sec • 908 i
EXIT REQUIREMENTS:
FL NAME OCCUPANT NUMBER EXIT PANIC RATED DOOR MOTES
LOAD REQUIRED WIDTH HDWR CORRIDOR SWING
-------------------------------------------------------------------------------
2 PARTS STORAGE * 5 1 0.01 No No N/R
2 LUNCH RMIREC*STORAGE* 8 1 0:01 No NO N/R
2 Locker Room * 10 1 0.92 No No N/R
TOTAL 23 2 0.6 No No N/R 1
1 Retail Sales Room * 93 2 1-e6 No Yes Out
1 CAR SERVICE AREA * 47 2 0,M8 No Yes N/R
1 OFFICES * b 1 0.1 No No N/R
1 PARTS STORAGE * 9 1 0.2 No No N/R
1 BODY SHOP * 18 2 0.3 No No Out 8
1 TRUCK SHOP * 16 2 0.3 No No Out 8
TOTAL 189 2 3.2 No Yes Out
Cade review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
NOTE This area is being treated as an accessary f or 4ccupant loads.
-_ Sec - 3 3 0 2. (a) exception
Rated corridors are to have 1hr f
ire protection an both s 'deg of walls
Ceiling. --� pec . 3 3 0 5 . (a) no�r openings are regt�ired to be prot
and 20 minute assemhl�.es and�aindvw openings are reuirpr�
with labeled 3�4 hc�uwith
� assemblies.
cr
Elevators vper�ing into a rated corridor
I-obbv at PA, -4h -Pi I
sec, 3305. (h)
shall
�-+��� �=�n�a�n�.n�} a rated corridor, �rov�ded
Walls and openingsbetween the carridvr and the __ Seg.
required to be per sections 3305, elevator
(g} and 3305.(h) above.
• i"
acted.,
protected
With an elevator
3305,6(l)
lobby are
In meas where 2 exits are required, the minimum s�para�ion
maximum diagonal of the area or floor:. �-- Sec. 330 3 ,
Emit signs �r� requ required from all areas serving an �accu (c)
an
__ sec. 3 314. (a) p �
Door swing is basted. on Seca 3 3 Q4 . ( b ) except as noted .
Occup�nt load is based an Table 33-A.
Number of exits is basted on Tables 33-A except as noted.
Exit width is in feet and based on SEc, 3303 . (b).
Emit width isto be divided a�,�,^�,F;���-n I
is 1/2 of the
1oad of 5 0 or more ,
'- y ,:�-
uaiiy
width Shawn for all areasis~basec��om�a�therqexits,among exits.,
Width shown for 1s,t floor is used an other exits, (0.2)
Width shown f or other flours & basements is basted c�n0stai
For the minimum width of doors, see Sec. 3304*(f}
For the m�nimum width of corridors, see Sec. 3305.(b)
For the minimum width of stairways, sem Sec. 3306.(b)
FOOTNOTES
1) The second f loor is required to
is 10 or more. --- Sec. 3303.(a)
S) The number of exits is based an
HANDICAPPED ACCESS:
1) Handicapped access
to this building.
2) If a ramp is used
ft
is
MORM�
for
rways.
h-aVe 2exits when the Q.vad
Sec. 3 319.
required to
Sec. 3103, (a)
handicapped
,>eC 3307. (c)
Handicapped access may not be
entry level* --- Seco 3103(a)
at least one primary entrance
& (b)3m
access, the max slope is
required to levels other than the primary
exc # 2
Cede review for: page # 5
Project Id.: TAYLOR CHEVROLET LXPANSIDN
Address: 871 5O. YELLOWSTONE
STAIR NOTES,*
The maximum rise of a step is 7 inch -es and the minimum run is
-- Sec.. 3306. (c)
TY�e -Minimu.m width of a stairway is 36 inches, 44 inches.
is greater than 49. -- Sec3306.(b)
Also see ex�.t table above to see if minimum width
Provide handrails on both siders of a stairway 34 to
(May be an one side if less than 44 inches wide)
Provide a guard rail where drop off is greater than
if toccupant load
is greater than 44 inches.
3 8 inches above the nosing,
336.(3)
30 inches. Minimum heig
ht
42 inches, maximum opening � 4 inc�.es.
The m�niinum headroomis E ftemon 8 inches, -- Sec.
R"i"TnC9nhA "it4ni"O 10 1
-- Sec. 1712. (a)
3306. (0)
unu.Ft..e -cne S 4+L.lirs 1a7 i.. AniiirGA
I or lair fire-��S 15�1'V'2 ct]l"15t�'L�C�1Qn . s -e"
Provide a landing withzn 1
access) of the threshold..
9 0
1 - [ i o '1'1i 1 i1 '1 7!R .2* -' --
Sec. 3306. (1)
be protected as required
inch (1/2 inchr
_� sed for handicapped
Sec. 33�4.(i)
w1E�C�I lS S[3.fi� as i'��C'�rl'f"
__ Sec,, 3304,(j)
The maximum travel
_-� sec. 3303.(d)
- CIA AA LIl
e minimum length is 44 inches,
distance in:Ps building �.s 150 feet.
ROOFING REQUIREMENTS:
1) The roofing on this building is required to be Class C -- Table
2) See section 3204, and ICBG research reports for requirements.
AUTOMATIC SPRINKLER SYSTEMS:
If openings are not -rouTanA
32-A
�cL %':I� �u reer of exterior wall or there is
floor area more than 75 feet from an exterior opening, an automatic
sprinkler system is required. -- Sec. 380�.{b}
An automatic sprinkler system is required in retail saps rooms with a
floor area greater than 12,000 sq.ft. -- Sic. 3802.(d)
An autamatic sprinkler system is requ�.r�d in an H4 c�ccupanc more than
30Uv square feet. -� Sec. 38Q2 . (f ) 2 Y
If there are loo or more sprinklers, the automatic sprinkler system s
supervised by an approved cental ryprietary,� hall tae
or a Iocal alarm. which. will gi�re an�audible signal at ����i°n service
attended location, -�-- Sec. 3803,
� constantly
STANDPIPE REQUIREMENTS:
A class II standpipe is required. -- Table 3 8 -A
A hose is required. -- Table 38-A
FOOTNOTES:
1) The location is to be per Sec.
