HomeMy WebLinkAboutPLAN ANALYSIS JUNE 27 - 95-00018 - Taylor Chevrolet - ExpansionF3 city of Rexburg Engineering Department 12 North Center/P.o. Box 280 Rexburg, Idaho 83440 (208) 359-3020 Plan analysis based an the 1991 Uniforms Building Code Project Number: tay1chev Name: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE Dates. June 27, 1995 Occupancy: B1,B2,H4arH4,B1jH2,B2 Type of Const.&III-N,II-N NOTE*.The code items listed in this report listing of all possible Cade requirements selected erections of the code. Contractor: GENE PALMER CONST. Designer: GENE PALMER Engineer: NONE Plans Examiner: JOE LAIRD are not intended to be a complete in the 1991 UBS. It is a guide to Report created using Plan Analyst software by b w Portions of the material contained in this program uniform Building Cede 1991 editions with permis Conference of Building Off icials . Sion (719) 599-5622 reproduced from of International RIM �� � r ��. s...�_ �� � � � � �..irr� rr� � �w� +rr � � � � � � r..r� � �� �*yew s�� �s �i �a�r � rwr� � � �e�.� ie!r. r�4 �'� �r �rrr�r�ar.���.drr�k �:r a.�a r�.i r�r rrrt. rri. �'� ����®r a�� a+���f �■�r�� � � �r�n� �w �� �r �r ����e �� a��� �� �� �U �iF SECTION # 1 DIRECTION BOUNDARY NORTH Property line EAST Separation wall SOUTH Property line WEST Public way Area increased 7_00.00% FL NAME 130.0 oleo 120. 0 180.0 for open Feet Feet Feet area FIRE PROTECTION 130.0 Feet 0.0 Feet 120.0 Feet 140.0 Feet on 3 sides. MAX FLR AREA ALLOWED RATIO STATUS 400& � � � VMW � � mop& � OWD -tsw � @� *PW MMW � � � � � . & ME. � � *PW � � �n � mop* mwp- M— 0-W —MW mopm MONA. "W ~ � &=a 4� -a" � � ffibor on" MWW � � � *00 � � Mh= P** AW =*& Omm 2 PARTS STORAGE B2 2 LUNCH RMRREC,STORAGE B2 2 Locker Room 82 TOTAL FOR FLOOR 1 Retail Sales Room 1 CAR SERVICE AREA 1 OFFICES 1 PARTS STORAGE 1 BODY SHOP TOTAL FOR FLOOR BUILDING TOTAL B2 Bl B2 H4 ok ok ok ok ok 9450 630 2572 3575 19027 24000 24000 24000 24000 24000 24000 24000 24000 15000 21568 43719 o.o7 09-03 0.02 0.12 0.12 0.39 0.03 0011 0.24 0.88 04,50 ok ole ok ok ok ok ok ok ok ok ok 0 11 Im Code review Project Id.: address: 871 for: TAYLOR CHEVROLET EXPANSION S0. YELLOWSTONE The actual height of this building is 20.0 feet. Em mi The maximum height of the building is 55.o feet. -- Table 5-D EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 17-A & Table 5-'A Exterior wail ratings for H -occupancies are based on Table 9-C NORTH OCC BRG NON-BRG OPNG WALL WALL PROT B1 Ohr B2 Ohr H4 Ohr Ohr Ohr Ohr EAST BRG NON-BRG OPNG WALL WALL PROT SOUTH BRG NON-BRG OPNG WALL WALL PROT BRG NON-BRG OPNG WALL WALL PROT None S.W.* S.W.* S.W. Ohr Ohr None Ohr Ohr Nol"in None S.W.* S.W.* S.W. Ohr Ohr None Ohr Ohr None None S.W.* S.W.* S.W. Ohr Ohr None Ohr Ohr None rhe exterior walls are required to be of NONCOMBUSTIBLE material . Sec .19D1. gone -- Na fire protection requirements for openings. Prot --- openings are to be protected with 3/4 hr, fire assernblies , 509o- of the area of the wall maximum. Sic. 504.(b) & Sec.1903.(b) & Table 5----A Maximum single window size is 84 sq.ft with no dimension greater than 12 feet,. -- Sec. 4306.(h) 90P -- openings are not permitted in this walk. OTHER BUILDING ELEMENTS Table 17-.,-A ELEMENT MATERIAL RATING NOTES Enterior Bearing wall Noncombustible p hr Enterior nonbrg wall Noncombustible o hr See Footnot� �5 :31tructural Frame Noncombustible 0 hr Exterior Struct Frame Noncombustible Q hr See footnote #1 shaft Enclosure Noncombustible 1 hr Floor/Ceiling Assembler Noncombustible 0 hr See Footnote #9 hoof/Ceiling Assembler Noncombustible 0 hr 3tairs Noncombustible None 40TE: See Sec. 1706.(a) for Shaft Enclosure exceptions. iQ4TN4TES. I ) Elements in an exterior wall located where openings are not permitted or where protectian of openings is requiredr shall be protected against eternal fire exposure as required for exterior bearing walls or the structural frame, whichever as greater, -- Table 17-A. footnote 1 5) Nonload-bearing walls within a tenant space that are not pari of a 1hr corridor may be of a} Noncombustible (nonrated) materials b} Fire retardant -treated wood c} One-hour construction {any material} -- Sec,. 1705 a (b) I. 9 ) In areas with vehicles or airplanes, the floor surface shall be of noncombustible, nonabsorbent materials, --- Sec. 702.(c) & 902,P(b) I Code review Pro j'ect Id.: Address; 871 for: TAYLOR CHEVROLET EXPANSION SO. YELLOWSTONE OCCUPANCY SEPARATIONS B1 -B2 1hr Ofifces separation. B1 -H4 1hr B2 -H4 1hr Off ices separation. ADDITIONAL SEPARATIONS -- Table 5-B less than 250 -- Sec. 503. (a) of major use do not require a ex #2B less than 25% of magyar use do not require a -- Sec. 503, (a) ex #2B FOR Ba. OCCUPANCY: A 1hr occupancy separation is required aground rooms containing a bailer or central heating unit greater than 400,000 BTU input. --- Seca ?08. Storage aromas in excess of 10D0 sq, ft. are rewired to be separated from the retail area by a 1hr occupancy separation. --� pec, 702.(b)2, FOR B 2 OCCUPANCY a A 1hr occupancy separation is required aroundrooms containj.ng a bol""leror o central heating unit greater than 400,000 BTU input. __ Sec, lag. Storage areas in excess of 1000 sq -ft. are required to be separated from the retail area by a Thr occupancy separation. -- Sic. 702. (b) 2. FOR H4 OCCUPANCY: A 2hr occupancy separation is required, around rooms containing a bailey or central heating unit. -- Sec, 908, SECTION // 2 DIRECTIQN BOUNDARY NORTH Property line EAST Property line SOUTH Property line WEST Separation wall SEPARATION AREA INCREASE 150.0 70.0 izo.o 0 area increased 100.00% for open Feet Feet Feet Feet area FIRE PROTECTION 150. 0 Feet 70. 0 Feet 120.0 Feet 0.0 Feet on 3 sides. FL.NAMEOCCMAX FLit AREA ALLOWED RATIO _ STATUS 1 PNTeSPRePREP AREA H4 ok 960 15000 0.06 ok 1 PAINT BOOTH H4 ok 190 15000 0.01 ok 1 PAINT MIXING H2 ok 110 7400 0.01 ok 1 Mechanical Room B2 ok 110 24000 0.00 ok 1 REASSEMBLY ROOM B1 ok 1030 24000 o,.04 ok 1 TRUCK SHOP H4 ok 3200 15000 0. 21 ok POTAL FOR FLOOR 5600 15893 0.35 ok 9UILDING TOTAL 5600 15893 0.35 ok 'ode review for: 'roject Id.: TAYLOR CHEVROLET EXPANSION address: 871 SO. YELLOWSTONE `he actual height of this building is 20.0 feet. 0 a Emit signs are required from all areas --�- Sec , 3 3 14 . ( a ) nr-zr-% r c r.T y w, rr 4 _ _. ..._ _ .. serving an occupant load.of 50 or more. �►��=Iy -�� �a��u vn pec . J J U4 , (xO ) except as noted, occupant load is based on Table 33-A. Number of exits is based on Table 33-A except as noted, Exit width is in feet and based on Sec. 3303*(b)w Exit width is to be divided approximately equally Width shown for all areas is based on ether exits width shown for 1st f loor i s based an other Width shown for other floors & basements is For the minimum width of doors, see Sec. 33U For the minimum width of corridors, see Sec, For the minimum width of stairways, see Sec, FOOTNOTES: among exits. . (0. 