Loading...
HomeMy WebLinkAboutPLAN ANALYSIS MAY 1 - 95-00012 - Madison Memorial Hospital - Expansion Phase 1r City of Rexburg En gineering Department 12 North Center/P.O. Box 280 Idaho 83440 359-3020 Rexburg, (los) Plan analysis based on the 1991 Uniform Building Code Project Number: Name: MADISON HOSPITAL Address: HYDROTHERAPY & MEETING ROOM 112 Date: May I r 1995 Contractor: NOT KNOWN Occupancy: Jj.1,A3,E2 Type of Const: II -N Architect: JOHN WATSON Engineer: LEON TANNER Plans Examiner: JOE LAIRD NOTE:The cads i�em� listed in this report are not intended to be a complete 0 listing of all possible code requirements in the 1991 UBC. It is a guide to selected sections of the code. Report created using Plan Analyst software by b w & a . (719) 5 Portions of the material contained in this program ars reproduced from the Uniform Building Cade � 1992 edition) with permission olf InternatiQnal Conferent"e of Building Offica.als . Sprinkler system used for area increase NORTH Building EAST Separation wall SOUTH Separation wall WEST Separation wall SEPARATION IR "Ir .0 i4 4 FIRE PROTECTION 16 0 Feet 8 * 0 Feebt 0 0 Foet 0 e 0 Feet 0- 0 Feet 0 a 0 Feet 0 0 Feet 0 e 0 Feet gi, NAME OCC MAY... FLR AREA ALLOWED RATIO STATUS 1 HYDROTHERAPY ROOM I1. 1 ok 1644 13500 0.12 ok 1 POOL EQUIP. STORAGE I1.1 ok 150 13500 0,01 ok 1 STORAGE ROOM B2 ok 142 36000 0.00 ok 1 MEETING ROOM # 112 A 3 ok 796 27300. 0. 03 ok 1 REST ROOMS I HALLS I ETC I1.1 ok 614 13500 0.05 ok TOTAL FOR FLOOR 3345 15822 0.21 ok BUILDING TOTAL 3346 15822 0.21 ok Allowed area for I1.1 based on section 1002.(a) exc. # 3. Codes review fore z .r a Project Id.! MADISON ROSPITAL Address: HYDROTHERAPY & MEETING ROOM 112 The actual height of this building "'is i7.0 feet. The maximum height of the building is 55.0 feet. -- Table 5-D EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 17,x -PA & Table 5-A W. NORTH 0CC BRG NON�BRG OPNG TWALL V',&.LL PROT I1.1 A3 B'2 EAST BRG NON-*oBRG OPNG T47.4.LL TITALL PROT ihr 1hr Prot SOW** sewo saw** seww* lhr 1hr Prot S.W.* hr S.W.* lhr 1hr Prot S.W.* sows* S.W.* sown* shall be installed and maintained in accordance with Nonflammable supply cylinders located inside the be separated from the rest of the building by not less e --resistive construction. Openings shall be protected S.W. S.W. S.W. SOUTH BRG NON"-BRG OPNG WALL BRG NON�BRG OPNG FRALL WALL PROT sawv-* f�:et. 40ww slwwoo* (h) sewo are not seww* this wall. stwe* hr S*W* hr SOW** Sawa* s aw& sows* sown* S - Owe sowe* s*Wo* sow* Sawa* Sawa* sow* The exterior walls are required to be of NONCOMBUSTIBLE Material. Sec.19(31. None No fire protection requirements for openings. Prot openings are to be protected with 3/4 hr fire assemblies. area of the wall maximum. Sec.. 504.(b) & Sec.19o3.(b) & Table Maximum single window size is 84 sq,.ft With no dimension greater than 12, f�:et. 40ww *AMP Sec. 4306 * (h) NOP �-F& openings are not permitted in this wall. ELEMENT Interior Bearing wall Interior nonbrg wall Structural Frame Exterior Si�ruct Frame Flvoar/deiling Assembly Roaf/Ceiling Assembly Stairs MATERIAL Noncombustible Noncombustible Noncombustible Noncc��nbustible Noncombustible Noncombustible Noncombustible Table 17-A RATING 0 hr 0 hr 0 hr 0 hr 0 hr 0 hr None NOTES 50% of the 5-A See f ootnote # 1 FOOTNOTES ,1) Elements in an exterior wall located where openinqs are not permitted or where protection external fire' exp structural fran�e, of openings is required, shall be protected against a -W osure as required for exterior bearing walls or the whichever is greater,. *�Mft=17-A,footnote I 1 Table Code review fore Project Id.: MADISON HOSPITAL Address: HYDROTHERAPY & MEETING ROOM 112 OCCUPANCY SEPARATIONS mwft- Table 5-B I1.1 -A3 2hr I1.1 -B2 2hr A3 -B2 Ohr, ADDITIONAL SEPARATIONS 0 FOR I1.3 OCCUPANCY. Medical gas systems the Fire Code. building shall than 1 hour fir X, by self-closing smoke and dr aft- control assemblies hav,ing a t ire- protection rating of not less than 1 hour., -- sec. 1002 0 (b) With an exterior wall `here shalI be not less than 2 vent inches in area. one vent shall be wi one shall be within 6 inches of the Without an exterior wall of not less than 36 square thin & inches -of the f loor and ceiling. An automatic sprinkler system is required in the room. The room shall be vented to the exterl'or through ducting contained within a one-hour shaft enclosures. Approved mechanical ventilation shad provide 6 air charges per hour for the room. A 1hr occupancy separation is required around roams containing a boiler or central heating unl*t. ---- Sec. 1008 & TABLE 1 4-A Room or Area Separation Employee locker room nano Gift/retail shops Wane Handicraft shops none kitchens none Labs using Hazardous material (nit H occ.) 1 hour Laundries greater than 100 sq.ft. 1 hour Paint shops using 1H' material(not H occ , ) 1 hour Physical plank maintenance ship 1 hour Sailed. linen roam 1 hour Storage rooms, 10U sq.ft. or less none Storages rooms more than 100 sq.ft. l hour Trash collection roams 1 hour FSR A 3 OCCUPANCY A 1hr occupancy separation is required around rooms containing a boiler or central heating unit greater than 400,,000 BTU input.; -- Sec. G08. FOR B2 OCCUPANCY -op A 1hr occupancy separation is required around rooms containing a boiler or central heating unit greater than 400,000 BTU input.. -�- Sec. 708. gage # 4 Code review for. Project Id.: NIADISQN HflSPITAL Address: HYDROTHERAPY & MEETING ROOM 112 EDIT REQUIREMENTS: FI., SAME OCCUPANT NUMBER EXIT PANIC RATED DOOR NOTES LOAD REQUIRED WIDTH HDWR CORRIDOR SWING 1 HYDROTHERAPY ROOM 21 2 0.3 No Yes NIR 15 1(} 1 PGOL EQUIP. STORAGE 2 1 0.0 No No NSR 15 10 1 S TORAGE ROOM 0 1 000 No No N jR 1 MEETING ROOM # 112 53 2 4. 