Code review
Project Id.;
Address: 871
38o5.(c),(d),and/or (e)
for: Page # 6
TAYLOR CHEVROLET EXPANSION
SO. YELLOWSTONE
WALL AND CEILING FINISH:
Z} Wall and oiling finish materials are required to comply with
Sec-* 4204.(a} and Table 42-5.
2) Carpeting an the ceiling is required to have a Class I flame
spread rating. -- Sec. 4204.(b)
3 Textile wall coverings shall have Class I flames spread rating,
and shall be protected by automatic sprinklers or meet the
acceptance criteria of U.B.C. Standard No. 42-2 --- sec. 4205.,
INSULATION NOTES
1 ) A.11 insulation material including facings are required to have a flame--
spread rating 4f 2-5 yr less and a maximum smoke density of 450 unless
it is in a concealed space and the facing is in contact with a wall or
ceiling. _~ Sec. 1714.(C) enc.#2
2) Foam plastic insulations are required to be protected. -- Sec. 1713,
GLAZING REQUIREMENTS:
All glazing in hazardous
glazing material. -- Sec.
ADDITIONAL REQUIREMENTS:
For B1 occupancy
locations is required to be of safety
5406 a (d)
Devices generating a glow or flame ars required t.o be is inches above
the floor,. -� Seg. 708.
The minimum clear height is required to be 7 feet, -- pec, 709 . (c) 5.
Parking garages require a ventilation system that exhausts 1,.5 cpm
per sq . ft . of floor area,, -- Sec. 705.(b) 2.0
For B2 occupancy
In all aromas customarily
artificial light
occupied by humins, provide natural or
and ventilation. �- Sem. 705, ( a ) & ( b)
For H4 occupancy
If required by the Fire Code,, spil.i cantrvl,
shall be provided, --- Sec. 902.(c),
Smoke and heat venting shall be provided as
Cade. -- Sec. 902.(f)
drainage, & containment
(d) & (e)
set Earth in the Fire
uev_Lces generaring a glow or flame are required to be 18 inches above
the floor. -- sece 908.0
�. ve"tilativn system that exhausts 1.0 cfm per sq , ft . of
An exhaust pipe is also required at each stall..
905 . (c)
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
HANDICAPPED REQUIREMEATTS:
NOTE: Section numbers listed below
WATER FOUNTAINS:
f 100
-"&- Sec.
are from ANSI A1.17.1 - 1986
1 ) One must have. a spout within 36 inches of the floor:, ---- Sec. 4,15.2
2) Spout must be at the front of the unit, --- Sec. 4.15.3
3) Controls must be at or near the front of the units -- Sec. 4.15.4 & 4*25*4
4 } A cantilevered unit is required to prov de a clear area under the unit of
22 inches high, 30 inches wide, and 17 inches deep. --- Sec. 4.15.5 (1)
5) A dear area of 30 X 48 inches is required at the fountain. The clear
area is required to provide for a forward approach with a cantilever�ad.
unit and for a side approach otherwise, --- Sec, 4.15.5 & Fi *27 bfcrd
TOILET FACILITIES
1) A `5' diameter unobstructed turning space is required in the toilet room.
Sec. x.2.3 & Flogs 3(a)
2) When wader closet is not in a compartment, the clear area required is:
a) 4$ inches wide by 56 inches deep with a side appraac�. 0.
-- 10c%:. 4.
io. u
a r'igo
28
b) 4 8 inches
wide
by 66
inches
mmp- Sec. 4.16.2
& Fig.
28
C) 60 inches
wide
by 56
inches
deep with a front approach.
deep with doth approaches
.
3)
ft-- sic. 4.36. 2 & Fig. 28
d) Side bar is required to
extend t0 54 inches from
The rear hay- is ret�ui red
WIhCM
tart within 12 inches of the back wal
the back wall. -- Sec. 4.16.4 & Fig.
to be 36 inches lona_ -- V;n
1 and
29
i S in a compartmen.. , the area requiredisa} 5+5 inches deep by 60 inches wide with a grab bar at
at the side. Door is at front or side. - the back and ���
b) X56 inches deep by 36 or 48 inches wide wi�n�l30(a)
bars or
and door a� front . ---� Fige 30(b) grab on bath s ices
mounted water closet is used, the depth dimension
shown wave mint be increased 3 inches. --
- Fig. 30(a) & (b)
e) Side harms are required to start with.�n 12 inches of the back w
extend t0 54 inches from the back wall, -- Fig. 7o56& & 7*56b
X11 a'�'he rear bar is r�:quired tc� stawithin 6 i�.ches of the sidw
and be 36 inches 1 nr," _ _�. ,�4 ,� .,,,. _ . ail
The
4) The bars are to be 33 to36 inches above the
Fig. 30(c),(d51 tnn of +ro.>
floor., -- Fig. 29(a),(b) &
vr� zne wate�- closet is required to be �.7 to �.�
�above the flc�ar. -- dig. 29(b) & Fig. 3D�d)
�.T�'inals are rPrngi�-ewi ��, v. -
inches
-� "���� Hype a�' have an elongated rim and be
within 17 inches of the Elaut. -� Sec. 4,18.2 & Fig. 29(c
7 } A clear area of 30 X 48 inches is required in f rond o� the u�'
-- Sec. 4.18.3 urinal
S Accessible lavatories shall Provide
c
29 W41 n!Nfd a
m
10)
-
oCc.
4.15�.�.1
& Fig. 31
A clear
dYAA
of '2A
Y
n e
:._..ti
_
under the lavatory of
Sec,. 4.1.3 & Fig. 32 Illulles is required in fromof the lavatory.
The bottom of mirror is required to be within 40 inchespec. 4.19.6 & Fig -9 31
of the door.
City of Rexburg
Engineering Department
12 North Center/P.O. Box 280
Rexburg, Idaho 83440
(208) 359-3020
the
R07 PI- z
�Y.
