199 Una"So FjLre Code
Plan Rev;iew
Building Name
i
P.O. Box 280
2 6 North Centex
Rexburg , Idaho 8 3 4 4 0
(208) 359-w3010
Birch Apartments
Plan Dates: 06-P99
Review Data: 07-08-99
pm�
Building Address: 2nc' Kniest and 3rd South
Stories Two Type of Construction: V -N
Occupancy Classification: R--1 Existing Floor Area.
New Construction Floor Area: 4,400 X 3 = 13, 2p0
1).Required Fire Flow (Appendix III -A): 3, 000 M
N/A
2 } .dater Suppler (Article J, Section 903) Required: Yep
Fire Hydrant Location: 1st Wept and 3 -rd South, 2nd West and 3rd youth
Firs hydrant Flows: 3, 16.5 @.. 20psi-
Fire
Flow 'fest Location: 2nd West and 3rd South
Fire Flaw Supplied By: Firms Department
Water Supply Acceptable: Yes
Fire Hydrant Location Acceptable,: NQ
Water Supply Comments.: Add one fire hydrant in
need a site plan of the complex
the complex
.
3.)Fire Apparatus Access Roads (Article 9 Section 90,2) Required:
The fust buildina will be okay. I Mill need a site nlAn of the
complex.
C 04mplete Road Acceptable: No
4 ) .����s� Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed. And Mace Servicoable Prior To And During
glace Review
Page 2
Time of Construction
(Article 9 Sec-t�an 901.3) : Ye.s
5} .Installation Of Portable F-nLre Extinguisher (Article 10 Section
1002) Required: des Location Acceptable: Not Shawn
Type Provided Acceptable:
each unit
6 } . Automatic
Required.*
No
7).Standp12pes
Not
shown
Fire Extinguishing Systems:
Comments
(Article 10 Section 1004)
Comments
Minimum 2-A 10 -BC
(Article 10 Section 1003
Based on two stor
Required: No
8) .Ventilating Hood And Duct Fire Extinguishing System (Article ld
Section 1006.2) Required: No
Comments: Not commercial
9) .Fire Alarm Systems (Article 10 Section 1007)Required,: No
Comments; Based on two star
Plans
As Submitted
Are
Acceptabie. No
Plays
Checked By:
Dee
Owens
I need anew site plan
Date: 07-08-9
DATE: 7-21-99
T0: GEORGE BENSON
SUBJECT: SITE PLAN FOR BIRCH APARTMENTS
i
The Site Plan for the Birch Apartments needs to be updated to show tli-e
correct size and location of the apartment building. Also, the exterior
sidewalks and right-of-wx
ramp to the apartment buil
lines and the interior sidewalks, handicapped
ding and the parking lot all need to be drawn
on correctly. You also need to show which of the, apartments on the
lower floor is going to be designated as the "handicapped accessible"
apartment and which will be "handicapped adaptable". The 6", Mvaterline,
valve and fire hydrant and the 1211 storm drain line and manholes also
The h" waterline and fire hydrant and the storm
Aram line and manholes all need to be completed as part of the "under
construction" apartment building complex. Also please show how
much of the parking lot will be constructedi'sn conjunction with this
present apartment building an
d how much with the Future bul'Iding.
need to be added
As you know., the Fire Dept. has a problem with access into the perking
lotto the back building (southeast comer of the site). Il you ire going
io move it to ti -le front near 3
Otherwise, the Fire Dept-,
satisfying their concerns.
r
South St., this also needs to be shown.
and you need to discuss other ways of
ti
DEAN BIRCH APARTMENT SITE PLAN
1 --- Entire proposed developmen
t is within what is presen
Business District Zone kHBD); therefore he will need t
change from FIBD to High Density Re
sidential (HDR).
ti
o get
y a Highway
a zone
2 --- The very preliminary Site Sketch I saw did not show the entire
proposed development. It only showed one apartment, but did not show
the other two apartmentsthat are also planned for the, site.
J
Ihe Street
s
ROW Lines were not shown. Without the future apartment building
shown., it was impossible to determine whether or not the parking -space
and. landscaping requirements were met.
3 --- The east side of the one apartment building shown should have a
t.; inst
rd Distance of 20 f
ead of the SI"deyard Distance of 8.5 ft.
T
he Sideyard Distance of 8.5. ft. on the south side of the proposed
apartment bu
the building.
ilding would, probably be OK depending upon the height of