HomeMy WebLinkAboutPLAN ANALYSIS - 97-00001 - Sears - Retail StoresProject
Project
Address:
Gi�y of ����urg
Building Of f ical
12 North Center Street / P.O.
Rexburg, Idaho 83440
(208) 3 59 -3024
I
Plan analysis based on
the 199A Uniform Building Code
Number: sears
Name: dears Brand Central
North 2nd East St .
Occupancy: M, SZ , B
Construction: I I -N
Date: November 12,
Contractor
Designer:
Engineer:
Report By
Siivertree
1995
Builders
Brett Hastings
not known fret
JOE LAIRD
NOTE: The cods items listed in this report are not
complete fisting of all possible code requirements
It is a guide to selected sections of the Cade.
Report created using Plan Analyst software by b w &
Portions of the material contained in this program
from the Uniform Building Code with the permission
International Conference of Building Officials.
DIRECTION
NORTH
EAST
SOUTH
WEST
allowable
-- Sec.
SEPARATION
AREA. I NCRE.AS E
Property line
Property line
Property line
Pub 1 i c way
area increased
505.1
5. 0 Feet
1. Q Feet
71. C} Feet
146.Q Feet
50 . a f or open
intended to
11
in the 1994
be a
UBC.
a. (719) 599-5622
are reproduced
of the
FIRE PROTECTION
5.0 Feet
z.o
73.0
96.5
area on
Feed
Feet
Feet
2 sides.
Code review dor:
Project Id.: Sears
Address: North grid
FL
NAME
Page $$ 2
Brand Central
East St.
OCC MAX FLR AREA ALLOWED RATIO STATUS
1
1
Retain SaleS Room
Warehouse
M
S1
ok
ok
6 0 14
1774
zaoao
18000
Material
required
0.33
0.1
ok
ok
1 Loading dock
1 Office
1 Rist Room
TOTAL FOR FLOOR
BUILDING TOTAL
Sl
B
B
ok
ok
ok
255
149
64
8256
8256
18000
18000
18000
18000
18000
0.01
0.01
0.0
D.45
0.46
ok
0k
ok
ok
ok
The
actual height of this
building
is
17.
feet.
The
maximum height of the
building
is
55.
feet.
--
Table
5-B
EXTERIOR WALL FIRE RATINGS ANIS OPENING PRJTECTInN
NORTH
For fearing
Oc cupancy Wall
M 1 hour
Sl 1 hour
B 1 hour
EAST
For Bearing
Occupancy Wall
M l hour
Sl 1 hour
B 1 hour
SOUTH
For Beaming
Occupancy Wall
M 0 hour
S1 0 hour
B 0 homer
W7 -ST
For Bearing
Occupancy Wall
Table
Non -Bearing
Wail
I hour
1 hou r
1 hour
Non -Bearing
Wall
l hour
1 hour
I hour
Non -Bearing
Wall
Q hour
0 hour
d hour
Awl
Opening
Protection
3/4 hour
3/4 hour
3 /4 hour
Construction
Material
Non - Comb
Non - Comb
Non - Comb
Opening Construction
Protection Material
Not AllowedNon-Comb
Not A11awedNon-iamb
Not AllowedNon-Comb
Opening
Protection
Construction
Materiel
Non - Comb
Non - Comb
Non - Comb
Parapet
Required
No
No
No
Parapet
Required
No
No
Na
Parapet
Required
No
Non -Bearing
Opening
Construction
Parapet
Wall
Protection
Material
required
Code review for
-.
Project Id.: Sears
Address: North 2nd
Brand Central
East St.
M
0
hour
0 hour
S1
0
hour
0 hour
_B
0
hour
0 hour
None
3/4
hour
Not Allowed - -
ELEMENT
Page # 3
None
Non -
Comb
None
Nom -Comb
not
None
Nan -Comb
hr
No
X30
Na
No fire prequirements far openings.
Openings are to he protected with 3/4 hr fire
5 0 %- of the area of the wall maximum. Table
Footnote 5 & Sec. 503.2.2
Maximum single window size is 84 sq.ft. with
greater than
12
feet. -- Sec.
713.8
Openings are
not
permitted in
this wall..