Plan analysis based on
1991 Uniform Building Code
rrc,lcc:L rvumDer: taylcllevName:
Address: 871 SO. YELLOWSTONE
Occupancy: B1,B2,H4;B1,H4,H2,B2
Type of Con
sto V-lhr,,V-lhr,
TAYLOR CHEVROLET EXPANSION
Date: June 25,
NOTEeThe code items fisted in this report
listing of all passible code requirements
selected sections of the rode.
Report created wing Plan Analyst software
Portions of the material contained in this
Uniform Building bode E 1991 editions with
Conference of Build
SECTION # 1
ing �ff.�cials.
SEPARATION
DIRECTION BOUNDARY AREA INCREASE
NORTH Property line 13 0. 0 Feet
EAST Separation wall o_n FPP+-
SOUTH Property line
WEST Public way
.9
120.0
180-00
Area increased 100*00% for
Nam
Feet
deet
area
1995
c:onLractor: GENE PALMER CONST.
Designer: GENE PALMER
Engineer: NONE
Plans Examiner: JOE LAIRD
are nab in ended to be a complete
in the 1991 UBC. It is a guide t�
by b w & a. (719) 599-5622
program are reproduced from the
permission of International
FIRE PROTECTION
13 0. 0 Feet
0. 0 Feet
120. 0 Feet.
140. 0 Feet
on 3 sides.
FF'Nwab � ALLOWED RATIO STATUS
------------NAMEOCC MAX FLR AREA
-----------
--------------------------
�=06 mobil
2 PARTS STORAGE B2 ok 1601 28000� o 06 ok
2 LUNCH RM,REC.STORAGE B2 ok 800 28000 0.03 ok
2 Locker Room B2 ok 48Q 28000 0.02 ok
TOTAL FOR FLOOR
1 Retail Sales Room
1 CAR SERVICE AREA
1 OFFICES
1 PARTS STORAGE
1 BODY SHOP
1 TRUCK SHOP
TOTAL FOR FLOOR
BUILDING TOTAL
Z�s�sl Lzsooo 0.10 ok
132 ok 2800 28000 0.10 ok
B1 ok 9450 28000 0.34 ok
BZ ok 630 28000 0.02 ok
BZ ok 2572 280000.09 ok
H4 ok 3575 17600 0.20 ok
H4 ok 3200 1760.0 0.18 ok
22-227 23727 0.94 ok
25108 48299 0.52 ok
a
Code review for: Page # 2
Project Id..:TAYLOR CHEVROLET EXPANSION
Address,* 871 SO. YELLOWSTONE
The actual height of this building is 20. 0 feet.
The maximum height of the building is 50. 0 feet. -- Table 5-D
EXTERIOR WALL FIRE RATINGS AND OPEATING PROTECTION
Table 17-A & Table 5-A
Exterior wall ratings for H,-oc p ncies are based on Table 9.%-C
SOUTH
BRG NON-BRG OPNG
WALL WALL PROT
1hr
1hr
1hr
WEST
BRG NON-BRG OPNG
WALL WALL PROT
1hr
None
NORTH
1hr
1hr
EAST
1
OCC
BRG
NON-BRG OPNG
BRG
NON-BRG
OPNG
B1
B2
H4
WALL
1hr
1hr
1hr
WALL
1hr
1hr
1hr
PROT
None
None
None
WALL
S.W.*
S.W.*
S.W.*
WALL
S.W.* S.W.
S.W.* S.W.
S.W.* S.W.
PROT
SOUTH
BRG NON-BRG OPNG
WALL WALL PROT
1hr
1hr
1hr
WEST
BRG NON-BRG OPNG
WALL WALL PROT
1hr
None
1hr
1hr
1hr
None1hr1hr
1
hr
1hr
None1hr1hr
1
hr
The exterior walls may be of COMBUSTIBLE material. Sec.2201.
None -- No fire p�otectian requirements for openings.
Prot �- i)C]P_1'11 i"3[`y'c arra to i�,� �,•,,...,.��.....��a __! .. . _ _ .
�0�
None
mane
None
N--; NLu�.en.;c.�u w,�Ln j/4 nr tire assemblies. 50o a�' the
area of the wall maximum. Sec., 504,, (b) & Sec.2203, & Table 5-A
Maximum single window size is 84 sq.ft with no dimension
greater than. 12 feet. -�- Sec. 4306.(h)
NDP --- Openings are not permitted. in this walk..
* -- These walls may be require, to have a parapet wall 30
above the roofing. the parapet wall is required to have the
fire rating as the waZ1, dee section 1710* for details and
ELEMENT
OTHER BUILDING ELEMENTS
Interior Bearing wall
interior nonbrg wall
Structural Frame
Exterior Struct Frame
Shaft Enclosure
Floor/Ceiling Assembly
Roof /Cei�.inc� Assembly
stairs
M^W W :"a W. Awl 1.
Any
Any
Any
Any
Anv
Any
Any
Any
Table 17-A
RATING
1
hr
1
hr
1
hr
1
hr
1
hr
1
hr
1
hr
None
N OTES
inches
same
exceptions.
Footnote # 5
f ootnote #i
see ovtnvte � 9
NOTE . See Sec. 1706. (a) for Shaft Enclosure exceptions.
FOOTNOTES ;
1} Elements in an exterior wall located where openings are not permitted
where protection of openings is required, shall be protected against
external fire exposure as required for exterior bearing walls or the
structural frame, whichever is greater, __ Table 17 --*A, footnote 1
5 } Nonload-bearing walls within a tenant spaces that ars nv-k part of a
1hr corridor may be of
�. } Noncombustible (nonrated) m�.-�eri aI s
b} Fire retardant -treated wood
C) +ane-Oneconstruction T (any matel'1r31) �_ Sec. 1705,(b)l,
9} In areas with vehicles yr airplanes, the floor surface shall be of
nvncombustible, nonabsorbent materials. -w Seg. 7a2.(c) & 9�2,w(b)
W
Code review for w Page # 3
Project Ick.: TAYLOR CHEVROLET EXPAr►TSIQN
Address: X71 SQ. YELLOWSTONE
DRAFT STOPS:
If there is combustible construction in the floor/pealing assembler, draft
stops shall be installed so that the ara v� concealed spaces does not
exceed 10x0 square feet and so that the -horizontal dimension between stops
does not exceed 60 deet . MM Ulm Sec . 2516 . ( f ) 4 . A . ( iii
If there is combustible construction in the roof /���.1ing assembly, draft.