2) exits. (0.2) based on stairways. 4. (f ) 3305. (b) 3 306.(b) 1) The second floor is required to have 2 emits when the occupant is la or more. -- Sic. 3303. (a) 8) The number of exits is based on Sec. 3319. HANDICAPPED ACCESS: 1) Handicapped access is required to to this building. -- Sec. 3103 . (a) Z j If a ramp is used for handicapped 1:12. -- sec 3307o(C) Handicapped access may not be entry level. --- Sem. 3103(x) at least one primary entrance & (b) 3 -w access , the max slope is (0403) load required to levels other than the primary ext # 2 STAIR NOTES; The maximum rise of a step is ? inches and the minimum run is 11 inches . --_ Sec. 3346.(c) The minimum width of a stairway is 36 inc s, 44 inches if the occupant load is greater' than 4 9. ---- SSC . 3306. (b) Also see exit table above to see if minimum width is greater than, 44 inches. Provide handrails on bath sides of a stairway 34 to 38 inches above the nosing. (May be on one gide if less than 44 inchese)wid-- Sec, 3306.(j) Provide a guard rail where drop off is greater than 30 inches. minimum height 42 inches, maximum opining �iZe = 4 inches. --- Sec, 1712. (a) The minimum headroom is 6 f t - 8 inches, -- Sec* 3306.(o) Enclosed usable space under the stairs is rewired to be protected as required for 1hr fire-resi sti ire construction. --- SSG , 3306a (1) Provide a landing within 1 inch (1/2 access) of the threshold., -- Sec. The minimum width is same as door wi --- Sec. 3 3Q4 The maximum travel distance in __ Sic. 3303 e (d) this inch at doors used �vz handicapped 3304a { dth and theImnimum length is 44 inches, *1-i 1-ig ode review tor: Project Id.: TAYLOR CHEVROLET EXPANSION address: 8.71 SO. YELLOWSTONE 200FING REQUIREMENTS: 150 feet,, M =* e _1 } The roof ing on -- Table 32-A this building is required to be Class B or wetter. Z) see section 3204. and ICBG research reports for requirements. AREA SEPARATION WALL REQUIREMENTS: l) The area separation wall is required to be a 2 hr fire assembly. lftft� Sec. 505.(f)2. 2) If the building has a projection with concealed space at the area separation wall, 1hr protection is required on the Projection and the. exterior wall each side of the area separation wall equal to the depth of the projection.-- Sec. 505(f)3. 3} if the area separation wall terminates at ars inside corner. see ICBG article in 'Building Standards' Sep/Oct 1982 for requirements. AUTOMATIC SPRINKLER SYSTEMS: If openings are not provided in each 50 feed of exterior wall or there is floor area more than 75- feet from an exterior opining, an automatic sprinkler system is required. Sec. 3802.(b) An automatic sprinkler systemis required in retail sales roams wia floor area greater than 12,000 sq, ft. -- Sec. 3802. (d) An automatic sprinkler system is required in ars H4 occupancy more than 3000 square feet. -- pec. 3802.(f)2. If there are 1D0 or more sprinklers, the automatic sprinkler system shall be supervised by an approved central, proprietary, or remotes station service al - arm a local which will dive an audible signal at a constantly attended location. -- Sec. 3803. STANDPIPE REQUIREMENTS: There is no requirement for a standpipe. -- Table 38-A A hose is not required. -- Table 38-A FOOTNOTES: 1) The location is to be per Sec. 3805. (c), (d),and/or(e) WALL AND CEILING FINISH: 1) Wall and ceiling finish materials are required to comply with Sec. 4204. (a) and Table 4 2-8. 2) Carpeting an the ceiling is required to have a Clays I flame spread rating. Sec* 4204,w(b) 3} Textile wall coverings shall have Class I flame spread rating, and shall be protected by automatic sprinklers or meet the acceptance criteria of U.B.C. Standard No'. 42-2 -- Sec, 4205. INS[ILATIOhT NOTES 1) All insulation material including facings are required to have a flame - spread raking of 25 or less and a maximum. smoke density of 45096 ....-- Sec. 114, 2) Foam plastic insulations are required to be protected.. -�- sem, 1713, GLAZ ANG REQUIREMENTS: A.11 glazing in hazardous glazing material. -- Sec. locations is required to be of safety 5406, (d) A Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION A. Address: 871 SO. YELLOWSTONE ADDITIONAI, REQUIREMENTS For B1 occupancy Devices generating a glow or flame are required to be 18 inches above the f Ivor, --- pec. 7D8. The minimum clear height is required to be 7 f eet Sec, Parking garages require a ventilation system that exhausts per sq.ft. of floor area. -- pec. 705.(b) 2. For Bz occupancy In all areas customarily artif1"cial light 709.(c)5. 1. 5 cfm occupied by humans, provide natural or and ventilation. ­� sec. 705.(a)&(b) For H4 occupancy If required by the Fire Code, spill control. drainage, & containment shall be provided. --- Sec,. 902.(c), (d), & (e) Smoke and heat ventingshall be provided as set forth in the Firs: Code, -- Sec. 902.(f) Devices generating a glow or flaTtie are required to be 18 inches above the floor. --- Sec. 908. A ventilation system that exhausts 1.0 cfm per sq.ft. of floor area. An exhaust pipe is also required at each stall. -- Sec., 9054 (C) HANDICAPPED REQUIREMENTS NOTE: Section numbers 101 sted below are from ANSI A117.1 - 1986 1) one must have a spout within 36 inches of the floor.. -- Sec. 4.15.2 2 } Spout must be at the front of the unit. -� Seg. 4.15.3 3) Controls must be ,at or near the front of the unit. -- Sec. 4.15.4 & 4*25o4 43 A cantilevered unit is required to provide a clear area under the unit of 27 inches high, 30 inches wider, and 17 inches deep_ -- Sec . 4 . 15 . 5 ('1)305) A clear area of � X 48 inches is required at the fountain, The clear area is requiredto provide for a forward approach with a cantileveredunit and far at approach otherwise,.--- Sec. 4,15..5 & F,]*.gw27 b c d TOILET FACILITIES: 1 A 5' diameter unobstructed turning space is required in the toilet roan. --_ Sec. 4.2.3 & Fig. 3(a) 2) When water closet is not in a compartment, the clear area required, is: aj 48 inches wide by 55 inches deep with a side approach. --ft Sec. 4,16.2 & Fig. 28 bj 48 inches wide by 56 inches deep with a front approach. -- pec. 4,16.2 & Fig. 28 c} 60 inches wide by 56 inches deep with bath approaches, -- Sec. 4.16.2 & Fig. 28 d) Sides bar is required to start within 12 inces of the bask wall and extend to 54 inches from the back wall. -- Sec. 4.1G.4 & Fig. 29 Page ;y 9 Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE the rear bar is required to be 36 inches long, Fig. 2 9 . 