OTHER BUILDING ELEMENTS
j
Interior Bearing wall
Interior nonbrg wall
Structural Frame
Exterior Strut Frame
Floor/Ceiling Assembly
Roof /Ceiling Assembly
Stairs
MATERIAL
Noncombustible
Noncombustible
Noncombustible
Noncombustible
Noncombustible
Noncombustible
Noncombustible
no W Ar -
NOTES
assemblies
s -A.1
See Footnote
See footnote
i. I
mension
FOOTNOTES:
i) Elements in an exterior wall located where openings are not permitted
or where protection of o-oenincrs is recruired, shall be nrotected
-5),
against external fire exposure as
or the structural frame., whichever
required for exterior bearing walls
is ureater. Table 6-A, footnote
Nonioad-bearing walls witftin a tenant
1 hr. corridor may be of -%
a) Noncombustible (nonrated) materials
b) Fire retardant --treated wood
space that are not part of a
c) One-hour construction (any material)
OCCTJPANCY SEPARATIONS
M -S1 1hr
M - 13 l hr
separation
S1 -B Ohr
separation.
Offices
-- Sec.
Qf f ices
-- Sec.
- - Table
less than
302.1
less
302.1
of
exc.
than 25% of
exc. 2. 2
major
major
-- Sec.
mmwe.re,
use do
601.5.2.1
not require
not require
toll
1
Table
RATING
0
hr
0
hr
0
hr
0
lir
0
hr
0
hr
None
no W Ar -
NOTES
assemblies
s -A.1
See Footnote
See footnote
i. I
mension
FOOTNOTES:
i) Elements in an exterior wall located where openings are not permitted
or where protection of o-oenincrs is recruired, shall be nrotected
-5),
against external fire exposure as
or the structural frame., whichever
required for exterior bearing walls
is ureater. Table 6-A, footnote
Nonioad-bearing walls witftin a tenant
1 hr. corridor may be of -%
a) Noncombustible (nonrated) materials
b) Fire retardant --treated wood
space that are not part of a
c) One-hour construction (any material)
OCCTJPANCY SEPARATIONS
M -S1 1hr
M - 13 l hr
separation
S1 -B Ohr
separation.
Offices
-- Sec.
Qf f ices
-- Sec.
- - Table
less than
302.1
less
302.1
of
exc.
than 25% of
exc. 2. 2
major
major
-- Sec.
mmwe.re,
use do
601.5.2.1
not require
not require
toll
1
Codes review far:
Proj ect Id. Sears
Address: North 2nd
Brand Central
East St.
HEATING EQUIPMENT SEPARATION:
FOR M OCCUPANCY:
A 1 hr.
boiler
-- Seca
occupancy
or central
302.5
FOR Sl OCCUPANCY:
A 1 hr. occupancy
boiler or central
-- Sec. 302.5
FOR S OCCUPANCY:
A Z hr.
boiler
-- Sec.
occupancy
or cental
302.5
Page # 4
separation is required around roams containing
heatin� unit greater than 40�,DnQ BTL i nput.
0
separation is required around roams containing a
hewing unit greater than 400,000 BTU input.
separation is
heating ani
ADDITIONAL SEPARATIONS:
required around rooms containing a
greater than 4 0 0, 0 0 0 BTU input.
refrigeration machinery room shall b
of the building as required dor an H7
horizontal occupancy separation may be
area of the machinery room. Structural
protected for the type of construction
A 1 hour separation is required from a
FOR M OCCUPANCY:
EXIT REQUIREMENTS:
FL
1
1
1
1
1
TOTAL
Orty-uw
Retai
Sales
Warehouse
Loading Dark
Off ice
Reit Room
Room
e separated from the remainder
occupancy regardless of area. A
limited to the actual floor
supporting elements shall Joe
only. -- Sec. 2802
n M occupancy.
NUMB MIN MIN
DCC EXITS WIDZ'H
200
4
1
NATE: Areas with 1AC1 before the
treated as an accessory for
-- Sec. 102.1.1 exception
Rated corridors are to have 1 hr.
PANIC RATED DOOR NOTES
HDWR CORRIDOR SWING
2
3.3
Door,
No
Yes
Out
1
1
0.l
0.0
1005.8.1 Window openings
No
No
No
No
N/R
N/R
1
2
0.0
0.0
3.4
Na
No
No
Na
Na
Yes
N/R
N/R
Out
number of occupants area is being
occupant loads.
9
fire protection on both sides of walls
and ceiling. --
Sem. 1005_7
Door,
openings are required to
be pi7ctected
with 20 minute
assemblies. --
Sec.
1005.8.1 Window openings
are required
to be protected
witk-a. labeled
3/4
hear assemblies. -- Sec. 1005.8.E
Page 4 5
Code review for:
Project Id.: Sears Brand Central
Address: North 2nd East St.
In areas where 2 exits are required, the minimum separation is 1/2 of
the maximum diagonal of the area or floor,. -- Sec. 1003.3
When 2 exits are required, exits must be arranged so that it is possible
to go in either direction from any point in a corridor to a separate exit,
except for dead ends not exceeding 20 fejt in length. -- Sec. 1005.5
Exit signs are required from all areas where 2 or exits are required.
