We have reviewed the plans for the Furniture buildin�; and have "Identified ed the need to
address the following items:
� . Show dimensions on plot planf'rom buRdi.ng to lot hnes. The south wall of the buflding
mush be at le ast S feet from the property Line, otherwise openings are not allowed 'in this
wadi as per 1994 UBC Table 5A. The south wall scales out at 3 foot from the property
Zine. .
2. Show' the south door (and any openings added to the -south wall) as 314 hour ire protected
as per 1994 UBC Fable 5A #5.
3. Two exterior walls must have apexvngs _for Fire'Department access in every 50 feed of
UBCwalL. As per Section 904.2.2 #1. 'Remember any neve openings in the south wall
must be 314 hour fire protected as per 1994'UBC Table 5A #5-
4.
Provide adequate waterline dor fire hydrant to front landscaping island on the north end of
the property.
�. Show garbage dumpster location on plot pian.
G. Identify 10' di stance b e-�ween any water lines and sewer dines.
?. Satisfy -Fire Department requests as per the data included from the Fire Department
review which is attached.
8. Provide Architect or Engineering scamps an all pages of the drawings.
9. Please provide prefabricated truss, and girder details,
10. Required parking must be within 20Q' of the primary entrance of the building as per the
Parking Regulations para�raph 5.2 of the ReXburg Coning ordinance. A few of the
required spaces do not meet this criteria. 'why is the parking an the opposite sides of the
doors? Wouldn't 'it be better to move the buRding to the east the wzdth
parking on the east end. and move that row to the front ofbuilding.
°� the one row of
the There must be a
dozen different solutions which wouldprovide parking much closet to the main entrance.
Please het me know if you have any quest'
i
359-3020 Ext.314. ons. I can be reached during the work dad at
.
Sincerely,
U G�
Val Christensen'a
Assistant engineer
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 Korth Center
Rexburg, Idaho 83440
(208) 359-3010
1994 Uniform Fire bode
Plan Review
1ding Name: n ted Fern] -tune Warehouse
Building Address: ? North 2 na East
Stories: one
Occupancy Classification: M
Flan Date
Revi ew Date
Type of Construction: V-1HR
11-08-99
Existing Floor area: N/A
New Construction Floor Area: 10,050 square feet
1 ] . Required Fire Flow (Appendix. III -A) 1,750_gpm
Comments:
Based on
0
e V-- l HR
2 ) .Nater Supply (Article 9, Section 903) Required: Yes
Fire Hydrant Location: 1000 N. 2y" ED , Grand Auto, Sta les
Firs Hydrant Flows: Okay Fire Flow Test Location: Grand Autn
Fire Flow Supplied By: Fire Department
ether Approved Vater Source: N/A Water Supply Acceptable: des
Fire Hydrant Location Acceptable: No
Water Supply Comments: Water line will need to be -extended and a
fire -hydrant installed on site
3.)Fire Apparatus Access Roads Article 9 Section 9Q2)
Required:
Complete Road Acceptable: Yes
4) Roads and Water Supply, IncludingFire Hydrants Are
Required To Be Installed And Made Serviceably Prior To And During
Time Of Construction {Article 9 Section 901.3) -yes
5}.znstallat, -on of Portable Fire Extinguisher Article 10 Section
dF
1002)
Review
2
Required : Y
Location Acceptable: Not shown
'hype Provided Acceptable. Not shown
Comments: Minimum 2-A 10 -BC within travel distance
6}.Automatic
Requiree,d:Yes
Fire Extinguishing
unless youaddress
Systems: (Article
th'r
is code
10 Section 1003
section 10-03.2.2 All
occupancies except Group R. Division 3 and Group—U occupancies.
Except for Group Rr Division 3 and Group U occupancies, an
automatic sprinkler system shall be installed:
1. Irl every story or basement of all buildings when the floor
area exceeds 1,500 square deet (139.4 m2) and 'C -here is not
provided at least 20 square feet (1.8.6 m2) of opening entirely
above the adjoining ground bevel in each SQ lineal feet X15 X40
mmj or fraction thereof of exterior wall in the story or basement
on at leapt one side of the building. Openings shall have a
minimum dimension of not less than 30 inches �762 mrnj Such
openings shall be accessible to the fire department from the
exterior and shad not be obstructed in a manner that
firefighting or rescue cannot be accomplished from the exterior.
When openings in a story are provided on only one side and the
opposite wall of such story is more than 75 feet {22 86D mm} from
such openings, the story shall be provided with an approved
automatic sprinkler system, or openings as specified above shall
be provided on at least two sides of an exterior wail of the
story.
If any portion of a basement is located. more than 75 feet (22 gip
mm) from openings required in Section 10Q3,2,2, the basement
shall be provided with an approved automatic sprinkler system.
7) . Standpipes (Article 10 Section
8) .Fire
Plan
Pans
Tease
As
Alarm Systems
Submitted Are
(Article 10
Acceptable:
Checked By.- Dee Owens
furnish comments back
manner: Address hi
1004) Required: No
Section 1007)Required:
No
I$�
Date: 11-D8-99
to the plan reviewer in the following
hlighted items