HomeMy WebLinkAboutPLAN ANALYSIS JUNE 23 - 95-00018 - Taylor Chevrolet - ExpansionProject
Project
Addre s s
Number:
Name+
City of Rexburg
Building Official
12 North Center Street \ P.O.
Rexburg, Idaho 83440
(2 08) 3 5 9- 3 024
Plan analysis based an
the 1934 Uniform Building Code
Date* June
Contractor:
Occupancy: S3fH4rS1jMjB-S3,H4,H2,S1 Architect:
Construction: ITI-lhr,III-N0Engineer
Analysis By: JOE
NOTEThe code items fisted in this rampart are not
complete listing of all possible cede requirements
It is a guide to selected sections of the code.
Report created using Plan Analyst soare by b w
Portions of the material cantained in this program
from the Unifax�m Building Code (199q edition} with
International conference of Building Officials.
1
1995
LAIRD
intended to be a
in the 1994 UBC.
& a. (719) 599-5622
are reproduced
permission of the
DIRECTION BOUNDARY
NORTH
EAST
SOUTH
WEST
Allowable
-- Sec.
Property I-ine
Separation wall
Property line
Public way
area increased
505.1
SEPARATION
AREA INCREASE
130.0
0.0
120. 0
180.0
10 0. 0 0%
Beet
Feet
Feet
Fejt
for
open
FIRE PROTECTION
130.0
0. 0
120.0
140.0
Feet
deet
Feet
Feet
3 sides.
R
3
Code review f or
Proj ect Id,
Address:
FL ------ NAME OCC MAX F LR AREA ALLOWED RATIO STATUS
- - --------- -- - - --
---------------------------------
- - - -
2 Storage/Stock Room Sl
2 Locker Room g
2 lunch room B
TOTAL FOR FLOOR
1 Sales doom
1 Repair Garage
1 Office
1 Storage/Stack
l Repair Garage
1 Repair garage
TOTAL FOR FLOOR
BUILDING TOTAL
Roam
S3
B
S1
H4
H4
ok
ok
ok
ok
ok
ok
ole
ok
ok
16
0
1
480
35Q00
- Comb
800
Comb
3600p
2881
Non -
Comb
2800
0.07
94$0
3600
. 1�
630
36000
2572
0.41
3575
3200
36000
22227
22400
25108
36000
Material
Non
- Comb
35Q00
- Comb
Non -
Comb
3600p
Comb
Non -
Comb
36Q00
0.07
3600
. 1�
0.14
36000
0.41
36000
36000
22400
2240Q
30378
5186
The actual height of this building- is 30.0 feet.
The maximum height of the building is 65. 0 feet. -
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table
NORTH
For Bearing Non -Bearing
Occupancy Wall Wall
S3 2 dour D hour
H4 4 hour 0 hour
S1 2 haat D hour
M 2 hour D hour
S 2 hour 0 hour
EAST
Opening
Protection
None
None
None
None
None
Constriction
Material
Non
- Comb
Non
- Comb
Non -
Comb
Non -
Comb
Non -
Comb
0.02
0-04
-Bearing
0.01
2
0.02
4
0.08
2
0.08
2
0.26
2
0.02
0.07
D
. 1�
0.14
0.73
0.41
Table
ok
ok
ok
0
ok
ok
ok
ok
ok
ok
ok
ok
Parapet
Required
No
Na
No
Na
No
AREA SEPARATIDN WALL - See requirements listed later i
SOUTH n this report.
For
Occupancy
S3
H4
S1
Mow
WEST
I. •
Occupancy
Bearing
-Bearing
Wall
2
hour
4
hour
2
hour
2
dour
2
hour
Bearing
Wall
Nan
-Bearing
Nan-
Wall
D
hour
0
hour
0
hour
D
hour
Q
hour
Opening
Protection
None
None
NC)ne
None
None
Construction
Material
Nan-
Comb
Non
- Comb
Non -
Comb
Non--
Comb
Non -
Comb
Non -Rearing Opening Construction
wal! Protection Material
Parapet
Required
No
No
No
No
No
Parapet
Required
Code review for
Project Id .
Addre s s
Page # 3
S3 2 hour 0 hour None Non - Comb No
H4 4 hour 0 hou r None Non - Comb No
S1 2 hour 0 hour None Non - Comb No
M 2 hour 0 hour Nang Nin - Comb No
E 2 h,DZ1Y' t] hn7_ix- _NT,--, i--% r. x-irsIi CcjrFiL Nay
In two hour walls, fire -retardant -treated woad framing may be used
within the assembler provided the exposed, outer and inner faces are
noncombustible, -- Seg. 503.4.3
None-- No fire protection requirements for openings.
3/4 hour -- Openings are to be protected with 3/4 hr fire assemblies.
5Qof the area of the walk max50'1mum. -- Table 5-A,
Footnote 5 & Sec. 503.2.2
Maximum jingle window sire is 84 sq -ft with no dimension
greater than 12 feed. -- Sec. 713,g
Not Allowed -- Openings are not permitted in this walk.
OTHER BUILDING ELEMENTS Table 6-A
ELEMENT MATERIAL RATING NATES
Interior Bearing wall Any 1 hr
Interiar nonbrg wall Any l hr See Footnote #5
Structural Frame Any 1 hr
Exterior Struct Frame Any 1 hr See footnote #1
Shaft Enclosure Any 1 hr
F1oor/ceiling Assembly Any 1 hr See Footnote #9
Roof/Ceiling Assembly Any 1 hr Sem Footnote #8
Stairs Any None
NOTE: See Section 711 for shaft enclosure except�or�s.
C�
F�TNOTES
I} Elements in an exterior wall located where openings are not permitted
or where protection of openings is required, shall be protected.
against eternal fire exposures as required for exterior bearing wads
or the structural frame, whichever is greater. -- Ta}�1e b --A, footnote
5 } Nonload-bearing walls within a tena
1hr corridor may be of nt space that are not dart of a
a] Noncombustible (nonrated) materials
b) Fire retardant -treated woad
C) ane -hour construction tarry materia) -- -- Sec. 601.5.2.1
8} If the entire roof structure is 2S feet or more above above any floor
I
the fire rating may be allowed to be eliminated. See limitations and
req
u.iremen.ts . - - Sec* 604.5
9} In areas with vehicles or airplanes, the floor shall be of
noncombustible, nonabsorbent materials. -- Sic. 307.2.2
1
Code review
Project Id.