-- Sec. 1013.1
Main exterior exit doors which obviously and clearly are identifiable
as exits need not be signed when approved,, -- exc. I
Door swing is based on Sec. 1004.2 except as noted.
occupant load factor is based on Table 10-A.
Number of exits is based on Table '10-A except as noted.
Exit width is in feet and based on Sec. 1003.2.
Exit width is to be divided approximately equally among exits.
Width shown for all areas is based on other exits. (0.2)
Width shown for 1st floor is based on other exits. ( 0. 2 )
Width shown for other floors & basements is, based on stairways. ( 0. 3 )
For
the
minimum
width
of
doors, see
Sec. 1004.6
For
the
minimum
width
of
corridors,
see Sec,.
1005.2
For
the
minimum
width
of
stairways,
see Sec.
1006.2
FOOTNOTES:
9) If this entire story has an automati I c sprinkler system and an
automatic smoke -detection system is installed within the corridor,
and actuation of any detector shall activate alarms is all areas
served bar the corridor,, the corridor need not be rated if' the
occupant load is less than 100. -- Sec. 1005-V exc. 5
FLUS14 AND SURFACE BOLTS:
Manually operated edge or surface -mounted flush bolts
bolts are prohibited. When automatic flush bolts are
leaf having the automatic flush bolt shall not have. a
surface -mounted hardware. The unlatching of any leaf
require more than one operation, -- Sec. 1004,.3
and
used,
door
shall
surface
the door
knob or
not
Code review dor:
Proi ect Id _ o. Sears
Address: North 2nd
LOCKS AND LATCHES:
Brand
East
All means of egress
from which egress is
knowledge or effort.
Central
St.
doors shall he readily
to be made without the
-- Sec. 1004.3,
openable f rorn
use of a key
Key -locking hardware may he used on the main exit when
the side
or special
the main exit
L
consists or a singles aoor or pair or- aoors ii: mere is a sign stating
THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS. When unlocked,
door(s) must swing without operation of any latching device* -- exc.
LANDINGS AT DOORS:
1) A floor or landing shall be provided on each side of doors. When
access for personas with disabilities is required. the floor or landing
shall not be more than 1/2 inch lower than the threshold. When access
is not required, the maximum 'is 1 inch. -- Sec. 1004.9
2) Landings shall have a width not less than the width of the stairway
width of the doorway, I
o r w whichever is the greater, The minimum
length in the direction of exit travel is 44 inches. -- Sec. 1004.10
TRAVEL DISTANCE:
The maximum travel distance in this building is 150 feet. Sec. 1003.4
Code review for:
Project Id„ Sears
Address: North end
Brand Central
East St.
BUILDING ACCESSIBILTTY:
l} This building including each tenant
one entrance which complies with the
Page # 7
shall be provided with at least
accessible routes provisions of
CABG/ANSI A117. 1. - least t
accessible. Sec. 110-3.2.3
of all entrances shall be
2} When more that one exit is required from any accessible space, each
accessible portion of the space shall be served by not less than two
accessible means of egress_ -- Sec. 1104.1.1
3) When an emit stairway is part of an accessible means of egress, the
stairway shall have a clear width of not less than 48 inches between
the handrails. The stairway shall either incorporate an area of refuges
within an enlarged story -level landing or shall be accessed from
an area of refuge,10. -- Sec. 1104.1. 2
The area of refuge shill have direct access to the stairway that serves
L
t . -- - Sec. 11 4 . 2 . 1
4) Each arear_ of refuge shall be sized to accommodate one wheelchair space
not less than 30 inches by 48 inches for each 200 occupant, or
portion thereof . -- - Sec. 1104 . 2 .3
5} If the area of refuge is not within the stairway, it shall be separated
from the rest of the story by a smoke barrier having at least a one-
hour dire -resistance rating. Smoke barriers shad expend to the roof or
floor deck above. Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes. --- Sec. 1104.2.4
5} Tura --way communications are required. -- Sec. 1104.2.5
7) Each area must be identified by a sign stating AREA OF REFUGE and the
international symbol of accessibility.
S} NATE: Exit stairways in buildings protected throughout by an approved
automatic sprinkler system are NOT required to incorporate an area of
refuge. -- Sec. 11 C?4 , 1 . 2 exception #2
ROOFING REQUIREMENTS
1 ) The woofing on this building is required to be Class B or better,,
- - Table 15 -A
2) See section 1504 and ICBG research reports for requirements.