9 Yes Yes Out 4 1 REST ROOMS I HALLS i ETC 8 2 001 ND No N/R 15 1(] TOTAL 84 2 1.4 Yes Yes Out Rated corridors are to have 1hr fire protection on hath sides of walls and ceilingSec. 3305.(g) Door openings are required to be protected. with 20 minute assemblies and window openings are required to be protected with labeled 3 j4 hour assemblies* -�- Seg. 3305.(h), in meas where 2 exits are required, the minimum separation is 1/2 of the maximums diagonal of the area or floor. -- SSC. 3303.(C) Exit signs are required from all areas serving an occupant load of 50 or mars*. -- See. 3314.(a) Door swing is based on Sec. 3304.(b) except as noted. Occupant load is based on Table 33-A. Number of exits is based on Table 33-A except as noted. Exit width is in feet and based on pec. 3303.(b). Exit width is to be divided approximately equally among exits. Width Sec . 3 304 shown for all For the areas is width. based on ether exits. corridors, (0,.2) 3305.(b) Width shown f or ist f loor is based on ether exits. (0 -a 2 ) Width shown for other floors & basements is basted on stairways. (0..3) For the minimum width of doors, see Sec . 3 304 . (f0 ) For the minimum width. of corridors, gee Sec, 3305.(b) For the minimum width of stairways, see Sec. 3306.(b) FOOTNOTES 4) Panic hardware is based on Sec. 3 317. (d). See exception fir main emit in A-3 occupancies and churches. 10) All required exterior doors are required swing out. -�- Sec. 3320. (a) i5) Nurses stat �.ons are net required to be separated from the corridor. Waiting areas may not need to be separated. See restrictions. Closers are not required on sleeping rooms. Glazing along corridor may be fully --tempered or laminated glass,. See limitations. -- Sem. 3320.(c) HANDICAPPED ACCESS: 1) Handicapped access is required to at least one primary entrance 4o this building. w� Sec. 3103.(a) & (b)30 2) If a ramp is used dor handicapped access the mix slope is ].:12. -- sec 3307.(c) Code review for: Pro)ect Id.0 MADISON HOSPITAL Address: HYDROTHERAPY & MEETING ROOM 1.1.2 Prov ide a landing within 1 inch (1/2 inch at doors used for hand icapped access) of the threshold. -- Sec. 3304.(i) The minimum width is same as door width and the minimum length is 44 inches, -- Sec. 3304.(j) The maximum travel distance �.n this building is 200 feet. __ Sec. 3303.(d) ROOFING REQUIREMENTS: AUTnMATIC 5PRINKLER SYSTEMS: If thereare 20 or more sprinklers, the automatic sprinkler system shall be supervised by an approved central, proprietary, or remote station service or a local alarm which will give an audible signal at a constantly attended location. -- Sec. 3803.. 0 STANDPIPE REQUIREMENTS: There is no requirement for a standpipe. -- Table 38-A A hose is not required. -- Table 38---A FOOTNOTES: 1) The location is to be per Sec. 3805.(c),(d),and/or(e) WALL SND CEILING FINISH; 1) Wall and ceiling finish materials are required to comply with eco A. 4.1a anJ Tabl(? A9'.4"Ba 2) Carpeting on the ceiling is required to have a Class I flame 4k spread rating. -- Sec, 4204.(b) 3} Textile walk coverings shall have Class I flame spread rating. and, shall be protected by automatic sprinklers or meet the acceptance criteria of U . B, C . Standard No . 42-2 �-%~ sec. 4205. INSULATION N 1) All insulation material including facings are required to have a flame -- spread rating of 25 or less and a maximum smoke density of 450. _-- Sec. 1714.(c) 2} Foam plastic insulations are required to be protected. --- Sec. 1713. GLAZING REQUIREMENTS: All glazing in hazardous glazing material. -- Sec. locations is required to be of safety 5406. (4) Code review for: Project Id.: MADISON HOSPITAL Address: HYDROTHERAPY & MEETING ROOM 112 ADDITIONAL REQUIREMENTS For I1. 1 occupancy in all areas customarily occupied by humans provide natural or artificial light and ventilation. -- Sic. 1005. Provide an approved fire alarm system --- Sec. 1x09. Provide a smoke detector in all roams used dor sleeping. -- Sec* 1010. N€3TE: Provide at least 2 compartments with. a smoke stag partition between them. -- Sec. 1002,.(b) The minimum door width when patients are transported through them in litters or beds is 44 14l'iCh[?5 clear. _-. SSC. 3320.(b) The minimum corridor width when there are nvnambulatory patients is 8 feet Clear. �- Sec. 3320.