Address:
DRAFT STOPS:
for:
.
If there is combustible
Mops shall be installed
exceed 1, 000 square feet
stops does not exceed 60
If there is combustible
stops shall be installed
emceed. 3,0p0 square feed
stops dotes not exceed 60
Page # 4
construction in the f loor/ceiling assembly, craft
SO that the area of concealed space does not
and so that the horizontal dimension between
feet, -- Sec. 708.3.1.1.3
construction in the roof/ceiling assembly, draft
so that the area of concealed space cues not
and so that the horizontal dimension between
feet+ -- Sec. 708.3-1.2.2
OCCUPANCY SEPARATIONS -- Table 3-B
S3 -H4 1hr
S3 -Sl 1hr
S3 --M 1hr
S3 -B lhr A customer waiting room not
sq.ft, with an emit to the exterior
be separated. -- Sec. 302.1 exc. 2.5
H4 -S1 1hr
H4 -M 1hr
1-14 -B lhr Offices less than 25 p of mai o�- use da not
-- Sec. 302.1 enc. 2.2
exceeding 454
is not required to
require a separation.
S3 -M 1hr
sl -B ohr officers less
require a separation.
M -B 1hr Offices less
require a separation,
than 25-0,--
-
- Sec.
than 25-0,-,-
-
-- sec
HEATING EQUIPMENT SEPARATION:
FOR S3 OCCUPANCY:
of mai or use do not
302.1 exc. 2.2
of major use do not
302.1 enc. 2.2
A 1hr occupancy separation is required
bailer or central heating unit greater
-- Sec. 302.5
around roams containing a.
than 4 0 0,0 0 0 BTU input.
FOR H4 OCCUPANCY:
A 2hr occupancy separation is required around rooms containing a
boiler or central heating unit. -- Sec, 302.5
FOR S1 OCCUPANCY:
A 1hr occupancy separation is
boiler or central heat -Ing unit
- --
Sec. 302.5
FOR M
OCCUPANCY
A 1hY occupancy separation is required
boiler or cental heating unit greater
-- Sec. 32.5
FOR B accUP,cY
A 1hr occupancy separation is required
boiler or central heating unit greater
-- Sec. 30.5
required around rooms containing a
greater than 400,000 BTU 'input,
ADDITIONAL SEPARATIONS:
A refrigeration
of the building
machinery room
as required for
around roomscontaining a
than 400,000 BTU input.
around rooms containing a
than 400f 000 BTS input.
shall be separated from the remainder
an H7 occupancy regardless of area. A
Code review for
Project Id, .
Address:
horizontal occupancy separation may be
area of the machinery roam. Structural
P�-otected for the type of construct -ion
A 1 dour separation is required from an
FOR M
OCCUPANCY
SECTION # 1
EXIT REQUIREMENTS:
L
2 Storage/Stock
2 Locker Room
2 lunch room
TOTAL
1 Sales Room
1 repair Garage
1 office
1 Storage
1 Repair
1 Repair
TOTAL
ft�i�11
/Stock Room
Garage
Garage
limited to the actual floor
supporting dements
only. --- Sec. 2802
S3 occupancy.
NUMB MIN MIN
QCT EDITS WIDTH
shall be
PANIC RATED DOOR
HDWR CORRIDOR SWING
5
1
0.1
No
No
N/R
10
1
0.2
No
No
N/R
8
1
0.1
No
No
N/R
23
2
0.6
No
No
N/R
93
2
1.6
No
Yes
Out
47
2
0.
8
No
Yes
N/R
6
1
0.1
No
No
N/R
9
1
0.2
No
No
N/R
18
2
0.3
No
No
Out
16
2
0.3
No
No
Out
189
2
3.2
No
Yes
Out
No
W1,
11
s
dated corridors are to have Thr fire protection on bath sides of walls
and ceiling. -- Sec, 1005.7 Door openings are required to be protected
with 20 minute assemblies. -- Sec. 1005.8.1 Window openings are required
to be protected with labeled 3/4 hour assemblies. -- Sec, 1005,8,2
Elevators opening into a rated corridor shall be provided with an
elevator lobby at each floor containing a rated corridor. -- Sec. l005.10
Walls and openings hetween the corridor and the elevator lobby are
required to be per sections 1005.7 and 1D05_ R ahnzr�
4
Cade review f or
Project Id.:
address:
In areas where 2 exits are required.,
the maximum diagonal of the area or
i� 7 f' Cy 7 !'Y 7"i C--! .1
� Z 't
the minimum separation is 1/2 of
floor. -- Sic. 1���_�
awl areas where 2 or
-- Sec. �O13.1
xis.s are
required
Main exterior exit doors which obviously and clearly are identifiable
as exits named not be signed when approved. -- enc, I
Door swing is based on Sec. 1004.2 except as Hated.
Occupant Toad factor is based on Table. 10-A.
Number of exits is base. on Table io-A except as noted.
Exit width is in fejt and based on Sec. 1003.2.
Exit width is to be divided approximately equally among exits.
Width shown for all aromas is based on other exits. (0.2)
Width shown for 1st floor is based on other exits. (0.2)
Width shown for other floors & basements is based on stairways. (0.3)
For the minimum width of doors, see Sec. 1004.6
For the minimum width of corridors, see Sec. 1005.2
For the minimum width of stairways, see Sec. 1006.2
FOOTNOTES:
l) The second floor is required to have z exits when the occupant load
iS 10 or mare. -- Sec. 1043.1 exc. 1
8) The number of exits is based, on Sec.. 1018,
9} If this entire starer has an automatic sprinkler system and an
automatic smoke -defection system is installed. within the corridor,
and actuation of any detector shall activate alarms is all areas
served by the corridor, the corridor need not be rated if the
occupant load is fess than 100. -- Sec. 1005.7 exc. 5
FLUSH AND SURFACE BOLTS:
Manually operated edge or surface -mounted flush bolts and surface
bots are prohibited. When automatic flush bolts areu.se�, the doter
leaf having the automatic flush bshall not have a door knob or
surface -mounted hardware. The unlatching of any leaf shall not
require more than one operation. -- Sec. 1004.3
LACKS AND LATCHES:
A11 means of egress
from which egress is
knowledge or effort.