stops shall be installed so that the area �f concealed spare does not
exceed 3040 square feet and so that the horizontal dimension between staffs
does not exceed 60 feed. -- Sec. 2516,D (f 4,a B a (iii)
OCCUPANCY SEPARATIONS -- Table 5-B
Bl -B2 1hr offices less than 25a of major use do not require a
separation. Sec. 503o(a) ex #2B
B1 --H4 1 -hr
B2 --H4 1hr offices legis than 25s of mayor use do not require a
separation, -� Seco 503*(a) ex #2B
ADDITIUNAL SEPARATIONS
FOTO B 1 OCCUPANCY
A 1hr occupancy separation i.s required around rooms containing a boiler or
central heating unit greater than 404,t300 BTU input. -- Sec. 708.
Storage areas in excess of 1000 sq.ft, are required to be senarated frnm
the retail area by a itir occupancy
FOR B 2 OCCUPANCY ;
A 1hr occupancy separativn is required
central heating unit greaten than
Storage areas in excess of 10D0 sq.ft«
i--- -, �" -��
separation . Sec . 702 . (b) 2 .
around roams contain1k
ing a boiler or
400,000 BTU input. �M" Sec. 708,
are ret1U i rpa ccs.-.�,.•. -.�..a
the retail area by a 1hr occupancy sep►a�ation . --- See , 702 .� (b) �
FOR x4 accuF�,xc�
A Thr occupancy separation is required- around rooms containing a boiler car
central heating unit, -- Sec. 908,
SECTION ,y 2
DIRECTION BOUNDARY
NORTH Property line
EAST Property line
SOUTH Property line
WEST Separation wall
AREA INCREASE'
Area increased 100*00% for
FL
NAME
50.0
70.0
200.0
0.0
open
Fejt
Feet
Feet
Feet
area
FIRE PROTECTION
15.0 Feet
70.0 Feet
120. D Feet
o,o Feet
an 3 sides.
OCC MAX FLR AREA ALLOWED RATIO STATUS
----------------
PNT * SPR -a PREP AREA, H4 ok 960 17500 0.05 ok
1 PAINT BOOTH B1 ok 190 28000 0.01 ok
1 PAINT MIXING H2 pk 110 8800 0.01 ok
1 Mechanical Room B2 ok 110 2 8 0 0 0 0.00 ok1 REASSEMBLY ROOM B1 ok 1030 28000 0.04 ok
TOTAL FOR FLOOR 2400 20952 0.11 ok
$UILDING TOTAL
2400 20952 0.11 ok
Page # 4
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
The actual height of this building is 2 0. 0 feet.
The maximum height of the building is 50. 0 feet. -- Table 5-D
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 17-A & Table 5t --A
Exterior wall ratings for H -,-occupancies are based on 'Table 9-C
NORTH EAST SOUTH
OCC BRG NON-BRG OPNG BRG NON-BRG OPNG BRG NON-BRG OPNG
WALL WALL PROT WALL WALL PROT WALL WALL PROT
B1 1hr 1hr None 1hr 1hr None 1hr 1hr None
H4 1hr 1hr None 1hr 1hr None hr lhr None
H2 1hr 1hr None 1hr 1 h None 1hr 1hr None
B2 1.hr 1hr None 1hr 1hr None 1hr 1hr None
The exterior walls may be of COMBUSTIBLE material. Sec.22016.
'one --- No fire protection requirements for openings,.
WEST
BRG NON -BRC OPNG
WALL WALL PROT
SROW
W. *
S
.0 W-8 *
S
ewiw *
S
a Ww *
S.W.*
S.W.
S.W.*
S.W.
S,W
W's *
S.
W.
S.W.*
S.W.
,. ..��..�...�� YL v ce-czea wizn J 4 nr tire assemblies . 50% of the
area of the wall maximum. Sec. 504.(b) & Sec.2203, & Table 5-A
-b
Maximum single window sire is 84 sqo ft with no dimension
greater than 12 feet. -- Sec. 4306.(h)
NOP -- Openings are not permitted in this wall.
These walls may be required to have a parapet wall 30
above the roofing. Thep�.rapet wall i s required to have the
fire rating as the wall. See section X710. for details and
ELEMENT
OTHER BUILDING ELEMENTS Table 17-A
RATING
1 hr
1 hr
i hr
Interior Bearing wall
Interior nonbrg wall
Structural Frame
Exterior Strutt Frame
Floor/Ceiling Assembly
Roof /Oiling Assembly
Stairs
FOOTNOTES 0
1)
5)
MATERIAL
Any
Any
Any
Any
Any
Any
Any
NOTES
inches
same
exceptions.
i n See
l hr See
1 hr
Nine
f C3otriate #1
Footnote #9
in an exterior wall located where openings are not permitted or
where protection of openings is required, shall be protected against
external fire exposure as required for exterior bearing walls or the
structural f rame, whichever is greater. -- Tables 17-A . fnn-l-nrsi-,�
Nonlvad--bearzng walls within a tenant space that
lh�r corridor may be of
a) Noncombustible (nonrated) materials
b) Fire retardant -treated wood
c) One -&-hour Construction (any material ) MEOW in areas with vehicles or airplanes the floor
noncom
bustible� nonabsorbent materials. -- Sec.
are not part of a
Sec. 1705. (b) 1.
surface shall be of
702. (c) & 902.(
b)
CC}CIe review
Project Id.:
Address: 87z
for:
TAYLOR CHEVROLET EXPANSION
S0. YELLOWSTONE
If there is combustible construction in the roof/ceiling assembly, draft
stops shall be installed so that the area of concealed space dogs not
exceed 3000 square feet and so that the horizontal dimension between stop
does not exceed 60 feet. --
Sec. 2516.(f)4.B.(iii)
OCCUPANCY SEPARATIONS -- Table 5-B
B1 -H4 1hr
B1 -H2 2hr
B1 -B2 1hr
H4 -H2 1hr
H4 --&B2 1hr
H2 -B2 2hr
ADDITIONAL SEPARATIONS
FOR B1OCCUPANC'Y,,
A 1hr occupancy separation is required around rooms containing a boiler or
central heating unit greater than 400,00-0 BTU input. -- Sec. 708.
