1994 Unif ossa Fire Code
Plan Review
Building Name: Castlerock Industries,
Plan Date:
ew Da.tes 05-181-99
Rexbur2 Busines5 'ark
Building Address : No�th Salem & Dividend Drive
Stories: one Type of Construction: V -N
Occupancy Classification: B existing Floor Area*
New Construction Floor Area: 6342 square feet
Required Fire Flow (Appendix III -A): 2,250 qpm
Comments:
type V -N constructi,on
2) Water Supply (Article, 9, Section 9Q3) Required: Yes
Fire Hydrant Location v Dividend & Salem,, Bond Ave, Dividend &
Stacks
Fire Hydrant Flows: 2,270 @-.20p_§l
Fire
Flaw
Test Location:
Dividend & Stocks
Fire
Flow
Supplied By:
Fire Department
Water Supply Acceptable: Yep
Fire Hydrant Location Acceptable: des
3.w)Fire Apparatus access Roads (Article 9 Section 902)
Required: No
Comments.* Access frommai roads
4) Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construct -ion (Article 9 Section 901.3) NIA
��.InstallationQf Portable Fire Extinguisher Article 10 Section
Plan Review
Page 2
1002) Required: Yes
Type Provided Acceptable ,,
each complex
Location Acceptabl,e: Not Shown
Not. shown Comments 4. Minimum 2 -A 1O -BC
��.Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: No
7)_Standpipes
(Article 10 Section
8}.Ventilating Hood And Duct Fire
Section 1 0 0 6.2 ) Required : No
9 ) -Fire Alarm Systems (Article
IQ}.other Corrections That Are
1004) Required: No
Extinguishing System
1 0 Section
Required By
Conditions:
Plans As SubmItted Are Acceptable�
Plans Checked By: Dee Owens
Yes
(Article
1007)Required:
Special Occupancy Or
Date
05-18--99
W7
liq
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208)
1994 Uniform Fire Code
Plan Review
11
Building Name: office Comdex,
359-3010
4
Plan r)ate 0
Revlew Date:
Building Address : North Salem- & Dividend Drive
Stories,.
Assume one
Occupancy Classification,:
04-72-99
Type of Construct�on : Used t I V -N
Not shown Existing F'loox Area : N/A
New Construction Floor Area: 6342 scruare feet
1).Required Fire Flow (Appendix !IT -A) 2.,250 gpm
Comments,: Based on one stor
type V--NQonstruction
2) .Water Supply (Article 9, Section 903) required: Yes
Fire Hydrant Locataan : Dividend & Salem.,Bond- -Ave, Dividend &
Stocks
Fire Hydrant Flows-** 2,270 @ 20psi
Fire Flow Test Location : Dividend & Stocks
Fire Flow Supplied By,* Fire Department
Water Supply Acceptable : Yes, based Qn type V -N one stor
Fire Hydrant Location Acceptable: Yes,
based on
t
V -N one stor
3. ) Fire Apparatus Access Roads (A.rticle 9 Section 902 )
Required,-, No
Comments: Access from main roads
4}.Aecess Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And. facie Serviceable Prior To And Du.�ing
Time flf Construction (Article 9 Section 901. 3 ) : N/A
5},Installaton Qf Portable Fire Extinguisher (Article
10 Section
Plan Review
Page 2
10 2} Required: Yes Location Acceptable:
Type Provided Acceptable: 'Not shown
within travel distances
6) Automatic Fire Extinguishing
Required :, Treed more information
7) . Standpipes
information
(Article
Systems
10 Sectian
A I,I T"i W M --
(Article
Not Shown
Minimum 2-A 10 -BC
10 Section
Required:
8 -Vent.I-lating Hood And Duct Fire Extinquishing System
Section 1 00 6. 2 ) Required : Need more information
Need more
(Article 10
-4
9 ) .Fire Alarm Systems (Article 1 0 Section 1007)Required
.
inforrRation
l0}.Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Subraitted Are AC-.-ceptablew., No
Plans Checked By: Dee Owens
Please
manner:
a,oD e a rs
Date*- 12-99
furnish
comments
back
to the
plan reviewer in
the
I need
the full
plans
dor a
complete review.
The
LoDeOKay ir tne assumptions are correct
following
site plan