3) When water closet is in a compartment, the area required is: 1=1 � I r% 9 ; " 4) 5) �l �G1=v ,�y uv 1flt:i%e5 wzae witri a graD bar at the back and one au the side. Door is at front or side, -- Fig. 30(a) -or b) 56 inches deep hv 3G or 48 inches wide with grab bars on both CX11uuuz dz rranz. --- Fig. 30(b) d) If a floor mounted water closet is used, shown above must be increased 3 inches. e Side bars are required to start within 1 extend to 54 inches from the back wall, The rear bar is required to, start wiqthin and be 36. inches long. --� Fig. 30(a) The bars are to be 33 to 3E .inches above the Fig. 30(c) , (d) sides the depth dimension -- Fig. 30(a) & (b) 2 inches of the back wall and --Fig. 7.56a & 7.56b 6 inches of the side wall floor. -- Fig. 29(a),(b) & Tne top or tne seat an the water closet is required to be 17 to 19 inches above the floor. --- Fid, 29{b} & Fig. 30(d) is required in Urinals are required to be shall type or have an elonaated rim and hp within 17 inches of the f loor. -- Sec. 4, 18, 2 7) A clear area of 30 X 48 inches is required in r7l 10) -- Sec. 4. 18. 3 Accessible lavatories shall provide a clear 29 Inches. -�- Sec* 4*19e2al & F�.g . 31 & Fig. 29 (c) ----- ---- -- front of the urinal, area under the lavatory of H c year area or :s u x 48 inches is required in front of the lavatory,, -- Sec. 4.19.3 & Fig. 32 The bottom of mirror is required to be within 40 inches of the floor, --- Sec. 4.19.6 & Fig -9 31 SECTION # 2 EXIT REQUIREMENTS: FL NAME OCCUPANT NUMBER EXIT PANIC RATED DOOR NOTES LOAD REQUIRED WIDTH HDWR CORRIDOR SWING --------------------------------------------------- ----------- 1 PNTeSPR,*PREP AREA * 5 1 0. 1 No No Out 1 PAINT BOOTH * 0 1 0,60 No No Out 1 PAINT MIXING * 1 2 0. 0 Yes No Out 3 1 Mechanical Room * 0 1 0-60 No No NIR 1 REASSEMBLY ROOM * 5 1 0.1 No No NIR 1 TRUCK SHOP * 16 2 0.3 No No Out 8 TOTAL 27 2 .0-45 No No Out Code review for. Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE Page # 10 * NOTE: This area is being treated as an accessory for occupant loads. WPM MWP Sec. 33o2.�a} ��ception In areas where 2 exits are required, the minimum separation maximum diagonal of the area or floor. --- Sec* 3303.(c) Door swing J_s used an Sec. 3304.(b) except as noted. Occupant load is based on Tables 33-A, Number of exits is based an Table 33-A except as noted. Exit width is in feet and bayed on Sec.. 3303..(b),. Exit width is to be divided approximately equally among Width shown for ail areas is based on ether exits. (0.2) is 1/2 of exits the Width shown for iso f loor Width shown dor other f lo For the minimum width of For the minimum width of For the minimum width of FOOTNOTES: 3) Panic hardware is based 8) The number of exits is is based on other exits. (0.2) ors & basements is based on stairways, (0.3) doors, see Sec. 3304.(f) corridors, see See. 3 3 05. (b) stairways, gee Sem. 3306. (b) on Sec. 3319. based on Sec. 3319. HANDICAPPED ACCESS: 1) Handicapped access is required to at least one primary entrance to this building. --- Spec. 3103,,,.(a) & (b)3. 2) If a ramp is used for handicapped access, the max slope is 1: 12. -- sec 3307 . (c) Provide a lending within 1 inch (1/2 inch at doors used for handicapped access) of the threshold. --- Sec. 3304.(i) The minimum width is same as doter width and the minimum 1 e __ ,pec. 3304.(a) The maximum travel distance in this building is 150 feet. __ Sec. 3303.(d) The maximum travel distance within an H1,H2 or H3 occupancy -- Sic. 33190 gth is 4 4 inches. V s 75 feet . ROOFING REQUIREMENTS: 1} The roafing on this bu4lding is required t.o be Class B or better. -- Table 32-A 2} See section 3204, and ICBo research reports for requirements. AREA SEPARATION WALL REQUIREMENTS; 1.) The area separation wall is required to be a 2 hr fire assembly. _- Sec. 505. (f)2. 2) If the building has a projection with concealed spaces at the area separation wail, 1hr protection is required an the projection and the exterior wall each jade of the area separation wall equal to the depth of the projection.-- Sec. 505(f)-3. 3 j If the area separation s►,ra1l terminates at an inside corner, see ICBO article in 'Building Standards' Sep/Oct. 1982 for requirements. 11 Code review f orPage # Pro j ect Id , : TAYLOR CHEVROLET EXPANSION Address: Sil SC?. YELLOWSTONE AUTOMATIC SPRINKLER SYSTEMS* If openings are not provided in each 50 feed of exterior wall or there floor area more than 75 feet from an exterior opening, an automatic sprinkler system is required, _- Sic. 3 80 2. (b) An automatic sprinkler system is required in an H4 occupancy mores than 3000 square feet. -- sec. 3802.(f)2. An automatic sprinkler system is required. in H 2 vcc. -�-� SeC. 3 8 0 2 f}1. i S ir Lnere are luu or more sprinklers r the automatic sprinkler system shall be 0 AP . supervised by an approved central, proprietary, or remote station service or a local alarm which will give an audible signal at a constantly attended location. �-- Sec. 3803., STANDPIPE REQUIREMENTS: There is no requirement for a standpipe. --*- T ab 1 e 3 8-A A hese is not required, -�-- Tables 38-A FOOTNOTES: 1) The location is to be per Sec. 3805-(c),(d),and/or(e) WALL AND CEILING FINISH: 1 ) fall and ceiling finish materials are required to comply with Sec. 42.04.(a) and Table 42-B. 23 Carpeting an the ceiling is required to have a Class I flame spread rating. -- Sem. 4 2 0 4. (b) 3 } Textiles wall coverings shall have Claims I flame spread. rating. and shill be protected by automatic sprinklers or meet the acceptance criteria of U.Q.C. Standard No. 42--2 --� Sec. 42050 INSULATION NOTES l j All insulation material includina facinas arp rpa"; rtna tn nniTa spread rating of 25 or less and a maximum smoke density of 450. -- sec. 1714.(c) 1 .1�' a 4 f lamewas r vcZILt P1Q3 L,6.1: "z5ula uiu"5 ar e t'equ1rea 'G(7 De proteCteU. ---" Sec. 1713-, GLAZING REQUIREMENTS: All glazing in hazardous glazing material, -- Sec. ADDITIONAL REQUIREMENTS: For H4 occupancy, locations is required to be of safety 5406 e (d) .LL requireu Dy tine mire coae, spill control, drainage, & containment shall be Provided. Sect 902..(c), (d), & (e) Smoke and heat renting shall be provided as set forth in Dade. �- Sec. 902.(f) Devices generating a glow or flame are required to be 18 the floor. Sec. 908. A ventilation system that exhausts 1.a cfm per sq,ft. of An exhaust pigs is also required at each stall. 905 . (c) Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE For Bl occupancy4 the Fire inches above f I-oor area. MAMb Seg Page # 12 uuW-Lc:us generaLing a glow or f lame are required to be 18 inches above tne lioor. -- Sec. ?OS. The minimum clear height is required to be 7 feet. Paring garages require a ventilation system that per sq.ft. of floor area. --- Sec. 705.(b) �� Sec. exhausts 20 709. (c)5_ 1.5 cfm For H2 occupancy If required by the Firs Code, Spill control, drainage, & containment 7 shall be provided. -- Sem. 902. (c), (d). & (e) Smoke and hetet venting shah be provided as set forth Code. --- Sec. 902.