Loading...
HomeMy WebLinkAboutSPECIAL INSPECTION REVIEW - 21-00208 - Goldenwest Credit Union - Branch OfficeARW Response: At the column locations, provide reinforcement as shown in the structural drawings with the vertical dowels epoxied a minimum of 8" into the footing. At every hold-down location, provide an anchor that extends to the top of footing. At designated hold-downs (as shown on the attached plan view), it is acceptable to provide a cage consisting of a minimum of (4) #4 bars that are epoxied 8" into the existing footing with tie spacing as shown in the structural drawings. Any epoxy listed in the general structural notes under the Adhesive/Mechanical Anchor section is acceptable. H SS5X5 X 1/4 H SS 5X 5X1/2 H SS 5 X5 X 1/2 H SS5X5 X 1/4 H SS 5 X5 X 1/4 H SS 5 X5 X 1/4 H SS5X5 X 1/4 H SS 5 X5 X 1/4 4' - 0 " 4' - 0 " 4' - 0 " 3' - 0"3' - 0" 3' - 0" F4 97' -0"H DU 4 (2 ) 2 x H DU 8 (3 ) 2 x H DU 8 (3 ) 2 x H DU 8 (3 ) 2 x H DU 2 (2 ) 2 x H DU 2 (2 ) 2 x H DU 2 (2 ) 2 x H DU 4 (2 ) 2 x H DU 4 (2 ) 2x H DU 4 (2 ) 2 x H DU 8 (3 ) 2 x SW-2 6' - 3" SW-1 24' - 6" SW-1 12' - 11" SW-2 9' - 10"SW-2 6' - 7" SW-2 6' - 0" SW-2 5' - 7" F4 98' -0" FC2 98' -0" FC2 97' -0" FC4 98' -0" FC2 98' -0" FC2 98' -0" FC2 98' -0" FC2 98' -0" FC2 98' -0" FC4 98' -0" FC2 98' -0" F4 98' -0" F4 98' -0" FC2 98' -0" FC2 98' -0" FC4 98' -0" F4 98' -0" F4 98' -0" FC2 98' -0" FC2 98' -0" F4 98' -0" FC3 98' -0" FC2 98' -0" FC2 98' -0" FC2 98' -0" FC2 98' -0" F4 97' -0" PROVIDE PLENIUM BOXES BELOW GRADE. SEE MECH. FOR DIMENSIONS, LOCATION, AND PENETRATION INFO. AT CONTRACTORS OPTION, THE BOXES MAY BE PRE-CAST CONCRETE OR CAST-IN-PLACE CONCRETE BOXES. FOR CAST-IN- PLACE CONCRETE BOXES USE 5" THICK CONCRETE WALLS REINFORCED W/ #4 BARS AT 12"o.c. EACH WAY FOR THE SLAB, WALLS, AND LID. ADD (1) ADD. #4 BAR TO EXTEND PAST OPENING 24" ON EACH SIDE OF ALL OPENINGS, AND (1) #3 BAR x 24" AT A 45 DEGREE ANGLE AT EACH CORNER AROUND EACH OPENING 7 S2.2TYP. 8 S2.2 7 S2.2TYP. TYP. AT HOLDOWN 3 7 S2.2 3 S2.2 S2.2 4 S2.2 4 TYP. S2.2 4 TYP. S2.2 1 6 S2.2 8 S2.1 7 S2.2 8 S2.2 TYP. 5 S2.2 8 S2.2 TYP.S2.2 4 H DU 4 H DU 4 FRAMING PLAN 6 S2.1 TYP. AT STEPS TYP. AT HOLDOWNS 5 S2.3 TYP. AT SHEARWALLS hold-downs marked in blue need an epoxied cage as described in the RFI Response.