(c) For A3 occupancy Permanent platforms shall be constructed of materials as required for the building type of construction. 6- Sec. 39x2. If the area under the platform is used for any purpose (including storage) other than equipment wiring or plumbing, then the floor construction shall be not less than 1 hour fire resistive. -- Sec. 3902. Floor -1st Occupancy -MEETING ROOM # 112 The capacity of this area is required to be posted at 53 occupants* 1�4=- Sec. 3302.(c) -!r P6� 92 888UPftnOY In all areas customarily occupied by humans, provide natural Or artificial light and ventilation. 44" moo Sec.. 705,(a)&(b) HAND ICAPPED REQUIREMENTS: _NOTE: Section numbers listed below WATER FOUNTAINS: are from ANSI A117.1 - 1986 1 ) one must have a spout within 36 inches of the f loor . -- pec . 4 . 15 . 2 2 ) Shout must be at the front of the unit. �--� Sec. 4.15.3 a) 56 3} Controls mint be at or near the front of the unit. -- Sem. 4.15.4 & 4.25.4 4 } A cantilevered unit a gide approach. is required to provide a clear area under the unit of Figo 27 inches high. 30 inches wide, and 17 inches deep. -- Sece 4.15.5 (1) 5 ) A clear area of 34 X 48 inches is required at the fountain. The clear Fig. area is required to provide far a f orward approach with a cantileverod by snit and fvr a sides inches deep with app��ach vtherw se. -� Sem. 4.15.E & Fig.27 b1crd TOILET FACILITIES: 1} A 5' diameter unobstructed turning space is required in the toilet room. -- Sem. 4.2.3 & Fig. -- Sec. 3(a) compartment, & Fig. 29 2) When wader closet is a) 56 not in a compartment, the clear area required is: a) 48 inches wide by 56 inches deep with a gide approach. _-- Sec. 4.14.2 b) 66 & Figo 28 wider b) 48 inches wide by 66 inches deep with a front approach.. __ Sec. 4.16,.,2 the peat & Fig. 28 be c) 60 inches wide by 56 inches deep with both approaches. -- Sec. 4. 16 . 2 & Ficj. 28 d} Side bar is required to start within 12 extend to 54 inches f rom the back wall. Code review for: Project Id.: MADISON H09PITAL Address:, HYDROTHERAPY & MEETING ROOM 112 inches of the back wall and -- Sec. 4.16.4 compartment, & Fig. 29 The rear bar is required to be, 36 inches long,. --- Fag. 29 3) When mater closet is in a compartment, the area required is.. a) 56 inches deep by 60 inches wide Frith a grab bar at the bank at the side. Door is at front or side. -- Fig. 3(3(a) or b) 66 inches deep by 36 or 48 inches wider with grab bars an beth and dear at brant. �- Fig. 30(b) 5) The dog of -k 0 an +rim sides ,d) If a floor mounted water closet is used, the depth 19 dimension shown above mint be .increased 3 inches. �- Fig. 30(a) & the e} Side bars are required to start within 12 inches of the hack wall and extend to 54 inches from the bask wall. -- Fig. 7.56a & 7-w56b floor. -- The rear bar is required to start within (d) G inches of the sides wall 5) and be 36 inches long. -- Fig, 30(a) 4) The bars are to be 33 to 36 inches above the floor. -- Fig. 29(a),(b) & Fig. 30(c), (d) 5) The dog of the peat an the water closet is required to be 17 to 19 inches above the floor. -- Fig. 29(b) & Fig. 30(d) 6) Urinals are required to be stab type or have an elongated rim and be within 17 inches of the floor. --- Sec. 4.18.2 & Fig. 29(c) 7) A clear area of 30 X 48 inches is rewired in front of the urinal. wra Sec. 4.18.3 8 ) Accessible lavatories shall provide a dear area under the lavatory of 29 I -- Sec. 4.19.2.1 & Fig. 31 9) A clear area of 30 X 48 inches is required in f ron -- Sec. 4.19.3 & Fig* 32 10) Tnc Dottom of Mirror ii r@Quiroa t0 bo 'witgin 0 1 --Sec. 4.19.6 & Fig. 31 t of the lavatory. 19ARD 81 AA IIAAP-G Project Number: NA Address: CAFETERIA & City of Rexburg Eng41 ineering Department 12 North Center/P.O. Box 280 Rexburg, Idaho 83440 (208) 359-3020 Plan analysis based on the 1991 Uniform Building Code Name,: MADISON HOSPITAL r tSU J1N 1''JJ Ur•r•tCE5 nira�, Occupancy: B2,A3;I1.1,A3,B2 Type of Const: II0MWNj I -N err.r��i NOTE,* The listing selected code items listed in this report of all Possible code requirements sections of the code . 0 a s� _Z Contractor: NINE I r 1995 Architect: JOHN WATSON Engineer: LEON TANNER Plans Examiner: JOE LAIRD are not intended to be a complete in the 1991 UBS. It is a guide to Report created using Plan Analyst software by b w & a. (719) 599-5622 :portions of the material contained in this program a reproduced f rom Uniform i Code 1991 edition) wit iissi Intprnational no -W& i. meq. = , yrs - �a5 eieeey ..rte �� � � � �'�r4����r,e.. �� �� �� �.w. � �F .-..rte � s.�srr� ..�� � i•� ii�a�F+�® - � �� �� erg � � w -.v �. � � :.;eat •sr� � SECTION' rinkler systera used DIRECTION NORTH EAST SOUTH WEST for area & increas SEPARATION AREA INCREASE Separation wall Separation wall Separation wall Property line 0. 0 Feet 0. 0 Feet 0. 0 Feet 200.0 0 Feet k'IRE PROTECTION 0. 0 Feet 0. 0 Feet 0. 0 Feet 200. 