HomeMy WebLinkAboutREVIEWS & DOCS - 99-00013 - Occidental Financial - Dental OfficeL3 DATE: APRIL 9,1999 TO: GUY ROBERTSON THE PINNACLE GROUP FAX: 522-7508 FROM: JOE LAIRD F,EXBURG CITY- ENGR. FAX: 359-3022 9 TEL 359-3020, Ext. 324 SUBJECT: OCCIDENTAL FINANCIAL FLP (DENTIST OFFICE) Included herewith is the Rexburg/Madison County Fire Department's review of the plans for the subject building. Please contact Dee Owens at 359-3010 19f you have questions regarding their comments. RE UR(; 14AD 'PARTMZbq IsON COUNTY FIRE DE 26 North Center Rexburg, Idaho 83440 (Z4@� 1994 U3rai:Eo Fire Cade P �evPlanew Building Name Occidental Financial FLS' . ,� East 1�� North Building Address ee . Stories: One occupancy classificatiQn; Nevi Construction Floor 1 . Required Fire Flow 0 Comments . W Area Plan Date 03-15 9 9 Review Date: 03-25-99 Type of Csan.structiQn: Not Shawn l Existing Floor Area: N/A 2,352 (Appendix III -A): Based on V ---N construction..t N -I 2 ) , Water Supply tAr ti.cle 9, Section 903 ) Required : des lst North & 2�'d East1at. North 3rd East Fire Hydrant Locatic��.: Fire Hydrant Flows: Qkay Water Supply Acceptable: Yes Fire Hydrant i,ocatian Acceptable : Yes (Article 9 Section 9��) 3.,)Fire Apparatus Access Roads 0 Required* Yes Complete Road Acceptable: No 902. 2 Fire Apparatus Access Roads . 902.2.1 Required access. Fire apparatus access reads shall be I ��� in ;ic-c-oidance with Sections 901 and 902. 2 for every t-11 facility, bor portion of a building hereafter constructed or moved inta -or within the j uri3diction when any portion of the wall of the fir�� storY Of facility or any por'�ic�r� of an exterior or the building is located more than 150 feet (45 720 mm) from fire appa�atu3 access as measured by an approved route around the See -2 for exterior of the building or facility. also section -MUMS& DATE-: JULY 20, 1999 TO: GUY ROBERTSON THE PINNACLE GROUP FAX: 522-7508 FROM: JOE LAIRD, P.E. REXBURG CITY ENGINEER &BUILDING OFFICIAL FAX: 359-3022 TEL. -3-59-3020 Ext. 324 SUBJECT: OCCIDENTAL FINANCIAL FLP (DENTIST OFFICE) INCLUDED HEREWITH IS INFORMATION REGARDING THE SUBJECT BUILDING THAT NEEDS YOUR IMMEDIATE ATTENTION. � ; � wt 1 ;Io 1: aej a v r 4, 111, 1P �A_Jmxlff 117 _1P VIT -Op sty *,.r? M� 26 North Center Rexburg, Idaho 83440 (208) 359&.1-3010 1994 Uniform Fire Cade Plan Review Building Name Occidental Financial FLP Building Addresso? East 1st North L 76 Stories . Plan Date: 03--&15-099 Review Date: 03-w25-99 One Type of Construction Not shown occupancy Cla3Sificatian: B New Construction Floor Area: Exiting Floor J�rea : N f .A 2,352 1).Requirefl Fire Flow (Appendix ITT -A) 1500, qpm Camments; Based on V --N construction t 2).Water Supply (Article 9, Section 9,03) Required:. Yes Fire Hydrant Location : 1'5t North & -2 nd East, - 15t 0 North & 3rd East. Fire Hydrant Flows : Qka� Water Supply Acceptable : Yes Fire Hydrant Location Acceptable : Yes IF 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: Yes Complete Road Acceptable: No 902,2 Fire Apparatus Access Roads. 902.2.1 Required access. Fire apparatus access roads shall be provided 'in accordance with Sections 901 and 902. 2 for every facility, building or portion of a building hereafter constructed or moved into or within the j ur"sd*ct' 1 1 ion when any portion of the faci��ty or any portion of an exterior wall of the first story of the building is located more than 150 feet (45 720 mm) from fire apparatus access as measured by an approved route around the exterior of the building or facility. See also Section 902. 