HomeMy WebLinkAboutMECHANICAL COMCHECK - 21-00586 - Just4Kids Pediatric Urgent CareCOMcheck Software Version 4.1.5.3 Mechanical Compliance Certificate Project Information Energy Code: Project Title: Location: Climate Zone: Project Type: Construction Site: Salem Highway US 20 Artco Business Park - Block 1, Lot 2 Rexburg, ID 83440 Additional Efficiency Packages) Credits: 1.0 Required 1.0 Proposed Reduced Lighting Power, 1.0 credit Mechanical Systems List Quantity System Type & Description 1 RTU -1 (Single Zone): 2018 IECC Just4Kids Urgent Care Rexburg,Idaho 6b New Construction Owner/Agent: CASCO 12 Sunnen Dr, Suite 100 St. Louis, MO St. Louis (314)821-1100 Designer/Contractor: CASCO 12 Sunnen Or, Suite 100 St. Louis, MO 63143 (314) 821-1100 Heating: leach -Central Furnace, Gas, Capacity = 110 kBlu/h Proposed Efficiency = 80.00 % Et, Requlred Efficiency: 80.00 % Et or 80% AFUE Cooling: 1 each - Single Package DX Unit, Capacity = 51 kBtu/h, Air -Cooled Condenser, Air Economizer Proposed Efficiency = 14.00 SEER, Required Efficiency: 14.00 SEER Fan System: 1 I Lobby -- Compliance (Motor nameplate HP method) : Passes Fans: FAN 1 Supply, Constant Volume, 2000 CFM, 1.5 motor nameplate hp, 0.0 fan efficiency grade RTU -2 (Single Zone): Heating: leach -Central Furnace, Gas, Capacity = 96 kBtu/h Proposed Efficiency =80.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE Cooling: 1 each - Single Package DX Unit, Capacity = 65 kBtu/h, Air -Cooled Condenser, Air Economizer Proposed Efficiency = 11.00 EER, Required Efficiency: 11.00 EER + 12.6 IEER Fan System: 2 1 Nurse / Office / Exam -- Compliance (Motor nameplate HP method) : Passes Fans: FAN 2 Supply, Constant Volume, 2400 CFM, 1.7 motor nameplate hp, 0.0 fan efficiency grade RTU -3 (Single Zone): Heating: leach -Central Furnace, Gas, Capacity = 120 kBtu/h Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE Cooling: 1 each - Single Package DX Unit, Capacity = 65 kBtu/h, Air -Cooled Condenser, Air Economizer Proposed Efficiency = 11.00 EER, Required Efficiency: 11.00 EER + 12.6 EER Fan System: 2 1 Nurse / Office / Exam -- Compliance (Motor nameplate HP method) : Passes Fans: FAN 2 Supply, Constant Volume, 2400 CFM, 1.7 motor nameplate hp, 0.0 fan efficiency grade Mechanical Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care�ust4Kids\Protects\Rexburg ID 2100882\CDs\Calcs\Mechanical\2100882 - 2018 Page 1 of 13 IECC.ttk requirements listed in the Inspection Checklist, Mike Kindle - Mechanical Designer, /x zw Name -Title ignat a Date Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care�ust4Kids\Projects\Rexburg ID 2100882\CDs\Calcs\Mechanical\2100882 - 2018 Page 2 of 13 IECC.cck COMcheck Software Version 4.1.5.3 Inspection Checklist Energy Code: 2018 IECC Requirements: 57.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section & Req.l[ C103.2 [PR2J' C406 [PR9J1 Plan Review I Complies? Plans, specifications, and/or calculations provide all information with which compliance can be determined for the mechanical systems and equipment and document where exceptions to the standard are claimed. Load calculations per acceptable engineering standards and handbooks. Plans, specifications, and/or calculations provide all information with which compliance can be determined for the additional energy Additional Comments/Assumptions: Comments/Assumptions iplies ;Requirement will be met. s Not Observable Applicable s Not Observable Applicable j 1 High Impact (Tier i) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care�ust4Kids\Projects\Rexburg ID 2100882\CDs\Calcs\Mechanical\2100882 - 2018 Page 3 of 13 IECC.cck Section # & Re .ID Additional Comments Footing / Foundation Inspection Complies? Comments/Assumptions C402.2.6 ;Radiant heating systems panels❑Complies Care�ust4Kids\Projects\Rexburg See the Envelope Assemblies table for values. [FO12]3 'Insulated to >=R-3.5 on face opposite Not ,'space being heated. ❑Not