0 Feet FL NAME OCC MAX FLR AREA — -ME "M moo ii i ! MR NOW Moo � MM � 4210 H i fam � 1'* 4— do— —P -MAW MWED -ft" 4� i emelt VUW 4&Mhw as amw FrvW .aio aiefF E=14b � 'K.. fbw "W, 1 BUSINESS OFFICES B2 1 KITCHEN/SERVING AREA A3 1 CAFETERIA SEATING A3 1 RST RMS & CORRIDORS B 2 TOTAL FOR FLOOR BUILDING TOTAL Code review for. Project Id.: MADISON HOSPITAL ok 2244 36000 ok 1036 27300 ok 2038 27300 ok 1916 36000 7234 31L706 7234 31706 0.06 ok 0.04 ok 0. 07 ok 0.05 ok 0. 2 3 ok 0.23 ok the Address : CAFETERIA & BUSINESS OFFICES The actual height of this building is 17.0 feet. NOTE.* The height of the aircraft hanger may be unlimited if the minimum clear area around the building is not -less than one and one-half times the building height. -- Sec 507 Exc. #2 The maximum height of the building is 55.0 feet. -- Table 5-D EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 17-A & Table 5a -,&A The exterior walls are required to be of NONCOMB€7S`PIBLE material. Sec.1901,, Nine -- No firms protection requirements for vpenings. Prot --- Openings are to be protected with 3/4 hr fire assemblies. 50,0..o of the area of the will maximums. Sec., 504,.(,b) & Sec.1903.(b) & Tables 5-A Maximum singles window sizes is 84 sq.ft with no dimension greater than 12 feet. d~- Sec. 4306 9 (h) NOP-- openings are not permitted in this wall. [$100014HARIMP 00MMEWIMA %ZUR ELEMENT Interior Bearing mall Interior nonbrg will Structural Frame Exterior Struct Frame F1vvr/Ceiling Assembly Roof /ceiling Assembly Stairs MATERIAL Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Table 17-A RATING 0 NORTH 0 EAST SOUTH hr 0 WEST OCC BRG NON-BRG OPNG BRG NON-BRG OPNG BRG NON-BRG OPNG BRG NON-BRG OPNG WALL WALL PROT WALL WALL PROT WALL WALL PROT WALL WALL PROT B2 S.W.* S.W.* S.W. S.W.* S.W.* S.W. S.W.* 5.W.* S.W. Ohr Ohr None A3 S.W.* S.W.* S.W. S.W.* S.W.* S.W. S.W.* S.W.* S.W. Ohr Ohr None The exterior walls are required to be of NONCOMB€7S`PIBLE material. Sec.1901,, Nine -- No firms protection requirements for vpenings. Prot --- Openings are to be protected with 3/4 hr fire assemblies. 50,0..o of the area of the will maximums. Sec., 504,.(,b) & Sec.1903.(b) & Tables 5-A Maximum singles window sizes is 84 sq.ft with no dimension greater than 12 feet. d~- Sec. 4306 9 (h) NOP-- openings are not permitted in this wall. [$100014HARIMP 00MMEWIMA %ZUR ELEMENT Interior Bearing mall Interior nonbrg will Structural Frame Exterior Struct Frame F1vvr/Ceiling Assembly Roof /ceiling Assembly Stairs MATERIAL Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Table 17-A RATING 0 hr 0 hr 0 hr 0 hr 0 hr 0 hr None See Footnote #5 See footnote #1 FOOTNOTES 1} Elements in an exterior wall located where openings are not permitted or, where protection of openings is requ�.red , shall be protected against external firms exposure as required for exterior bearing walls or the structural frame, whichever is greater. -- Table 17-A, footnote 1 5 ) Nonload--&bearing malls within a tenant spacethat are �.c�t part of a 1hr corridor may be of a} NoncombustiLble (nonrated) materials b) Fire retardant --treated wood c} One-hour construction (any material) -- Sec. 1705 a (b) I Code review f or. Project Id.: MADISON HOSPITAL Address: CAFETERIA & BLPSINESS OFFICES OCCUPANCY SEPARATIONS -- Table 5-B B2 -~A3 Ohr ADDITIONAL S&PARATIONS FOR B 2 OCCUPANCY: A 1hr occupancy separation is required around rooms containing a central heating unit greater than 400,000 sou input,. -- seg. FSR A 3OCCUPANCY4& A 1hr occupancy separation is required central heating unit greater than 9ECTION 2 sprinkler system used for area lancrea-se DIRECTION BOUNDARY AREA INCREASE bo 1Ier or around rooms containing a boiler or 400,fOOO BTU input. -- Sec, 608. FIRE PROTECTION NORTH Build -ling 16. 0 Feet 8.00 STATUS EAST Separation wall 0. 0 Feet 0.0 OPNG SOUTH Separation wall 0. 0 Feet 0.0 0..01 WEST Separation wall 0. 0 Feet 0.0 13500 Feet Feet Feet Feet FL NAME OCC MAX FLR AREA ALLOWED RATIO STATUS ------------------------------------------------------------------- BRG NON-BRG OPNG BRG NON-o-BRG OPNG 1 POOL EQUIP.RiyI# 113 I1.1 ok 150 23500 0..01 I1. 1 ok 1 HYDROTHERPY ROOM I1.1 ok 1644 13500 0.12 1hr ok 1 STORE ROOM # 111 B 2 ok 142 36000 0-.00 1hr ok 1 MEETING RM # 112 A3 ok 796 27300 0.03 ok 1 RST RMS. & HALLS 'Il 0 1 ok 614 13500 0.05 ok TOTAL FOR FLOOR 3346 15822 0.21 ok BUILDING TOTAL 3346 15822 0.21 ok Allowed area for I1.1 based on section 1002.(a) exc. 3. The actual height of this building is 17.0 feet. The maximum height of the building is 55.0 feet. -- Table 5-D EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 17-A & Table 5-A SOUTH BRG NON-BRG OPNG WALL S.W.* Sow* * S -8 W'M * WALL S.W.* S.W.* S'W Ww * sows S 0 W S0� 11,10n -i BRG NON—BRG OPNG WALL WALL PROT s4kwo* S 0 W 0* S.W.* s,owd.* S -OW -0 sown* s9wo Sows,* -OW-0 The exterior walls are required to be of NONCOMBUSTIBLE material. Sec.1901, None ---- No fire protection requirements for openings . 4 Prot-- Openings are to be protested with 3,/4 hr fire assemblies. 50% of the area of the wall maximum. Sec. 504.