(f) Standby power shall be provided. It shall required electrical equipment. -- Expiasian venting may b� ��quired , -�- Sec . A ventilation system is required if there fumes-, vapors or cases emitted, -- If quantities of hazardous materiels are i in the Fire supply power to all Sec,, 9 0 2.Cg� 910.6 are hazadrous dusts, mists, pec. 905.(b) n excess of those set forth in Table 9�-E, building shall not exceed one story and shall be without a basement or crawl space. �-- Sec. 902 . (j ) Floor-ist C7ccupancy-pAINT MIXING If Class I, IIS or Class III -A flammable or combustible liquids are used. dispensed or mixed in open containers, then the following is required. This area is required to be separated from other areas by at least a 1 hour occupancy separation. --- Sec. 901.(c)3,, For S2 occupancy In all areas customarily artificial light Cady review Project Id. Address. 871 occupied by humans, provide natural or and ventilation. -- Sec. 705 . (a) & (b) for: TAYLOR CHEVROLET EXPANSION SO. YELLOWSTONE Page # 13 HANDICAPPED REQUIREMENTS NOTE: Section numbers listed below are from ANSI A117.1 1986 WATER FOUNTAINS: 1) One must have a spout within 36 inches of the floor. ---- Sec. 4,15.2 2 ) Spout mist be at the front of the unit. -- Sec. 4.15.3 3) Controls must be at or near the front of the unit. ---.Sec. 4.15.4 & 4s25 -s4 4) ,A cantilevered unit is required to provide a clear area under the unit of 27 inches high, 34 inches wider, and 17 inches deep. -- Seg. x.15,5 (1) 5} A clear area of 30 X 48 inches is required at the fountain. The clear area is required to provide for a forward approach with a cantileveredit and f or a s ide approach otherwise. �-- Sec. 4.15.5 & Fig.27 b,c,d TOTI,,E'T' FACILITIES e. 1) A 5"" diameter unobstructed turning space is �-- Sec. 4.Z.3 & Fig. 3(a) 2 } When water closet I -S not in a compartrnent, a) 48 inches wide by 56 inches deep with _- pec. 4.1G.2 & Fig. 28 bj 4 8 inches wide by 56 inches deep with -- Sec. 4 . 16 . 2 & Fig. 28 cj 60 inches wide by 56 inches deep with -- Sec. 4.16.2 & F.ig. 28 3) required 41 in the toilet room. the clear area re-quired is a side approach. a front approach , both apprvaches. a� 5lae bar is required to start within 12 inches of the back wall and extend to 54 inches from the back wall. --- Sem. 4.16.4 & Fig. 29 The rear bar is required to be 36 inches Iona* -- F.1ba _ ?q When water closet is in a compartment, the a) 56 inches deep by 60 inches wide with a at the side. Door is at front or side, bj bd inches deep by 36 or 48 inches wide -W area required is: grab bay at the ~� Fi0g. 30(a) or with crab wars on hack and one both sides 4) 5) 7) �l 10) Tne top cit tris seat on the water closet is required to be 17 t0 19 inches above the and door at front . ---- Fig, 30 (b) 29(b) & Fig. 30(d) Y d) If a floor mounted water claret i S used, the depth dimensi on rim and be shown above must be increased 3 inches. -- Fig. 30(a) & (b) e) fide bates are required to start within 12 inches of the beck wall front of extend to 54 inches from the back wall, --- Figs 7o56a & 7.5G�a The rear bar is required to start within � all of the side wall a clear area ander and be 36 inches long. -- Fig. 30(a) -- Sem. 4.13.2.1 & Fig* The bars are to be 33 to 35 inches above the floor,. -- Fig.. 29(a) (b) Fig. 3 0 (c) ► (d) front of the lavatory,. _4� Sec. 4.19.3 , Tne top cit tris seat on the water closet is required to be 17 t0 19 inches above the floor. -- Fig. 29(b) & Fig. 30(d) Y Urinals are required to be Mall type or have an elongated rim and be within 17 .inches of the floor . --- pec. 4 . X8. 2 & Fig. 29(c) A clear area of 30 X 48 inches is required in front of the urinal. ---- Sec. 4.18.3 Accessible lavatories shall provide a clear area ander the lavatory of 29 inches. -- Sem. 4.13.2.1 & Fig* 32 A clear area of 34 X 48 inches is required in front of the lavatory,. _4� Sec. 4.19.3 & Fig. 32 The bottom of mirror is required to be within 40 inches of the f loor. -- Sec.. 4.x.9,6 & Fig. 31 ri City of Rexburg Engineering Department 12 North Center/P.O. Box 280 Rexburg, Idaho 83440 (208) 359-3020 Plan analysis based on the 1991 Uri form Building Code Project Number: taylchev Name TAYLOR CHEVROLET EXPANSION Address; 871 SO. YELLOWSTONE Date: June Occupancy: H4,B2;H4,B1,H2,B2 ..Type of Const: NOTE:The code items listed in this report listing of all possible code requirements selected sections of the code, Report created using Plan Analyst software. Port -ions of the material contained ifi this Uniform Building Code ( 1991 edition) with Conference of Building Officials. SECTION # 1 DIRECTION BOUNDARY SEPARATION AREA INCREASE NORTH Property line 130v0 EAST Separation wall 000 a, SOUTH Property line 120.0 WEST Public way 18,000 Area increased loo -00% for open Feet Feet Feet Feet area 27, 1995 contractor: GENE PALMER CONST. Designer: GENE PALMER Engineer: NONE Plans Examiner: JOE LAIRD are not..................... complete UBC in the 1991 It is a guide tv by' b w & a. (719) 599-5622 program are reproduced from permission of International FIRE PROTECTION 130.0 Feet 0.0 Feet 120.0 Feet 140.0 Feet a on sides. . FL NAME occ MAX FLR AREA ALLOWED RATIO STATUS `' � --------------------------------- —4ww--~--Mom—=Mw—Mbb-40= 2 PARTS STORAGE B2 ok 1601 24000 0e07 ok 2 LUNCH RM,REC.STORAGE B2 ok 800 24000 0003 ok 2 Locker Room B2 ok 480 24000 0902 ok TOTAL FOR FLOOR �Qo, ...,,,,,, ,. 1 Retail Sales Room I CAR SERVICE AREA 1 OFFICES I PARTS STORAGE I BODY SHOP TOTAL FOR FLOOR WARNING mwn- This BUILDING TOTAL ok- ok ok ok 01r floor is over th� 945 63, 257 3571 19027 allowed area. 2400# 24000 15000 E-7012 amwo-A U 0 12 0912 0*63 0-a03 0.11 0.24 1 -v 12 mmw-� OVER OVER the Code review fors k Project Id.: TAYLOR CHEVROLET EXPANSION Address : 871 SO. YELLOWSTONE The actual height of this building is T 4n mA'St i 3n" -m hi rrh4- -P +i•,.. 0 't..,, � '� a .� w Y _ 20.0 feet. _••-- •••-•,�„�yu� vi nuc LU13Ulf1(J 15 55.0 feet. -- Table 5---D EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 17-A & Table 5-A Exterior wall ratings for H -Occupancies are based on Table 9"10C NORTH EAST SOUTH WEST OCC BRG NODI-BRG OPNG BRG NON-BRG OPNG BRG NON--BRG OPNG BRG NON-BRG OPNG WALL WALL PROT WALL WALL PROT WALL WALL PROT WALL WALL R�aT H4 Ohr Ohr None S.W.* S.W.* S.W. Ohr Ohr None Ohr Ohr None B 2 Ohr Ohr None S.W.* S.W.* S.W. Ohr Ohr None Ohr Ohr None Tie exterior walls are required to b� of NO�NC�NlBUSTIBLE materfm ial. Sec.,l90�. done --- No fire protection requirements for openings. Prat -- openings are to be protected with 3/4 hr fire assemblies. area of the wall maximum. Sec. 504.(b) & Sec.1903.