Observable; I ❑Not Applicable C403.12.2 i Snow/ice melting system and freeze ;❑Complies :Exception: Requirement does not apply, protection systems have sensors and ❑Does Not C403.12.3 i controls configured to limit service for Observable [FO9]3 'pavement temperature and outdoor❑Not ❑Not temperature, future connection to Applicable controls. /Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Protect Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care�ust4Kids\Projects\Rexburg ID 2100882\CDs\Gaits\Mechanical\2100882 - 2018 Page 4 of 13 IECC.cck Section Just4Kids Urgent Care Report date: 07/27/21 # Plumbing Rough-in Inspection Complies? Comments/Assumptions & Re .ID IECC.cck C404.50 'Heated water supply piping conforms ❑Complies 'Exception: Requirement does not apply. C404.5.11 Ito pipe length and volume❑Does Not; C404.5.2 requirements. Refer to section details. ;❑Not Observable [PL6]3 ;❑Not Applicable j C404.5, Heated water supply piping conforms I❑Complies Exception: Requirement does not apply. C404.5.11 to pipe length and volume :[]Does Not C404.5.2 requirements. Refer to section details.❑Not Observable; [PL6]3❑Not Applicable C404.5, 'Heated water supply piping conforms ;❑Complies ; Exception: Requirement does not apply. C404.5.1, Ito pipe length and volume ;❑Does Not C404.5.2 requirements. Refer to section details. ; Observable [PL6]3 ,❑Not ❑Not Applicable C404.6.3 j Pumps that circulate water between a❑Complies I Exception: Requirement does not apply. [PL7]3 L heater and storage tank have controls❑Does Not that limit operation from startup to Observable' <= 5 minutes after end of heating❑Not Applicable ; cycle.❑Not C404.6.3 j Pumps that circulate water between a ;❑Complies !Exception: Requirement does not apply. [PL7]3 heater and storage tank have controls f❑Does Not that limit operation from startup to I❑Not Observable <= 5 minutes after end of heating ;❑Not Applicable cycle. C404.6.3 Pumps that circulate water between a ;❑Complies Exception: Requirement does not apply. [PL7]3 heater and storage tank have controls I❑Does Not that limit operation from startup to ;❑Not Observable <= 5 minutes after end of heating 'Not Applicable cycle, C404.7 , Demand recirculation water systems❑Complies 'Exception: Requirement does not apply. [PL8]3 I have controls that start the pump❑Does Not upon receiving a signal from the ;❑Not Observable' !action of a user of a fixture or Applicable appliance and limits the temperature❑Not of the water entering the cold-water piping to 104°F. 0404.7 I Demand recirculation water systems❑Complies ,Exception: Requirement does not apply. [PL8]3 'have controls that start the pump❑Does Not I upon receiving a signal from the❑Not Observable; :,appliance ,action of a user of a fixture or and limits the temperature❑Not Applicable I of the water entering the cold-water piping to 104°F. C404.7 I Demand recirculation water systems ;❑Complies ; Exception: Requirement does not apply. [PL8]3 ; have controls that start the pump❑Does Not upon receiving a signal from the I❑Not Observable' action of a user of a fixture or appliance and limits the temperature I❑Not Applicable ; of the water entering the cold-water 1 piping to 104°F. Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care�ust4Klds\Projects\Rexburg ID 2100882\CDs\Calcs\Mechanical\2100882 - 2018 Page 5 of 13 IECC.cck Section # Mechanical Rough-In Inspection Complies? Comments/Assumptions & Re .ID IECC.cck C402.2.6 ',Thermally ineffective panel surfaces of;❑Complies Exception: Requirement does not apply. [ME41]3 :'sensible heating panels have ❑Does Not ;insulation >= R-3.5.