August I , 1997
Nor. John Watson
JRW & Associates
49 Professional Plaza
Rexburg, Idaho 83:440
-STATE OF IDAHO
RE: HEALTH & WELFARE BUELDING @ 333 WALKER DRIVE
Dear John,
Our comments an the preliminary plans available for review are as follows,
P.O. gax 280
12 NQRTH CENTER STREET
REXBURG, IDAHO 83440
PHONE �208) 359-3020
FAX {2q8} 359-3022
A Flood Elevation Certificate is required for the property as it is in the Teton River Flood
Plain. The Base Flood Elevation for the site 'is 4567.5 (based an National Geodetic Vertical
Datum of
1929).
This is a
critical Pi eGe of information.
floor level
is above
the BFE
as soon as possible.
We need to know that the building
2. — It maybe desirable to move the two handicapped harking stalls one or two stall widths to
the east so that the shaped section of sidewalk is off to one side of the main doors, thereby leaving
a larges level area in front of the doors for the person in a wheel chair trying to open the front
door.
3. —�- � had thought that the building was going to be moved a little farther south so that the
future south right of way dine of the 13arney Dairy Road mould be 42 ft. south of the north sides of
Lots 2 & 3 . It looked like we needed to get 12 ft. from the Phaco gallery and 48 ft. from the
Youth Services (old Amdahl Building) property to make a best fit th-rough the area. Is getting 10
to 12 more feel of right of way on the north side of this building going to be a problem for you?
4. — It would be desirable 'if the doors to Conference Room I I I were located an opposite ends
of the zoom rather than being bath together an the same end.
5 .—'ULre need to talk about the needed water and sanitary sewer extensions in 'talker Dr. as well
as the extension of Walker Dr. itself.
Send me over an updated version of the plans when you get thein more complete.
JVJGpll h. Ld11 U� Y.r,
CITY ENGINEER & BUI]LDING OFFICIAL
PHILIP E_ BATT
ou em r
DATE:
TO:
FROM:
State of /rialto
DIVISION OF BUILDING SAFETY
KALDING BUREAU
October 17., 19 9 7
SRW & Associates
John Dinucci
Building Plans Examiner
New office Building, Rexburg,
TRANSMITTAL
(2D8) 334-3896
ID PA #RQ -176
Thelanpre�riew for this project has
are returning to you our findings
have any questions regarding the
please feel free to cvntact john
321 (Bu ilding) , Alien Hubble at
277 N. 6th, Suite 10
I.O. Box 83720
Boise, ID 83720-0060
FAX (208) 334-2683
been carnpleted and we
dated e
findings or other
0
I f you
issues
llinucci at X34-3895
334-2183
kaiecUrlcatj, ana tsob xawlings 334-344.2
Ext.
Ext .
C : Duane Johns. Department of Health and Welfare
Blair Manwaring, Rexburg Building Department
Sc"N'1179 In Th c Inlertv Of- A i h flc
343
333
Ext.
(Plumbing).
rC,UILDING BUREAU PLAN REVI'EW FINDING,",d!
F1
DIVISION OF BUILDING SAFETY
277 NORTH 6TH STREET
P4OeBOX 83720
BOISE, IDAHO 83720-0060
PH 12O8/334,w-3896 FAX 2683
To 4.p4
iRW & Assocates
PA NO:
DPW I
RQ -176
DATE: 10-15-97
PAGE 1 OF 3
From.a John Dinucci, Plans Examiner, Building Bureau
Project and Location: H & W -- New Office Building in Rexb�zr�
Project Owner: JRW & Associates
Findings: 1997 UBC, Vol. I, 1997 UMC & other adopted codes as noted
1. Overflow drains having the same size as the roof drains shall
be installed with the inlet flow line located 211 above the low
point of the. roof or overflow scuppers raving three times the
size of the roof drains may be installed in adjacent parapet
walls with the inlet flaw line .located 21' above the law point
of the adjacent roof and having a minimum opening height of
4110
Overflow drains shall be connected to drain lines independent
from the roof drain lines per Sec. 1506.3 UBCe
2. Provide structural calculations wet -stamped and signed by an
Idaho licensed architect or engineer. Potential unbalanced
accumulation of snow at valleys shall be considered per Sec.