(b) & Table Maximum single window size is 84 sq,ft with no dimension greater than 12 feet,, -- Sec. 4306.(h) NOP -� Openings are not permitted in this wall. OTHER BUILDING ELEMENTS CLEMENT MATERIAL interior Searing wall Noncombustible Interior nvnbrq wall Noncombustible Structural. Frame Noncombustible Exterior Struct Frame Noncombustible Shaft Enclosure Noncombustible Fluor/Ceiling Assembly Noncombustible Roof /Ceiling Assembly Noncombustible Stairs Noncombustible Table 17-A RATING 0 hr 0 hr 0 hr 0 hr 1 hr 0 hr 0 hr None See See NOTES 50% of the 5-A Footnote #� footnote #1 -ee 00 note #1_8 NOTE : See Sec . 1705 . (a) for Shaft Enclosure exceptions . FOOTNOTES 1) Element s in an exterior wall located where openings are not permitted where protection of vper�ings is req�.ire+d shall be protected against external fire exposure as required for �xteriar fearing wally or the structural frame, whichever is greater. --- Table 17 -PPA, footnote 1 5) Nonload-p-bearing wally within a tenant spice that are not part of a Thr corr�.d�J- may bt=! of a) Noncombustible (nonrated) materials b} Fire retardant -treated wood c) One --hour construction zany material) M-- 9} In areas with vehicles or airplanes, the floor nvncoLmbustible, nonabsorbent materials, pec. 18) Ire areas containing hazaradous materialst the noncombustible, liquid -tight construction. --_ , Sec. 17 0 5. (b) 1. surface shall be of 702.(c) & 902.(b) floor surface shall be Sec. 902. (b) Code review f or: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE OCCUPANCY SEPARATIONS -- Table 5-B H4 -B2 1hr Offices less than 25% of major separation. -- Sec. 503.o(a) ex #2B ADDITIONAL SEPARATIONS FOR H4 OCCUPANCY: Page # 3 use do not rewire a vvc:uyuncy separateion is required around rooms containing a boiler or central heating unit, -- Seca 9D8. FOR B 2 OCCUPANCY A 1hr occupancy separation is required central heating unit greater than Storage areas in excess of 1000 sq.ft. the regal area by a 1hr occupancy SECTION # 2 DIRECTION BOUNDARY NORTH Property line EAST Property line SOUTH Property line WEST Separation wall SEPARATION AREA INCREASE 150.0 70.0 120.Q 0.0 Area increased 100-00% for open around rooms containing a boisler or 400,000 BTU input. -- Sec. 70$. are required to be separated from separation. -- Sic. 702.(b)2. FIRE PROTECTION Feet 15 0. 0 Feet Feet 70. 0 Feet Feet 120.0 H2 Feet Feet 0. 0 Feet area on 3 sides. Bl ok MAXFL NAME occ FLR AREA ALLOWED RATIO STATUS. mmp� 4=W M 4 � dhoft � 4EMP � � i � � dbmw C=31P � qn� � 9MW � � � =Pp1h � � � APUP � � - - y 1 PNTaSPR*PREP AREA H4 ok 1 PAINT BOOTH H4 ok 1 PAINT MIXING H2 ok 1 Mechanical Room B2 ok 1 REASSEMBLY ROOM Bl ok 1 TRUCK SHOP H4 ok TOTAL FOR FLOOR BUILDING TOTAL Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE 960 15000 0.06 ok 190 i5000 0.01 ok 310 7400 0.01 ok 110 24000 0.00 ok 1030 24000 0.04 ok 1940 15000 0.13 ok 5600 20867 0.27 ok 5600 20867 0.27 ok The actual height of this building is 2 0. 0 feet. The max0 imum height of the building is 55.0 feet. -- Table 5-D EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 17-A & Table 5-A Exterior wall ratings for Hm-voccupancies are based on Table 9-C OCC BRG NON-BRG OPNG BRG NON-BRG OPNG SOUTH I'Mme =Dv WALL WALL PROT WALL WALL PROT WALL WALL H4 Ohr Ohr None Ohr Ohr None Ohr Ohr BI Ohr Ohr None Ohr Ohr None Ohr Ohr H2 Ohr Ohr None Ohr Ohr None Ohr Ohr B2 Ohr Ohr None Ohr Ohr None Ohr Ohr done Nine None None WALL S OW -W* S -OW a* S .0 W -a* S.W.* WALL S .9 W -0 SOW* hr S.0 W.6 s i w # S.W. saw* sowe S 0 W a The exterior walls are required to be of NONCOMBUSTIBLE material,. Sec.1901-. None -- Na dire protection requirements for openings . Prot -- Openings ars to be protected with 3/4 hr fire assemblies area of the gall maximum. Sec. 504.(b) & Sec.1903. b & Table Nk Maximum single window sine is 84 sq -ft with no dimension greater than 12 feet. -- Sec. 4306.(h) NOP --- Openings are not permitted in this wall. ELEMENT Interior Bearing Interior nonbrg Structural Frame OTHER BUILDING ELEMENTS gra 1 I wall Exterior Strutt Frame Floor/Ce il ing Assembly Roof /Ceiling Assembly Stars MATERIAL Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Nancombustibl e Table 17-A RATING 0 hr 0 hr 0 hr 0 hr o hr 0 hr None NOTES Seg Footnote . 5 0g of the 5-A #5 Sem footnote #1 See Footnote #18 FOOTNOTES, 1) Elements in an exterior wall located where openings are not permitted where protection of apenings is require, shall be protected against external fire exposure as required far exterior bearing walls or the structural frame, whichever is greater-, Table 1? --A, footnote 3 5) Nonload-bearing walls within a tenant space that are not.. part of a 1hr corridor may he of.: aj Noncombustible (nonrated) materials bj Fire retardant-treated wood &--$I n V1iG"-11V"L t:vnt� uL uc;zian tany material) -- Sec. 1705.(b)l, 9 j In areas with vehicles or airplanes, the floor surface shall b�: �o� noncombustible� nanahsorbent n�a�e�i�l�d --- Sec. 702..(c) & 902e(b) 18) In areas containing hazaradous materials the floor surface shall he of nancombustible, lzquid-tight cQnstructivn. -- Sec. 902 (b) # 5 Code review far Page Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SD. YELLOWSTONE OCCUPANCY SEPARATIONS -- Table 5-B H4 -B1 1hr H4 -H2 1hr H4 -B2 1hr Bi -H2 2hr B1 -B2 lhr H2 -B2 2hr ADDITIQNAL SEPARATIONS FOR H4 OCCUPANCY: A 2hr occupancy separation is required around roams containing a bailer or central heating unit. FOR B 1 OCCUPANCY: -- Sec. 90 8. A 1hr occupancy separation is required around rooms cont centrad heating unit greater than 400, 000 BTU input FUR H2 OCCUPANCY 0 aining a boder or �-� Sec 7 08 A Jnr occupancy separat-lon is required around reams containing a boiler or central heating unit. --- Sec. 908. There shall be no openings in such occupancy ducts and piping. -� Sec. x(38. FOR B 2 OCCUPANCY A ihr occupancy separation is required central heating unit greater than SECTION # 1 separaion except for necessary ground rooms containing a boiler or 400,000 BTU input. -- Sec. 708. EXIT REQUIREMENTS: FL NAME OCCUPANT NUMBER EXIT PANIC RATED DOOR NOTES LOAD REQUIRED WIDTH HDWR CORRIDOR SWING ------------------------------------------------------------------------------- 2 PARTS STORAGE * 5 1 0. 1 No No N/R 2 LUNCH RM , RE C a STORAGE* 8 1 0,61 No No N/R 2 Locker Room * 10 1 0.2 No No N/R TOTAL 23 2 0.6 No No N/R 1 1 Retail Sales Room * 93 2 1. 6 No Yes Out 1 CAR SERVICE AREA * 47 2 0,08 No Yes Out 8 1 OFFICES * 6 1 0. 1 No No N/R 1 PARTS STORAGE * 9 1 0.2 No No N/R 1 BODY SHOP * 18 2 0.3 No No Out 8 TOTAL 173 2 2.9 No Yes Out * NOTE: This area is being treated as an accessory for occupant loads. -- Sec. 3302. (a) exception Rated corridors are to have 1hr fire protection on both sides of walls and ceiling. -- sec. 3305. (g) Door openings are required to be protected,. with 20 minute assemblies and window openings are required to be protected with labeled 3/4 hour assemblies. --Sec. 3305.