DATE: APRIL 9,1999
TO: GUY ROBERTSON
THE PINNACLE GROUP
FAX: 522-7508
FROM: JOE LAIRD
F,EXBURG CITY- ENGR.
FAX: 359-3022
9
TEL
359-3020, Ext. 324
SUBJECT: OCCIDENTAL FINANCIAL FLP (DENTIST OFFICE)
Included herewith is the Rexburg/Madison County Fire Department's
review of the plans for the subject building. Please contact Dee Owens
at 359-3010 19f you have questions regarding their comments.
RE UR(; 14AD 'PARTMZbq
IsON COUNTY FIRE DE
26 North Center
Rexburg, Idaho 83440
(Z4@�
1994 U3rai:Eo Fire Cade
P
�evPlanew
Building Name
Occidental Financial FLS'
.
,� East 1�� North
Building Address ee .
Stories: One
occupancy classificatiQn;
Nevi Construction Floor
1 . Required Fire Flow
0
Comments .
W
Area
Plan Date 03-15 9 9
Review Date: 03-25-99
Type of Csan.structiQn: Not Shawn
l
Existing Floor Area: N/A
2,352
(Appendix III -A):
Based on V ---N construction..t
N -I
2 ) , Water Supply tAr ti.cle 9, Section 903 ) Required : des
lst North & 2�'d East1at. North 3rd East
Fire Hydrant Locatic��.:
Fire Hydrant Flows:
Qkay
Water Supply Acceptable: Yes
Fire Hydrant i,ocatian Acceptable : Yes
(Article 9 Section 9��)
3.,)Fire Apparatus Access Roads
0
Required* Yes
Complete Road Acceptable: No
902. 2 Fire Apparatus Access Roads .
902.2.1 Required access. Fire apparatus access reads shall be
I
��� in ;ic-c-oidance with Sections 901 and 902. 2 for every
t-11
facility, bor portion of a building hereafter constructed
or moved inta -or within the j uri3diction when any portion of the
wall of the fir�� storY Of
facility or any por'�ic�r� of an exterior or
the building is located more than 150 feet (45 720 mm) from fire
appa�atu3 access as measured by an approved route around the
See -2 for
exterior of the building or facility. also section
-MUMS&
DATE-: JULY 20, 1999
TO: GUY ROBERTSON
THE PINNACLE GROUP
FAX: 522-7508
FROM: JOE LAIRD, P.E.
REXBURG CITY ENGINEER &BUILDING OFFICIAL
FAX: 359-3022
TEL. -3-59-3020 Ext. 324
SUBJECT: OCCIDENTAL FINANCIAL FLP (DENTIST OFFICE)
INCLUDED HEREWITH IS INFORMATION
REGARDING THE SUBJECT BUILDING
THAT
NEEDS YOUR IMMEDIATE
ATTENTION.
� ; � wt 1 ;Io 1: aej a v r 4, 111, 1P �A_Jmxlff 117 _1P VIT -Op sty *,.r?
M�
26 North Center
Rexburg, Idaho 83440
(208) 359&.1-3010
1994 Uniform Fire Cade
Plan Review
Building Name Occidental Financial FLP
Building Addresso? East 1st North
L
76
Stories .
Plan Date: 03--&15-099
Review Date: 03-w25-99
One Type of Construction Not shown
occupancy Cla3Sificatian: B
New Construction Floor Area:
Exiting Floor J�rea : N f .A
2,352
1).Requirefl Fire Flow (Appendix ITT -A) 1500,
qpm
Camments;
Based on V --N construction t
2).Water Supply (Article 9, Section 9,03) Required:. Yes
Fire Hydrant Location : 1'5t North & -2 nd East, - 15t 0 North & 3rd East.
Fire Hydrant Flows : Qka�
Water Supply Acceptable : Yes
Fire Hydrant Location Acceptable : Yes
IF
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: Yes
Complete Road Acceptable: No
902,2 Fire Apparatus Access Roads.