1605v4 i
3.4 Total area of all openings other than doors in any ovrtion of interior corridor shall not exceed 25a of the area of the
corridor wail of the roam which it is separating from the
corridor per Sec. 1005.8.2 UBC, It appears this percentage is
exceeded on plans.
4. Glazing within 24" arc of either edge of doors in the closed
position shall be safety glazing (tempered) complying with
Sec. 2406 vBc,
5,w Fmanufacturers specifications for skylights - must be
tested for 4Q# sq, ft, live load for snow. Sloped glazing
shall comply with pec. 2409 UBC.
6. Provide 1 -hour fire resistive exit corridor details that
comply with Sec. 1}04.3.4 UBC, (See UBC Handbook, Figure 1005--
6. for complying designs, 1994 Edition
. �
Page 2 of 3
7. Suspended T -w -Bar ceiling installation shall comply with UBC
Standard 25-2, 199? Edition. Provide complying details and/or
notes per Sec. 2502 USC.
Be Corridors shall not be used to convey air to or from rooms
when the corridor is required to be of fire resistive
construction by Sec. 10x4.3.4 UBC per Sec. 601.1.1 UMCO
9. Ducts which penetrate firms resistive corridor walls that have
openings into the corridor shall be equipped with combination
smoke/fire dampers per Sec. 713-.10 & 713.11 UBC.
100 Supply a&M "o mecha111cai room per Ch. 7 b'wMCf 1997
Edition and manufacturer's spec i f icat ions . Denote on plans (If
fuel burning appliances are installed).
11. Provide mechanical equipment schedules for mechanical room
and/or use of room. Other cede provisions may apply depending
on use of roam.
1Z. The minimum riser dor stairs is 4", the maximum riser height
is 7", the minimum tread run. is 1111 per Sec. 1Q43.3,3.3 UBC.
Denote on plans.
13. Panic hardware shall be installed at all exterior exit doors
per See. 1003.3-.1.9 UBC., except for the main entrance which
may be key locking hardware so long as the requirements of
Sec. 1003.3.1.8 UBC, Exception #1 are complied with.
14. All doors shall have hardware of a type that is easy to grasp
with one hand and does not require dight grasping, dight
pinching, or twisting of the wrist to operate per CABC3/ANSI
A117. 1, Sec, 4. 1, 9 (1992 Edition) .
15. Provide restroom accessibility and drinking fountain details
4na�. comp' win CABO/ANSI A117.1 (1992 Edll..ion) (With
dimensions) .
16. Provide, international .symbol of accessibility signage at
restrooms and accessible parking stabs per Sec. 1103.2.4.1,
and directional signage at inaccessible building entrances
indicating the saute to the nearest accessible dement per
Sec. 1103.2.,4,.2 UBC.
17. Provide underfloor ventilation per Sec. 23D5.7 UBC. (1 sq, ft,,
150 sq. ft, of area).
18 . Provide documentation/ information about "Hypalan"' rowing and
manufacturer's listing and installation requi&
instructions
.
Page 3 of 3
19.. Install illuminated exit signage at main ��its per Sec.
1003.2.8.2 UBC and at intersection of corridors and waiting
areas to clearly indicate the direction of ("'»rrQnt
supply to one of the
the premises wiring
provided by battery
accordance with the
lamps for exit
systemf power
or an an --site
Electrical Cod
signs shall be provided by
to the other lamp shah be
generator set installed in
e.
20... Wheelchair ramps shall comply with CABS/ANSI A117.1 Seg. 4.8,
(1992 Edition) .
2i. Provide a minimum underf? goer a�^ess oppna nrT of 18+' x 2 4 " pell-
Sec.
2306.3 USC,
22. Provide draft stops at roof /ceiling concealed area above T -Bar
ceiling per Sec, 708.3.1.2.2 UBC. Draft stops shall not exceed
60F horizontal spacing, nor 3000 sq. Vit, of area between draft
stops. Draft stop construction shall comply with 708,,3,1.3
UBC,s
23. Make provisions for minimum ventilation of rafter spaces
enclosed by 6 mil visqueen per Sec, 1505.3 UBC.
