ffL%'EXBURG MADISON COUNTY FIRE DEPAR9rMENT
P a 0 . Box
280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1994 Unl*form Fire Cade
P1 an Review
Building Name, GAL Ranch Stare
Building Address.:404 Narth 2nd Easy
Stories: 1
Occupancy Classif'cation: M
New Construction Floor Area: -5.,760
Plan Date: 03-11-96
Review Date: 03-25-96
Type of cons t ruction: ii -N
Existing Floor Area : lg 400
total of 24
�1*1
1).Required Fire Flo
w (A�apen�.i x I I I -A) 3 250 p, m
Comments@_ -Up to 75% reduction for -automat ic sprinkler-- system
not less than- 1.,500 a p m
e 0
2)mWater Supply (Article 9, Section 903) Required:
Fire Hydrant Locations. 8-31 2nc�
Fi�� Hydrant Flows, 0
Fire. Flow Test Locatioll.
Fire Flow Supplied By:
Other Approved Water Source:
Water SuPPly Acceptable.** Yes --..X No
Fire Hydrant Location Ac.. eptabl e : yes X No
Wader SuPPlY Comments;
8-37 3r
Yes K Na
3. }Fire Apparatus Acce sRoads �tic�.e !I Section 902}
Required: Yes- X No
but
E.& 4th Na
Acceptable,* Width* 30-- feet Length: Pull throuQh Surface : As haI t
Turning Radiu�s : �3�31�� Grade ; t- kay �ehicl e Vertical Clearance.* 0�a
Turn Around: NZA___.
IA
Flan Review
Page 2
Complete Road Acceptable: Yes Comments;
4 } .Access Roars and Water Supply, including Fire Hydrants Are
Required To Be Installed And Mads Serviceable Prior To And wring
Time Of Construction
Comments 0
(Article 9 Section 901.3) Yes X No
5 ) . Instal lation Of Portable Fire Extinguisher (Arti:cle 10 Sec 3 -on
1002) Requireds, Yes X No---- Location Acceptable: YesNo
Type Provided acceptable: Yes No-- comments: Size and
IA r, o rn Q n * r% ^ 4- m" 1,.,L ., v. -w . 0-1- U.M
dans,
6).Automatic Fire Extingu ishingI
SYStems;(Article 10 Sect'vn 1003
Required: YesX Na Type Of System Being Installed; Sec,.
1003. 2. 7 over
12,000 scuare fppt
Not shown on the
lens,
Sprinkler System Monitoring Required. (Artisc1� 1� Section 1 43.3)
Required; Yes.,, -,,X No Comments: If over 100 heads
7)wStandpipes (Article 10 Section 1Q04) Required: Yes No X
Type Required:
Comments:
Not requi red i f_bu`1dJL,n
has a s rinkler system
8} -Ventilating Hood And Duct Fire Xtinguishing System (Article 10
SectiOn 100 red
Type Being Provided:
Yes N 0 X
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4)
Yes N oX
Portable Fire Extinguisher shown (Article 10 section 1p06.2.?}
Yes..--. No X
Comments : No ,cook
�,ng
Plan Review
Page 3
g } *Fire Alarm Systems (Artic3. e 10 Section 1007 )
Required: Yes�„ div X
fiype Of System Required t Manual Automatic,Both
Pr
Type Of SSystemBeing Provided: Manual A ic Bath
Components Of System Shawn: Smoke Detectors Heat
Manual PuII Station Sounding
Devices.......--. -M. Visual
Detectors
Devi ces
4EMPOPED0106�
Door Holders � Duct Detectors Flow Alarm Sprinkler Valve
Monitoring Fire Alarm �ys�emwmmftfto� Acceptable:
Yes No,
10 ) - Other Correct'
ions That Are Required By Special Occupancy
Conditions: Additivnal exitsneedto be added. Exit throu
storeroom is not allowed.
Plans As Submitted Are Acceptable: Yes Ido X
the
Plans Checked By: Dee OwensDat�:0 96
Please furnish comments back to th lan reviewer in the tallowing
manner: Written comments. New
additional in,formation.
Plans.; Showinq