Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
Salem Highway US 20
Artco Business Park - Block 1, Lot 2
Rexburg, ID 83440
Additional Efficiency Packages)
Credits: 1.0 Required 1.0 Proposed
Reduced Lighting Power, 1.0 credit
Mechanical Systems List
Quantity System Type & Description
1 RTU -1 (Single Zone):
2018 IECC
Just4Kids Urgent Care
Rexburg,Idaho
6b
New Construction
Owner/Agent:
CASCO
12 Sunnen Dr, Suite 100
St. Louis, MO St. Louis
(314)821-1100
Designer/Contractor:
CASCO
12 Sunnen Or, Suite 100
St. Louis, MO 63143
(314) 821-1100
Heating: leach -Central Furnace, Gas, Capacity = 110 kBlu/h
Proposed Efficiency = 80.00 % Et, Requlred Efficiency: 80.00 % Et or 80% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 51 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency = 14.00 SEER, Required Efficiency: 14.00 SEER
Fan System: 1 I Lobby -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 2000 CFM, 1.5 motor nameplate hp, 0.0 fan efficiency grade
RTU -2 (Single Zone):
Heating: leach -Central Furnace, Gas, Capacity = 96 kBtu/h
Proposed Efficiency
=80.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 65 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency = 11.00 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: 2 1 Nurse / Office / Exam -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 2400 CFM, 1.7 motor nameplate hp, 0.0 fan efficiency grade
RTU -3 (Single Zone):
Heating: leach -Central Furnace, Gas, Capacity = 120 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 65 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency = 11.00 EER, Required Efficiency: 11.00 EER + 12.6 EER
Fan System: 2 1 Nurse / Office / Exam -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 2400 CFM, 1.7 motor nameplate hp, 0.0 fan efficiency grade
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
Project Title:
Just4Kids
Urgent Care
Report date: 07/27/21
Data filename:
K:\Urgent
Care�ust4Kids\Protects\Rexburg
ID 2100882\CDs\Calcs\Mechanical\2100882 - 2018 Page 1 of 13
IECC.ttk
requirements listed in the Inspection Checklist,
Mike Kindle - Mechanical Designer, /x zw
Name -Title ignat a Date
Project Title:
Just4Kids
Urgent Care
Report date: 07/27/21
Data filename:
K:\Urgent
Care�ust4Kids\Projects\Rexburg ID 2100882\CDs\Calcs\Mechanical\2100882
- 2018 Page 2 of 13
IECC.cck
COMcheck Software Version 4.1.5.3
Inspection Checklist
Energy Code: 2018 IECC
Requirements: 57.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
& Req.l[
C103.2
[PR2J'
C406
[PR9J1
Plan Review I Complies?
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
Additional Comments/Assumptions:
Comments/Assumptions
iplies ;Requirement will be met.
s Not
Observable
Applicable
s Not
Observable
Applicable j
1 High Impact (Tier i) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Just4Kids Urgent Care Report date: 07/27/21
Data filename: K:\Urgent Care�ust4Kids\Projects\Rexburg ID 2100882\CDs\Calcs\Mechanical\2100882 - 2018 Page 3 of 13
IECC.cck
Section
#
& Re .ID
Additional Comments
Footing / Foundation Inspection
Complies?
Comments/Assumptions
C402.2.6
;Radiant heating systems panels❑Complies
Care�ust4Kids\Projects\Rexburg
See the Envelope Assemblies table for values.
[FO12]3
'Insulated to >=R-3.5 on face opposite
Not
,'space being heated.
❑Not Observable;
I
❑Not Applicable
C403.12.2 i
Snow/ice melting system and freeze
;❑Complies
:Exception: Requirement does not apply,
protection systems have sensors and
❑Does Not
C403.12.3 i
controls configured to limit service for
Observable
[FO9]3 'pavement
temperature and outdoor❑Not
❑Not
temperature, future connection to
Applicable
controls.
/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Protect Title:
Just4Kids
Urgent Care
Report date: 07/27/21
Data filename:
K:\Urgent
Care�ust4Kids\Projects\Rexburg
ID 2100882\CDs\Gaits\Mechanical\2100882 - 2018 Page 4 of 13
IECC.cck
Section
Just4Kids
Urgent Care
Report date: 07/27/21
#
Plumbing Rough-in Inspection
Complies?
Comments/Assumptions
& Re .ID
IECC.cck
C404.50
'Heated water supply piping conforms
❑Complies
'Exception: Requirement does not apply.