3 for Projections bey extend beyond: and the exterior wall shall not 31.4" rax. PROJECTIONS Section 503.2.1 19 1/3 Distance to PL — Point v+rhere protection of openings is required personnel access to buildings. Plan Review Page 2 902.2.2 Specifications. 902.2.2.1 Dimensions., unobstructed width of unobstructed vertical (4 115 mom) . "ire apparatus access roads shall have an not less than 20 feet (6-096 mm} and an clearance of not less than 13 f eet 6 inches 4) Access Rads aid Water Supply, Including Fire Hydrants Are Requited To Be Installed And Made Serviceable Prior To Ansi During Time Of Construction (Article -9 Section 9U1.3) t Yes 53.Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: Yes Location Acceptable: Not shown Type Provided Acceptable: Not shown 0_w� Comments.a Min. 2-A la --BC 6 } .Automati� Fire Extinguishing Systems: (Article 10 Section 1003 Required : N 7).S ]. tandpipes (Article 0 Section 1004) Required: No 8 } . Ventilating Hood And. Duct Fire Extinguis-hing System (Article 10 Section 1006.2) Required: N/A 9) Fire Alarm Systems (Article 10 Section 1007)Required, No 10) Other Corrections That Are Required By Special Occupancy Or Conditions: Medical gas in the basement, haw much and how installed Plans As Submitted Are Acceptable; No Plans Checked By: Dee Owens Date: 03-25-99 Please furnish comments sack to the plan reviewer in the fallowing manner: Address fire lane, ODODODOOODDOO dire extinguishexs and medical qas WHERE ALLOWED COMBUSTIBLE PROJECTIONS SHALL BE OF ONEmo HOUR CONSTRUCTION OR HEAVY -TIMBER CONSTRUCTION WHERE OPENINGS ARE NOT PERMITTED OR PROTECTION OF OPENINGS IS REQUIRED PROJECTIONS Section 705 d ENT. 2 A 6L March 25,,1999 Mr. Guy Robertson The Pinnacle Group 1022 LincoEn Rd Idaho Falls,,, Idaho 83401 4 TV STATE OF IDAHO RE: Occidental Financial FLP (Dentist Office on 15{North St.) 'Dear Mr. Robertson; PO Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e H rexburg@srv.net ?-mai We have the follovving co=ents,regardm'g the plans for the subject Dental. Office Bul".1ding.: I --- On the Site Plan the Sanitary sewer is labeled as a waterline. 2 --- There appears to be some problem with the way the curb and gutter and sidewalk ins shown on the Site Plan. The front ed(ye of the 5 ft. sidewalk is 1 3 ).25 ftbehind the back of the c-Lirb and Z> gutter line. The Street Right Of 'Way Line 'is 23 ft. behind the back of the curb and gutter line. The sidewalk 'Is al I broken. up and needs to be replaced as part of this proj eci. The curb and gutter is also 'in poor shape. By the time you remove and replace the old, unused existing driveway and remove and replace the euxb and gutter for the two new driveways you will have had to remove and replace most of the existing curb and gutter, Attached is one of our standard drawings covering the installation of new driveways (Attachment 1). These would be 'dered "Commercial Driveways". consi 3 --- Dimensions of the parking spaces and the widths of the aisleways are not shown on the plans. There needs to be a detailed drawing of hover the handicapped ramps axe to be constructed (showing slopes, Widths.. etc-.). 4 -- There needs to be a guardrail- along the top of the concrete wall along the stairway coming from the basement up to the sidewalk near the parking lot*.. See UBC See. 509 for diniensions, etc. The stairway also needs a handrail, See UBC See,, 1006.9 and See, 509.3, 5 ­- The French Dram* Detail shows water draining away from the French Drain ln.1.1et instead of towards it,, All sheets are to stamped and sierned by an Architect or Enginecil registered in the State of Idaho-, 7 --- Design Values, i.e. snow Load and other roof loads, floor Toad, Wind Speed, Seismic done and ether such design criteria need is be shown on the plans. g --- Basement-_-- The area of the basement (2363 sq.ft) divided by the Occupant Load Factor (for Storage Area this equals 1 occupant per 304 sq. ft of floor areal from UBC Table 1 OA gives S as thetheoretieal number of occupants for the basement �l i� is used for storage. UBC Sec. 1003. 