Cade review f or -.
Project Id. . Smears
Address-. North 2nd
Brand Central
East St,
AUTOMATIC SPRINKLER SYSTEMS:
If openings are not
is f lour area
sprinkler
a minimum
opening in
more
system is
dimension
every 5 0
a
provided in each. 50 feet of exterior wall or there
than 75 feet from an exterior opening, an automatic
required. -- Seg. 904.2.2 Note: Openings shall have
of 30 inches. There must be at least 20 sq.ft, of
lineal fejt of wall.,
If theme are laa or more sprinklers, all valves controlling the
water supply and water -flow switches shall be electrically monitored.
Valve monitoring and water-flow alarm and trouble signals shall be
distinctly different and shall be automatically transmitted to an
approved central station, remote station or proprietary monitoring
station. -- Sec. 904.3.1
STANDPIPE REQUIREMENTS:
There is no requirement for a standpipe.
FOOTNOTES:
VENT I LAT I flN
All areas customarily occupied by humans
ventilation bv means of openable exterior
less than 1/2D of the total floor
mechanically operated ventilation
of supplying a minimum of 15 cubic
occupant.- -- Sec. 1202.2.1
area or
system.
r
-- Table 9-A
shall be provided with natural
openings with an area of not
shah be provided with a
Such system shall be capable
reec per minute of outside air per
WALL AND CEILING FINISH
1} Wall and ceiling finish materials are required
Sec. $04.1 and Table 8-B.
2 } Carpeting on the ceiling is required to have a
spread rating. -- Sec. 804.2
3} Textile wall coverings shall have Clays I flame
and shall be protected by automatic sprinklers
acceptance criteria of U.B.C. Standard No. 8-2
to comply with
Class 3 flame
spread
or meed
-
-- Sec.
INSULATION NOTES
1} All insulation material including facings are required
flame-spread rating of 25 or less and a maximum smoke
--- Sec. 707.3
2) Foam plastic insulations are required to be protected.
rating_
the
805
t c have a
density of 450.
- Sec* 2602
Code review for
:
Project Td. Sears
Address : North 2nd
Brand Central
East St.
GLAZING REQUIREMENTS
All
glazing hazardous locations is required to be of safety
in
glazing
material. Sec. 2406.3 2406.4
Locations
:
1)
Glazing in ingress and egress doors except jalousies.
2)
Glazing in fixed and sliding panels of sliding door assemblies
and panels 7' n swinging doors other than wardrobe doors.
3)
in
Glazing storm doors.
4)
Glazing in all unframed swinging doors.
5)
Glazing in doors and enclosures for hot tubs, whirlpools, saunas,
steam rooms, bathtubs and showers. Glazing in any portion. of a
building wall enclosing these compartments where tl-ie bottom exposed
edge of the glazing is less than 60 inches above a standing surface
and drain inlet.
6 )
Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24 -inch arc of
either vertical edge of the door in. a closed position and were the
is bottom exposed edge of the glazing less than 60 inches above the
walking surface.
7 )
Glazing in an individual f iced or operable panel, other than those
locations described in items 5 and 6 above, than meets all of the
following conditions:
A. Exposed area of an individual pane greater than 9 square feet.
B. Exposed bottom edge less. than 18 inches above the floor.
C. Exposed top edge greater than 36 inches above the floor.
D. One or more walking surfaces within 36 inches horizontally of
the plane of the glazing.
8)
Glazing in railings regardless of height above a walking surface.
Included are structural baluster panels and nonstructural "in -fill
panels.
9)
Glazing in walls and fences used as the barrier for indoor and
outdoor swimming pools and spas when the bottom edges is less than
60 inches above the pool side and the glazing is within 5 feet
of the pool or spa deck area.
10)
Glazing in walls enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottom edge is less
than 60 inches
above
the
walking
surface.
ADDITIONAL REQUIREMEN'T'S:
For M occupancy
For S1 occupancy
For B occupancy
Page # 10
Codes review for
Project Id.Sears Brand Central
Address: Nor'[ --h 2nd East St.
.ACCESSIBLE FACILITIES:
NOTE: Except as noted, section numbers listed below are from
CABO/ANSI A117.1 - 1992
WATER FOUNTAINS AND WATER COOLERS:
At least 50 percent of drinking fountains, but not less than one,
provided on every floor shall be accessible. -- UBC Sec. 1105.4.1
Accessible units mush comply with the following'.
1 } Spout is to be within 36 inches of the floor. -- Sec. 4.15.2.1
2 ) Spout arranged for parallel approach shall be vacated 3 inches
maximum from the front edge. Shouts of cantilevered units with
knee and toe Clearances shall be located 15 inches minimum from
the vertical support and 5 inches maximum from the front edge.