C404.5.11
Ito pipe length and volume❑Does
Not;
C404.5.2
requirements. Refer to section details.
;❑Not Observable
[PL6]3
;❑Not Applicable
j
C404.5,
Heated water supply piping conforms
I❑Complies
Exception: Requirement does not apply.
C404.5.11
to pipe length and volume
:[]Does Not
C404.5.2
requirements. Refer to section details.❑Not
Observable;
[PL6]3❑Not
Applicable
C404.5,
'Heated water supply piping conforms
;❑Complies
; Exception: Requirement does not apply.
C404.5.1,
Ito pipe length and volume
;❑Does Not
C404.5.2
requirements. Refer to section details.
; Observable
[PL6]3
,❑Not
❑Not Applicable
C404.6.3
j Pumps that circulate water between a❑Complies
I
Exception: Requirement does not apply.
[PL7]3
L heater and storage tank have controls❑Does
Not
that limit operation from startup to
Observable'
<= 5 minutes after end of heating❑Not
Applicable
;
cycle.❑Not
C404.6.3
j Pumps that circulate water between a
;❑Complies
!Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
f❑Does Not
that limit operation from startup to
I❑Not Observable
<= 5 minutes after end of heating
;❑Not Applicable
cycle.
C404.6.3
Pumps that circulate water between a
;❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
I❑Does Not
that limit operation from startup to
;❑Not Observable
<= 5 minutes after end of heating
'Not Applicable
cycle,
C404.7
, Demand recirculation water systems❑Complies
'Exception: Requirement does not apply.
[PL8]3
I have controls that start the pump❑Does
Not
upon receiving a signal from the
;❑Not Observable'
!action of a user of a fixture or
Applicable
appliance and limits the temperature❑Not
of the water entering the cold-water
piping to 104°F.
0404.7
I Demand recirculation water systems❑Complies
,Exception: Requirement does not apply.
[PL8]3
'have controls that start the pump❑Does
Not
I upon receiving a signal from the❑Not
Observable;
:,appliance
,action of a user of a fixture or
and limits the temperature❑Not
Applicable
I of the water entering the cold-water
piping to 104°F.
C404.7
I Demand recirculation water systems
;❑Complies
; Exception: Requirement does not apply.
[PL8]3
; have controls that start the pump❑Does
Not
upon receiving a signal from the
I❑Not Observable'
action of a user of a fixture or
appliance and limits the temperature
I❑Not Applicable
;
of the water entering the cold-water
1 piping to 104°F.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Just4Kids
Urgent Care
Report date: 07/27/21
Data filename:
K:\Urgent
Care�ust4Klds\Projects\Rexburg
ID 2100882\CDs\Calcs\Mechanical\2100882 - 2018 Page 5 of 13
IECC.cck
Section
#
Mechanical Rough-In Inspection
Complies? Comments/Assumptions
& Re .ID
IECC.cck
C402.2.6
',Thermally ineffective panel surfaces of;❑Complies Exception: Requirement does
not apply.
[ME41]3
:'sensible heating panels have
❑Does Not
;insulation >= R-3.5.❑Not
Observable;
❑Not Applicable
C403.8A
Motors forfans that are not less than
❑Complies Exception: Requirement does
not apply.
[ME142]2
11/12 hp and less than 1 hp are
;❑Does Not
electronically commutated motors or
have a minimum motor efficiency of
'❑Not Observable;
70 percent. These motors have the❑Not
Applicable
means to adjust motor speed.
C403.8A
Motors for fans that are not less than
;❑Compiles Exception: Requirement does
not apply.
[ME142]2
'1/12 hp and less than 1 hp are❑Does
Not
electronically commutated motors or❑Not
Observable!
have a minimum motor efficiency of
Applicable
70 percent. These motors have the❑Not
means to adjust motor speed.
C403.8A
Motors for fans that are not less than
;❑Complies ; Exception: Requirement does
not apply.
[ME142]2
1/12 hp and less than 1 hp are
;❑Does Not
(electronically commutated motors or❑Not
Observable
have a minimum motor efficiency of
'❑Not j
70 percent. These motors have the
Applicable
means to adjust motor speed.
C403.8.5
Each DX cooling system > 65 kBtu❑Complies
Exception: Requirement does
not apply.
[ME143]'
and chiller water/evaporative cooling
;❑Does Not
'system with fans > 1/4 hp are❑Not Observable',
designed to vary the Indoor fan airflow;
as a function of load and comply with❑Not
Applicable ;
',detailed requirements of this section.