1.paragraph 5 states that "occupants on stories above the first and 'in basements shad have access to not less than two separate exits from the dory or basement." The Rexburg Mayor and City Council added an EXCEPTION $ to thi's Section that reads as follows: EXCEPT10N 8 --- An occupancy having an Occupmi-ey Group Classification of B-.1,Y:,M., or S mai be served by only one exit if the total occupancy load served by that exit does not exceed 10. The total occupant load shall be calculated using the requirements and criteria sear forth in Chapters 3 and 10 of this Cede, Smoke detectors Ghali be installed 'in the, second floor or basement area as required in This Code or as directed by the Building Offielhal." EXCEPTION 8 would theref-or require this basement to have only one exit as the Occupant .Load of 8 'is fess than the occupant load of 10 established as the threshold number in the exception. Please be aware and make your owner aware that if the use in the basement should ehange to sameth�.x�g other than "Storage" that 'it would probably be requzred that a second basement exit be cansfixx-u.cted. EXAMPLE: occupancy =offices at 1 occupant per 100 sq. ft... Basementarea (23 63 sq. ft.) d ivided by 10 0 sq. ft. peg occupant = 24 occupants which i s greaser than the 10 occupants allowed by EXCEPTION S; t1jerefore 2 exit stairways would be required. g The basement doorwa37 in the northeast corner of the basement in the 42'-4°' fang wall Will satisfy the requirements of UBC Sec. 904.2.2 and eliminates the need for a sprinkling systeni in the basement.. 10 ---- UBC Sec. 712 indicates that the ceiling of the basement needs to have enough gypboard covering to gimme it a 1 -hr. fire rating (i.e. 2 layers of X12" gypboard or i layer of 5/8" gypboard). The colwmms or walls supporting the ceiling also have to have enough gypboard covering to give them a I -hr. rating. The basement door "shall be self-closing, tight -fitting, or solid -wood construction 1 318 inches in thickness or self-closing, ti0bfit-fitting doors acceptable as a pad: of an assembly havin,g a, fire -protection rating of nat fess than �� minutes". � 1. --- The south and easy: wails and their eves need to be I hour dire raked. dee Table S --A and deco 70:) �Projections. Openings (dooAs or windows) in'these two walls have to have a 314 hoax fire ratinb. (Table 5-A) Pg -2 IN IL 12 --- The exterior wall section shown does not appear- to be complete. It lacks some of the �tems normally found in an ex -tenor walk. section. (See Example I of walk section 'Included herewith) 'Will the exten*or walk section for the nortb and west wally be the sane as that for the easy: and south walls? Plans also need typical uFaII sections for the interior walls. 1.3 --- Plans need to Shaw details of handrail and guardrail for stairway coning from the basement into the Treatment Room an the ground floor. See Item 4 above for UBC See.. references. 14 --- Attic. ventilation and attic access opening not shown. 