HomeMy WebLinkAboutREVIEW RESPONSE - 99-00023 - Ricks College - Storage ShedHAZARDOUS rarA�rER:.�,s ��rrAG�,MErrr AREA
Ass, -a preface to the rensT �o�� cvera v�at �s�, s.
1. The facwty wig consist of: a rove a wad, and a floor. ate facifity v�1� �e open �n t ��
sides. There will be no docxrLs, no electricity, and no exit route.
2. The materials stored at this facility will be in the primary containers, ie. &runis or bottles
as appropriate. The containers wBI be stored in Factory Mutual Rated storage containers
with secondary containment as a part of the storage containers. I previously submitted the
brochures to the City of Rexburg Building Department for information. If the brochures
are not avaable, I will be gW to provide additional copies, an intemet address, or a
contact from the manufacturer. We da not intend oar wig we avow incompa#ible
serials to be contained in the same moorage cabinet. The cabinets are on site and
ava-flable for inspection if you desi're.,
Co mment Comment Response
Number
� e
Please. provide details describing the "New complied. See Sheep Titled:
Cinder Storage Building"" which has been Cinder Storage Building
shown next to the Ha=dous Matefials Storage FoundatiProject #v.. PPLT-
Iola,Builonthe plot plan.. 006,F Sheep 1. The buRding is
being relocated from the area
old to the'Navoo Haase
AP artrnents t o the indicate d
location.,
k2, Provide all dimensions for building from. Complied
property lines and other buildings on the Plot
Plan.
3.
Aff pages must be stamped by a licensed Complied
engineer or architect per 94 UBC Section 106.
�e Kexb�g Fire Departmenthas included a The requested Occupancy is
F
list of iterns that must be addressed. I have changed from H-3 to H-7.
a�ached a copy of the list. They have a��
issued a statement t. says the quantilles
provided. on the Ricks CoUege Hazardous
Wasle Storage Inventory List would mace a
`:S" Occupancy possible as lag. as you do not
store any ma.tenal above the revo�C,!!d quantity
limits for the life of the structure. I have also
attached a copy of that list. The other
possib�li ould be an H-7 not and H-3. An
H-7 occupancy would require additional
requ�rements.
Fire
Department
Review
1. Required Fire Flow No response required
2. Water Supply No response required
3. Fire apparatus access roads No response required
4. Access Roads and water supply, are required to No response required
be installed and mads serviceable privy to and
during times of construction
5. Installation of portable fire extinguisher A weather-proof cabinet will
be provided to house a 10#
ABC �xtingu�s�er.
6. Automatic Fire Extinguishing Systems No response required
7. Standpipes No response required
S. VcnWatm-g Hood No response required
94- Firs Alarm No response required
la-] Hazardous Materials Management Flan This document was submitted
with the original pians I year
' ago. A copy is submitted
herewith. Please notify Tam.
Leman (356-2457) of the
n� location. This will allow us
4F
to infonn the appropriate
person if there are any
chanes in the future_
�. 0-21 Hazardous Materials Inventory Stat An inventory was submitted.
Is a second one rewired with
this package?
t �
MSDS � � ,t'` ' �The MSDS are managed by
Tom Leman. Copies ars;
��� •� _-�-
Thereis no location on site to
keel the MSDS.,
10-4 Isigma Si gnage currently �s placed on
the outside of the cabinets
defining the contents as acids,
bases, or solvents. There are
no doors or other enclosures
that can be signed,
10-5 No Smoking Signs W� I Comply
I0-6 SOUTce of ignition Will Comply
10--7 Fire Department Limon Tarn Deman, 356-245 7
Ries College Safety Officer
10-8 Protection from vehicles. The East} Soutk &rest
sides are protected by
concrete foundations wall that
extend 4` above grade. The
north elevation is protected
by the same foundations walls
plus the 4" steel cal.
Supporting, the roof. Each
cabinet i's constructed from
1/40T steel.
10-9 Sof i�acoatible materials Will Co ly. The four
cabinets are labeled for acids,
bases,r and solvents. They are
avaiable for i«sp+ection at the
site.
10-1Q Outdoor Control Areas Will Comply. weeds will be
controlled with appropriate
spraya and manual removal..
Stockpfflng or storage of
materials will be cantrofled.
Spfll Control Each storage cabinet has the
sgifl control as an. integral
_
pill of the desi V
Monitor* wffl })e
incoTarated.
10-12 � Tt--Nmperatue Control No temperature control is
� required to prevent reactions.
EmergencyAlarrm An approved emergency UFS 8003.. I , 10 sates that
al= system shall be provided in buildings, the akrrms wiH be year each
grooms, or areas used for starn.ge of bazardous interior exit. The facility has
materials. Emergency alam-inrtiatmg devises none. The warm is
shall be mstaffed outside of each interior exit or desigmted to alert accupauts.
exit access door of storage buildings, rooms, or There are no occupants
areas. Activation of an emergency alarm- assigned to the facility to be
initiating device ShaU SDartd a local alarm to alerted. What is the best way
alert occupants of an emergency situation to address this?
involving hazardous materials-,
10-14 Superwsion At this point, we do not
intend to have emergency
alarms, detection or
automatic fire-,extinguishng
sys~tem&
1X1--15 Clearance from Combustible Agree and will camEply.