(b) & Sec.1903,(b) & Table 5~A Maximum single window sire is 8.4 sq.ft with no dimension greater than 12 feet.. �-- Sec* 4306o(h) NOP �- openings are not permitted in this wall. Code review for: Project Id.: MADISON HOSPITAL Address: CAFETERIA & BUSINESS OFFICES OTHER BUILBING ELEMENTS Table 17-A NORTH EAST OCC BRG NON-BRG OPNG BRG NON-o-BRG OPNG WALL WALL PROT WALL WALL PROT I1. 1 1hr 1hr Prot S.W.* S.W.* S.W. A3 1hr 1hr Prot S.W.* S.W.* S.W. B2 1hr 1hr Prot S.W.* S.W.* S.W. SOUTH BRG NON-BRG OPNG WALL S.W.* Sow* * S -8 W'M * WALL S.W.* S.W.* S'W Ww * sows S 0 W S0� 11,10n -i BRG NON—BRG OPNG WALL WALL PROT s4kwo* S 0 W 0* S.W.* s,owd.* S -OW -0 sown* s9wo Sows,* -OW-0 The exterior walls are required to be of NONCOMBUSTIBLE material. Sec.1901, None ---- No fire protection requirements for openings . 4 Prot-- Openings are to be protested with 3,/4 hr fire assemblies. 50% of the area of the wall maximum. Sec. 504.(b) & Sec.1903,(b) & Table 5~A Maximum single window sire is 8.4 sq.ft with no dimension greater than 12 feet.. �-- Sec* 4306o(h) NOP �- openings are not permitted in this wall. Code review for: Project Id.: MADISON HOSPITAL Address: CAFETERIA & BUSINESS OFFICES OTHER BUILBING ELEMENTS Table 17-A ELEMENT Interior Bearing wall Interior rion.brg wall Structural Frame MATERIAL Noncombustible Noncombustible Noncombusti'ble Exte-rior Struct Frame NoncombustIble Fl+c�or /Ce 'x I inq Roof /Ce i 1 ing 1 9 ItnIF1 Assembly Noncombustible Assembly Noncombustible nOnGOail i -I RATING 0 hr 0 hr 0 hr 0 hr 0 hr. 0 hr ff royl M_ See f oatnote #1 FOOTNOTES 1) Elements in an exterior walk. located, where openings are not permitted were protection of openings is required, shall be protected against external fire exposure as required for exterior bearing malls or the structural frame, whichever is greater,. -- Table 17-A, footnote 1 OCCUPANCY SEPARATIONS -- Table 5-B Il. 1-A3 I1. 1 -B2 A3 -B2 2hr 2hr Ohr ADDITIONAL SEPARATIONS FOR Ilal OCCUPANCY medical gas systems shall be installed and rnainta the Fire Cade. Nonflammable supply cylinders building shall be separated from the rest of ined in accordance with located imide the or the building by not less than 1 hour fire -resistive construction. Openings shall be protected by self -clasing smoke and draft-control. assernbllies hiving a f ire- protection rating of not less than 1 hour. --- Sec. 1002.(b) VENTING With an exterior wall There shall be not less than 2 inches in area. one vent shall one shall be within 6 inches of Without an exterior wail An automatic sprinkles system vents of not fess than 3 6 squares be within 6 inches of the floor and the ceiling. �.s required in the room. The room shall be vented to the exterior through ducting contained within a one-hour shaft enclosure. Approved mechanical ventilation shall provide 6 air chanaes mer hour for the room. A 1hr occupancy separation is required around rooms containing a bailer or antral heating snit. --*- Sic. 1D08. Code review for. Project Id.: MADISQN HOSPITAL Addresses CAFETERIA & BUSINESS t]FFICES 0.91�11_103. Employee Tacker room Gi f t/retail shops Handicraft shops Kitchens dabs using Hazardous material (not Laundries greater than 100 sq . ft . Paint shops using 'H' materiai(noi Separation none one none Wane H occ . j l hour 1 hour Hocc.) 1 hour Page # 5 Physical plant maintenance shop Soiled linen rovn Storage rooms, 100 sq. ft. or less Storage rooms mors than 100 sq . f t . Trash collection roams FOR A3 OCCUPANCY: 1 hour 1 hour none 1 hour I hour A 1hr occupancy separation is required around ronmq central heating unit greater than 400 ,000 BTU FOR B 2 OCCUPANCY: A 1hr occupancy separation central heating unit SECTION # 1 conta 16ninq a Inputi #A6w� boiler or is required around rooms containing a boiler or greater than 400,000 BTU input. �- Sec. 708. EXIT REQUIREMENTS: FL NAME OCCUPANT NUMBER EXIT PANIC RATED DOOR NOTES LOAD REQUIRED WIDTH HDWR CORRIDOR SWING ------------------------------------------------------------------------------- 1 BUSINESS OFFICES 1 KITCHEN/SERVING AREA 1 CAFETERIA SEATING 1 RST RMS & CORRIDORS TOTAL 22 1 0.4 NO NO N/R 11 * 5 1 0.1 No No N/R * 136 2 2.3 Yes Yes Out 4 * 2 1 0. 0 No No N/R 143 2 2.4 Yes Yes Out * NOTE: This area is being treated as an accessory for occupant Loads. _-" Sec. 3302.(a) exception dated corridors are to have 1hr firms Protection on both sides ceiling. ---� Sec. 3305.(g) Dior openings are required to be with 20 minute assemblies and window openings are required with labeled 3/4 hour assemblies. -- pec. 330,5.(h) Co -de review for: Project Id: . MADISON HOSPITAL Address: CAFETERIA & BUSINESS OFFICES In areas where 2 exits are require, the minimum separation maximum diagonal of the area or floorS -- Sec. 3303.(c) Exit signs are required from all areas serving an occupant -- Sec. 3314.(a) Door swing is based an Sec. 3304.(b) except as noted. occupant load is based on Table 33-A. Number of exits is based an Table 33-A except as noted. Exit width is in feet and based on Sec.. 3303.