Keir- locking hardware
consists of a singe
doors shall be readily opera.able
to be made without the use of
--- Sec. 1004.3
may be used on the main
door or pair of doors. i f
from the side
a key or special
exit when the main emit
-lp-rfm THIS DOOR MUS'.' REMAIN UNLOCKED DURING BUSINESSt�IQUR.S1�Whenig� stating
door(s) must swing without operation of any latching device. unlocked
Code review
Project Id.
Addre s s
STAIR NOTLES -*
l}
2)
3)
4)
for
Page #
The rise of steps shall not be less than 4 inches
inches. The minimum run is 11 inchesb The maximum
inch in a flight of stairs. -- Sec. 1006.3
7
or grater than 7
variation is 3/8
11i� Lll.i lliLf LiM v,, .amu iii oi a s -c airway -is 36 inches, 44 inches if the
occupant load is greater than 49. -- Sec, 1005.2
Also see exit table above to gee if minimum width is greater than44 inches.
Provide a handrail on both sides of stairway 34 to 38 inches above
nosing. May be on one side of stairways less than z14 inches wide.
--- Sec. 1005.9 & exception 1
Provide a guard rail where drop off is. greater than 30 inches.,
-- Sec, 509.1
The minimum height is 42 inches. -- Sec_ 509.2
Open guardrails shall have intermediate rails or ornamental pattern
such that a sphere 4 inches in diameter cannot pass through.
-- Sec. 509.3 The triangular opening formed at the riser, tread and
the
y uar-urai 1 may ne b inches, T- 509.3 exc. 2
7} The minimum headroom is 5 ft,-- S inches. Such clearance shall be
measured vertically from a plane paraded and tangent to the stairway
tread mo -sing to the soffit move at all points. -- Sec. 100G. 15
8 ) Enclosed usable space under the stairs is required to be protected
as required for lh.r fire -resistive construction„ -- pec. 1006.12
LA_NDINGS AT DOORS:
,1) A floor or landing shall be provided on each side of doors. When
access for persons with disabilities is required. the floor or landing
shall not be more than 1/2 inch lower than the threshold. When access
is not required, the maximum is 1 inch. -- Sec. 1004,9
2) landings shall have a. width not less than the width of the stairway
or width of thedoorway, whichever is the greater. The minimum
length in the direction of exit travel is 44 inches. --- Sec. 1004.10
TRAVEL DISTANCE:
The maximum travel distance in this building is 150 feet'. -- Sec. 1003.4
Code review dor:
Praj est Id
Address;
BUILDING ACCESS IBIL,ITY:
1) This building including each tenant
one entrance which complies with the
C-17Mn /ANTO
2)
3)
4)
Page # 8
shall be nrovil rl P r�
-L -L / - j- - iAc feast bu percent
accessible. �- Sec. 1103.2.3
accessible route
of all entrances
with at least
provisions of
shall ]oe
nnen more tnat one exit required required from any accessible space, each
accessible portion of the space shall be served by not lcssfaccessible means of egress,, -- Sec. 1104.1.1 0
When an exit stairway is part of an accessible means of egress, the
stairway shall have a clear width of not less than 48 inches between
the handrails. The stairway shall eitherincorporate an area of refuge
within an enlarged story -level landing or shall be accessed from
a -r1 oz rer-uge. Sec. 1104. 1-. 2
~�--� -°� -����� Ex -L -L iiave uirecr, access to the stairway that serves
it. Sec. 1104.2.1
Each area of refuge shall he sized to accommiodate one wheelchair space
inches not less than 30 by 48 inches for each 200 occupants, or
mon
port Liik7,'.Lt,`UL_M -- Sec . I1 U4. 2. 3
5) If the area of refuge is not within the stairway, it shall be separated
from. the rest of the story by a smoke barrier having at least a one-
hour fire -resistance rating. Smoke barriers shall extend to the roof or
flaor deck above,, ]Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes. -- Sec. 1104.2.4
67 Two-way communications are required. -- Sec. 1104.2.5
7) Each area must be identified by a 0 sign stating AREA OF REFUGE and the
international symbol of accessibility.
ROOFING REQUIREMENTS:
1) The roofing on this building is required to be Class B or better.
- - Table 15 -A
2) See section 1504 and IC$4 research reports for
P requirements.
Cade review for ;
Project Td.
Address:
AREA SEPARATTON WALL REQUIREMENTS:
1) The area separat ion wall is required to he a 4 hr fire assen�.bl�r .
Openings are limited to �5 percent o� the length of the wall and
protected with a 3 hour assembly. -- Sec. 504.E.2
2} If the building has a projection, lir protection is required on
the exterior wall each side of the area separation wall equal to
the depth of the projection.-- Sec. 504.6.3, exceptions
If the project'on has a concealed space at the area separation,
walk, the area separation wall must extend through the projection.
3) If the area separation wail terminates at an inside corner, gee
the article in 'Buil-ding Standards' Sep/pct 1582 for requirements.
4 } A 3 d inch high parapet wallis required above aof ing .
-- Sec.504-6.4
The faces shall be momcombustilale for the uppermost 18 inches
including count erf 1 ashing and coping materials. -- Sec.. 504.x.5
5} See section 504.6.G for requirements when an area separation wall
separates buildings of different heights.
AAUTOMATIC SPRINKLER SYSTEMS:
If openings are not
is floor area more
sprinkler system is
a minimum dimension
opening in every 50
provided in each 50 feet of exterior walk or there
than 75 feet from an exterior ripening, ars automatic
required. -- Sec. g p4 _ 2 . 2 Note: Openings shall have
of 30 inches_ There must be at least 2p sq.f t of
lineral feet of wall.
An automa�ic sprinkler system is required in ars 114 occupa�.cy more than
3000 square feet. -- Sec. 904.2.S.2
An automatic sprinkler system is required in retail sales rooms with a
floor area greater than 12,000 sq -ft- -- Sec_ 904,2,7
If there are 100 or more sprinklers, all valves contralirig the
water supply and water-flow switches shall be electrically�.onitored.
Va1�re monitor and water-flow alarm and trouble signals sha11 be
distinctly different and shall be automatically transmitted to ars
approved central station, remote station or proprietary monitoring
station. --- Sec. 904.3.1
STANDPIPE REQUIREMENTS:
A class II standpipe is required.
A hose is required. -- Table 9--A
FOOTNOTES:
2) The location is to be per
mmnfinear;:�
Section 904 .5.4_
Code review
Proi ect Id.