❑Not Observable; ❑Not Applicable C403.8A Motors forfans that are not less than ❑Complies Exception: Requirement does not apply. [ME142]2 11/12 hp and less than 1 hp are ;❑Does Not electronically commutated motors or have a minimum motor efficiency of '❑Not Observable; 70 percent. These motors have the❑Not Applicable means to adjust motor speed. C403.8A Motors for fans that are not less than ;❑Compiles Exception: Requirement does not apply. [ME142]2 '1/12 hp and less than 1 hp are❑Does Not electronically commutated motors or❑Not Observable! have a minimum motor efficiency of Applicable 70 percent. These motors have the❑Not means to adjust motor speed. C403.8A Motors for fans that are not less than ;❑Complies ; Exception: Requirement does not apply. [ME142]2 1/12 hp and less than 1 hp are ;❑Does Not (electronically commutated motors or❑Not Observable have a minimum motor efficiency of '❑Not j 70 percent. These motors have the Applicable means to adjust motor speed. C403.8.5 Each DX cooling system > 65 kBtu❑Complies Exception: Requirement does not apply. [ME143]' and chiller water/evaporative cooling ;❑Does Not 'system with fans > 1/4 hp are❑Not Observable', designed to vary the Indoor fan airflow; as a function of load and comply with❑Not Applicable ; ',detailed requirements of this section. C403.8,5 Each DX cooling system > 65 kBtu❑Complies Exception: Requirement does not apply. [ME143]' and chiller water/evaporative cooling ❑Does Not system with fans > 1/4 hp are❑Not Observable; designed to vary the Indoor fan airflow; Applicable I as a function of load and comply with❑Not ;detailed requirements of this section. C403.8.5 'Each DX cooling system > 65 kBtu ❑Complies Exception: Requirement does not apply. [ME143]2 land chiller water/evaporative cooling❑Does Not system with fans > 1/4 hp are designed to vary the Indoor fan airflow;❑Not Observable las a function of load and comply with❑Not Applicable ,detailed requirements of this section. C403.12.1 I Systems that heat outside the building❑Complies ; Exception: Requirement does not apply. [ME71]' 'envelope are radiant heat systems ;❑Does Not controlled by an occupancy sensing 'device Observable or timer switch.❑Not ❑Not Applicable C403.2.3 'HVAC equipment efficiency verified.❑Compiles ;See the Mechanical systems list for values. [ME55]2❑Does Not '❑Not Observable '❑Not Applicable j C403.5.5 Fault detection and diagnostics❑Complies 'Requirement will be met. [ME113]2 :installed with air-cooled unitary DX❑Does Not units having economizers. ;❑Not Observable; ❑Not Applicable C403.5.5Fault detection and diagnostics❑Complies Requirement will be met. [ME113]2 I installed with air-cooled unitary DX❑Does Not ; units having economizers. ;❑Not Observable I ❑Not Applicable 1 High Impact (Tier 1) :2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:�Urgent CareV ust4Kids\Projects\Rexburg ID 21008821CDs\Gaits\Mechanical\2100882 - 2018 Page 6 of 13 IECC.cck Section # Mechanical Rough -in Inspection Complies? Comments/Assumptions & Re .ID 7 of 13 IECC.cck C403.2.2 Natural or mechanical ventilation is❑Complies ; Requirement will be met. [ME59]1 'provided in accordance with ;❑Does Not ;International Mechanical Code Observable 'Chapter 4. Mechanical ventilation has❑Not :❑Not Applicable capability to reduce outdoor air supply ;to minimum per IMC Chapter 4. C403.7.1; Demand control ventilation provided '❑Complies ; Requirement will be met. [ME59]1 $'for spaces >500 ft2 and >25 j❑Does Not people/1000 ft2 occupant density and ❑Not Observable ;served by systems with air side I❑Not Applicable 1 economizer, auto modulating outside I air damper control, or design alrflow >3,000 cfm. C403.7.2 Enclosed parking garage ventilation ;❑Complies ; Exception: Requirement does not apply. [ME115]3 'has automatic contaminant detection❑Does Not land capacity to stage or modulate❑Not Observable; 'fans to 50% or less of design capacity. ❑Not Applicable C403.7.6 HVAC systems serving guestrooms in I❑Complies ; Exception: Requirement does not apply. [ME141]3 Group R-1 buildings with > 50 ;❑Does Not guestrooms: Each guestroom is, ❑Not Observable' provided with controls that Applicable automatically manage temperature❑Not setpoint and ventilation (see sections C403.7.6.1 and C403.7.6.2). C403.7.4 Exhaust air energy recovery on❑Complies Exception: Requirement does not apply. [ME57]1 systems meeting Table C403.7.4(1)❑Does Not ;and C403.7.4(2). ;❑Not Observable' ❑Not Applicable C403.7.5 IKitchen exhaust systems comply with ;❑Complies 'Exception: Requirement does not apply. [ME116]3 replacement air and conditioned I❑Does Not j supply air limitations, and satisfy hood UNot Observable I 'rating requirements and maximum ;❑Not Applicable ; lexhaust rate criteria. C403.11.1, HVAC ducts and plenums insulated In I❑Complies 1 Exception: Requirement does not apply. accordance with C403.11.1 and❑Does Not C403.11.2 constructed in accordance with Observable [ME60]1 C403.11.2, verification may need to❑Not Applicable occur during Foundation Inspection.❑Not C403.5, ;AIC economizers provided where ;❑Complies :Requirement will be met. C403.5.11 required, meet the requirements for❑Does Not C403.5.2 ;design capacity, control signal, Observable; [ME62]1 'ventilation controls, high -limit shut-off,;❑Not integrated economizer control, and❑Not Applicable provide a means to relieve excess loutsideair ng opeIn. C403.5, Al;r economizers provlded where ;❑Complies :Requirement will be met. C403.5.11 1 required, meet the requirements for❑Does Not C403.5.2 ;design capacity, control signal, Observable [ME62]1 ;ventilation controls, high -limit shut-off, I❑Not I❑Not Applicable ; 1 integrated economizer control, and provide a means to relieve excess ;outside air during operation. C403.5.3. I Air economizers automatically reduce I❑Complies ; Requirement will be met. 3 I outdoor air intake to the design I❑Does Not [ME124]1 ; minimum outdoor air quantity when :❑Not Observable 1 ,'outdoor air Intake will not reduce cooling energy usage. See Table❑Not Applicable C403.53.3 for applicable device types ;and climate zones. 1 High Impact (Tier 1) 2' Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care1Ij ust4Kids\Projects\Rexburg ID 2100882\CDs\Gaits\Mechanical\2100882 - 2018 Page 7 of 13 IECC.cck Section Just4Kids Urgent Care Report date: 07/27/21 # Mechanical Rough -In Inspection Complies? Comments/Assumptions & Re .ID IECC.cck C403,53, ;Air economizers automatically reduce I❑Complies 'Requirement will be met, 3 %outdoor air intake to the design❑Does 'minimum Not [ME124]1 outdoor air quantity when 'outdoor Observable air intake will not reduce❑Not Applicable :cooling energy usage. See Table❑Not C403.533 for applicable device types !and climate zones, C403,53, System capable of relieving excess❑Complies I Requirement willbemet, 4 outdoor air during air economizer❑Does Not [ME125]1 operation to prevent overpressurizing :❑Not Observable ;the building, The relief air outlet Applicable :located to avoid recirculation into the ;❑Not building, C403.53. System capable of relieving excess❑Complies :Requirement will be met. 4 .outdoor air during air economizer❑Does Not [ME125]1 ;operation to prevent overpressurizing Observable I ;the building, The relief air outlet❑Not Applicable located to avoid recirculation into the❑Not ;building, - C403,53, ;Return, exhaust/relief and outdoor air❑Complies !Requirement will be met, 5 dampers used in economizers have❑Does Not [ME126]1 motorized dampers that automatically when not in use and meet❑Not Observable' ,shut maximum leakage rates, Reference❑Not Applicable ;section C403,73 for details. C403,53, 'Return, exhaust/relief and outdoor air ❑Complies ! Requirement will be met, 5 dampers used in economizers have❑Does Not [ME126]1 ;motorized dampers that automatically 'shut when not in use and meet❑Not Observable maximum leakage rates, Reference❑Not Applicable 'section C403.7.7 for details. C403,4,1, Heating for vestibules and air curtains ;❑Complies Exception: Requirement does not apply, 4 ,with integral heating include❑Does Not [ME63]' :automatic controls that shut off the❑Not Observable; heating system