Plan analysis based on
the 1994 Uniform Building Code
Date: May
name;
i:�eenive
House
Assisted Living Center
UNLIMITED
Main
St.
west
of 4th
wPqi- .c-�-
Occupancy: R4
Construction: V -N
i
Contractor:
Architect*
Engineer:
Report BY
241
1999
Medical Design
Joe Laird
NOTE: The. code items listed it this report are not
complete listing of all possible code requirements
it is a guide to selected sections of the code.
Report created using Plan Analyst software by b w &
Portions of the material contained in this pro -gram
from the Uniform Building Cade with the permission.
International Conference of Building Officials.
- Sprinkler-
systern used for allowable area increase
DIRECTION
NORTH
EAST
SOUTH
WEST
Allowable
-- Sec.
FL
SEPARATION
BOUNDARY AREA INCREASE
Property line
Building
Property 1 ine
Property line
area increased
505.1
X5. 0 Beet
30. E Feet
60. Q Feet
S_a Feet
12. 5 o for
Group
L
ntended to be a
in the 1994 UBC.
a. (719) 599-5622
are reproduced
of the
FIRE PROTECTION
25.0
15.0
60.0
8.0
open area an
Feet
Feet
Feet
Feet
3 sides_
NAME
OCC MAX FLR AREA ALLOWED RATIO STATUS
-- - - - - - - - - - - - - - - --- - ----
---------- - - - - --
--------- - - - - - -
Assisted Living
TOTAL FOR FLOOR
BUILDING TOTAL
ok 4063
4063
4053
t]NLIMITED
ARES
UNLIMI'I`ED
AREA
UNLIMITED
AREA
Code review f or:
Project Id. : Beehive douse
Address: Main St. west of
The actual
The maximum
Assisted Living
4th West St.
Page # 2
Center
height of this building is 24, feet...
height of the building is 40 . feet.
`able 5-B
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table
NORTH
For
Occupancy
R4
EAST
For
Occupancy
R4
SOUTH
For
Occupancy
R4
WEST
I' •
Occupancy
R4
None
3/4
Bearing
Wall
0 hour
Bearing
Wall
0 hour
Bearing
Wall
0 hour
Bearing
Wa1.1.,-
0
hour
fan -Bearing
Wall
0 hour
Non. --Searing.
Wall
0 hour
Non -Bearing
Wall
d hour
Nan -Bearing
Wall
D hour
Opening
Protection
None
Opening
Protection
None
opening
Protection
None
Construction
Material
Any
Construction
Material
Any
Construction
Materia.
M_
Opening Construction
Protection Material
,- No fire protectionhour �- Openings are to be
50-'-.- of the area of
Any
Parapet
Required
No
Parapet
Required
No
Parapet
Required
Na
Parapet
Required
No
requirements fir openings.
protected with 3%4 hr firms
the wail maximum. -- Table5 -At
assemblies.
Cade review f or:
project Id.; Beehive House
Address: Main St . west of
Not Allowed. - -
ELEMENT
Assisted diving Center
4th. West St.
Footnote 5 & Seg. 503.2.2
Maximum single window size is
greater than 12 feet. -- Sec.
Openins are no permitted. in
OTHER BUILDING ELEMENTS
Interior fearing wall
Interior nonbrg wall
Structural Frame
Exterior Struct Frame
Floor/Ceiling Assembly
Roaf/Ceiling Assembly
Stairs.
FOOTNOTES:
-1 � U1
MATERIAL
Any
A.y
Any
Any
Any
Any
Any
84 sq. ft.
713.$
this wall.
with no
NOTES
See footnote
dimension
�a �1Gm6-:�uLs in an exterior wall 10cated where openings are not permitted
or where protection of openings is requi-red, shall be rotes
against external fire exposure as required exterior beari�d
or the structural frame, whichever is reater. - 'meg walls
g - Table � -A, footnote l
]DRAFT STOPS:
If there is cambustible construction in the roof /ceiling assemblYOFcar
aft
exceed 3
stops shall be- instal.Ied so that the area of concealed space doteno,t,00� installed
feet and so that the horizontal dimension b
stops does not exceed 60 feet. - - sec,, 708.3-1-2.2 etween
When sprinklers are installed in the attic, the area mayhe g,p0Q sfand the greatest horizontal dimension may be 10p feet.. � �'
OCCUPANCY SEpARATIONS -- Table 3-B
None required
HEATING EQUIPMENT SEPARATION:
FOR R4 UCCUPANCY
ADI3ITIONAL SEPARATIONS:
A refrigeration machinery room shad be sena-r;:ifipr-a -F ,.-,.