FOR H4 OCCUPANCY:
A 2hr occupancy separation is required around rooms containing a boiler or
central heating unit. -- Sec. 908.
FOR H 2 OCCUPANCY:
A 2hr occupancy separation is required around rooms containing a boiler or
central heating unit. -- Sec,, 9a8,
There shall he no openings in such occupancy separaion except for necessary
ducts and piping. -- Sec. 908.
FOR B 2
OCCUPANCY:
A 1hr occupancy separation is required around rooms containing a boiler or
central heating unit greater than 400,000 BTU input. -- Sec. 708.
SECTION # 1
EXIT REQUIREMENTS:
FL NAME OCCUPANT NUMBER EXIT PANIC RATED DOOR NOTES
LOAD_ REQUIRED WIDTH HDWR CORRIDOR SWING
-----------
2 PARTS STORAGENNW
*--------
5 1 0.1 No No N/R
2 LUNCH RM,REC.STORAGE* 82 i 0.1 No No NIR
TOTAL Room * 10 1 0-o2 No NoN/R
1 Retail23 2 0Sales Room * .6 No No N/R 1
93 2 1-e6 No,Yes Out
1 CAR SERVICE AREA
47 2 0,08 No Yes Nig
1 OFFICES * 6 1 0. 1 No No N/R
1 PARTS STORAGE 9 1 0 * 2 No
1 BODY SHOP * 18 2No
0.3 No No Out 8
1 TRUCK SHOP * 16 2
TOTAL 189 2 0.3 NO No Out $
3.2 No Yes Out
A
Code review
Project Id.
Address : 871
for:
TAYLOR CHEVROLET EXP7iNSION
S0. YELLOWSTONE
+�. t
* NOTE: This area is being treated as ori ��GeSS�ry tor OCCUPant 10adS�
_� Sect 3302*(a) exception
Rated corridors are to have.
1hr fire protection on both
sides of walls and20ceiling. M-- Sic. 3305•(g) Dovr Qpeninc�s �.re required to be protected.
with �minute assembli�s and window openings are require. to bewith labeled 3j� hour assemblies. --- Sec. 33�35,(h) protected
Elevators openinginto a ratted corri.dor shall be provided with an elevator
lobby at each floor containing a rated corr�
Walls and openingsdar.Sec. 3305,,(
openings between the corridor and the eleva� y
required to be per sections 3305.(g)
Qr lobby are
and move,
In areas where 2 exits are required, the minimumration is i/� of the
maximum diagonal of the area or floor, -�- Sec. 3303 . (c)
Exit signs are required from a.11 areas serving an occupant load of 50 yr m
�-- Sec. 3314 . (a)
v�-e ,
Door swing is based on Sec. 3304. (b) except as noted.
Occupant load is based. on Table 33-A.
Number of exits is based on Table 33--A except as nQted.
Exit width is in feet and based on Sec. 3303.(b).
Exit width is to be divided approximately equally among exits,
Width shown for all areas is based an other exits. (0.2)
Width shown for 1st floor is based an aer exits. (o.2)
Width shown for other floors & basementsis based on stairways .p . 3
For the minimum width of doors, see Sec,. 33-04.(f)
� �
For the minimum width of corridorssee Sec* 3-3u!3.,(b)
For the minimum wFI
idth. of stairways, see Sec, 3306.(b)
FOOTNOTES
1) The second floor is required to haus 2 exits When the occupant load
is 10 or more. --- Sec, 3303.(a)
8) The number of exits is bayed on Sec. 33190
HANDICAPPED ACCESS:
1) Handicapped access is
to this building. --
2) If a ramp is used for
16@12a -- Sec 3307,(c)
required to
Sec. 3103 . (a)
handicaw%Vped
at least
& (b) 3
access ,
one primary entrance
the max slope is
nal��..�ua�,pea access may not be required to levels ether than the primar�r
entry level, --- Sec. 3103(a) e�€c #2
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 87I SO. YELLOWSTONE
Pace # 7
STAIR NOTES.,
The maximum rise of a step is 7 inches and the minimum run is 11 inches.
0
--- seg. 3306.(c)
The minimum width of a stairwaY is 36 inches, 44 inches if the occupant load
is greater than 49. -- Sec. 3346.(b)
Also see exit table above to see if minimum width is greater than 44 inches.
provide handrails on both sides of a stairway 34 to 38 inches above the nosing
(May be on one side ifless than 44 inches wide) -- Sec. 3306.(j) s
Provide a guard rail where drop off is greater than 30incheso minimum height
�-
42 inches, maximum opening size -= 4 inchesS --- Sec . 171 2 , (a)
The minimum he�.dra�om i s � ft . - 8 inches... -- Sece 3306:.(o)
Enclosed usable space under the stairs is requiredto be protected as requzred
for 1hr fire -resistive construction. --- Sec, 3306,(J)
Provi de a landing within 1 inch (1/2 inch at doors used fog handicapped
access) of the threshold. -- Sec_. 3304.(i)
The minimum width is same as dace width and the minium length is 44 inches.
-M-" Sec. 3304. (j)
The maximum trammel distance in this building is, 15Q feet.
--*- Sec. 3303.(d)
ROOFING REQUIREMENTS
1) The roofing an this building is required to be Class B or better.
---- Table 32�A
2) dee section 32D4, and ICBG research reporter for requivrements.
AREA SEPARATION WALL REQUIREMENTS
1 j The area separation wall is required to be a 2 hr fire assembly.
-- sec. 505, (f)2.
2) If the building has aprvjectian,with congealed space at the area
6.
separation wall, 1hr protection is required an the projecti-on and
the exterior wall each side of the area separation wall equal to
the depth of the pro&ect�ivnsec. 505(f)3,
3) If the area separation wall terminates at an inside corner, see ICB0
article in 'Building Standards' Sep/Oct 1982 for requirements.