(h) Elevators opening into a rated corridor shall be provided with an elevator lobby at each floor containing a rated corridor. -- Sec_. 3305.(j) Walls and openings between the corridor and the elevator lobby are required to be per sections 3305.(8) and 3305.(h) above. Code review for. Project Id.: TAYLOR CHEVROLET EXPANSION Address.* 871 SO. YELLOWSTONE Page # 5 In areas where 2 exits are required, the minimum separation maximum di a,gona 1 of the area or f I oor . -�- Sec . 3 3 0 3 , (c) exit signs are required from all areas serving an occupant -- Sec. 3314,(a) Door swing i s based onSeC . 3304.(b) +except as gated occupant load is based on Table 33-A. Number of exits is based on Table 33-A except as noted, �s 1/2 of the load of 50 or more . Exit wide is in feed and based on Sec. 3303.(b). Exit width is to be divided approximately equally among exits. Width sown for all area Width shown for 1st f loor 41 is based on other exits. is based an other exits. Width spawn for other f loors & basements For the minimum width For the minimum width For the minimum width FOOTNOTES: of doors , see Sec. of corridors, see of stairways, see 1 ) the second f loor is required to I s 10 or more. -_ Sec. 3303.(a) 8 j The number of exits is based on HANDICAPPED ACCESS: (0e2) (0.2) is based on stairways_ f0_i1 3304. (f ) Sec. 3305.(b) Sec. 3306.(b) have Z exits when the occupant load Sec. 3319. z) xanclicapped access is required to at least one to this building. mob 40M Sec. 3103.(a) & (b)316 1% primary entrance z) _Lt a ramp is usec€ ror nana3-capped access, the max !*812* -- Sec 3307.(c) Handicapped access may not be entry level. -- Sec. 3103(a) STAIR NOTES slope is required to levels other than the primary exp # 2 The maximum rise of a step is 7 inches and the minimum run is 11 inches. � Sec. 3306. ( C) The minimum width of a stairway is 36 inches, 44 inches if the occupant load is greater than 49. -- Sec. 3306. (b) Also see exit table above to see if minimum width is greater than 44 inches,, Provide handrails on both sides of a stairway 34 to 38 inches above the nosing. (May be on one sides if less, than 44 inches wider -- Sec. 330d.(j) Provide a guard rail where drip off is greater than 30 inches. Minimum height = 42 inches, maximums opining sine = 4 inches. Sem. l7l2.(a.) The minimum headroom is � ft,.- 8 inGh,es, -- Secs 3306.(o) Enclosed usable space under the stairs is required to be protected as required for 1hr fire -resistive Gonstruction . Sec, 3306,(l) Code review for: Page # 7 Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE Stairways are required to be in exit enclosures. --- Sec. 3309, (a) Exception #1 The walls of the enclosure are required to be 1 hr The openings into the exit enclosure are required to -- Sec. 3309,(c) Note: Openings into enclosure are necessary for exiting normally occupied space. A connection to thin ; ;�,- fire assemblies, be .ssemblies- be 1 hr assemblies, limited to those z =y,uL t:u w1 Lf! LI3@ Salil£'' exit enclosure. -- Sec. 3349. (4.) '1'hP CY1n["'►C 77"AeNr *10% &... 0 ......,. I .r�,.'s firms protection as the ,4 �t=� Z>�.Q�.� � k �rnclosea or not) may not be used for any purpose& °-�- Sec. 3309. (f ) Provide a landing within l inch (1/2 access) of the threshold. The minimum width is same as -_ Sec. 3304, (j �� Sec. door wi inch at doors used for handicapped 3304, (i) 4th and the minimum length is 44 inches . The maximum travel -_ Sec. 3303.(d) distance in this building is 150 feet. ROOFING REQUIREMENTS: 7} The roofing on this building is required to be Class B or better. --- Table 32-A 2} See section 3204. and ICBO research reports or requirements. AREA SEPARATION WALL REQUIREMENTS, l ) The area separation �a31 is required to be a 2 hr fire assembly. _-- Sec, 5a5. (f)Z. 2) If the building has a projection with concealed space at the area separation wall 1hr protection is required on the projection and the exterior wall each side of the area separation will equal to the depth of the projection.-- Sec. 505(f)3. 3) If the area separation wail germinates at an inside corned see ICBG article in 'Building Standards" Sep/Oct 1982 for requirements. AUT4TIC SPRINI{LER SYSTEMS If openings are not provi*ded in each 50 feet of exterior wall or there is floor area more than 75 feet from an exterior opening, an automatic sprinkler system is required, --� Sic. 3802,.(b) An automatic sprinkler system is required in an H4 occupancy more than 3000 square feet. -- Sec. 3802a(f)2w An automatic sprinkler system is required in retail sales roomy with a f loor area greater than 12, 000 sq . f t . --- S,Ac . 3802o(d) If there are 1U0 or more sprinklers, the automatic sprinkler system shall be supervised by an approved central, Proprietar�r � car remote s�atic�n service a local alarm which will dive a� audible signal at a constantly attended locat ion. amp 44W Sem. 38030 STANDPIPE REQUIREMENTS There is no requirement A hose is not required. FOOTNOTES: 1) The location for a standpipe. -- Table 38-A -- Table 38-A is to be per sec. 38.05. (c), (d).. and/or (e) Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE SMOKE AND HEAT VENTING REQUIREMENTS* If there is over 15000 sq.ft. of undivided H -occupancy area, vents are required. -- 3206. (a) 2. 1) Vends shall be fixed in the open position or vents shall be activated by temperature and shall open automatically in the event of dire. --Sec. 3206.(c) 2) Vents may not be located closer than 20 feet to an adjacent property line, --- Sec. 3246.(c) 3 ) The effective venting area sha31 be not less than if sq. ft. with no dimension less than 4 feet, excluding ribs or gutters whose total width does not exceed 6 inches,, -� Sec. 3206.(e) 1. 4 ) The maximum enter-ta-center spacing between vents within the building shall be 100 f eet Sec a 3206 . (e) 2 a 5 } The following ratites of effective area of vend openi shall be 1:50. -�- Sec. 3 .2 05 , ( e ) 3. 6 ) Curtain Boards shall be provided to subd�.�r�.de a vented building. ags to floor are4 - Sec. 3206.(f) 1. 7} Curtain boards shall be sheet metal, asbestos board,, lath and plaster,, gypsum wallboard or other approved materials, -- Sec., 32(36.(f) 2. 8 ) Curtain boards shall extend darn from the ceiling for a minimum depth of 12 feet but need not extend closer than 8 feet to the floor provided the curtain is not less than 6 feet in depth. Sec. 3206o(f) 3. 9) The maximum distance between curtain boards is 100 feet. The maximum area area between curtain boards is 15.0,00 sq.ft. --- Sec. 3206.(f) 4. WALL AND CEILING FINISH: 1} fall and ceiling finish materials are required to comply with Sec,. 