24. Access to rooftop equipment shall be provided per Sec. 3p7
UMC.
All of the above
bmf ore approval
items Must be adequately addressed
for this project can be granted.
If you have any questions
please call me at (208)
by resubmittal
-9
concerning the above listed requirements,
334-389G Ext. 321. Thank you.
G: Duane Johns, Department of Health and Welfare
Blair Manwaring, Rexburg Building Department
EF -0 1
11/18/96R
P.A.:
D.P.W.:
AP PL I CANT/ARC H I TE UO' T.:
PROJECT -./J/
STATE OF IDAHO
DIVISION OF BUILDING SAFETY"
ELECTRICAL BUREAU
277 NORTH 6TH, SUITE 107
P.O. BOX 83720
BOISE, ID 83720-0028
(208) 334-2183
LANSIELECTRICAL) EXAMIN
IPM
ON F
COPIES TO:
SCHOOL DIST., #:
IN
i.
0
NOTE: ll work will be subject to compliancewith the current National Electrical Codi
Idaho Code, title 54 chapter 10, and the codes enumer2ted-in Idaho Codi this 39
chapter 41 (Contact 10C21fire jurisdiction for Uniform FireCode Review/Approval).
review of the subject project finds the plans and specifications in essential accord
with the above referenced codes except as follows:
THE FOLLOWING ACTION IS DETERMINED AND BASED, UPON REVIEW OF SUBMITTED PLANS:
PLANS ON HOLD - Additional information is required.
PLANS REJECTED - New plans or permits. with proper corrections as noted to be resubmitted.
PLANS APPROVED - Subject to compliance with correction as noted.
PLANS APPROVED - No correction noted.
wip
CHECKED BY
AMI
DIN
LEA
FINDINGS
0
ATTACHED
DATE /
b "/S l
PF -38 STATE OF IDAHO
6/24/94R DEPARTMENT OF LAB -OR AND INDUSTRIAL SERVICES
PLUMBING DIVISION
277 NORTH 6TH, SUITE 100
P.O. BOX 83720
BOISE, ID 83720-0068
(208) 3343442
PLANS (PLUMBING) EXAMINATION FINDS
D.P.W.:
APPLICANT]ARCHITECT,
J
t�i � A �
. pmffifi�
COPIES TO:
SCHOOL DIST. #-Mo
dr
PROJECT: iJ e W CL kA
NATE; �i work will be subject to compliance with the current Uniform Plumbing Cede,
Idaho Cade title 54 chapter 10, and the codes enumerated in Idaho Code, tiffs 39 chapter
41 (Contact local fire jurisdiction for Uniform Fire Code Review/Approval). A review of the
subject project finds the plans and specifications in essential accord with the above
referenced codes except as follows.
THE. FOLLOWING ACTION IS DETERMINED AND BASED UPON REVIEW OF SUBMITTED PLANS:
X
PLANS ON HOLD - Additional information is required.
PLANS REJECTED - New plans or permits with proper corrections as Hated to be resubmitted.
PLANS APPROVED - Subject to compliance with correction as noted.
PLANS APPROVED - No correction noted.
Fi�c� 15 ar�'1 e�7-�lc�
FINDINGS
ADDITIONAL FINDINGS, PLEASE SEE ATTACHED
CHECKED BY 1�,� DATE
110-:20- f - b1JVM
11
Ej
77JMY EDWARDS
Deputy Firs Narsha!
FkUM UEPL! VY F- IRS MARSHAL 208 525 7066
DEPARTMENTState Of 061ho
OF INSURANCE
State Fire Harshal - Ristritrt 3Ii
PO Box 2699
14Mo Fat1s.Id 93403
1994 UMfonn Firs Code.
Pian Review
JAS
Director
DON MCCBY
Project Number; P.A. #RQ. 176
Pian Date' JaIy 97
review Date: Oct. 20, 1997
Building Narne: JRW Health andWelfare"V
BuDding Addrema, 333 Walker Drive Rexburg, Id.