Address:
VENTILATION:
:
Ail areas customarily occupied by humans
ventilation by means of openable exterior
less than 1f20 of the trial floor area or
mechanically operated ventilation system.of nn] Vi nrT A rn� n-' ? 7 -nit rri -F
Page # 10
shall be provided. with natural
openings with an area of not
shall be provided v�rit-h a
Such system shah be capable
- --1 ��I;uj,1c Leet per minute of outside air per
occupant. --- Sec. 120.2.2.1
WALL AND CEILING FINISH:
17 Wall and ceiling finish materials are required
Sec. 804.1 and Table 8-B.
27 Carpeting on the Ce1I1I7.g 1S required to have a
spread rating. ,- Sec. 804.2
3) Textile wail Coverings shall have Glass I dame
and shah be protected by automatic sprinklers
acceptance criteria of U.B.C. Standard No. 8-2
INSULA'TION NOTES:
tO comply with
Class I
spread
or meet
_- Sec.
1j All insulation material including facings are required
flame. -spread rating of 25 or less and a maximum smoke
unless it -1 is �n a �oncealed._space and the facing is in
flame
rating.
the
805
to have
density
contact
a WcL -L Ul ceiling,, -- Sec. 707.3 etc . Z
2) Foam plastic insulations are required to be protected. -- Sec.
GLAZING REQUIREMENTS
All glazing in hazardous locations is required to be of safety
glazing material. -- Sec. 245.3 & 245.4
Locations
I ) r-" I ::) r7 � -r-) -11
of 450
with
2502
�j ill lf��-L elss dFlu egress c€oors except jalous'es.
2) Glazing in fixed and sliding pa�.els of sliding door assemblies
and panels in swinging doors other than wardrobe doors,
3} Glazing in storm doors.
4} Glazing in all unframed swinging doors.
5) Glazing in doors and enclosures for hit tubs, whirlpools, saunas,
steam rooms, bathtubs and showers. Glazing in any portion of a
building wall enclosing these compartments where the bottom exposed
edge of the glazing is less than 50 inches above a standing surface
and drain inlet.
6 ) Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24 -inch arm of
either vertical edge of the door in a cloyed osition and where
bottom exposed edge of the glazing is less than 5'0 inches above
walking surface.
7) Glazing in an individual fixed or operably panel, other than
locations described in items 5 and G above, than meets alI of
fallowing canditions:
the
thosethe
-
-
-----�---�---� �1�.q �.•«�l nLij-v-iuuai pane greater than 9 square feed .
reviewCode for :
Proi ect Td
Address
Page # 11
B. Exposed bottom edge less than 28 inches above the floor.
C. exposed top edge greater than 36 inches above the floor,
I F
une-a UL illU�� waiKing surzaces witnln 35 inches horizontally of
the plane of the glazing.
87 Glaring in railings regardless of height above a waling
Included are structural baluster panels and nonstructural
9)-1 1
panels.
surf ace.
in--fill
�71dG,1i1y _Ln wa�i-s an�a Lences useci as the barrier for indoor and
outdoor swimming pools and spas when the bottom edgers is fess
GO inches above the pool side and the gla z inq i s within 5 feet
of the pool or spa deck area.
10} Glazing in walls enclosing stairway landings or within
then bottom and top of stairways where the bottom edge
than 60 inches above the walking surtace.
A.DDITIUNAL REQUIREMENTS:
For S3 occupancy
1} Tn parking garages where
the adjacent grade, vehicle
2) The minimum clear height
3} Parking garages require
cfm per sq, ft. of floor
than
5 feet of
is less
any parking is located.moreli tan 5 fejt move
barriers shall be provided. -- Sec. 311.2.3.E
is required to be 7 feet., -- Sec. 311.2.3.3
a ventilation system that exhausts 1.5
area. -- Sec. 1202.2.7
For H4 occupancy
1} If required by the Fire Code, floors shall be reces�e�l a
4 inches �r shall �e provided with a liquid - tight raised
a minimums height of 4 inches. When la'quid-tight sills are
they may be omitted at door openings by the installation
open -grates trench which connects to an approved drainage
-- sec. 307,2.3
2 } Smoke and heat venting shall be provided as set forth in
Fire Code. -- Sec. 307.2.6
For S1 occupancy
For M occupancy
For B occupancy
minimum of
s11 with
provided,
of an
system.
the
Code re -view for:
Project Id..
Address:
ACCESSIBLE FACILITIES:
NOTE: Except as notedE section numbers
CABS/ANSI A117.1 - 1992
WATER FOUNTAIIiTS AND WATER. COOLERS.
Page # 12
listed below are from
At least 50 percent of drinking fountains, but not fess than one,
provided an every floor shall k)e accessible. -- UDC Sec. 1105.4.1
Accessible units must comply with the following-
1)
Spout is to be within 36 inches of the floor, - - Sec. 4.15.2.1
2) Spout arranged for parallel approach shall be located 3 inches
maximum from the front edge. Spouts of cantilevered units with
knee and toe clearances shill be located 15 inches minimum from
the vertical support and 5 inches maximum from the front edge.
-- Sec. 4.5.2.2
3) Spouts shall provide a flow of water 4 inches height minimum.
-- Sec. 4.15.2.3
4) Operable partes shall be located at or near the front edge of the
unit, and shall comply with 4 .2 5 .4 -- Sec. 4.15.3
5} A cantilevered unit is required to extend 17 inches minimum from
the vertical support. Clear knee space must provide a clear area
of S inches in. depth at 27 inches high and 13 inches at 9 inches
minimum above the fiocr, -- Sec. 4.15.4.1
5} Forward approach unity shall comply with 4.2. Units in alcoves
shall comply with 4.2.4.4. Units not having the necessary knee
and toe clearance or dear space under them shall comply with
4.2.4 and have a clew floor space that allows a, person in a
wheelchair to make a parallel approach. -- Sec. 4.15.4.2
TOILET FACIZ,ITIES:
1) A 50 inch diameter unobstructed turning space is required in
the toilet room. -- sec. 4.16.3, 4.2.3 & Fig. B4 . 2 . 3
2 ) Water closest shall be mounted adjacent to a side v►ra11 or
partition. The distance from the side wall or partition to the
centerline of the water closet shall be 18 in. Sic, 4.17.1
3} '(then the accessible water closet is not in a stall:
The clear floor space shall be 48 in minimum in front
of the water and 42 in f rom the center line of the
grater closet on the side not adjacent to the wall.