C403.8,5
Each DX cooling system > 65 kBtu❑Complies
Exception: Requirement does
not apply.
[ME143]'
and chiller water/evaporative cooling
❑Does Not
system with fans > 1/4 hp are❑Not
Observable;
designed to vary the Indoor fan airflow;
Applicable
I as a function of load and comply with❑Not
;detailed requirements of this section.
C403.8.5
'Each DX cooling system > 65 kBtu
❑Complies Exception: Requirement does
not apply.
[ME143]2
land chiller water/evaporative cooling❑Does
Not
system with fans > 1/4 hp are
designed to vary the Indoor fan airflow;❑Not
Observable
las a function of load and comply with❑Not
Applicable
,detailed requirements of this section.
C403.12.1
I Systems that heat outside the building❑Complies
; Exception: Requirement does
not apply.
[ME71]'
'envelope are radiant heat systems
;❑Does Not
controlled by an occupancy sensing
'device
Observable
or timer switch.❑Not
❑Not Applicable
C403.2.3
'HVAC equipment efficiency verified.❑Compiles
;See the Mechanical systems list for values.
[ME55]2❑Does
Not
'❑Not Observable
'❑Not Applicable j
C403.5.5
Fault detection and diagnostics❑Complies
'Requirement will be met.
[ME113]2
:installed with air-cooled unitary DX❑Does
Not
units having economizers.
;❑Not Observable;
❑Not Applicable
C403.5.5Fault
detection and diagnostics❑Complies
Requirement will be met.
[ME113]2
I installed with air-cooled unitary DX❑Does
Not
; units having economizers.
;❑Not Observable I
❑Not Applicable
1 High Impact (Tier 1) :2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Just4Kids Urgent Care Report date: 07/27/21
Data filename: K:�Urgent CareV
ust4Kids\Projects\Rexburg
ID 21008821CDs\Gaits\Mechanical\2100882 - 2018 Page 6 of 13
IECC.cck
Section
#
Mechanical Rough -in Inspection
Complies?
Comments/Assumptions
& Re .ID
7 of 13
IECC.cck
C403.2.2
Natural or mechanical ventilation is❑Complies
; Requirement will be met.
[ME59]1
'provided in accordance with
;❑Does Not
;International Mechanical Code
Observable
'Chapter 4. Mechanical ventilation has❑Not
:❑Not Applicable
capability to reduce outdoor air supply
;to minimum per IMC Chapter 4.
C403.7.1;
Demand control ventilation provided
'❑Complies
; Requirement will be met.
[ME59]1
$'for spaces >500 ft2 and >25
j❑Does Not
people/1000 ft2 occupant density and
❑Not Observable
;served by systems with air side
I❑Not Applicable
1 economizer, auto modulating outside
I air damper control, or design alrflow
>3,000 cfm.
C403.7.2
Enclosed parking garage ventilation
;❑Complies ;
Exception: Requirement does not apply.
[ME115]3
'has automatic contaminant detection❑Does
Not
land capacity to stage or modulate❑Not
Observable;
'fans to 50% or less of design capacity.
❑Not Applicable
C403.7.6
HVAC systems serving guestrooms in
I❑Complies ;
Exception: Requirement does not apply.
[ME141]3
Group R-1 buildings with > 50
;❑Does Not
guestrooms: Each guestroom is,
❑Not Observable'
provided with controls that
Applicable
automatically manage temperature❑Not
setpoint and ventilation (see sections
C403.7.6.1 and C403.7.6.2).
C403.7.4
Exhaust air energy recovery on❑Complies
Exception: Requirement does not apply.
[ME57]1
systems meeting Table C403.7.4(1)❑Does
Not
;and C403.7.4(2).
;❑Not Observable'
❑Not Applicable
C403.7.5
IKitchen exhaust systems comply with
;❑Complies 'Exception:
Requirement does not apply.
[ME116]3
replacement air and conditioned
I❑Does Not
j supply air limitations, and satisfy hood
UNot Observable I
'rating requirements and maximum
;❑Not Applicable ;
lexhaust rate criteria.
C403.11.1,
HVAC ducts and plenums insulated In
I❑Complies 1
Exception: Requirement does not apply.
accordance with C403.11.1 and❑Does
Not
C403.11.2
constructed in accordance with
Observable
[ME60]1
C403.11.2, verification may need to❑Not
Applicable
occur during Foundation Inspection.❑Not
C403.5,
;AIC economizers provided where
;❑Complies :Requirement
will be met.
