HomeMy WebLinkAboutPLAN REVIEW - 96-00020 - Madison County Jail - New BuildingREXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3-010 1994 Uniform Fire Code Flan Review Buil-ding Name: Madison Count Plan date: June 1.996 Rev.6 iew Date: May 151, 1996 Criminal just'ice Fac.i 1 it Building Classification: Address; 149 East Mein Stories: New Construction 2 Type of Construction: Occupancy Classification: I--3 New Construction Floor Area: 34,38'7 Type II F.R. existing Floor Area: NJA Required Fire Flow (Appendix III -A): 2e000 -9-S SMO. Comments: Reduction _up to be less- than 1,500 cr.p.m. 75% for-aprinkler sYstem,_ but shall not 2) Water Supply (Article 9, Section 903) Required: Yes Faire Hydrant Location: S-8 2nd East and 1st earth, D--2 2nd. East and Main Fire Hydrant Flow -s: B-8 43 si out of 2 residual for 1185 of 58 psi. Total Fire Flow Test Location's Fire Flow Supplied By: Ct 4 0"% IT q 4M a-% -a '00) IL q, Static far 1D85 ressure of U f I ow for test was 2270 W , m. s and a end East and 1st North, 2nd East and fain Fire Department Other Approved dater Source: tV A Water Supply Acceptable: Yes Fire Hydrant Location Acceptably: Yes Water Supply Camrnents : Install' n Werth side of the buildin . a new hydrant in the al I 3..)Fire Apparatus access Roads (Article 9 Section 9Q2) on the P I an Remi. ew Page 2 Required3 Yes Acceptable: Width: 'burning Radius: Vehicle Vertical Yes Length. Yes Grade: Clearance: Yes Complete Road Acceptable: Yes Yes Yep Surf ace: Yes Turn Around: r1 -.L Comments: Alley on the north side and Main street on the south side, Parking Sot to the west. � would like to see a plot plan showing the Arkin spaces to maks sure the width of access does not drop under 24 feet. 4).Access Roads and dater Supply, Including Fire Hydrants Are Required To Be Installed And Mace Serviceable Prior To And During Time Of Construction Yes (Article 9 Section 9Q1.3); Comments*. As close as possible. 5),Installation of Portable Fire Extinguisher 1002) Required: Yes, Location Acceptable. Yes (Article 10 Section om Type Provided Acceptable: Yes Comments: 4--A Being 60 -BC shown Wet pipP 6).Automatic Fire Extinguishing Monitoring Required Systems: (article (Article 10 Section 10U3 'I Required: Yes Type Of System Being Installed: over l00 heads Wet pipP Sprinkler System Monitoring Required (Article 10 Section 1443.3} Required: Provided,: Yes Comments : I f over l00 heads 7).Stand-pipes (Article 10 Section 1004) Required: No 8} .Ventilating Hood And, Duct Fire Extinguishing System (Article la Section 100G.2) Required: Yes Type Being Provided,: Ansul R-102 Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Yes Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): No Comments: A 40-B sodium bicarbonate orotassium bi carbonate dry M Flan Review Page 3 rm czx rn -' e -v n 1 nj e_ extinguisher needs to be located within 30 feet. 9 } . Fire Alarm Systems (Article 14 Section 1007) Required: Yes Type Of System Required; Manual: Automatic: Holders: Type Of System Being Provided: Manual: Automatic!: Components Of System Shown: Smoke Detectors: Heat Detectors: Visual Devices: Flow Alarm: Yes 14 Manual Pubs Station 4 Door Holders: 1 0 �3 Both: Yes Both: Yes Sounding Devices: 34 Duct Detectors*, 2 Sprinkler Vale Monitoring: Yes Fare Alarm System Acceptable: Yes 10) Other Corrections That Are Required By Special Conditions: Automatic dire extinguishin by--the—State Fire Marshal. Plans As Submitted Are Acceptable: Yes Pans Checked By: Dee Owens Please furnish comments back manner: Occupancy Or system subject to a' Date: Jane 11, 1996 to the plan, revi ewer in the raval f 0 11 Owing