-- Sec. 4.17.2 & Fig. X4.17.2
4} when the accessible water closet is in a stall:
The stall shall be 50 in wider minimum and 56 in deep minimum
for wall hung water closets and 59 in deep minimum for f
mounted water closets. -- Sec. 4.18.3. 1
If the door swingy into the stall, the required depth shall
be increased by 35 inches minimum. -- Sec, x.18.3.2 &
Fig. B4.18.3. 1
5} The bates are to be 33 to 36 inches above the floor and shall
be provided on the rear wall and on the side wall closest to
Cede review for:
Project fid. :
Address
to the water closet. -- Sec. 4.24.2,E & Figs.
and B4. 18. 3. 1
a) Side grab bar is required to start within
backwall and extend to 54 inches from the
minimum length of the bay- is 42 in} - - Sec
Figs. B4. 17.3 and B4.18.3. 1
13
B.1#1
12 inches
back wail.
. 4.17.4.1
B4.17.4
of the
(The
lig i Gds- d -L siia1l jDe z4 in long minimum, centered on the
water claret. Where space permits, the bar shall be 35 in
long minimum, with the additional length provided on the
transfer gide. -- pec. 4.17,4.2 Figs. B4.17.31 B4.17.4
and B4.18.3. 1
5) The top of the seat on the water closet is required to be 17
to 19 inches above the floor. -- Sem. 4.17 .3 & Fig. X4. 17. 3
7} Accessible urinals shall be of the stall type or v,Tall hung with
the rim at 17 inches maximum above the. floor4, -- Sec. 4 . 19 .2
8} A clew area of 30 X 48 inches minimum is required in front
of the urinal. Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 34 inches apart
minimum. -- Sec. 4.19.3
9} Accessible lavatories shall be mounted with the rim 34 inches
maximum above the floor and a clearance of 29 inches minimum
from the floor to the bottom of the front edge of the apron.
-- Sec. 4.2U.2.1 & Fig. B4.20.3.1
107 It shall extend 17 inches minimum from the wall. The dear knee
space shall be 8 inches in depth minimum at 27 inches minimum
above the floor and 11 inches in depth minimum at 9 in minimum
above the floor. The dip of the overflow shall be ignored when
checking the clearances, -- Sec. 4.20.3.1 & Fig. B4.20.3.1
11) A dear floor space of 30 X 48 inches minimum shall he provided
in front of the lavatory and shall expend 19 inches maximum
under the lavatory. - - Sec. 4.20.3.2 & Fig. B4.20.3.2
12 ) Water supler and drain pipes under lavatories shall be
.2-
insulated or otherwise treated to protect against contact.
-- Sec. 4.20.4
13} The bottom of mirror is required to be within 38 inches of
the floor* -- Sec. 4.16.6 & Fig. B4.20-3.1
=_=--`
SECTTON # 2
DIRECTION
NORTH
EAST
SOUTH
WEST
Allowable
-- Sec&
Property line
Property line
Property line
Separation wall
area increased
505.1
SEPARATIQN
AREA. INCREASE
1 Feet
70 0 Feet
120
0. 0 Feet
1 for
FIRE PROTECTION
150.0
70+0
120.0
0. 0
open area on
Feet
Feet
Feet
Feet
3 sidles
.
Code review for:
Project Id.
Address:
F L NAME occ MAX FLR AREA ALLOWED RATIO STATUS
1
Prep. to spray paint H4 0k 960 1 0.06 ok
I paint spray booth H2 ok 190 7400 0.03 ok
I pant mixing roam H2 ok 110 7400 0.01 ok
1 Mechanical Roam Sl ok 110 24000 0.00 ok
1 Repair Garage S3 0k 1030 24000 0.04 ok
'I'DiAL FOR FLOOR 2400 15755 0,15 ok
BLTILDING TOTAL 2400 15785 0 ok
The actual height of this bu'ldkng is 20.0 f
The maximum height of the building is 55.0 feet. -- Table 5-B
EXTERIOR WALL FIRS RATINGS AND OPENING PRQTECTION
Table 5,A
NORTH
For Baring Non-Pear-ing Opening COnstruction Parapet
Occupancy Wall Wall Protection Material Required
S3 2 hour 0 hour None Non - Comb No
H4 4 hour 0 hour Nene Non - Comb No
H2 4 hour 0 hour Nonce Non - Comb No
S1 2 'hour Q hour Nave Non - Comb No
EAST
For Bearing Non -Bearing Opening Construct'ari Parapet
occurotection Material Requi
pancy Wall 'fnTa11 Pred
S3 2 hour a hour None Non - Comb No
H4 4 hour D hour Node Non - Comb NQ
H2 4 hour 0 haus None Non - Comb No
S1 2 dour 0 hour None Non - Comb No
SOUTH
For Bea- ring Non -Bearing Opening Construction Parapet
occupancy Wall Wall Protection Material Required
S3 2 hoar 0 hour None Non - Comb No
H4 4 hoax' D hour Name Nan - Comb No
H2 4 hour 0 hour Nonce Nan - Comb No
S1 2 hour 0 hour None Non - Comb No
Code review
Project Id.;
Address:
for
WEST
AREA SEPARATION WALL -
See requirements
In two dour walls, fire-retardant- treated
within the assembly provided the exposed
noncombustible. -- Sec. 5D3.4.3
Page ## 15
lIt
isted
wood
outer
dater
framing may be
and inner faces
None -- No f ire protection requirements for
3 /4 hour -- Openings are to be protected with 3/
500 of the area of the wall maximum.
Footnote 5 & pec. 503.2.2
openings.
4 hr fire
- - Table
report.
used
are
1�OLA.-LMuM 6-L1191E: winaow size is 84 sq. ft with no dimension
greater than 12 feet. Sec. 713.8
Not Allowed --- Openings are not permitted in this wall.