4204.(a) and Table 42-B.. 2 } Carpeting on the oiling is required to have a Class I flame spread rating. -��- Sec. 4204.(b) 3} Textile wall coverings shall have Class I flame spread rating. and shall be protected by automatic sprinklers or meet the acceptance criteria of I.B.C. Standard No. 42-2 -- Sem. 4205. INSULATIDA1' NATES 1) All insulation material including facings are required to have a flame- spread rating of 25 or less and a maximum smoke density of 450. -- Sec. 1714. (c) 2) Foam plastic insulations are required to be protected. -- Sec. 1713. GLAZING REQUIREMENTS: All glazing in hazardous glazing material. -- Sec. locations is required to be of safety 5406 -o (d) Code review f or: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE ADDITIONAL REQUIREMENTS: For H4 occupancy If required by the Fire Coder spill controls drainaget shall be provided. -� Seg. 902 * (c) r (d), & (e) Smoke and heat senting shall beP rovided as yet forth i Code Sec 902 * (f & containment n the Fire devices generating a glow or flame are required to be 18 the floor. -- Sec. 908. A ventilation system that exhausts 1.0 cfm per sq. ft. of An exhaust pipe is also required at each stall. soy. {c} inches wave floor area. �� Sem For B2 occupancy in all areas customarily occupied by humans' provide natural artificial light and ventilation. -- Sec. 705 . (a) & (b) HANDICAPPED REQUIREMENTS : NN EXIT REQUIREMENTS: FL NAME OCCUPANT NUMBER EXIT LOAD REQUIRED WIDTH PAAIC RATED DOOR HDWR CORRIDOR SWINJ am lo! it .i iw it amp ii #. *No � ii' Ww a" 0� 40� � amp 1 PNTaSPR*PREP AREA * 5 1 0 -al No No Out 1 PAINT BOOTH * 0 1 0.0 No No Out 1 PAINT MIXING * 1 2 0.0 Yes No Out 1 Mechanical Room * 0 1 06,0 No No NIR 1 REASSEMBLY ROOM * 5 1 0.1 No No N/R 1 TRUCK SHOP * 10 2 0e.2 No No Out TOTAL 21 2 0.3 No No Out Page # 11 Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address,: 871 S0. YELLOWSTONE 3 0 * NOTE. This area is being treated as an accessory far occupant loads. -l� Sec. 3302. (a) exCeption In areas where 2 exits are required, the minimum separation maximum diagonal of the area or floor,. -W- Sec. 3303.(c) Dour swing is based on Sec. 3304.(b) except as noted. occupant load is based on Table 33-A. Number of exits is based an Table 33-A except as noted. Exit width is in feet and based on Sic. 3303.(b). 9 & is 1/2 of hxlL wlatn is to bye cxiviaea approximately equally among exits . Width shown for all aromas is based on other exits. (0.2) Width shown for Ist flooris based an other emits. (0.2) Width shown for ether floors & basements is based on stairways. For the minimum width of doors, see pec. 3304.(f) For the minimum width of corridors, see Sec. 3305.(b) For the minimum with of stairways sem Sec. 3306.(b) FOOTNOTES s 3) Panic hardware is based on Sec. 3319. 8 ) The number of exits is based on Sec. 3319., HANDICAPPED ACCESS: 1) Handicapped access to this bul'Iding, D, is required to -- Seg. 3103.(a) It a ramp is used for handicapped 1:1.2. --- See 3307.(e) at least one prto imary entrance & (b) 3 * access, the max slope is Provide a landing within 1 inch (1/2 znch at access) of the threshold. The minimum width is same as �- sec. 3 3 04.{7) The maximum travel distance *"- Sem. 3343. (d) The maximum travel elastance �-_ Sec, 3319, ROOFING REQUIREMENTS: -- Sec. 3304. (1) door width and in this building within an H11H2 NOTES the (0.3) doors used dor handicapped the minimum length is 44 inches. i� 150 feet, or H3 occupanc�r is 75 feet. 1) The roofing an this building is required to be Class B or better,. 2) See section 32Q4. and ICBO research reports for requirements. AREA SEPARATION WAIL REQUIREMENTS: 1) The area separation wall is required to be a 2 hr fire assembly. -- sic. 505, (f)2. 2} if the building has a projection with concealed space at the area separation wall, 1hr protection is required xeon the projection and the. exterior wall each side of the area separation wall equal to the depth of the projection.-- Sec. 505(f)3, 3) If the area separation wall germinates at an article in 'Building Standards' Sep/Oct 1982 Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE inside corner, see ICBG for requirement . f AUTOMATIC SPRINKLER SYSTEMS ; If openings are not provided in each 50 feet of exterior wall or there is flag area more than 75 feet front an exterior opining � an automaticsprinkler system is required. -�- pec. 3802.(b) An automatic sprinkler systems is required in an H4 oecupan.cy more thaw 3000 Square feet,, -- Sec. 3802.(f)2, An automatic sprinkler system is required in H 2 gcc. Sec. 3802.(f)l,. If there are 100 or, more sprinklers, the automatic sprinkler system shall be supervised by an approved central, proprietary, or remote station services or a local alarm which willgive an audible signal at a constantly attended location, -- Sec. 3803. STANDPIPE REQUIREMENTS: There .is no requirement for a standpipe. -ft- Table 38-A A hose is not required. v-- Table 38-A FOOTNOTES 1) The location is to be per Sec. 3805*(C)j(d),and/or(e) WALL SND CEILING FINISH6 1) fall and ceiling finish materials are required to comply with Sec. 4204.(a) and. Table 42-4-B. 2) Carpeting on the ceiling is required to haus a glass I flame spread ratingSec. 4204.(h) 3 ) Textile wall coverings shal 1 have Class I f lame spread rating. and shall be protected. by automatic sprinklers or meet the acceptance criteria of U.B.C. Standard No. 42-2 --- sec. 4205. INSULATION NOTES: 1) All insulation material ino-l"Hinn f�,.;,,nC4 ,r,. 1.0�____ 2) �.a•.� � �•.•-�-s�y•� Baa. � � C�u1.L iii 1�t� ,[iGtV� a spread rating of 25 or leers and a maximum smoke density of 450. -- sic. 1714,(c) Foam b__as�-ic� ,r��,3��f-,.,,-,c �,�.6 .1.,,..�.,.�,�,._.�� prorecrcn�a, Sec* ---u,sc tGLAi.��tinti �.C3 �3$ ""w"" + GLAZING REQUIREMENTS 4.6 All glazing in hazardous locations is required to be of safety NOTE: Section numbers listed below are from ANSI A1-17-.1 - 1.986 WATER FOUNTAINS: 1) One Must have a spout within 36 inches of the floor. --- See. 4.15.2 2} Shout must be at the front of the unit. -- Sec. 4 e 15 . 3 3} Controls must be at or near the front of the unit, -- Seg. 4.15.4 & 4,Z5.4 4 ) A cantilevered unit is required to provide a clear area under the unit of 27 inches high, 30 inches wide, ani. 17 inches deep. �°� Sec 4. 