(b'), Exit width is to b -e divided approximately equally Width shown for all areas is based on other exits. WI'd-th shown for Ist floor is based on other exits. Width shaven for other floors & basements is based For the minimum width of doors,, see Se.c. 3304o(f) of wa i 1 s and protected . to be protected It 1/2 of the load of 50 or more , among exits. (0.2) (4.2) on stairway's. rear zne minimum wzatn or corriavrs . see Sec . 3 3 0 5 . (b) For the minimum width of stairways, seg Sem, 3306.(b) FOOTNOTES 4) Panic hardware See exception is bayed on Sec. 3317.(d). for main exit ire A -m-3 occupancies and churches. (0.3) Y 11 } Corridors within a tenant occupant load less than 1Q0 may not require a rated corridor. �4- Sec. 3305.(g) exc. #5 HANDICAPPED ACCESS: 1) Handicapped access is required to to this building. -- Sec. 3103.(a) 2) if a ramp is used for handicapped 1:12. -- Sec 3307.(c) Provide a landing within I inch (1/2 access) of the threshold,. --- Sec. The minimum width is same as --_ Sec,. 3304.(�� The maximum trammel distance -� Sec. 3303.(d) ROOFING REQUIREMENTS: 1) 2) at least one primary entrance & (b) 3 access, the max slope is inch at dooms used f or handicapped 3304 o ( i) door width and the minimum length is 44 inches. in this building is 2Q0 feet, The roofing an this building -_ 'fable 32-A is required to be Class B or better . See section 3204. and, ICBO research reports f or requirements. AREA SEPARATION WALL REQUIREMENTS. 1) The area separation wall is required to be a 2 hr firs assembly, -- Sec.. 505.(f)2,. 2) If the building has a projection with concealed space at the area separation wall, 1hr protection is required on the pro3ection and the exterior wall each side of the area separation wall equal to the depth of the projection . &-- See. 505(f)3. 3} If the area separation wall terminates at ars inside corner, see article in `Building Standards' Sep/Oct 1982 for requirements. Code review for: Project Id.: MAbISON HOSPITAL Address!. CAFETERIA & BUSINESS OFFICES t IQ. l7 AUTOMATIC SPRINKLER SYSTEMS: If -there are 100 or more sprinklers, the automatic sprinkler system shallbe superviby sed an approved central, proprietary,,or remote station service or a local alarm which willgimme ars audible signal at a constantly attended location. --- Sec. 3803. STANDPIPE REQUIREENTS: N� There is no requirement A hose is not required. for a standpipe, -&-- Table 38-A -- Table 38-A FOOTNOTES: 1) The location is to be. per Sec. 3805e(c),(d),and/or(e) WALL ASD CEILING FINISH. 1 ) wale. and Geiiing rinisn materials are required to comply with Sec. 4204.(a) and Table 42---.B,. 23 Carpeting on the ceiling is required to have a Class I flame spread ratingr. �-- Sec. 4204. (b) 3) Textile wall coverings shall have Class I flame spread rating. and shall be protected by automatic sprinklers acceptance criteria of U.B.C. Standard Na. 42--2 INSULATION NOTES: 1) All insulation material spread rating of 25 or -- Sec. 1714.(c) or meet the ~-- Sec. 4245. including facings are required to have a flame- less and a maximum smoke density of 45D, 2 ) Fo,am plastic ins�.lations are required to be protected. -- Sem. 1713, GLAZING REQUIREMENTS: All glazing in hazardous glazing material. -- Sec, locations is rewired to be of safety 5406 . (d) ADDITIONAL REQUIREMENTS: For B2 occupancy In all areas customarily artificial light occupied by humans, provide natural or and ventilation* --- Sec. 705. (a)&(b) For A3 occupancy Permanent platforms shall be constructed of materials as required for the building type of construction. -- Sec. 3902a If the area under the platform is used for any purpose (including storage) other than equipment wiring or plumbing, then the floor construction shall be not less than Z hour firs resistive . ---- Sec. 3902. Floor -1st Occupancy --KITCHEN f SERVING AREA Floor-wist Occupancy- CAFETERIA SEATING The capacitor of this area is required to be posted at 136 occupants. sec. 3302,(c) Code review for. Project Id.: MADISON HOSPITAL Address: CAFETERIA & BUSINESS OFFICES HANDICAPPED REQUIREMENTS: NOTE: Section numbers listed below are WATER FOUNTAINS: from ANSI A117.1 - 1986 1 ) one must have a spout within 36 inches of the floor. -- Sec. 4.15.2 2) Spout must be at the front of the unit. --- Seca 4.15.E 3) Controls must be at or near the front of the unit. -- Sec. 4. 5.4 & 4.2 .4 4 ) A cantilevered unit is required to provide a clear area under the unit of 27 inches. high, 30 inches wide. and 17 inches deep. --- Sec. 4.15.5 (1) 5) A dear area of 30 X 48 inches is required at the fountain. The clear area is required to provide dor a forward approach with a cantilevered unit and for a sides approach otherwise* -�- Sec. 4,,15.5 & Fig-927bfcrd TaILET FACIL�'�IES 1} A 5' diameter unobstructed turning space is --- Sec. 4.2.3 & Fig. 3 ( a ) Zj When water closet is not in a camt3artment. a) 48 inches wide by 56 inches deep with a -- Sec. 4.16.2 & Fig. 28 b) 48 inches wide by 66 inches deep with a -- Sec. 4.16.2 & Fig. 28 required in the toilet room. the dear area required is: side approach. front approach. 