when outdoor air Applicable j temperatures > 45F, Vestibule❑Not I heating and cooling systems ; controlled by a thermostat In the ]vestibule with heating setpoint <_ :60F and cooling setpoint >= 80F, C403,33 Hot gas bypass limited to: <=240 ;❑Complies :Location on plans/spec: N/A [ME35]1 : kBtu/h - 50% >240 kBtu/h - 25%❑Does Not ❑Not Observable ❑Not Applicable C403,33 'Hot gas bypass limited to: <=240 I❑complies Location on plans/spec: N/A [ME35]1 ! kBtu/h - 50%>240 kBtu/h - 25%❑Does Not ❑Not Observable' ❑Not Applicable C40333 :Hot gas bypass limited to: <=240❑Complies 'Location on plans/spec: N/A [ME35]1 kBtu/h - 50% >240 kBtu/h - 25% 1❑Does Not '[_-]Not Observable ❑Not Applicable C408.2.2. ;Air outlets and zone terminal devices Complies Requirement will be met. 1 have means for air balancing. ❑Does Not [ME53]3 ;❑Not Observable; I ❑Not Applicable 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care�ust4Kids\Projects\Rexburg ID 2100882\CDs\Colts\Mechanical\2100882 - 2018 Page 8 of 13 IECC.cck # Mechanical Rough -In Inspection Complies? Comments/Assumptions & Re .ID C403.5, Refrigerated display cases, walk-in ;❑Complies 'Exception: Requirement does not apply. C403.5.1, I coolers or walk-in freezers served by❑Does Not C403.5.2 remote compressors and remote [ME12313 'condensers not located In a UNot Observable I ' condensing unit, have fan -powered j❑Not Applicable ; ;condensers that comply with Sections IIC403.5.1 and refrigeration compressor: systems that comply with C403.5.2.. j Additional Comments/Assumptions: 1 High Impact (Tier 1) '�2'�' Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent CareV ust4Kids\Projects\Rexburg ID 2100892\CDs\Colts\Mechanical\2100882 - 2018 Page 9 of 13 IECC.cck Section Just4Kids Urgent Care # Rough-In Electrical Inspection Complies? Comments/Assumptions & Req.ID - 2018 Page 10 of 13 C405.6 Low-voltage dry-type distribution❑Complies [EL26]2 'electric transformers meet the :❑Does Not minimum efficiency requirements of i❑Not Observable; ;Table C405.6. ❑Not Applicable C405.7 Electric motors meet the minimum Complies [EL27]2efficiency requirements of Tables Not I C405.7(1) through C405 7(4) Observable' i'Efficiency verified through certification❑Not Applicable under an approved certification ; program or the equipment efficiency 'ratings shall be provided by motor manufacturer (where certification programs do not exist). C405.8.2, Escalators and moving walks comply❑Complies C405.8.2. with ASME A17.1/CSA B44 and have ❑Does Not 1 automatic controls configured to 'reduce Observable [EL28]' speed to the minimum❑Not Applicable permitted speed in accordance with❑Not ; ASME A17,1/CSA B44 or applicable 'local code when not conveying I passengers. C405.9 (Total voltage drop across the❑Complies [EL29]� combination of feeders and branch❑Does Not circuits <= 5%. ❑Not Observable ; ❑Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care�ust4Kids\Projects\Rexburg ID 2100582\CDs\Gaits\Mechanical\2100882 - 2018 Page 10 of 13 IECC.cck Section 1ust4Kids Urgent Care Report date: 07127/21 Data filename: # Final Inspection Complies? Comments/Assumptions & Re .ID C303.3, Furnished O&M manuals for HVAC❑Complies (Requirement will be met. C408.2.5. systems within 90 days of system ❑Does Not 3 I acceptance. ,[]Not Observable I [FI813❑Not I Applicable C403.2.2 HVAC systems and equipment❑Complies :Requirement will be met. (FI27]3 capacity does not exceed calculated ❑Does Not loads. ❑Not Observable ❑Not Applicable C403.2.4. Heating and cooling to each zone is ❑Complies ;Requirement will be met. 1 I controlled by a thermostat control.❑Does Not [FI47]3Minimum one humidity control device❑Not Observable; per Installed humidification/dehumidification ❑Not Applicable system. C403.2A, Heating and cooling to each zone is ❑Compiles ;Requirement will be met. 1 controlled by a thermostat control.