OL the building as required for an H7
horizontal occupancy separation may be
area of the machinery room. Structural
protected for the type of construction
A 4 hour separation is required from a
11-JUL - e- L c2mainaer
occupancy regardless of area. A
limi, e to the actual floor
supporting elements shall be
only. -- Sec. 2802
a R4 occunAnr,tr
Table
RATING
a
hr
0
hr
Q
hr
D
hr
d
hr
a
hr
None
with no
NOTES
See footnote
dimension
�a �1Gm6-:�uLs in an exterior wall 10cated where openings are not permitted
or where protection of openings is requi-red, shall be rotes
against external fire exposure as required exterior beari�d
or the structural frame, whichever is reater. - 'meg walls
g - Table � -A, footnote l
]DRAFT STOPS:
If there is cambustible construction in the roof /ceiling assemblYOFcar
aft
exceed 3
stops shall be- instal.Ied so that the area of concealed space doteno,t,00� installed
feet and so that the horizontal dimension b
stops does not exceed 60 feet. - - sec,, 708.3-1-2.2 etween
When sprinklers are installed in the attic, the area mayhe g,p0Q sfand the greatest horizontal dimension may be 10p feet.. � �'
OCCUPANCY SEpARATIONS -- Table 3-B
None required
HEATING EQUIPMENT SEPARATION:
FOR R4 UCCUPANCY
ADI3ITIONAL SEPARATIONS:
A refrigeration machinery room shad be sena-r;:ifipr-a -F ,.-,.
OL the building as required for an H7
horizontal occupancy separation may be
area of the machinery room. Structural
protected for the type of construction
A 4 hour separation is required from a
11-JUL - e- L c2mainaer
occupancy regardless of area. A
limi, e to the actual floor
supporting elements shall be
only. -- Sec. 2802
a R4 occunAnr,tr
Page # 4
Cade review for*1W
Project Id.: Beehive House Assisted Living Center
Address: Main Stp unrest of 4th Weser St .
EXIT REQUIREMENTS
FL NAPE NUMB MI11T MIN PANT C RATED DOER NOTES
OCA EDITS WIDT14 HDWR CORRIDOR SWING
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
1 Assisted Living Home 51 2 0.9 No Yes Out
TOTAL 51 2 0.9 No Yew Qui
Rated corrihavedors are to 1 fir. fire protection on doth sides of walls
and ceiling. -- Sec. 1005.7 Door openings are required to be protected
with 20 minute assemblies. --- Sec. 1005,8.1 Window openings are required
to be protected with labeled 3/4 hour assemblies. -- Sec. 1005-8.2
In areas where 2 exits are required, the minimum separation is 1%2 of
the maximum diagonal of the area or floor. -- Sec. 1003.3
When. 2
to go
except
emits are
in either
for dead
required, exits must be arranged so that
direction from any point in a corridor to
ends not exceeding 20 feet in length., =-
Exit signs are required from all areas where 2 or
-- Sec. 1013.1
�.t is possible
a separate exit,
Sec. 1005.5
exits are required.
Main exterior exit doors which obviously and clearly
as exits need not be signed when approved. --- exc . 1
Doter swing is based on Sec, 1004.2 except as noted.
Cccupant load factor is based on `Fable l0 -A.
NT V-1
are ident 'if fable
U<<<u=1 O -L is casea an Ta-ule 10-A except as noted.
Exit width is in feet and based an Sec. 1003_2.
Exit width is to be divided approximately equally among exits.
Width shown for all aromas is based on other exits. (0.2)
Width shown for 1st floor is based„ on other exits. (0.2)
Width shown for other floors & basements is based on stairways.
For the minimum with of doors, see Sec. 1004.6
For the minimum width of corridors, see Sec. 1405.2
For the minimum width of stairway, see Sec. 1006.2
FOOTNOTES:
(0.3)
��ode review for:
2roject
Id. - Beehive House
Assisted
Living Center
Address:
Main St. west of
nth West
St.