OTHER BUILDING ELEMENTS
ELEMENT
Interior fearing wall
Interior nonbrg wall
Structural Frame
Exterior Struck Frame
Floor/Ceiling Assembly
Roof/Ceiling Assembly
Stairs
FOOTNOTES:
MATERIAL
Any
An, y
Any
Any
Any
Any
Any
Table. 5-A
RATING
0
hr
0
hr
0
hr
0
hr
0
hr
0
hr
See footnote 41
See Footnote #9
1} Elements in an exterior wall located where openings are not permitted
or were protection, of openings is required, shall be protected
against external dire exposure as required for exterior bearing walls
or the structural frame, whichever is greater., -- Table. 6-A, footnote
9) In areas with vehicles or airplanes, the floor shall be of
noncombustible, nonabsorbent materials. ,- Sec, 3p7,2,2
DRAFT STOPS :
If there is
stops shill
exceed 3, 000
combustible
be installed
square feet
suops Qaes not exceed 60
ocCupAvcY SEPARATIONS
�3-H4
the
lhr
S3 --H2
andd so
2hr
S3
-S1
lhr
H4
-H2
lhr
H4
-SI
lhr
H2
-Sl
2hr
construction in the roof/ceiling assembly, draft
so that
the
area of
concealed space does not
andd so
that
the horizontal
dimension between
feet, --
Sec.
708.� _
1 . �) )'
Tale 3 -B
Code review fQr:
Project Id,.
0
Address S
KEATING EQUIPMENT SEPARATIQN:
FOR S 3 OCCUPANCY:
A 1hr occupancy separation
boiler or central heating
-- Sec. 302.5
FOR H4 OCCUPANCY:
A 2hr
boiler
FOR H2
A 2hr
boiler
There
Page ff iG
is required around rooms containing a
unit greater than 400,000 BTU 'input,
occupancy separation is required around rooms containing a
or central heatingunit 0 Sec 302 . 5
OCCUPANCY:
occupancy separation is required
or central heating unit, -- Sec.
shall be no openings in such
necessary ducts and piping. Sec..
FOR S 1 OCCUPANCY:
A lhr occupancy separation
boiler or central heating
-- Sec. 302. 5
ADDITIONAL SEPARATIONS:
around
302.5
occupancy
302.5
rooms containing
sle araion except
W
f or
is required around rooms containing a
unit greater than 400,000 BTU input.
L
A refrigerat-ion machinery room shall b
of the building as required for an H7
horizontal occupancy separation may be
area of the machinery room. structural
protected for the type of construction
A 1 hour separation is required from a
SECTION # 2
e separated from the remainder
occupancy
pancy regardless of area. A
to the actual floor
supporting elements shall be
only. -- Sec. 2802
n S3 occupancy,,
EDIT REQUIREMENTS:
FL NAME NUMB MIS MIN PANIC RATED DOOR NOTES
occ EXITS WIDTH HDWR CORRIDOR SWING
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
1 Prep - to spray paint 5 i 0. 1 No Na out
1 paint spray booth 1 1 0.0 Yes No Out 3
1 paint mixing room 1 1 0.0 Yes No Out 3
1 Mechanical Room 0 0 0.0 No No NIR
1 Repair Garage 5 1 0.1 Na Na N/R
TOTAL 12 1 0.2 No Na Out
Door swing is based on Sec,, 1004.2 except as noted.
Occupant load factor is based on Table 10-A.
Number of exits ie based on Table 10-A except as noted.
Exit width is in fee -L-- and based on Sec. 1003.2.
Exit width is to be divided approximately equally among exits.
I
Width shown for all areas is based on other exits. ( 0. 2 )
Width shown for 1st floor is based on other exits. ( 0. 2 )
Width shown for other floors & basements is based on stairways.
For the minimum width of doors, see Sec. 1004,5
For the minimum width of corridors, see Sec. 1005.2
Por the minimum width of stairways, see Sec. 1006.2
(0.3)
Code review f or:
Project 1d.
Address:
FOOTNOTES
3) Panic hardware is based on Sec. 1o18
FLUSH AND SURFACE BOLTS:
Manually operated edge or surface -mounted flush bolts and
bolts are prohibited. When automatic flus. bolts are used
leaf h
the automatic flush bolt shall not have a door'
surface -mounted hardware. The unlatching of any leaf shall
require more than one operation. -- Sec. 1004,.3
LOCKS AND LATCHES:
All means of egress
from which egress is
knowledge or effort.
fey- locking h
consists of a single
doors shall be readily
to be made without the
-- Sec. 1004.3
surface
the door
knob o r
not
openable from the side
use of a key or special
may
Oe used
on
the main
door
or pair
of
doors i f
exit when the main exit
iQI rthrn�-rp M C"__1 +-I
THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS �J" stating
door (s) must swig f I . When unlocked,
without operation of any latching device, -- exc,
wi
LANDINGS AT DOORS:
1 ) A floor or landing shall be provided on each side of doors. When
access for persons with disabilities is required. the floor or landing
shall not he more than 1/2 inch lower than
the threshold. When access
i s not required, the maximum is I inch., -- Sec. 1 0 0 4. 9
2) Landings shall have a width not less than the width of the stairway
or width of the doorway, whichever is the greater. The minimum
length in the direction of exit travel is 44 'Inches., --- Sec, l004.10
TRAVEL DISTANCE:
The maximum travel distance xn this building is 150 feet, Sec. 1003 .4
The maximum travel distance within an H1rH2 or H3 occupancy is 75 feet.
-- Sec. 1018
Cade review for;
Project Id.:
Address:
BUILDING ACCESSIBILITY:
1 }
z)
This building
one entrance
including each tenent
which complus with the
shall be provided with at least
accessible route provisions of
cABo/.sT A117.1, At least 50 percent
accessible. -- Sec. 1103.2.3
of all entrances shall be
nen more
that one
emit is
required from
any accessible
space, each
accessible
portion
of the
space shall
be
served
bv not
leers than two
accessible means of egress. -- Sec. 1104.1.1 +
3) When an exit stairway is dart of an accessible means of egress, the
stairway shad have a clear width of not less than 48 inches between
the handrails. The stairway shall e therincorporate an area of refuge
within an enlarged stogy -level landing or shad be accessed from
an area of refuge. -- Sec. 1104.1.2
The area of refuge shall have direct access to the stairway that serves
Sec. 1104.2.1
4) Each area or' refuge shall be sized to accommiodate one wheelchair spare
not leis than 30 inches by 4$ inches dor each 200 occupants, or
portion thereat. --- Sec. 1104.2.3
5) If the area of refuge is not within the stairway, it shall be separated
from the rest of the story by a smoke barrier having at least a one-
hour fire-resistance rating. Smoke barriers shall extend to the roof or
floor deck above. Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes. -- Sec. 11 4.2.4
5) Two-way communications are required. -- Sec. 11a4.2.5
73 Each area must be identified by a sign stating AREA OF REFUGE and the
international symbol of accessibility.