902.2.1 Required access. Fire apparatus access roads shall be
provided 'in accordance with Sections 901 and 902. 2 for every
facility, building or portion of a building hereafter constructed
or moved into or within the j ur"sd*ct' 1 1 ion when any portion of the
faci��ty or any portion of an exterior wall of the first story of
the building is located more than 150 feet (45 720 mm) from fire
apparatus access as measured by an approved route around the
exterior of the building or facility. See also Section 902. 3 for
Projections bey
extend beyond:
and the exterior wall shall not
31.4"
rax.
PROJECTIONS
Section 503.2.1
19
1/3 Distance to PL
— Point v+rhere protection
of openings is required
personnel access to buildings.
Plan Review
Page 2
902.2.2 Specifications.
902.2.2.1 Dimensions.,
unobstructed width of
unobstructed vertical
(4 115 mom) .
"ire apparatus access roads shall have an
not less than 20 feet (6-096 mm} and an
clearance of not less than 13 f eet 6 inches
4) Access Rads aid Water Supply, Including Fire Hydrants Are
Requited
To Be Installed And
Made Serviceable
Prior To Ansi During
Time Of
Construction (Article
-9 Section 9U1.3)
t Yes
53.Installation Of Portable Fire Extinguisher (Article 10 Section
1002)
Required: Yes
Location
Acceptable:
Not
shown
Type
Provided Acceptable:
Not shown
0_w�
Comments.a
Min.
2-A la --BC
6 } .Automati� Fire Extinguishing Systems: (Article 10 Section 1003
Required : N
7).S ].
tandpipes (Article 0 Section 1004) Required: No
8 } . Ventilating Hood And. Duct Fire Extinguis-hing System (Article 10
Section 1006.2) Required: N/A
9) Fire Alarm Systems (Article 10
Section 1007)Required, No
10) Other
Corrections That
Are
Required
By
Special Occupancy Or
Conditions:
Medical gas in
the
basement,
haw
much and how installed
Plans
As Submitted
Are
Acceptable; No
Plans
Checked By:
Dee
Owens
Date: 03-25-99
Please furnish comments sack to the plan reviewer in the fallowing
manner: Address fire lane,
ODODODOOODDOO
dire extinguishexs
and medical qas
WHERE ALLOWED COMBUSTIBLE
PROJECTIONS SHALL BE OF ONEmo
HOUR
CONSTRUCTION OR
HEAVY -TIMBER CONSTRUCTION
WHERE OPENINGS ARE NOT PERMITTED OR
PROTECTION OF OPENINGS IS REQUIRED
PROJECTIONS
Section 705
d
ENT. 2 A 6L
March 25,,1999
Mr. Guy Robertson
The Pinnacle Group
1022 LincoEn Rd
Idaho Falls,,, Idaho 83401
4 TV
STATE OF IDAHO
RE: Occidental Financial FLP (Dentist Office on 15{North St.)
'Dear Mr. Robertson;
PO Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e H rexburg@srv.net
?-mai
We have the follovving co=ents,regardm'g the plans for the subject Dental. Office Bul".1ding.:
I --- On the Site Plan the Sanitary sewer is labeled as a waterline.
2 --- There appears to be some problem with the way the curb and gutter and sidewalk ins shown
on the Site Plan. The front ed(ye of the 5 ft. sidewalk is 1 3 ).25 ftbehind the back of the c-Lirb and
Z>
gutter line. The Street Right Of 'Way Line 'is 23 ft. behind the back of the curb and gutter line.
The sidewalk 'Is al I broken. up and needs to be replaced as part of this proj eci. The curb and
gutter is also 'in poor shape. By the time you remove and replace the old, unused existing
driveway and remove and replace the euxb and gutter for the two new driveways you will have
had to remove and replace most of the existing curb and gutter, Attached is one of our standard
drawings covering the installation of new driveways (Attachment 1). These would be
'dered "Commercial Driveways".
consi
3 --- Dimensions of the parking spaces and the widths of the aisleways are not shown on the
plans. There needs to be a detailed drawing of hover the handicapped ramps axe to be
constructed (showing slopes, Widths.. etc-.).