FLUSH AND SURFACE BOLTS:
Manually operated edge or surface-mounted
bolts are prohibited. when automatic flush
leaf having the automatic flush bolt shall
flush dolts
dolts are
not have a
narczware. `zrae unlatching of any leaf
require more than one Operation. -- Sec, 1004.3
and
used,
door
shad
surface
the door
knob or
not
LACKS AND LATCHES:
All means of egress doors shad be readily openable f rom the side
from which egress is to be made without the use of a key or special
knowledge or effort. -- Sec. 1004.3
LANDINGS AT DOORS:
i } A floor or landing shall be provided on each side of doors. When
access for persons with disabilities is required. the floor or landing
shall not be more than 1/2 inch lower than the threshold. When access
is not required, the maximum is 1 inch. -- Sec. 104.9
2 } Landings shall have a width not less than the width of the stairway
or width of the doorway, whichever is the greater. The minimum
length in the direction of exit travel is 44 inches. -- Sec. 1004.10
TRAVEL DISTANCE:
The maximum travel distance in this building is 200 feet.
- Sec, 1003;
Code review far:
Froi ect Id - : Beehive House Assisted
Address: Main St. west of 4�h West
Page # 6
Living Center
St.
BUILDING .ACCESSIBILITY:
lj This building includi'ng each tenant
one entrance which complies with the
r_1
N
3)
Shall be nrnvi dprl
ieast 5 U percent
acce��ib1� . -- Sec. 1103 .2 . 3
accessible rause
of all entrances
with at least
pravisions of
shall be
wnen more tnat one exit is required from any accessible spaces, each
accessible portion of the space shall be served by not less than two
accessible mean.s of egress, -- Sec, 1104.1.1
When an exit stairway is part of an accessible means of egress, the
stairway shall have a clear width of not less than 48 inches between
the handrails. The stairway shall either incorporate an area of refuge
withiel
n an narged st--
orylevel landing or shall be accused from
an area of refuge. -- Sec. 114.1.2
The area of refuge shall have direct access to the stairway that serves
I
t . -- Sec. 1104.2.2-
4)
Each area of refuge shall he sized to accommodate one wheelchair space
not less than 30 inches by 48 inches for each COQ occupants, or
portion thereof . - -- Sec. 1104 . ,2 . 3
5} If the area of refuge is not within the stairway, it shall be separated
from the reit of the story by a smoke barrier having at least a one
hour fire -resistance rating. Smoke barriers shall extend to the roof or
floor desk above. Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes. -- - Sec. 1104.2-4
5) Two --way communications are required. -- Sec. 114.2.5
7} Each area must be identified by a sign stating AREA CSF REFUGE and the
international symbol of accessibility.
8} NOTE: Exit stairways in buildings protected throughout by an approved
automatic sprinkler system are NOT required to incorporate an area of
refuge. -- Sec. 1104.1.2 exception. 42
RC30FING REQUIREMENTS:
1} The roofing on this huildin
-- Table 15-A g is not required to be fire retardant.
2) See section 1504 and ICBG research reports for requirements'.
r
reviewfor 1h
L
rrojecL Icx.: .beehive douse Assisted Living Center
Address : Main St. west of 4th West St .
AUTOMATIC SPRINKLER SYSTEMS:
If there ars 14a or more sprinklers, all valves controlling the
water supply and water -flow switches shall be electrically monitoreds
Valve monitoring and water -flow alarm and trouble signaler shall be
distinctly different and shall be automatically transmitted to an
approved central station, remote station or proprietary monitoring
station... -- Sec., 904 . 3 _ 1
STANDPIPE REQUIREMENTS
There is no requirement for a standpipe.
FOOTNOTES:
-- Table 9-A
LIGHT ,AND VENTILATION
1} All habitable rooms require exterior glazed openings equal to 1/10
or more of the floor area. (min 10 std , f t . 7 -- Sec. 1203.2
Exception: Kitchens may be provided with' artificial light.
2} All habitable rooms require an operable exterior openings equal to
1/20 or more of the floor area . (ruin 5 sq . f t . ) -- Sec. 1203.3
The minimum area in bath rooms and laundry rooms is 1 1/2 sq.ft.
In lieu of required exterior openings for ventilation, a mechanical
ventilation system may be provided.6 such system shall be capable of
providing two air changes per hour.