RQflFING REQLTIREMENTS
1} The roofing on this building is required to be Class C. -- Table 15-A
27 See section 1504 and ICB4 research reports for requIt
irements.
AREA SEPARATION WALL REQUIREMENTTS -.
3) The area separation wall is required to be a 4 hr fire assembly.
Openings are limited to 25 percent of the length of the wall and
protected with a 3 hour assembly. -- sec. 504.6.E
2) If the building has a projection', lhr protection zs required on
the exterior wall each side of the area separation wall equal to
the depth of the projection.--- Seg, 504.6.3, exceptions
Ol1 "ds d conceaiea space at the area separation,
wa11, the area separation wall must extend through the projection.
3} If the area separation wall terminates at an inside corner, see
the article in 'Building Standards' Sep/Qct 1982 for requirements.
4} A 30 inch high parapet wall is required above the roofing.
--- Sec . 5Q4 . 6 _ 4
The daces shall be momcombustible for the uppermost 18 inches
including eaunterflashing and coping materials. -- Sec. 504.5.5
5) See section 504.6.5 for requirements when an area separation wallseparates buildings of different heights..
reviewCode z
Project Id.
Address 4
AUTOMATIC SPRINKLER SYSTEMS:
If openings are not
I'
is f ioor area more
sprinkler system IS
a minimum dimension
opening in every 50
provicieci in each 50 feet of exterJ_or wall or there
than 75 feet from an exterior opening, an automa-tic
required. -- Sec. 904.2.2 Note: Openings shall have
of 3 D inches. There must be at least 2 0 sq. ft of
lineral feet of wallm,
An automatic sprinkler system is required in an H13 occ.
-- Sec. 9Q4.2,5.1
If there are 100 or more sprznklers, all valves controling the
water supply and water -flaw switches shall be electrically monitored.
Valve monitoring and water -flow alarm and trouble signals shall be
distinctly different and shah be automatically transmitted to an
approved central station, remotes station or proprietary monitoring
statiori. -- Sec. 904.3.1
STANDPIPE REQUIREMENTS:
There is no requirement for a standpipe.
FOOTNOTES:
VENT I LAT I ON
All areas customarily occupied by humans
ventilation by means of openable exterior
less than 1/20 of the total floor
mechanically operated ventilation
of supplying a minimum of 15 cubic
occupant, -- Sec. 1202.2.1
area or
system.
r
- - Table 9 -
shall be provided with natural
openings wa.th an area of nat
shad be provide. with a
Such system shall be capable
=eeE per minute of outside air per
WALL AND CEILING FINISH:
1} Wall and ceilingfinish materials are required
Sec. 804.1 and Table 8-B.
2} Carpeting on the ceiling is required to have a
spread rating. -- Sec. 844.E
37 Textile wall coverings shall have Class I flame
and shall be protected by automatic sprinklers
acceptance criteria of U.B.C. Standard No. 8-2
1 NsuLAT z ozv NOTES mo
1} All insulation material including
flame -spread rating of 25 or less
unless it is in a concealed space
to comply with
Class I flame
spread
or meet
- Sec.
facings are required
and a maximum smoke
and the facing is in
R
VV OL ;IJ _L C 6=2 1111g. -- pec. VU`I . 3 exc . 2
2} Foam plastic insulations are required to be protected.
rat
the
805
to have
density
contact
of 450
with
-- Sec. 2602
Cade review for
Project Id.:
Address:
GLAZING REQUIREMENTS
All glazing in hazardous locations is required to be of safety
glazing material. -- Sec. 2406.3 & 2405.4
Locations:
1) Glazing in ingress and egress doors except jalousies.
2} Glazing in firmed and sliding panels of sliding door assemblies
and panels in swinging doors other than wardrobe doors..
3) Glazing in storm doors.
47 Glaring in all unframed swinging doors.
5 } Glazing in doors and enclosures for hot tubs, whirlpools, saunas,
steam rooms, bathtubs and. showers. Glazing in any portion of a
building wall enclosing these compartments where the bottom exposed
edge of theglazing is leers than 50 inches above a standing surfaces
and drain inlet.
6} Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24 -inch arc of
either vertical midge of the door in a closed position and where the
bottom exposed edge of the glaring is less than. 60 inches above the
walking surface,
7} Glazing in an individual firmed or operable panel, other than those
locations described in items 5 and 6 above, than meets all of the
following conditions.-
A.
onditions:A. Exposed area of an individual pane greater than 9 square feed.
B. Exposed bottom edge less than 18 inches above the. floor.
C. Exposed top midge greater than 35 inches above the floor.
D. One or more walking surfaces within 36 inches horizontally of
the plane of the glazing.
8} Glazing in railings regardless of height above a walking surface_
Included are structural baluster panels and nonstructural in -fill
panels.
9 ) Glazing in walls and f ences used as the barrier f or indQor and
outdoor swimming pools and spas when the bottom edges is Less than
60 inches above the pool suede and the glazing is within 5 feet
of the pooh or spa deck area.
10} Glazing in wars enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottomedge is less
than 60 inches above the walking surface.
ADDITIONAL REQUIREMENTS:
For S3 occupancy
1 i zx1 parking garages where
the adjacent grade, vehicle
27 The minimum clear height
3} Parking garages require.
cf m per sq. f t. of f loor
any parking is located more than 5 feet above
barriers shall be provided. -- Sec. 311.2.3.5
is required to be 7 feet, -- Sec. 311.2-3.3
a ventilation system that exhausts 1.5
area, -- Sec. 1242.2.1
Page # 21
Code review forle
Proj eCt Id.
Addre S S
For 144 occupancy
1) If required by the Fire Code, floors shall be recessed a
4 inches or shall be provided with a liquid -tight raised
a minimum height of 4 inches. When liquid --tight sills are
they may be omitted at door openings by the installation
aper -grate trench which connects to an approved. drainage
-- Sec. 307.2.3
2) Smoke and heat venting shall be provided as set forth in
Fire Code. -- Sem. 307.2.6
For H2 occupancy
1} If required by the Fire bode, floors shall be recessed a
4 Winches or shall be provided with a liquid -tight raised
a minimum height of 4 inches. When liquid --tight sills are
they may be omitted at door openings by the installa 'ion
open -grate trench which connects to an annrovPd bra � -narrA
-- Sec. 307.2.3
2} Smoke and heat venting shall be
Fire Code. -- Sec. 307.2.6
3} Standby power shall be provided.
r E C`F�,11 Y'P C9 P l P C 1' Y' i r-1 � �1 n rrz i -i r, m � �-, +-
provided as set forth in
1---- -�iA1.11 J_JL1iz=11 L.. . -
For Sl occupancy
minimum of
sill with
provided,
of an
system.
the
minimum of
sill with
provided,
of an
system.