3) 7l 5) 37 7) 9) 10) 60 inches wide by 56 .inches deep with both approaches. mm pec. 4. 16 , 2 & Fict 28 J d) Side baris r�quired to start within 12 extend to 54 inches from the back The rear bar is required to he 36 When water closet is in a compartment inches of the back wall and -- Sec. 4,.16,.4 Door is. & Fig. 29 �nches long, -- Flug-o 29 the area rewired is a) 56 inches deep by 60 inches wide with a grab bar at the back and one at the side. Door is. at front or side, -- Flog. 30(a) or b) 66 inches deep by 36 or 48 inches wide with grab bars on both sides and door at front . --� Figs 30(b) d.} If a floor mounded water closet is used, sham above mint be increased 3 inches. e} Side bars are required to Mart within 1 extend to 54 inches from the bask wall. The rear bar is required to start within and be 36 inches long. --- Fig. 30(a) The bar's are to be 3 3 to 3 +5 inches above the Fig. 3,0(c),(d) the depth dimension -- Fig. 30(a) & (b) 2 inches of the back wall and -- Fig. 7..56a & 7.56b 6 inches of the side wall f loor.. The top of the swat on the water closet is required above the floo.r. �-� Fig. 29(b) & dig. 30(d) Urinals are required to be stall type or have within 17 inches of the floor. --- Sec. 4.18.2 m Fig. 29(a),(b) & be 17 to 19 inches an elongated rim and be & Flog. 29(c) A clear area of 30 X 48 inches is required in brant of the urinal, -- Sec. 4.18.3 Accessible lavator 16es shall provide a clear area under 2 9 inches Sec . 4. 19. 2.1 & FiF g .9 3 1 A clear area of 3.0 X 48 inches a5 required in �aw Sec. 4.19.3 & Figs 32 The bottom of mirror is required to be within __ Sec. 4.19.6 & Figs 31 Code review for: Project Id.: MADISON HOSPITAL Address: CAFETERIA & BUSINESS OFFICES SECTION # 2 EXIT REQUIREMENTS: FL NAME front of 40 inches the lavatory of lavatory. OCCUPANT NUMBER EXIT PANIC RATED DOOR LOAD REQUIRED WIDTH HDWR CORRIDOR SWING f loor . NOTES 1 POOL EQUI P RM# 113 * 2 1 0.0 No No N/R 15 10 1 HYDROTHERPY ROOM * 21 2 0.3 No Yes N/R 15 10 1 STORE ROOM # 111 * 0 1 0.0 No No N/R 1 MEETING RM # 112 * 53 2 0.9 Yes Yes Out 4 1 RST RMS. & HALLS * 8 2 0.1 No No N/R 15 10 TOTAL 84 2 1.4 Yes Yes Out * NOTE: This area is being treated as an accessory for occupant loads. -- Sec. 3302.(a) exception Rated corridors are to have 1hr fire protection on both sides ceiling. ---- Sec. 3305. (g) Dior openings are required to be with 20 minutes assemblies and window openings are requir°ed With labeled 3/4 hour assemblies. d-� Sec. 3305. (h) of walls and protected to, be protectel In areas where 2 ex "its are required, the minimum separation maximum diagonal of the area or floor. -- See. 330!3.(c) Emit signs are required from all areas serving an occupant .._ SSG. 3314. (x) Door swing is based on Sec.. 3304. (b) except as noted. Occupant load is based ars Table 33 -m -A. Number of exits is based on Table 33"--A except as noted. is 1/2 of the load of 50 or more. Exit width -.is in feet and based on Sec,. 3303,.(b),. Exit width is to be divided approximately equally among exit. Width shown for all areas is based on other exits. (0.2) Width shown for lit floor is based on other exits . (0,.2) Width shown for other floors & basements is basted on stairways. For the do minimum width of doors, see Sec. 3304o(f) For the minimum width of corridors, see Sic. 3305.(b) For the minimum width of stairways, see Sec. 3306.(b) FOOTNOTES: (0.3) 4} Panic hardware is based on Sec. 3317 o (d) w dee exception for maim exit in A-3 occupancies and churches . 10) x,11 required exterior doors are required swing out. -- Sec. 3320.(a) 15 ) Nurses stations are not required to be separated from the corridor. Waiting areas may not need to be separated. See restrictions. Closers are not required on sleeping rooms. Glaring along corridor may be fully -tempered or laminated glass. See limitations. -- Sec. 3320.(c) HANDICAPPED ACCESSs 1 } Handicapped access is to this building, -�� 2} If a rami is used for 1:12. --- pec 3307. (c) 41 required t4 sec. 3103. (a) handicapped Code review for: Project Id.: MADISON HOSPITAL Address: CAFETERIA & BUSINESS OFFICES Provide a landing within 1 access) of the threshold. 4 at least & (b)3. access . inch (1 /2 inch at '1',C3e miLnimum wi-azn is same as --�- Sem. 3304,(j) -- Sec. 3304,(i) door width and one primary entrance the max slope is doers used the minimum The maximum travel distance in this building is __ Sem. 33(13. (d) ROOFING REQUIREMENTS: for handicapped. length is 44 inches . 200 feet. AREA SEPARATION WALL REQUIREMENTS: 1) The area separation wall is required to be a 2 hr fire assembly. -- Sec. 505. (f)2. ZIf the building has a projection with concealed space at the separation wall,, 1hr protection is required an the projection the exterior wall each side of the area separation wail equal the depth of the projection. 