4 --
There needs to be a
guardrail- along the top of the
concrete wall along the stairway coming
from
the basement up to
the sidewalk
near the parking
lot*.. See UBC See. 509 for diniensions,
etc. The stairway also needs a handrail,
See UBC See,, 1006.9 and See, 509.3,
5 - The French Dram* Detail shows water draining away from the French Drain ln.1.1et instead of
towards it,,
All sheets are to stamped and sierned by an Architect or Enginecil registered in the State of
Idaho-,
7 --- Design Values, i.e. snow Load and other roof loads, floor Toad, Wind Speed, Seismic done
and ether such design criteria need is be shown on the plans.
g --- Basement-_-- The area of the basement (2363 sq.ft) divided by the Occupant Load Factor
(for Storage Area this equals 1 occupant per 304 sq. ft of floor areal from UBC Table 1 OA gives
S as thetheoretieal number of occupants for the basement �l i� is used for storage. UBC Sec.
1003. 1.paragraph 5 states that "occupants on stories above the first and 'in basements shad have
access to not less than two separate exits from the dory or basement." The Rexburg Mayor and
City Council added an EXCEPTION $ to thi's Section that reads as follows:
EXCEPT10N 8 --- An occupancy having an Occupmi-ey Group Classification of B-.1,Y:,M.,
or S mai be served by only one exit if the total occupancy load served by that exit does
not exceed 10. The total occupant load shall be calculated using the requirements and
criteria sear forth in Chapters 3 and 10 of this Cede, Smoke detectors Ghali be installed 'in
the, second floor or basement area as required in This Code or as directed by the Building
Offielhal."
EXCEPTION 8 would theref-or require this basement to have only one exit as the Occupant .Load
of 8 'is fess than the occupant load of 10 established as the threshold number in the exception.
Please be aware and make your owner aware that if the use in the basement should ehange to
sameth�.x�g other than "Storage" that 'it would probably be requzred that a second basement exit be
cansfixx-u.cted. EXAMPLE: occupancy =offices at 1 occupant per 100 sq. ft... Basementarea
(23 63 sq. ft.) d ivided by 10 0 sq. ft. peg occupant = 24 occupants which i s greaser than the 10
occupants allowed by EXCEPTION S; t1jerefore 2 exit stairways would be required.
g The basement doorwa37 in the northeast corner of the basement in the 42'-4°' fang wall Will
satisfy the requirements of UBC Sec. 904.2.2 and eliminates the need for a sprinkling systeni in
the basement..
10 ---- UBC Sec. 712 indicates that the ceiling of the basement needs to have enough gypboard
covering to gimme it a 1 -hr. fire rating (i.e. 2 layers of X12" gypboard or i layer of 5/8" gypboard).
The colwmms or walls supporting the ceiling also have to have enough gypboard covering to give
them a I -hr. rating. The basement door "shall be self-closing, tight -fitting, or solid -wood
construction 1 318 inches in thickness or self-closing, ti0bfit-fitting doors acceptable as a pad: of an
assembly havin,g a, fire -protection rating of nat fess than �� minutes".
� 1. --- The south and easy: wails and their eves need to be I hour dire raked. dee Table S --A and
deco 70:) �Projections. Openings (dooAs or windows) in'these two walls have to have a 314 hoax
fire ratinb. (Table 5-A)
Pg -2
IN
IL
12 --- The exterior wall section shown does not appear- to be complete. It lacks some of the �tems
normally found in an ex -tenor walk. section. (See Example I of walk section 'Included herewith)
'Will the exten*or walk section for the nortb and west wally be the sane as that for the easy: and
south walls? Plans also need typical uFaII sections for the interior walls.
1.3 --- Plans need to Shaw details of handrail and guardrail for stairway coning from the
basement into the Treatment Room an the ground floor. See Item 4 above for UBC See..
references.