0
4} A 30 inch high parapet wall is required above the roofing, -- sec.505.(f)4,
See exceptions for alternate protection at roof.
AUTOMhATIC SPRINKLER SYSTEMS..6
If openings are not provided in each 54 feet of exterior wail or there is
floor area more than 75 feet from an exterior opening, an automatic
sprinkler system is required. -- Sec.0802(h}
An automatic sprinkler system is required in retail gales rooms with a
floor area greater than 12,000 sq,ft. --- Sec. 3802.(d)
An automatic sprinkler system is required in an H4 c�ecupancy more than
300Q square feet. --- Sec. 3802.(f)2,
if there are 1Q0 or more sprinklers, the automatic sprinkler system shall be
superv�sed by an approved central, proprietary, car remote station service
or a local alarm which will give an audible signal at a constantly
attended location, -- pec. X803,
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
IT.F. M�FJW.04,
STANBPIPE REQUIREMENTS:
A class II standpipe is required. -- Table 38-A
A hose is required. -- Table 38-A
FOOTNOTES:
i) The location is to be per Sec. 3805. (c) , (d) and/or(e)
WALL AND CEILING FINISH;
1 } mall and ceiling f finish materials are required tO comply with
Sec. 4204. (a) and Table 42-B.
2 ) Carpeting on the ceiling is required to have a Class I flame
spread rating. -- Sec. 4204.(b)
3) Textile wall coverings shall have Glass I flames spread rating,
and shall be protected by automatic sprinklers or meed the
acceptance criteria of U.B., Standard No. 4Z--2 ---- Sec. 4205..
INS'ULATION NOTES
1} All insulation material including facings are required
spread mating of 25 or less and a maximum smoke density
it is in a concealed spare and the f acing is �.n contact
ceiling. -- Sec. 1714e(c) exc,#2
2) Foam plastic insuiativns are required to be protected,
GLAZING REQUIREMENTS:
All glazing in hazardous
glazing material. -- Sec.
ADDITIONAL REQUIREMENTS:
to have
of 450
W1 a
a f lame -
unless
wall or
-- Sec.. 17 13.
locations is required to be of safety
5406 9 (d}
For Sl occupancy
Devices generating a gnaw or flame are required to be 1$ inches above
the floor, -- Sec. 708.
The minimurm clear height is r� aired to be 7 feet.q -o_ pec. 709.(c)5,
Parking garages require a ventilation system that exhausts 1.5 cfm
per sq.f-t. of floor area. -�- Sec, 705.(b) 2.
For 82 occupancy
In all areas customarily occupied,by humans, P OVie natural or
artificial l�.ght and ventilation. -- Sec. ) (b)
For H4 occupancy
If required by the Fire Cade, spill control, c�rainage, &
shall be provided.. -- Sec. 902 (c)► (d). & (e)
Smoke and heat venting shall be provided as set Earth in
Code. --- Sec. 902.(f)
Devices generating a glow or flame are regt�ired to be 18
the floor. -- Sem. 908.
A ventilation system that exhausts 1. 0 cfm per sq. ft. of
An exhaust pipe is also required at each stall.
905. (c)
Cede rear i ew far-0
Project Id.: TAYLOR CHEVROLET EKPANSION
Add-ress-o. 871 So. YELLOWSTONE
containment
the dire
inches above
floor
�� Sec
area.
:
HANDICAPPED REQUIREMENTS
rurr:: 5ecr.ion numbers listed below are from ANSI A117.1 - 1986
WATER FOUNTAINS:
1) One must have a spout within 36 inches of
2) Spout must be at the front of tr,P
3)
4)
Controls
A cantilevered
h'a
igh,
9
the floor. -- Sec. 4.15.2
Sec. 4.15.3
mush be at or near thp front of -t-ha "r,i *
27
5J A
inches
.0
unit is required to provide a clear
30 inches wide, and 17 inches deeD.
MEW 0" S ec. 4.15.4
area under the
-- Sec, 4.15.5
vicar- arra nr _� ., ..
& 4.25.4
unit of
(1)
--~� � i � v = u �-�l��l�� � � � �y,ul.cea a� ane t ountain . The clear
area is required to Provide for a forward approach with a cantilevered
unit and for a sides approach otherwise. �-- Sec. 4,15.5 & Fige27 b,c,d
TQILET FACILITIES:
1) ,A 5' diameter unobstructed turning space is required in the toilet room.
_- sic. 4.2.3 & Fig. 3(a)
2] When water closet is not in a compartment, the clew area required is:
a) 48 inches wide by 55 inches deep with a side approach,
WNW _ sec. 4.15.E & Figs 28
�i) 48 inches wide by 6 6 inches deep with a front approach.
_- Sec. 4.1G.2 & Fig. �8
C) 50 inches wide by 5 6 inches deep with both approaches.
pec. 4.16.2 & Fige 28
d) Side bar is required to start �r�rit�.in 12 inches of the back wall and
extend to 54 inches from the back wall. -- Sec. 4. 16. 4 & Fig. 29
The rear bar i5 required to be 35 inches long. -- Fid. 29
3 } When water closet is in �. compartment, the area required is:
a) 56 inches by 60 inches wide with a grab bar at the back and one
a-� the side. Door is at front or side. -- Fig. 30(a) or
b} GF inches deep by 36 or 48 inches wide with grab bars on both side
JL. ." L.Lullum �� rigs Ju(n)
d} 3f a floor mounted water closet is used, the depth dimension
shown above must �e in��eased 3 inches. -- Fig, 30(a) & (b)
e) Side bars ars reauirP,� tri �ta�+ r.�; }I,;,� _ � _ _
YYJ' -,.jj .Lc incnes yr 'Crib back wall arid.
expend to 54 inches from the back wail. -- Fig. 7.56a & 7.56b
The rear bar is required to start within 6 inches of the sideA n A --z r. ; Ift
wall
tL41z> -Lunys �Mkfl= Ylgo 30(a)
4) The bares are to be 33 to 36 inches above the floor. --� dig. 29(a),(b) &
Fig. 30(c) , (d)
5} The top of the seat on the water closet is required to be 17 to 19inchesabove the flc�or. -- �iq. 29(b) & Fig, 3Q(d)
6Urinals are required to be stall tvne or have an elongated aim and be
within 17 inches of the floor. --- Sec. 4.18.E & Fig. 29(c)
7) A clear area of 30 X 48 inches is required in front of the urinal.