4who �- Sec. 505(f)3. :, 3) If the area separation wall terminates at an inside corner, see ICBO article in 'Building Standards' Sep/Oct 1982 for requirements. AUTOMATIC SPRINKLER SYSTEMS: If there are 20 or more sprinklers, the automatic sprinkler system Sl1d11 be supervised by an approved central proprietary, or remote station service or a local alarm whish will give an audible signal at a constantly attended location. -- sece 3803* STANDPIPE REQUIREMENTS: There is no requirement A hose is not required. for a standpipe. -- Table 38-A -- Table 38-A FOOTNOTES: 1) The location is to be per Sec. 3805.(c),(d),and/or(e) WALL AND CETLING FINISH: 1} fall and ceiling finish materials are required Sec,. 4204 . (a) and Table 42 -.*B -b 2) Carpeting an the ceiling is required to have a spread rating. --- pec. 4204.(b) 3) Textile walk coverings shall have Class I flame and shall be protected by automatic sprinklers acceptance criteria of U.B.C. Standard No., 42-m2 INSULATEON NOTES: 1) All insulation material including spread rating of 25 or less and a -- Sec. 1714. (c) to comply with Class I f lame spread rating. or meet the -"-- Sec. 42a5. facings are required maximum smoke density 2) Foam plastic insulations are required to he GLAZING REQUIREMENTS : All glazing in hazardous glazing material. -- Sec. Code review for,, locat 5406 Project Itl.: MADISON HOSPITAL ions is . (d) Address: CAFETERIA & BUSINESS OFFICES ADDITIONAL REQUIREMENTS: For I1.1 occupancy In all areas Customarily artificial light Provide an approved fire Provide a smoke detector 101x. required to have a f lame- of 4504, protected. -- sec. to be of safety occupied by humans, provide natural and ventilation. -ff- Sec. 10(15. alarm system 0 -�- Sec. 1009, in all roams used for sleeping. -- or 1713. For A3 occupancy Permanent platforms shall be constructed of materials as require. f or the building type of construction, --* Sec. 39v2, If the area under the platform is used for any purpose (including storages other than equipment wiring or plumbing, then the floor construction shall be not less than l hour fire resistive. -- Sic. 39U2, Floor -1st Occupancy -MEETING RM' # 112 The capacity of this area is required to be posted at 53 -� Sec. 3302.(C) For B2 occupancy in all ares customarily artificial light occupants . occupied by humans, provide natural or and ventilationSec, 705. (a) & (b) HANDICAPPED REQUIREMENTS: NOTE: Section numbers listed below are from ANSI A117,.1 - 1986 WATER FOUNTAINS: 1) 2) 3) 4) 5) One must have a spout within 36 inches of the floor,. --� Sec. 4.15.2 Spout must be at the f rant of the unit . --- Sec.. 4.15,.3 Controls must be at or near the front of the unit. -"- Sec. 4,15.4 & x.25.4 A cantilevered unit is required to provide a clear area under the unit of 27 inches high'. 30 inches amides and 17 inches deep, --- Sec. x,15.5 (1) A clear area of 30 X 48 inches is required at the fountain. The clear area is requiredto provide for a forward approach with a cantileveredunit and for a side approach otherwise. -- Sec. 4.15.5 & dig. 27 b,,c,d Tf)IL�T FACILITIES 1 ) z) A 51 diameter unobstructed _� Sec. 4.Z.3 & Fig. 3(a) a � turning space is rec�uired in the toilet roam. When water closet is not in a compartment, aj 48 inches wide by 56 inches deep with -- Sem, 4.16.2 & Fig. 28 the clear area required is: a side approach. 0) 48 inches wide by 66 inches deep with a front approach. -- Sec. 4.16.2 & Fig. 28 c) 60 inches wide by 56: inches deep with both approaches. -- Sec. 4.16.2 & Fig. 28- Side bar is required to stark within 12 inches of the beck wrap and extend to 54 inches from the back wail. -- Sec. 4,16.4 & Fig. 29 Code review for: Project Id,,: MADISON HOSPITAL Address: CAFETERIA & BUSINESS OFFICES The rear Saar is requ�red to be 36inches long. -�- Fig. 29 3) When water closet is in a compartment, the area required is; a} 56 inches deep by 60 inches wide with a grab bar at the back at the side. Dor�V--, N r, r, 11 1% A r is �front or side . -�-at Fig. 30(a) or and one u, ►� --11k-==�Z> =fc:y uY .au or qo jLncnes viae witn grab bars on doth sides anct cxoor at front.. -- Fig . 30 (h). d) If a floor mounted water closet is used, the depth dimension shIJLown above must be increased 3 inches. --- Fig. 30(a) & (b) zv start within 12 inches of the back walk and extend to 54 inches from the back wall,-- Fig. 7.56a & 7.56b The rear bar is required to start within C inches of the side wall If ana sae j6 inches long, -- Fig. 30(a) 4) The bars are to be 33 t0 3d inches above the floor. -- Piga ����.),(�� & Fig. 5} The tap of the seat on the water closest is raquireo be 17 to 19 above the flooywd -- Fig. 29(b) & Fig. 30(d) 6) Urinals are required to be stall hype or, have an elongated rim and within 17 inches of the floor. *-- Sec. 4.18.2 & Fig. 29(c') 7 ) A clear area of 30 X 4.8 inches is required in front of the urinal inches -- Sec. 4.18.3 S ) Accessible lavator 1*es shall provide a clear area under the lavatory Of 29 inches. ww-- Sec,. 4.,19,,2,.l & Figs. 31 9} A clear area of 34 X 48 inches is required in front of the lavatory. -� se -C-0 4*19*3 & Fig. 32 10 j The bottom of mirror is required to be within 40 inches of the f loor . 4�� pec. 4.39.6 & Fig. 31