3} In bathrooms containing a bathtub or shower and laundry roams, the
ventilation system shall be connected directly to the outside and
be capable of providing five air changes per hour. The point of
discharge shall be at least 3 feet from any openings which allows
air entry into the building.
Rooms which only contain a water closet and/or lavatory may be
vented using a mechanical recirculating fan designed to remove
odors from the air. -- Sec. 1203.3
WALL AND CEILING FINISH:
1 j Wall and ceiling fini'sh materials are required to comply with
Sec. 804-1 and Table 8-B.
2) Carpeting on the ceiling is required to have a glass I flame
spread rating. -- pec. 804.2
3 } Textile wall coverings shah. have Class I flame spread rating.
and shall be protected by automatic sprinklers or meet the
acceptance criteria of 7-B.C. Standard No. 8-2 -- ,Sec. 805
Code review for:
.eroj ec7-. icL Beehive Rouse Assisted sted Living Center
Address : Main St. west of 4th West St 0
INSULATION NOTES.
1) All insulation material including
flame -spread rating of 25 or less
unless it is in a concealed space
I I
facings are required
and a maximum smoke
and the facing irs in
to have
density
contact
a
of 45a
with
2 Foam plastic insulations, are required to he protected. -- Sec. 2602
GLAZING REQUIREMENTS
All glazing in hazardous locations is required to lam of safety
glazing material., -- Sec. 2406.3 & 2406.4
Locations:
1) Glazing in ingress and egress doors
2) Glazing in fixed and sliding panels
and panels in swinging doors other
3) Glazing in storm doors.
4 ) dazing in all untrained swinging doors.
5) Glazing in doors and enclosures for hot tubs, whirlpools, saunas,
steam rooms, bathtubs and showers. Glazing in any portion of a
except jalousies.
of sliding door assemblies
thaw. wardrobe doors.
-Ouiictlng
wall
enclosing
these compartments
where
the bottom
edge of
thee
glazing is
less than
60 inches
above
a stan(91na
and drain inlet.
Lied6) Glazing in or operable panels
nearest exposed edge of the glazing
either vertical edge of the door in
bottom exposed edge of the glazing
walking surface.
7) Glazing in an individual firmed or
locations described in items 5 and
following conditions :
exposed
surface
adjacent to a'door where the
is within a 24 -inch arc of
a closed position and where the
is less than 60 inches above the
operable panel, other than those
6 above, than meets all of the
4P b -i k-J)Z-3 7,1- CL � � C71L �ai i _Lnu-L v-Luuai pane
greater than
9 square feet.
Code review f or
Page # 9
�-LujucL
la.:
Eeena-ve House
L
Ass4 sted
.1
Living Center
Address
Main
St. west of
4th West
St.
B. Exposed bottom edge less than 18 inches above the floor.
C. Exposed top edge greater than 36 'inches above the floor.
D . One or more walking surfaces within 3 6 inches pari zontally of
tie plane of the glazing_
8 ) Glazing in railings regardless of height above a walking
Included are structural baluster panels and nonstructu
ra L
9)
Panels.
r--41 4 -11
surLace
-i.-
��a�
wca-Li-s anu Lences usect as the barrier for indoor and
outdoor swimming pools and spas when the bottom edges is less
60 inches above the pool side and the glazing is within 5 feet
than
of the pool or spa deck area.
10) Glazing in walls enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottom edr,-,fe is less
than 60 inches above the walking surface.
ADL I T I ONA,L REQUIREMENTS:
For R4 occupancy
ACCESSIBLE FACILITIES:
NOTE: Except as noted, section numbers listed below are from
CARO/ANSI A117.1 - 1992
WATER FOUNTAINS AND 'WATER COOLERS:
At least 50 percent of drinking but not less than one
providedfauntazns,
floor on every shall115.4.1
be accessible. UDC Sec.
Accessible .nits must comply with the following: -- Sec. 4.15.2.1
1) Spout is to be within 36 inches of the floor,,
2) Spout arranged for parallel approach shall be located 3 inches
maximum from the front edge. Spouts of cantilevered un -its with
knee and toe clearances shall be located 15 inches minimum from
the vertical support and 5 'Inches maximum from the front edge.
-- Sec. 4.15.2.2
3) Spouts shall provide a flow of water 4 inches height minimum.