14 --- Attic. ventilation and attic access opening not shown.
15 --- Engineered truss drawings required. These may be submitted to the City at a later dale but
before they are manufactured and delivered to the j ob site.
16 ---- Exit fight and sign required at front exit.
17 ----- Regarding rest rooms, SBC Sec. 2902.3 states that: "Separate facilities shall be provided
for each sex when the number of employees exceeds faux," Are there going to be more than
four employees at this business ?
'V i J ,
JOSEPH A. LAIRD, P.El,
CITY ENGINEER & BUILDING OFFICIAL
-.3
Y
0
9
The foilovA-ring items must be included an phot plansPriorto City preview:
Street I dentiffli cation
2. Right-of-way locafion and widfiix, curb to curb widtlas and sidewalk location
3. Peftinen� survey infoxxnatzon
4. Building locatioll
5. E,-.qxIsting easements
6. Exisfing utilities (waterlines, sanitary sewer dines, manlioles, stoma drains, dal lines, electrical
facilities, Tx. cable, telephone Iffies, etc.
7. PI-Foposed utilities (including die u1 locatioll to existing- services and proposed -easements)
8. Proposed storm drain and sanitary sewer elevations (for the various pipe inverts at rnariholes
mid catch basins)
9. Stoma drai'nage pian (for areas with parking Tots)
10. Fire hydrants and fire suppression lines (including tie to City lines)
1 1 , Parking (including parking dot elevation points, drainage arrows, dimensions for lot, stalis and
di*stance between rows)
12a Laxidscap'ng stype and �ota1 ��eaa inc�ud�ng dzmensians)
13. Lit layout (including bearing and distanecs)
14. Trash facill'ties (include screening)
15. worth arrow
16. Scale of drawing
17. Proposed street improvements (curb and gutter, sidewalk, pavtm-ient, etc.)
18. Legal descripti"on of proposed building site
0
r
0
Ll
PARKING SPAC E
Accessible parking spaces shall have surface slopes
not steeper than 1:48 (1 unit vertical in 46 units
horizontal (2% slop -e)) in all directions.
36 min
915 mm
ACCESSIBLE ROUTE
KM
1525
CGESS
ISLE
Van spaces shall have a height inches of 98 (2745 mm}
minimum at the space.
RVIA
19�
13
y
RUNNING �
SLOPE 1:20 i
(1 unit vertical in �
20 units horizontal �
(5% slope)) max �
+�.'ri�": :i...'..Y+*+: it :'.:�'� a+.ti . ra•��.r
1 Y'F'i
1�
RUNNING SLOPE i
1:12 (1 unit vertical in �
12 units horizontal i
(8.3% slope))max
Pi�Y•fi'a, card. r iw�� i t. ."+ • +a.-�Y+ Y rf ria�i +.� Y .. �.�
it f r •r Y� iYr�irf+ �'i�+ �+ t j"* " retiy.'F r' " �.+�f +F c + .ice.
+t "f •i ~�r �'..����i'1.rY� �w ::t'+ i Y'r��� � y..+ � rau"Y• `� Y"Y•� ti�e',L��� �fs�Yi.-y R�- �yti a�
r��"f t:"k t �� �����r!,i�..i4F i r ,"'� ++r ■� i�Y� is � 6 jai. Fr�'a'i i�Y +���4 � k F Y�F� Y a. � r � �1
4- +• :Y.• T R17�i FiF. Y. i. spa i �y"•
CURB RAMP
NOTE:
{1} Slope = y./x, where x 3s a level plane-
(2)
Counterslope shall not exceed 1:20.