-- Sec. 4.18.3
8 Accessible lavatories shall prc�vi�.e a clear area under the lavatory of
29 inches . -- Sec. 4,19.2..1 & Fick. 31
9 ) A clear area of 30 X 48 inches is require in front of the lavatory,
-- Sec. 4.19.3 & Fig. 32
loj The bottom of mirror is required to be within 40 inches ❑f` the fluor.
Sec. 4.19.E & Fig. 31
Cade r+�view
Project Id.;
Address: 871
for:
TAYLOR CHEVROLET
SO. YELLOWSTONE
SECTION # 2
EXIT REQUIREMENTS:
FL NAME OCCUPANT NUMBER EXIT PANIC RATED DOOR NOTES
LOAD REQUIRED WIDTH HDWR CORRIDOR SWING
MEN WW Mal. � 0� um am am ftM� �� � OEM, � � � � � � � &� mppw � N.. P.
I PNTmSPRePREP AREA * 5 1 0.1 No No Out
1 PAINT BOOTH * 1 1 0.0 NO NO N/R
1 PAINT MIXING * 1 2 0,00 Yes No Out 3
1 Mechanical Room * 0 1 0. 0 No No N/R
1 REASSEMBLY ROOM * 5 1 0.1 No No N/R
TOTAL 12 2 0.2 No No Out
* NOTE: This area is being treated as an accessory for occupant loads.
--- Sec. 33€ 2 . (a) exception
In areas where 2 emits are required, the minimum s�paratinr� is 1/2
maximum diagonal of the area or floor. -- Sec. 3303.(c)
Door swing is based. on Sem. 3304.(b) except as, noted.
Occupant load is based on Table 33--A.
Number of exits .is based an Table 33-A except as Hated.
Exit width is in feet and basted on Sec. 3303.(b).,
Exit width is to be divided approximately equally among exits.
Width shown for all meas is based on other exits . (0.2.)
Width snawr3 for 1st floor is basted on other exits. (0,,2)
Width shown dor other floors & basements is based an stairway.
For the minimum width of doors, see Sec. 3304,.(f)
For the minimum width of corridors, see pec. 3305.(b)
For the minimum width of stairways, see Sec. 3306.(b)
FOOTNOTES 0.
3) Panic hardware is based on Sec. 3319.
HANDICAPPED ACCESS:
1) Handicapped access is required to
11
to this building. -- Sec. 3 10 3. (a)
2) If a ramp is used for handicapped
1: 12. -- Sec 3 307. (c)
at least one primary entrance
& (b)3a
access, the max slope is
of the
Provide a lancing within 1 inch (1/2 idoors used for handicapped.access) of the threshoi�l -. - Sec. 3304.(j.)
The minimum width is same as dear width and the mindbwwwqimum length is 44 inches .
Sec. 3304.(j)
The maximum travel distance in this building is 150 feet.
-- Sem. 3303.{d)
The maximum travel distance within an H1,H2 or H3 occupancy is 75 feet..
-I- Sec, 3 319 _
ROC3FING REQUIREMENTS s
1) The roofing on this buildingis required to be Glaser B or better.
-- Table 32-A
2) See section 32Q4, and ICBO research reports for requirements.
Coda review for:
Page #
11
Project Id.: TAYLOR CHEVROLET EXPANSION
Address: 871 SO. YELLOWSTONE
AREA SEPARATION WALL REQUIREMENTS*
1) The area separation wall is required to be a
5 05.(f)2.
2) If the building has a projection with
seoarati on wa i 1 , ION _ _
2 hr firs assernbly,
concealed spa
--_ _ , 1{�L �,,� U L,�c:�lan IS required on the
the ��teriar wali each side of the area separation
the depth of the pra�e��ion.-- pec. 505 (f ) 3.
7 t rr iL
ce at the area
projection and
wall equal to
3 ) --L irn_ � area �eparativn wall terminates at an imide corner
articles in rSuild�Seploct, see ICBG
ng Standards'' 1g82 far requirements.
4 j A 30 inch high parapet Wall is requ-ired above the roofing5. Sec . 50
Sem exceptions fir alternate. protect ion at roof, � '�� ��'
AUTOMATIC SPRINKLER SYSTEMS:
If openings are not provided in each 50 deet of exterior walk. o�- there i
floor area more than 75 feet f �om an e�terior opening, an automatic �
sprinkler system is required. -- Sec. 3842. {b}
An automatic sprinkler system is required in H 2
Emomt
-
If
.�cc. Ji3UL.(LJ1.
SCC.
-1-- 1%
411w.L4' are IUu or more sprinklers, the automatic sprinkler system shall be
supervised by an approved central, proprietary, or remote station service
or a local alarm which will give an audibly: signal at a constantly
e
attended lo -cation'. -- Sec. 3803., �
STANDPIPE REQUIREMENTS:
There is no requirement for a standpipe. --- Table 38--mA
A hose is not required. -- Table 38-A
FOOTNOTES:
1) The location is to be per Sec. 380.5*(c),(d),and/or(e)
WALL AND CEILING FINISH;
1) Wall and ceiling finish materials are required to comply with
Sec. 4204. (a) and 'able 42-B.
2Carpeting an the celling is required to have a Class I flames
spread rating. "- 5eC, 42q4 a (b)
3 Textile wall coverings shah. haeme Class I flame
and shall be protected by automatic sprinklers
acceptance criteria of U.B.C. Standard No. 42-2
spread rating.
or meet the
--- sic . 05 o
INSULATIQN NOTES
1 } All insulation material including facings are required to have a flame --
spread rating of 25 or less and a maximum smoke density of 45U unless
it i R i n A rt^�ncealed space and the facing is in contact
ceiling, w-- pec. 1714.(c) exc.#2
2) Foam plastic insulations are required to be protected.