-- Sec. 4.15.2.2
3 ) Spouts shall provide a
flow of water 4 inches
height
minimum.
-- Sec. 4.15.2.3
4 } Operable parts shall be
located at or near
the front
edge of the
unit and shall comply with
4 . 25 . 4 -- Sec. 4
. 15 , 3
5} A cantilevered unit is
required to extend 17
inches
minimum from
the vertical suppart�. Clear
knee space must
provide
a clear area
of 8 inches in depth at
27 inches high and
13 inches
at 9 inches
minimum above the floor.
-- pec. 4.15.4.1
6} Forward approach units
shall comply with 4.2.
Units
in alcoves
shall comply with 4.2.4.4.
Units not having
the necessary
knee
Code review for:
Project Id.: Sears
Address: North end
Brand Central
East St.
and toe clearance or clear space under
q.2.4 and have a clear floor space that
wheelchair to make a parallel approach,
TOILET FACILITIES:
Page # 11
them shall comply
allows a person
-- Sec. 4.15.4.E
1) A 60 'Inch diameter unobstructed turning
space is required in
the toilet roam. -- Sec. 4.16.3, 4.2.3 &
Fig. S4.2.3
2) Water closet shall be mounted adjacent to
a side wall or
partition. The distance from the side wall
or partition to the
centerline of the water closet shall he
18 in. Sec. 4.17.1
'i
3) When the accessible water closet inot-
zn a stall:
The clear floor space shall be 48 in minimum
iri front
of the water closet and 42 in froom the
center line of the
water closet on the side not adjacent
to the wall,.
-- Sec. 4.I7.2 & Fig. B4.17.2
4) When the accessible water closet is. in a
stall:
The s-Eall shall be 60 in wide minimum
and 56 in. deep mini"MUM
for wall hung water closets and .59 in
deep minimum for floor
mounted water closets., -- Sec. 4.18.3.1
If the door swings .into the stall, the
required depth shall
be 'increased by 36 inches minimum. --
Sec. 4.18.3.2
Fig. D4.18.3.1
5) The bars are to be 33 to 36 'Inches above
the floor and shall
be provided on the rear wall and on the
side wall closest to
Code review for:
Project Id. : Sears
Address: North 2nd
Brand Central
East St .
Page # 12
the ,rater claset. -- Sec... 4.24.2.2 & Figs. B4.17.3, 84.17.4
and 84. 18. 3. 1
a) Side grab bay is required to stark within 12 inches of the
backwall and extend to 54 inches from the back wall. ('The
minium length of the bar is 42 in) -- Sec. 4.17.4.1 &
Figs. 84.17.3 and B4.18.3.1
b} The rear bar shall be 24 in long minimum, centred on the
wester closet. Where space permits, the bar shall be 36 in
long minimum, with the additional length provided on the
transfer side. -- Sec. 4.17.4.2 Figs. 84.17.31 X4.17.4
and B4. 18. 3. 1
6}
The top of the seat an the water closet is required to be 17
to 19 inches above the floor. -- Sec. 4.17.3 & Fig. B4.17.3
7}
Accessible urinals shall be of the stall type or wall hung with
the rim at 17 inches maximum above the floor. -- Sec. 4.19.2
8}
A clear area of 30 X 48 inches minimum is required in front
of the urinal. Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 inches apart
minimum. Sec. 4 ♦ 19 r 3
9 )
Accessible lavatories shall be mounted with the rim 34 inches
maximum above the floor and a clearance of 29 inches minimum
from the f ioor to the bottom of the front edge of the apron .
-- Sec. 4.2.2.1 Fig. 24.20.3.1
10)
It shall extend 17 inches minimum from the wall. The clear knee.
space shall be 8 inches in depth minimum at 27 inches minimum
ahove the floor and ll inches in depth minimum at 9 in minimum
above the floor. The dip of the overflow shah be ignored when
checking the clearances. -- Sec. 4.20.3.E & Fig. S4.20.3.1
11 }
A clear floor space of 30 X 48 inches minimum shall be provided
in front of the lavatory and shall extend 19 inches maximum
under the lavatory. -- Sec. 4.20.3.2 & Fig. 84.2(}.3.2
12)
Water supply and drain pipes under lavatories shall be
insulated. or otherwise treated to protect against contact.
-- Sec. 4.20.4
13}
The bottom of mirror is required to be within 38 inches of
the floor. -- - Sec. 4.16.6 & Fig. B4.20.3.1