C403.5.11
required, meet the requirements for❑Does
Not
C403.5.2
;design capacity, control signal,
Observable;
[ME62]1
'ventilation controls, high -limit shut-off,;❑Not
integrated economizer control, and❑Not
Applicable
provide a means to relieve excess
loutsideair ng opeIn.
C403.5,
Al;r economizers provlded where
;❑Complies :Requirement
will be met.
C403.5.11
1 required, meet the requirements for❑Does
Not
C403.5.2
;design capacity, control signal,
Observable
[ME62]1
;ventilation controls, high -limit shut-off,
I❑Not
I❑Not Applicable ;
1 integrated economizer control, and
provide a means to relieve excess
;outside air during operation.
C403.5.3. I
Air economizers automatically reduce
I❑Complies ;
Requirement will be met.
3 I
outdoor air intake to the design
I❑Does Not
[ME124]1
; minimum outdoor air quantity when
:❑Not Observable 1
,'outdoor
air Intake will not reduce
cooling energy usage. See Table❑Not
Applicable
C403.53.3 for applicable device types
;and
climate zones.
1 High Impact (Tier 1) 2' Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Just4Kids Urgent Care Report date: 07/27/21
Data filename: K:\Urgent Care1Ij
ust4Kids\Projects\Rexburg ID
2100882\CDs\Gaits\Mechanical\2100882 - 2018 Page
7 of 13
IECC.cck
Section
Just4Kids
Urgent Care
Report date: 07/27/21
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Re .ID
IECC.cck
C403,53,
;Air economizers automatically reduce
I❑Complies 'Requirement
will be met,
3
%outdoor air intake to the design❑Does
'minimum
Not
[ME124]1
outdoor air quantity when
'outdoor
Observable
air intake will not reduce❑Not
Applicable
:cooling energy usage. See Table❑Not
C403.533 for applicable device types
!and climate zones,
C403,53,
System capable of relieving excess❑Complies
I Requirement
willbemet,
4
outdoor air during air economizer❑Does
Not
[ME125]1
operation to prevent overpressurizing
:❑Not Observable
;the building, The relief air outlet
Applicable
:located to avoid recirculation into the
;❑Not
building,
C403.53.
System capable of relieving excess❑Complies
:Requirement
will be met.
4
.outdoor air during air economizer❑Does
Not
[ME125]1
;operation to prevent overpressurizing
Observable I
;the building, The relief air outlet❑Not
Applicable
located to avoid recirculation into the❑Not
;building, -
C403,53,
;Return, exhaust/relief and outdoor air❑Complies
!Requirement
will be met,
5
dampers used in economizers have❑Does
Not
[ME126]1
motorized dampers that automatically
when not in use and meet❑Not
Observable'
,shut
maximum leakage rates, Reference❑Not
Applicable
;section C403,73 for details.
C403,53,
'Return, exhaust/relief and outdoor air
❑Complies ! Requirement
will be met,
5
dampers used in economizers have❑Does
Not
[ME126]1
;motorized dampers that automatically
'shut when not in use and meet❑Not
Observable
maximum leakage rates, Reference❑Not
Applicable
'section C403.7.7 for details.
C403,4,1,
Heating for vestibules and air curtains
;❑Complies Exception: Requirement does not apply,
4
,with integral heating include❑Does
Not
[ME63]'
:automatic controls that shut off the❑Not
Observable;
heating system when outdoor air
Applicable
j temperatures > 45F, Vestibule❑Not
I heating and cooling systems
; controlled by a thermostat In the
]vestibule with heating setpoint <_
:60F and cooling setpoint >= 80F,
C403,33
Hot gas bypass limited to: <=240
;❑Complies :Location on
plans/spec: N/A
[ME35]1
: kBtu/h - 50% >240 kBtu/h - 25%❑Does
Not
❑Not Observable
❑Not Applicable
C403,33
'Hot gas bypass limited to: <=240
I❑complies Location on
plans/spec: N/A
[ME35]1
! kBtu/h - 50%>240 kBtu/h - 25%❑Does
Not
❑Not Observable'
❑Not Applicable
C40333
:Hot gas bypass limited to: <=240❑Complies
'Location on
plans/spec: N/A
[ME35]1
kBtu/h - 50% >240 kBtu/h - 25%
1❑Does Not
'[_-]Not Observable
❑Not Applicable
C408.2.2.