�1 unit vertical in 20 units horizontal (50/. slope))
Y
COUNTERSLOPE
1:20 (1 unit vertical in
20 units horizontal
(5% slope)) max
i
1+ -
STREET
N OT Em: If x c 48 in. (122 0 mm). ther� tng slope of the
fared sides shad not exceed 1-:12. (1 unfl erertica� in
2 units horizontal (8.3% slope))
43
am
SIDE
do
ri
HANDRA. IL EXTEN-SIONS
12min
3305 mm
T
iF
1
12 min
305 mm
F 4 -
. . . . . . .
ii°'• •iJr ``! i•Rti '• T • i;34�"i= a h
i'i#-�, + a may" :T.`tiizt .'a•'. "R': e . .. _ _. : "
F e '+'4'•Td` - ! ur+"}dt k'. r B'i' r ►'� _
alp+ :d'R .., �R,rl4 ._ •'T ysti,ta Y'a'Y+"r"°Y1.o1+ ,Y'd iR,
f #a r� sfia rT7{s++� � s+R 7'r r !�R F • 41�j • . F •_p• h.y-..
+�•; �•�`r�•{+'a}{}4�i'Y'F {$a'4i .'Y-. i`" fit`, -
! S
Rsi Y} r +�' -•4 Y TFT + F_ • a• b s�,+4 +•`� � It+tee +'.
Th •i '.F " . ... . R°4' +
�'a"�'4'= .....+..`ad.Fa�"+'R'.'i'P ..'f°+ _ ... +'t�•'i'- .
(a)
Elevation
F f. •"�... +ice* � R, ,+yli � s.E+ + y`� .�'ti {.'tl.:i { `.®at�+',4t_{ f _ .. F F w F
+ Y J_i�i i i+ �e+i' a�T i •'i i Y a�°�i a `a { • i+psi _ - jl+P
12 min
305 mm
(b) Plan
� u p
+'+
_ m'i'F • •u •'a _
1'+' •�!'T� �{� {` • X4'4 Y'{
i��•a}ate L',
12min
(a) Efevati"on
(b) Plan
(a) Elevation
(b) Plan
a
X
2 min
� mrn
(a) Elevation
(b) Plan
4LF�F4};i
12 min
305 mm
11
R.
P
1 2 max
7-9
ILITy
ACCESSIBILIT .,A
Co
12 min
3C)5mm
w_MF__l
IN,
i 1� 13os MM
* Where space permits, extend grab tsar on transfer side.
36 max
91 5 MM
TOILET. PAPER
DISPENSER
95,
li
X
E
E
E
E
CD
M
V)
C%Q
I
Cn
CO
Co
Cn
TOILET. PAPER
DISPENSER
95,
li
X
v
i OA
as
rn
.41
13
z
qo
W1
M,
J�
C
r
`
v
i OA
as
rn
.41
13
z
qo
W1
M,
J�
C
r
G. M. ROBERT SON & A
Guy M Robertson - owner
5550 Solitude L
Idaho FaNs, Idaho $34Q6
(208) 522-7374 Office
Quv&)dsif.com
.doe Laird
City Engineer
City of Rexburg
IZ North Center Street
Rexburg Idaho 83440
RE: accidental financial FLP (Dentist Office on I s` North St.)
Dear Mr. ::
The following is a point by point r esponse to your letter dated March 25, 1999.
I --- Corrected. See sheet SDI
--- Corrected. See sheet SDI
3 --- Corrected. See sheet SDI
4 --- Corrected. See North & East elevations sheet A4, Stair Detail sheet Al
5 --- Corrected. See sheet SY71
-_- Corrected.
7 --- Corrected. dee sheet A3
8 --- I have discussed the egress situation with the owner of the property. Apparently, there is quite a lot of
star -age required for this type of business. He ready his no intention of using the basement for any
other purpose.
10 --- Corrected. Seg General Notes sheet A I
I I --- Corrected. See General Notes sheet A2,
12 --- Corrected. See Details sheet A2
13 --- Corrected. See Interior handrail detail Sheet a5. The guardrail for the stairwell leading to the-
basement
he
basement is actually a. 42" hig11 half wall. Thee is a note on Sheet A2 indicating the half wall.
14. --- Corrected. See. sheet