Stories: One Type of Construction: Type, V -N
Occupancy Classi5c�on: "B" Existing Floor Area: New Construction
New Construction Floor Area.- 8,640 squ2re feet
1. Required Fixe Flow (AppendiX Iii -A): 2,500 GPM for 2 hours
IF
Comments A
2. Water Supply Requited (Article 9, section 903): Yes
Fire Hydrant Location.B-47300 1131ock Waitcer Dr. ; J3-37, 400 N, 3"' E.
fire Hydrant Flows., 4,045 GPM at 20 psi.
sue lviow'vest Location: Hydrant B-47 and Hydrant 5-37
Fire Flow Supplied By ; Rexburg Fire n eet.
Other Approved Water Sou.rce, None noted
Water Supply Acceptable,- Yes
Fire Hydrant Location Acceptable: Yes
Equal Opportunity Employer
- 10-20-1997 d _ SMPM FROM DEPUTY F IRE MARSHAL 208 525 7066
3, Fire Apparatus Access Roads required (Article 9 Section 902)- Yes
Comments: Walker Drive is an exiting city street and is acceptable to the Rexburg
Fire Dept-
4,
Access Roads and Water Sunply, Including Fire Hy
drantS Are Required To Be Installed
and Made Serviceable Prior To and during The Time Of Constru on (Article 4 section
94].3), Yes
5. Installation Of Portable Fire, Extinguishers (Article 10 section 1002)Required- Yes
U -cation AcwpWie.- Location of extinguishers is not shown on plan,
Type Provided Acceptable: 'Yes ; Specs call for UL listedextin
6d B. -C rating, guishers with 4A,
Comments: S�ac�n� end l�cat�€�n �ffir� ea��,guishers shau be as regWred by
Is ��UniamFire Code Standard 10-4 ��w ext���uIr
ons on plan-
6.
Automatic Fire Extinguishing Systems-( Article 10 sextion 1003)RequiredIF-, No
7. Standpipes Required:: (Afticle 10 section 1004): No
S. Ventilating Hood and Duct Fire Extinguishing Systems Required: (Article 10;W,fi on
1006.2): No
Comments: Nfmm�c�. c�,o� ora�ons are noted in the laps.
9, Fire Alarna Systems Required: (Article 10 section 1007): No
TYPO Of Syst= gig provided: Manual and Automatic
Components of System, Shown: Combination SmOke and Heat Detectors 19
Manual Pull Stations4Sounditag Devices....j. L -'Visa D
e,vqces 9
rice Alarm SystemdAzMptable: Yes
Comments: Even though alarm system is not required ane is to be installed.
System must comply with Unifoctr� fire Code section 1007 and NFPA 72.
Manual pull boxes and combination smoke and heat detectors appear to meet the
location and spacigg requirements of N�'PA 72.
P. 3
I I_dCX_ I UI.-itj /
ri
bb
Audio[Vimal devlc&s appear to mit t ie location and spadng requirements of
NFPA 72. However I would like to suggest the dio/visual d�v� i� waituag area
122 be moved to the north neu the intersection withmw�t�r 14�.
Approval of the fire alarm system is preliminary only. Before final approval is
given the equipment installer must provide all infonmtjon required bv Uniform
Fire Code seedon 100 1.3 to this office for review and approval.
C Section 100 1 .3 Plans for Fire Alann Systems." Complete plans and specifications for
fire alp Mems shall W submitted for revvieVv and approval prior to sy-stem instajjation.
Plans and spificatfans shall include, but not be limhed to, a floor, plan; location of all
alarm -initiating and alarrawsignahg., devij-&!a6, arm contro d troubjewrSignaling
equipment, annunciation; power connection, battery Wculations- conductor type and size;
voltage drop calrWations, and manufacturer, model numbers and fisting information for aU
equipment, devices and materials." Plzvxu,..)e inClu�� the I ength of each circuit loop including
drops with the voltage drop calculav*ons, Please prow'de alami plans on their -own sheet
and 1I$ or 'A scale is preferredIr
I4. (cher COrrections That Aye Required By Special Occupancy Or Condition: None
Plans as S, ubrritted Are Acceptable: Y(*'0pravded any correction or additional subwitWs
required under comments are provided as requested,
Plans Checked Byj
ECwAr.6
DenubirRa F�re
Date: 10!20!97
PIOM furnish commentS buk to the plan reviewer in the f0U�wing mannier
Written COMMents: X New Plans:
3
P_
1