15.5 �1} 5) A clear area of 30 X 48 inches is required at tie fountain. The clear area is required to proviode for a forward approach with a cantilevered unit and far a side approach otherw TOILET FACILITIES: ise. --- Sec. 4.15,5 & Fig.27 b,c,d I A 5diameter unobstructed turning space is required in the toilet ream. _- Sec. 4.2.E & Fig. 3 (a) Z) When water closet is not in a compartment, the clear area required is; a) 48 .inches wide by 56 inches deep with a gide approach. -� Sec. 4.16.2 & Fig. 28. b) 48 inches w�.de by 6 inches deep with a front approach. -- Sec. 4.16.2 & Fig. 28 c} 60 inches wide by 5 G inches deep with both approaches, 'r Sec, "& Fig a 28 d} Side bar is required to start within 12 inches of the back wall and extend to 54 inches from the back wall, -- Sec. 4.16.4 & Fig. 29 Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE The rear far is required to be 36 inches long. -- Fig. 29 3} When water closet is in a compartment, the area required is: a) 56 inches deep by 60 inches wide with a grab bar at the back and one at the side. door is at front or side, --- Fig. 3or b) 66 inches deep by 36 or 48 inches widewith graars on bath sides and door at front. -- Fig. 30(b) d} If a floor mounted water closet is used, the depth dimension shown above must he increased 3 inches.. --- Fig. 30(a) & (b) e} Side bars are required to start within 12 inches. of the back wall and extend to 54 inches from the back wall. -- Fig. 7.56a & ?.56b The rear bar is required to, Mart within 6 inches of the side wall and be 36 inches Song. 4-ffl- Flog. 30(a) 4 The bars are to be 33 to 36 inches above the floor. --- Fig. 9(a),(b) & Fid. 34(c),(d) 53 The top of the seat on the water closet is required to be 17 to 19 inches above the floor. -- Fige 29(b) & Fig* 30(d) G} urinals are required to be stall type or have an elongated rim and be within 17 inches of the floor, -�- Sec. 4.18.2 & Figo 29(c) 7) A clear area of 30 X 48 inches is required in front of the urinal. +.� ww Sec w `f' . 18 . J S) Accessible lavato, ries shall rvvide a clear ax -ea under the la�ratory of 29 inches. -- Sec. 4.19.2.1 & Fig. 31 9) A clear area of 30 X 48 inches is required in front of the lavatory. --" Sec . 4.19.3 & Fick . 3 2 lob The bottom of mirror is required to be within 40 inches of the floor., __ sic. 4.19.6 & Fig. 31 SECTION # 2 glazing material, -- Sec. 5406.(:d) ADDITIONAL REQUIREMENTS: For H4 occupancy If required by the Fire Code, spill control, drainage, & cantainment shall be provided. -- Sec. 902.(c), (d), & (e) Smoke and heat venting shall be Provided as set forth in the Fire Code,. -- Sec* 902*(f') Devices generating a glow or flame are required to be 18 inches above the floor. -- Seg. 9U8. A ventilation system that exhausts 1.0 cfm per sq.ft, of floor area. An exhaust pipe is also required at each stall. -- Sec. 905. (c) Code review for: Page # 13 Project Id.: TAYLOR CHEVROLET EXFANSION Address; 871 Sa. YELLOWSTONE For Bl occupancy Deices generating a glow or flame ars: required to be 18 inches above the floor. -� Sec, 708, The minimum clear height is required. to be 7 feet. �-- Sec. X09. (C)5o Parking garages require a ventilation system that exhausts 1.5 cfm per sq. ft. of f loor area -- Sic. ?05. {b} 2. For H2 occupancy If required by the Fire Codes, spill control, drainage' & containment shall be provided. �-- Sec. 902a(c), (d). & (e) Smoke and. heat vent ing shall be provided as set forth in the Fire Code . --- sec . 902 . ( f j Standby power shall be provided. ItPPly power to all required electrical equipment. -- Sec 902��� Explosion venting mai be required,-�- pec. 910. A ventilation system is required if there are hazadro s dusts 1 mists� fumes, vapors or gases ertitted . Sec. 905.(b) If quantities of hazardous materials arm in excess of Chase set f orth in Table 9-E, building shall not exceed one stork and shall be without a basement or crawl space. -- Sec. 942.(j� Floor*-ist Qccupanc�-PAINT MIMING If Class I, Ii. or Class III -A flammable or combustible liquids are used, dispensed �r mixed in np�n containers, trim the following is This area is required to be separated from other areas by 1 hour occupancy separation. --- Sec. 901.(c)3, For B2 occupancy In all areas customarily occupied by humans artifficial light and ventilation, -- required . at least a provide natural or Sec. 705. (a)& (b) Code review for: Project Id.: TAYLOR CHEVROLET EXPANSION Address: 871 SO. YELLOWSTONE HANDICAPPED REQUIREMENTS: NOTE: Section numbers listed below are from ANSI A117.1 - 1986 WATER FOUNTAINS: 1) 2) 3) 4) one mist have a shout within 3 6 inches of the f loor �-� SPOUt must be at the f ront of the "n; t .._ e^f. A Controls must be at A cantilevered unit 27 inches high, 30. 5) A clear area of 30 Sec. 4.15.2 .0 %..- & -P L ZJ or near, the front of the un�.t . -- Sec. 4.15.4 & 4e25@4 is required to provide a clear area under the unit of inches widef ani �7 inches deep. �- Sec. 4.15.5 Clj X 48 inches is required at the fountain. The clear area is required to provide f or a forward approach with a cantilevered unit and far a side approach otherwise . Sec. 4.x.5.5 & Figo27 bfcld TOILET FACILITIES 1 A 5diameter unobstructed turning spaces is required i -3(a)n the toilet room.. Sec. 4.2.3 & Fig. 2) When water closet is not in a compartment, the clear area required is.s a 48 inches wide by 55 inches deep with a side approach. __ Sec. 4.1.6.2 Sc Fig. 28 bj 48 inches wide by f5 inches deep with a front pproac.. _-Sec. 4,16.2 & Fig. 28 c� 6 o inches wide by 56 inches deep with both apprvachesSec. 4,16.2 & Figa 28. d) Side bar is required to stark within 12 inches of the back wall and extend to 54 inches from the hack wall . --- Sec. 6.4 & Fig. 29 The wear bay is requi.red to be 36 inches long,. --- Fig. 29 3 When water cioset is in a compartment, the area required is a 56 inches deep by 60 inches wide with a grab bar at the back and one at the side. Door is at front or side. -- F19-0 34(a) or b) GC inches deep by 36 or 48 inches wide with grab bars on both sides and door at front, -- Figs 30(b) d) If a floor mounted water closet is used, the depth d imension shown above must be increased 3 inches., --- Figs. 30(a) & (b). e) Side bares are required to start within inches of the back wall and extend to 54 inches from the back wall, -- Figo 7.56a & 7.56b The rear bar is required to Mart within 6 inches of the side wall and be 3.6 inches long . --- Fig , 3 0 (a) 4} The bars are to be 33 to 36 inches above the floor. -- Fig. 29(a) b & Fig. 3 0 (c) f (d) 5} The toy of the seat an the water closet is required to be 17 to 19 inches above the floor, --Fig* 29(b) & Fig. 30(d) 6} Urinals are required to be stall type or have ars elongated rim an be within 17 inches r�� ��� floor. �--� Sec, 4,18.2 & Fig. 29(c) 7 ) A Near area of 30 X 48 inches is required in front of the urinal . -- Sem. 4.1$.3 S) Accessible lavatories shall provide a clear area under the lavatory of 29 inches. -- Sec. 4.19.2.1 & Fig. 31 9) A clear area of 30 X 48 inches is required in brant of the lavatory. r� � Sec, 4 , 1 7 s 3 CL Fige 32 10) The bottom of mirror is required to �e within 4p inches of the f loc��-, -- sec. 4.19.E & Fig. 31