❑Does Not [FI47]3 I Minimum one humidity control device❑Not Observable; ',per installed humidification/dehumidification I❑Not Applicable system. C403.2.4. +Heating and cooling to each zone is i❑Complies Requirement will be met. 1 controlled by a thermostat control. UDoes Not [F]47]3 Minimum one humidity control device❑Not Observable; per installed (humidification/dehumidification❑Not Applicable system. C403.4.1. Thermostatic controls have a 5 °F❑Complies 'Requirement will be met. 2 deadband.❑Does Not [FI38]3❑Not Observable; ❑Not Applicable C403.2.4. Temperature controls have setpoint❑Complies Requirement will be met. 1.3 overlap restrictions.❑Does Not [FI20]3 (❑Not Observable ❑Not Applicable C403.2.4. ,Each zone equipped with setback❑Complies 'Exception: Zones operated continuously. 2 I controls using automatic time clock or❑Does Not [FI39]3 programmable control system. j❑Not Observable ❑Not Applicable j C403.2A. ,Automatic Controls: Setback to 55°F ❑Complies :Requirement will be met. 2.1, '(heat) and 85°F (cool); 7 -day clock, 2 -❑Does Not C403.2A. ,hour occupant override, 10-hour2,2 j❑Not Observable' [F[40]3 ';backup i ;❑Not Applicable j C403.2.4.iSystems include optimum start ;❑Complies Requirement will be met. 2.3 con trols.❑Does Not [F[41]3❑Not Observable; j❑Not Applicable j C403.2.4. ;Systems include optimum start❑Complies Requirement will be met. 2.3- icontrols.❑Does Not [FI41]3 []Not Observable I ❑Not Applicable C403.2.4. Systems Include optimum start I❑Complies Requirement will be met. 2.3 icontrols. ;❑Does Not [F]41]3❑Not Observable ❑Not Applicable ; 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: 1ust4Kids Urgent Care Report date: 07127/21 Data filename: K:\Urgent CareUust4Kids\Projects\Rexburg ID 2100882\CDs\Colts\Mechanical\2100882 - 2018 Page 11 of 13 IECC.cck Section # Final inspection Complies? Comments/Assumptions & Re .ID IECC.cck C408,1,1 ;Building operations and maintenance❑Complies [FI57]1 documents will be provided to the❑Does Not owner. Documents will cover 'manufacturers' ;❑Not Observable information, ❑Not Applicable jspecifications, programming ,procedures and means of Illustrating ;to owner how building, equipment and systems are intended to be Installed, ;maintained, and operated, C408,2.1 ;Commissioning plan developed by Complies [FI28]1 'registered design professional or❑Does Not ;approved agency, ❑Not Observable ❑Not Applicable C408,231 HVAC equipment has been tested to❑Complies ;Requirement will be met, 1 .ensure proper operation.❑Does Not [FI31]1 ;❑Not Observable; ❑Not Applicable C408,23, HVAC control systems have been !❑Complies ;Requirement will be met. 2 'tested to ensure proper operation,❑Does Not [FI10]1 calibration and adjustment of controls.❑Not Observable ❑Not Applicable C408.2.3. ,Economizers have been tested to ❑Complies Requirement will be met. 3 f ensure proper operation.❑Does Not [FI32]1 ;❑Not Observable' ❑Not Applicable C408,2A Preliminary commissioning reportI❑Complies [FI29]1 completed and certified by registered❑Does Not design professional or approved EI Not Observable ;agency. ❑Not Applicable C408,2,5, Furnished HVAC as-built drawings ;❑Complies ;Requirement will be met. 1 'submitted within 90 days of system❑Does Not [FI7]3 acceptance, ;❑Not Observable' ❑Not Applicable C408,2.5, ;An air and/or hydronic system ;❑Complies ;Requirement will be met. 3 'balancing report is provided for HVAC 1❑Does Not [FI43]1 jsystems, I❑Not Observable' ❑Not Applicable C408,2,5, 'Final commissioning report due to ❑Complies 4 'building owner within 90 days of❑Does Not P [FI30]1 receipt of certificate of occupancy, ;❑Not Observable; ❑Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent CareV ust4Kids\Projects\Rexburg ID 2100882\CDs\Colts\Mechanical\2100882 - 2018 Page 12 of 13 IECC.cck Protect Title: Just4Kids Urgent Care Report date: 07/27/21 Data filename: K:\Urgent Care\Just4Kids\Projects\Rexburg ID 2100882\CDs\Gaits\Mechanical\2100882 - 2018 Page 13 of 13 IECC.cck