It shall supply power to all
Sec. 307.2.6
Floor -1st Occupancy -paint spray booth
MIXING/DISPENSING
If Clays I. IT/ or Clasp III -A flammabie or combustible liquids
are used, dispensed or mixed in open containers, then the
following is required.
This area is required to be separated from other areas by at
least a 2 hour occupancy separation. -- pec. 307.1.3
Shelving, racks and wainscoting shall be of rio�rnmh��ct; r�
construction or wood not less than 1 -inch
-- SeC. 307.2.3
Flaflr-1st occupancy -paint
MIXING/DISPENSING
mixing room
nominal thickness,
If Mass I, II, or Gass III -A flammable ar combustible liquids
are used, dispensed or mixed in open containers, then the
foilowing is required.
This area is required to be ,separated from other areas by at
leash a l hour occupancy separation. -- Sem. 307.1.3
Shelving, racks and wainscoting shall be of noncombustible
construction or wood not less than 1 -tench nominal thicknco;5.
-- Sec. 307.1.3
Code review f or
Project Id.
Address:
Page # 22
ACCESSIBLE FACILITIES:
NOTE : Except as noted, section numbers listed below are from
CABO/ANST A117. 1 - 1992
WATER FOUNTAINS ANIS WATER COOLERS:
At least 50 percent of drinking fountains, but not less than one,
provided on every floor shall be accessible. -- UBC Sec. 1105.4.1
di
Accessible units Must comply with the following:1Spout is to be within 3 6 inches of the floor -- Sec. 4.15.2. 1
2) Spout arranged for parallel approach shall be*
JSpouts
located 3 inches
maximum from the front edge.I
of cantilevered units with
knee and tee clearances shall be located 15 inches minimum from
the vertical support and 5 inches maximum from the front edge.
-- Sec. 4.15.2.2
2) Spouts shall provide a flow of water 4 inches height minimum,,
-- Sec. 4.15.2.3
4) Operable parts shall be located at or near the front edge of the
unit and shall comply with 4.25.4 -- Sec. 4.15.3
5) A cantilevered unit is required to extend 17 inches minimum from
the vertical support. Clear knee space must provide a clear area
of 8 'Inches in depth at 27 inches high and 11 inches at 9 inches
minimum above the floor., -- Sec, 4.15.4.1
6) Forward approach units shall comply with 4.2. Units in alcoves
shall comply with 4.2-4.4. Units not having the necessary knee
and toe clearance or clear space under them- shall comply with
4.2.4 and have a clear floor space that allows a person in a
wheelchair to make a parallel approach., -- Sec. 4.15.4.2
TOILET FACILITIES:
1) A 60 inch diameter unobstructed turning space is required in
the toilet room, -- Sec. 4.16.3, 4.2.3 &: Fig. B4.2.3
2 ) Water closet shall he mounted adjacent to a side wail or
partition. The distance from the side wall or partition to the
centerline of the water closet shall be 18 in., Sec. 4.17.1
3) When the accessible water closet is not in a stall:
The clear floor space shall be 48 in minimum "in front
Of the water closet and 42 in from the center line of the
water closet on the side not adjacent to the wall,,
-- Sec. 4.17.2 & Fig. P4.17.2
4) When the accessible water closet is in a stall -
The stall shall be 60 in wide minimum and 56 in deep minimum
for wall hung water closets and 59 in deep minimum for floor
mounted water closets., -- Sec. 4.18-3.1
If the door swings into the stall, the required depth shall
be 'increased by 36 'inches minimum. -- Sec. 4.18.3.2 &
Fig. 34.18.3,.1
5) The bars are to be 33 to 36 inches above the floor and shall
be provided on the rear wall and on the side wall closest to
Code review for:
Prod ect Id.
Address:.
Page ## 23
to the ,rater Closet. -- Sec. 4.24.2.2 & Figs.
and B4. 18.3. 1
a} Side grab bar is required to start within
backwall and extend to 54 inches from the
minimum length of the bar is 42 in} ,- Sec
Figs. B4.17.3 and B4.18.3. 1
it � T h �s r a � ter- 7•, � .- ,-. L, -, 1 � 1.... ,_, r, h _ __
B4. 17. 3,
12 inches
back wall,
4.17.x.1
B4.17,4
of the
(The
�n long minirnum, centered an the
water closet. Where space permits, the bar shall be 3G in
long minimum, with the additional length provided an the
transfer side. --- Sec. 4.17.4,E & Figs. B4.17.31 84.17.4
and B4. 18. 3. 1
6} The tap of the seat on the water closet is required to be 17
to 19 inches above the floor, - - Sec. 4 .1'7.3 & F�.g . B4 .17 .3
7) Accessible urinals shall be of the stall type or wall hung with
the rim at 17 inches maximum above the floor. -- Sec. 4.19.E
8 } A char area of 30 X 48 inches minim.um .is required in front
of the urinal. Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 inches apart.
minimum. -- Sec. 4.19.3
9) Accessible lavatories stall �e mounted with the rim 34 inches
maximum above the f loor and a clearance of 29 inches minimum
from the floor to the bottom of the front edge of the apron.
--- Sec.. 4.2Q.2.1 & dig. B4.20.3.i
10) It shall extend. 17 inches minimum from the wall. The clear knee
space shall be 8 inches in depth. minimum at 27 inches minimum
above the floor and ll inches in depth minimum at 9 ice. minimum
above the, fiocr. The dip of the overflow shall be ignored s,,,rhen
checking the clearances. -- Sec, 4,20.3.1 & F ig, B4,20.3.1
11) A clear floor space of 30 X 48 J-nches'min'mum shall be provided
in front of the lavatory and shall extend 19 inches maximum
under the lavatory. -- Sec. 4.20.3.2 & Fig. B4. 2 0. 3 . 2
12) Water supply and drain pipes under lavatories shad be
insulated or otherwise treaded to protect against contact.
-- sec. 4.0.4
13} The bottom of mirror is. required to be within 38 inches of
the floor. -- Sec. 4.16.6 & Fig. B4.20.3.1