;Air outlets and zone terminal devices
Complies Requirement
will be met.
1
have means for air balancing.
❑Does Not
[ME53]3
;❑Not Observable;
I
❑Not Applicable
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Just4Kids
Urgent Care
Report date: 07/27/21
Data filename:
K:\Urgent
Care�ust4Kids\Projects\Rexburg ID 2100882\CDs\Colts\Mechanical\2100882
- 2018 Page 8 of 13
IECC.cck
# Mechanical Rough -In Inspection Complies? Comments/Assumptions
& Re .ID
C403.5, Refrigerated display cases, walk-in ;❑Complies 'Exception: Requirement does not apply.
C403.5.1, I coolers or walk-in freezers served by❑Does Not
C403.5.2 remote compressors and remote
[ME12313 'condensers not located In a UNot Observable I
' condensing unit, have fan -powered j❑Not Applicable ;
;condensers that comply with Sections
IIC403.5.1 and refrigeration compressor:
systems that comply with C403.5.2.. j
Additional Comments/Assumptions:
1 High Impact (Tier 1) '�2'�' Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Just4Kids Urgent Care Report date: 07/27/21
Data filename: K:\Urgent CareV
ust4Kids\Projects\Rexburg ID 2100892\CDs\Colts\Mechanical\2100882 - 2018 Page 9 of 13
IECC.cck
Section
Just4Kids
Urgent Care
#
Rough-In Electrical Inspection
Complies? Comments/Assumptions
& Req.ID
- 2018 Page 10 of 13
C405.6
Low-voltage dry-type distribution❑Complies
[EL26]2
'electric transformers meet the
:❑Does Not
minimum efficiency requirements of
i❑Not Observable;
;Table C405.6.
❑Not Applicable
C405.7
Electric motors meet the minimum
Complies
[EL27]2efficiency
requirements of Tables
Not
I C405.7(1) through C405 7(4)
Observable'
i'Efficiency verified through certification❑Not
Applicable
under an approved certification
;
program or the equipment efficiency
'ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
C405.8.2,
Escalators and moving walks comply❑Complies
C405.8.2.
with ASME A17.1/CSA B44 and have
❑Does Not
1
automatic controls configured to
'reduce
Observable
[EL28]'
speed to the minimum❑Not
Applicable
permitted speed in accordance with❑Not
;
ASME A17,1/CSA B44 or applicable
'local
code when not conveying
I
passengers.
C405.9 (Total
voltage drop across the❑Complies
[EL29]�
combination of feeders and branch❑Does
Not
circuits <= 5%.
❑Not Observable ;
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Just4Kids
Urgent Care
Report date: 07/27/21
Data filename:
K:\Urgent
Care�ust4Kids\Projects\Rexburg ID 2100582\CDs\Gaits\Mechanical\2100882
- 2018 Page 10 of 13
IECC.cck
Section
1ust4Kids
Urgent Care
Report date: 07127/21
Data filename:
#
Final Inspection
Complies?
Comments/Assumptions
& Re .ID
C303.3,
Furnished O&M manuals for HVAC❑Complies
(Requirement
will be met.
C408.2.5.
systems within 90 days of system
❑Does Not
3
I acceptance.
,[]Not Observable
I
[FI813❑Not
I
Applicable
C403.2.2
HVAC systems and equipment❑Complies
:Requirement
will be met.
(FI27]3
capacity does not exceed calculated
❑Does Not
loads.
❑Not Observable
❑Not Applicable
C403.2.4.
Heating and cooling to each zone is
❑Complies
;Requirement
will be met.
1
I controlled by a thermostat control.❑Does
Not
[FI47]3Minimum
one humidity control device❑Not
Observable;
per Installed
humidification/dehumidification
❑Not Applicable
system.
C403.2A,
Heating and cooling to each zone is
❑Compiles
;Requirement
will be met.
1
controlled by a thermostat control.❑Does
Not
[FI47]3
I Minimum one humidity control device❑Not
Observable;
',per installed
humidification/dehumidification
I❑Not Applicable
system.
C403.2.4.
+Heating and cooling to each zone is
i❑Complies
Requirement
will be met.
1
controlled by a thermostat control.
UDoes Not
[F]47]3
Minimum one humidity control device❑Not
Observable;
per installed
(humidification/dehumidification❑Not
Applicable
system.
C403.4.1.
Thermostatic controls have a 5 °F❑Complies
'Requirement
will be met.