-- Sec. 4.15.2.3
4) Operable parts shall be located at or near the front edge of the
unit and shall comply with 4.2 .4 -- Sec. 4.15,3
5) A cantilevered unit is required to extend 17 inches minimum from
the vertical support. Clear knee space mustr-% Cl-
--%
rovide a clear Ql"
of 8 inches in depth at 27 inches high and 11 inches at 9 inches
minimum above the floor. -- Sec. 4.15.4.1
G) Forward approach units shall comply'th 4.2. Units 'in alcoves
wl
shall comply with 4.2.4.4. Units not having the necessary knee
Code review f or#
Project I. i Rause
Address: Main f
Assisted Living Center
4th West st.
and tom clearance or clear space under
4.2.4 and have a clear flour space that
wheelchair to make a parallel approach.
`P
them shall comply with
allows a person in a
-- Sec. 4.15.4.E
V H t, .L
Z) A 60 inch diameter unobstructed turning space is required
the toilet room. -- See. 4.16.3, 4.2.3 & Fig. 84.2.3
2} Water closet shall be mounted adjacent to a side wall or
partition. TI -ie distance from the gide wall or partition to
centerline of the water closet shall be 18 in. Sec. 4.17.1
3} When the accessible water closetis not in a stall:
The clear floor spaces shall be 48 in minimum in front
_r
in
U� ���� w���r- c:ioset ar4a �� in from the center 1ine of the
water closet on the side not adjacent to the wall.
-- sec. 4.17.2 Fig_ B4.17.2
4) When the accessible water closest is in a stall:
The stall shall be 5o in wide minimum and 56 in deep minimum
for wall hung water closets and 59 in deep minimum for flown
mounted water closets. -- Sec. 4.18.3.1
If the do -or swings into the stall, the required depth shall
be increased by 36 inches minimum. -- Sec. 4.18.3.2 &:
Fig. B4.18.3.1
5) The bars are to be 33 to 36 inches above the floor
IDe provided on the rear wail and on the side wall
and shall
closest to
# 11
Cade review f or Page
Project 3d. Beehive House Assisted Living .Center
Address: Mai' n St. west of 4th Wiest St.
the water closet, -- Sec. 4.24-2.2 & Figs. B4.17.3, 34.17.4
and B4.18.3.1
a7 Side grab bar is required to start within 12 inches of the
backwall and extend to 54 inches from the back wall. (The
minimum length of the bar is 42 in) -- Sec, 4.17.4.1 &
Figs. B4.17.3 and B4.18.3.1
h) The rear bar shall be 24 in hong minimum, centred on the
water closet. Where space permits, the bar shall be 36 in
long minimum, with the additional length provided on the
transfer side. -- Sec. 4.17.4.2 digs. B4.17.3, B4.17.4
and E4 _ 18.3. 1
5} The top of the seal on the water closet is required to be 17
to 19 inches above the floor. -- Sec. 4.x`7,3 & Fig. B4.17.3
7} Accessible urinals shall be of the stall type or wall hung with
the rim at 17 inches maximum above the floor. -- Sec. 4.19.2
8} A clear area of 30 X 48 inches minimum is required in front
of the urinal. Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 inches apart
minimum. -- Sic. 4.19.3
9) Accessible lavatories shall be mounted with the rim 34 inches
maximum above the floor and a clearance of 29 inches minimum
from the floor to the bottom of the front edge of the apron.
-- Sec.. 4.20.2.1 Fig. B4.20.3.1
Zai It shall extend 17 inches minimum from the wall. The clear knee
space shall be 8 inches in depth minirnum at 27 inches minimum
above the floor and 11 inches in depth minimum at 9 in minimum
above the floor. The dip of the overflow shall be ignored when
checking the clearances. -- Sec. 4.20.3.1 & Fig. B4.20.3.1
11} A clear floor space of 30 X 48 inches minimum shall be provided
in front of the lavatory and shall extend 19 inches maximum
under the lavatory. -- Sec. 4.0.3.2 & Fig. B4.20,3,2
12} dater supply and drain pipes under lavatories sl--, be
insulated or otherwise treated to protect agaznst contact.
-- sic. 4.20_4
13} The bottom of mirror is required to be within 38 inches of
the floor. -- Sec. 4.16.fi � Fig. 134.20.3.1