GLAZING REQUIREMENTS:
All glazing in hazardous
glazing material. -- Sec.
With a wall or
mmw� Sec. 1713ID
locations is required to be of safety
5406 w (d)
Code review for:
Project Id.: TAYLOR CHEVROLET EXPANSION
Address:: 8 71 S0. YELLOWSTONE
ADDITIONAL REQUIREMENTS.
For Bl occupancy
Devices generating a glove or flame are required to be 38 inches move
the floor. --� Sec. 708.
The minimum clear height is rewired to be ? fejt , --- Sec. 709. (c)5,
Parking garages require a ventilation system that exhausts 1.5 Cfm
per sq.ft. of floor area., -- Sec. 705 * (b) 2.
For H4 occupancy
If required by the Fire Codes, spill control,
shall be provided., -- Sec* 902.(c),
Smoke and heat venting shall be provided as
Code. --- Sec. 902.(f)
drainages &
(d) & (e)
set forth in
Gi1..1,13Lr� d q1vw or r iame are required to be 18
the floor, --� secs 9080
A ventilation system that exhausts 1.D cfm per sq,ft:.. of
An exhaust pipe is also required at each stall.
905. (C)
For H2 occupancy
if required bv the F i r� r.�a� �.,;Ti,-
can.ta inment
the Fire
inches above
floor
__ Sic,
- e �r,,� �.� ���� �.��� , arainage , & containment
shall be provided. --- Sec. 902*(c), (d), & (e)
Smoke and heat venting s�.all be provided as set forth in the Fire
Cocq.e. -- Sec. 5Q2. t f }
Standby power shall be pravided . �t steal l suppler power to al 1
required electrical equipment. -- Sec. 902 a (g)
Explosion venting maybe requlred. 4-40M pec. 910.
A ventilation system is required if there are hazadrous dusts,
fumes, vapors or gases emittedSec. 905. (b)
If quantities of hazardous materials are in excess of those Set
It
lri Table 9--E. h��i1�3�ne►r chn7i ,....�----
forth
Ai� �. �xc:ee� one story and shall
be without a basement or crawl space. -- Sec. go�.(73
Floor�lst OGcupancy-PAIN' MIMING
If Class lip II, or Class III -A flammable or combusti3ale liqu"
ds ars used
dispensed or mixed in open containers, then the following is required, �
This area is required to be separated from other areas by at feast a
1 hour occupancy separation. -- Sem. 901.(c)3.
For B2 occupancy
In all areas custamarily occupied by humans
artificial light and ventilation, --
Code review
Project Id.:
Address. 871
for:
TAYLOR CHEVROLET EXPANSION
SO. YELLOWSTONE
HANDICAPPED REQUIREMENTSe
NOTE: Section numbers listed
WATER FQUI+TTAINS
prov*�.e natural or
sem. 705*(a)&(b)
p00d1hME
below are fYom ANSI A117.1 - 1986
l) One must have a spout within 36 inches
2) Spout must be at the front of the unit.
of the floor. -- Sec. 4.15.2
-- Sec. 4. 15. 3
3 } Controls mush be at or near the front of the unit Sec . 4 . 15 . 4 & 4 . 25 . 4
4 A cantilevered unit is required to provide a clear area under the unit of
27 inches hi
,gh, 30 inches 1 wide, and li inches deep. --- Sec. 4.15.5 (1)
5 } A clear area of 30 X 48 J.I`2ChLS is required at the fountain. The clear
area is required to provide fora forward aroach with a cantilevered
unit and for aside approach otherwise. -- Sec. 4.15.5 & Fig.27 b,c,,d
TOILET FACILITIES:
1} A 51 diameter unobstructed burning spice is required in the toilet room.
-- Sec, 4.2,3 & Fig. 3(a)
2) When water closet is not in a compartment the clear area required is:
a) 48 inches wide by 56 inches deep with a side approach.
-- Sec. 4.16.2 & Fig. 28
b} 48 inches wide by 66 inches deep with a front a�prva.c�..
--
Sec. 4.16.2 & Fig. 28
c) 60 inches wide by 56 inches deep with bath approaches.
__ Sem. 4.1C.2 & Fig. 28
d) Side bar is required to stat within 12 inches of the back wail and
extend to 54 inches from the back wall. Sec. 4.1-6.4 & Fig. 29
The rear bar is required to be 36 r�ci�es long. -- Figo 29
3) When weer closet is in a compartment. the area required is:
a} 56 inches deep by 60 inches wide with a grab bar at the back and one
at the side. Door is at front or side. -- Fig. 3+D(a) or
b) 66 inches deep by 36 or 48 inches wide with grab bars on both sides
and dear at front. -w- Fig* 30(b)
d} If a f loor mounted water closet is used, the depth dimension
shown above must be increased 3 inches. -- Fig. 3D(a) & (b)
e} Side bars are required to start within 12 inches of the Haack wall and
extend to 54 inches from the bask wall. -- Fig. 7.56a & 7.56b
The rear bar is required to start within 6 inches of the side wall
and be 36 inches long. --- Fig. 30(a)
4) The bars are to be 33 to 35 inches above the flour. --- Fig. 29 (a). {b) &
Pig, 30(c), (d)
5 ) The top of the seat on the wader closet is required to. be 17 to 19 in hnwm * 10% -P I nches
37
01
�l
10}
va,✓vv� :.Aim .L1.�V� t �� r-igr �y�D� UC i'Ig• 30(d)
Urinals are required to be stall types or have
within 17 .inches of the floor. -- Sem, 4. 18. 2
A clear area of 30 x 48 inches is required in
-- Sem. 4.18.3
CnP_CC 7 j"'7i A T=,f3+-�
an elongated rim and be
& Fig. 29(c)
front of the urinal,
YL-uvia a a er the lavatory of
29 inches. -- Sec,, 4.,1,9.,2,.l & Fig. 31
A clear area of 30 X 48 inc-hes is required in vr�t of
-- the lavaory.
Sec. x.13.3 & Fig. 32
The bottom of mirror is required to be within 40 inches of the floo-r,,
-- pec. 4,19.6 & Fig. 31