2
deadband.❑Does
Not
[FI38]3❑Not
Observable;
❑Not Applicable
C403.2.4.
Temperature controls have setpoint❑Complies
Requirement
will be met.
1.3
overlap restrictions.❑Does
Not
[FI20]3
(❑Not
Observable
❑Not Applicable
C403.2.4.
,Each zone equipped with setback❑Complies
'Exception: Zones operated continuously.
2
I controls using automatic time clock or❑Does
Not
[FI39]3
programmable control system.
j❑Not Observable
❑Not Applicable
j
C403.2A.
,Automatic Controls: Setback to 55°F
❑Complies
:Requirement
will be met.
2.1,
'(heat) and 85°F (cool); 7 -day clock, 2 -❑Does
Not
C403.2A.
,hour occupant override, 10-hour2,2
j❑Not Observable'
[F[40]3
';backup
i
;❑Not Applicable
j
C403.2.4.iSystems
include optimum start
;❑Complies
Requirement
will be met.
2.3
con trols.❑Does
Not
[F[41]3❑Not
Observable;
j❑Not Applicable
j
C403.2.4.
;Systems include optimum start❑Complies
Requirement
will be met.
2.3-
icontrols.❑Does
Not
[FI41]3
[]Not Observable
I
❑Not Applicable
C403.2.4.
Systems Include optimum start
I❑Complies
Requirement
will be met.
2.3
icontrols.
;❑Does Not
[F]41]3❑Not
Observable
❑Not Applicable
;
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
1ust4Kids
Urgent Care
Report date: 07127/21
Data filename:
K:\Urgent
CareUust4Kids\Projects\Rexburg ID
2100882\CDs\Colts\Mechanical\2100882 - 2018 Page 11 of 13
IECC.cck
Section
#
Final inspection
Complies?
Comments/Assumptions
& Re .ID
IECC.cck
C408,1,1
;Building operations and maintenance❑Complies
[FI57]1
documents will be provided to the❑Does
Not
owner. Documents will cover
'manufacturers'
;❑Not Observable
information,
❑Not Applicable
jspecifications, programming
,procedures and means of Illustrating
;to owner how building, equipment and
systems are intended to be Installed,
;maintained, and operated,
C408,2.1
;Commissioning plan developed by
Complies
[FI28]1
'registered design professional or❑Does
Not
;approved agency,
❑Not Observable
❑Not Applicable
C408,231
HVAC equipment has been tested to❑Complies
;Requirement
will be met,
1
.ensure proper operation.❑Does
Not
[FI31]1
;❑Not Observable;
❑Not Applicable
C408,23,
HVAC control systems have been
!❑Complies ;Requirement
will be met.
2
'tested to ensure proper operation,❑Does
Not
[FI10]1
calibration and adjustment of controls.❑Not
Observable
❑Not Applicable
C408.2.3.
,Economizers have been tested to
❑Complies Requirement
will be met.
3
f ensure proper operation.❑Does
Not
[FI32]1
;❑Not Observable'
❑Not Applicable
C408,2A
Preliminary commissioning reportI❑Complies
[FI29]1
completed and certified by registered❑Does
Not
design professional or approved
EI Not Observable
;agency.
❑Not Applicable
C408,2,5,
Furnished HVAC as-built drawings
;❑Complies ;Requirement
will be met.
1
'submitted within 90 days of system❑Does
Not
[FI7]3
acceptance,
;❑Not Observable'
❑Not Applicable
C408,2.5,
;An air and/or hydronic system
;❑Complies ;Requirement
will be met.
3
'balancing report is provided for HVAC
1❑Does Not
[FI43]1
jsystems,
I❑Not Observable'
❑Not Applicable
C408,2,5,
'Final commissioning report due to
❑Complies
4
'building owner within 90 days of❑Does
Not P
[FI30]1
receipt of certificate of occupancy,
;❑Not Observable;
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Just4Kids Urgent Care Report date: 07/27/21
Data filename: K:\Urgent CareV
ust4Kids\Projects\Rexburg ID 2100882\CDs\Colts\Mechanical\2100882
- 2018 Page 12 of 13
IECC.cck
Protect Title:
Just4Kids
Urgent Care
Report date: 07/27/21
Data filename:
K:\Urgent
Care\Just4Kids\Projects\Rexburg
ID 2100882\CDs\Gaits\Mechanical\2100882 - 2018 Page 13 of 13
IECC.cck