15 --- Engineered truss drawings required. These may be submitted to the City at a later dale but before they are manufactured and delivered to the j ob site. 16 ---- Exit fight and sign required at front exit. 17 ----- Regarding rest rooms, SBC Sec. 2902.3 states that: "Separate facilities shall be provided for each sex when the number of employees exceeds faux," Are there going to be more than four employees at this business ? 'V i J , JOSEPH A. LAIRD, P.El, CITY ENGINEER & BUILDING OFFICIAL -.3 Y 0 9 The foilovA-ring items must be included an phot plansPriorto City preview: Street I dentiffli cation 2. Right-of-way locafion and widfiix, curb to curb widtlas and sidewalk location 3. Peftinen� survey infoxxnatzon 4. Building locatioll 5. E,-.qxIsting easements 6. Exisfing utilities (waterlines, sanitary sewer dines, manlioles, stoma drains, dal lines, electrical facilities, Tx. cable, telephone Iffies, etc. 7. PI-Foposed utilities (including die u1 locatioll to existing- services and proposed -easements) 8. Proposed storm drain and sanitary sewer elevations (for the various pipe inverts at rnariholes mid catch basins) 9. Stoma drai'nage pian (for areas with parking Tots) 10. Fire hydrants and fire suppression lines (including tie to City lines) 1 1 , Parking (including parking dot elevation points, drainage arrows, dimensions for lot, stalis and di*stance between rows) 12a Laxidscap'ng stype and �ota1 ��eaa inc�ud�ng dzmensians) 13. Lit layout (including bearing and distanecs) 14. Trash facill'ties (include screening) 15. worth arrow 16. Scale of drawing 17. Proposed street improvements (curb and gutter, sidewalk, pavtm-ient, etc.) 18. Legal descripti"on of proposed building site 0 r 0 Ll PARKING SPAC E Accessible parking spaces shall have surface slopes not steeper than 1:48 (1 unit vertical in 46 units horizontal (2% slop -e)) in all directions. 36 min 915 mm ACCESSIBLE ROUTE KM 1525 CGESS ISLE Van spaces shall have a height inches of 98 (2745 mm} minimum at the space. RVIA 19� 13 y RUNNING � SLOPE 1:20 i (1 unit vertical in � 20 units horizontal � (5% slope)) max � +�.'ri�": :i...'..Y+*+: it :'.:�'� a+.ti . ra•��.r 1 Y'F'i 1� RUNNING SLOPE i 1:12 (1 unit vertical in � 12 units horizontal i (8.3% slope))max Pi�Y•fi'a, card. r iw�� i t. ."+ • +a.-�Y+ Y rf ria�i +.� Y .. �.� it f r •r Y� iYr�irf+ �'i�+ �+ t j"* " retiy.'F r' " �.+�f +F c + .ice. +t "f •i ~�r �'..����i'1.rY� �w ::t'+ i Y'r��� � y..+ � rau"Y• `� Y"Y•� ti�e',L��� �fs�Yi.-y R�- �yti a� r��"f t:"k t �� �����r!,i�..i4F i r ,"'� ++r ■� i�Y� is � 6 jai. Fr�'a'i i�Y +���4 � k F Y�F� Y a. � r � �1 4- +• :Y.• T R17�i FiF. Y. i. spa i �y"• CURB RAMP NOTE: {1} Slope = y./x, where x 3s a level plane- (2) Counterslope shall not exceed 1:20. �1 unit vertical in 20 units horizontal (50/. slope)) Y COUNTERSLOPE 1:20 (1 unit vertical in 20 units horizontal (5% slope)) max i 1+ - STREET N OT Em: If x c 48 in. (122 0 mm). ther� tng slope of the fared sides shad not exceed 1-:12. (1 unfl erertica� in 2 units horizontal (8.3% slope)) 43 am SIDE do ri HANDRA. IL EXTEN-SIONS 12min 3305 mm T iF 1 12 min 305 mm F 4 - . . . . . . . ii°'• •iJr ``! i•Rti '• T • i;34�"i= a h i'i#-�, + a may" :T.`tiizt .'a•'. "R': e . .. _ _. : " F e '+'4'•Td` - ! ur+"}dt k'. r B'i' r ►'� _ alp+ :d'R .., �R,rl4 ._ •'T ysti,ta Y'a'Y+"r"°Y1.o1+ ,Y'd iR, f #a r� sfia rT7{s++� � s+R 7'r r !�R F • 41�j • . F •_p• h.y-.. +�•; �•�`r�•{+'a}{}4�i'Y'F {$a'4i .'Y-. i`" fit`, - ! S Rsi Y} r +�' -•4 Y TFT + F_ • a• b s�,+4 +•`� � It+tee +'. Th •i '.F " . ... . R°4' + �'a"�'4'= .....+..`ad.Fa�"+'R'.'i'P ..'f°+ _ ... +'t�•'i'- . (a) Elevation F f. •"�... +ice* � R, ,+yli � s.E+ + y`� .�'ti {.'tl.:i { `.®at�+',4t_{ f _ .. F F w F + Y J_i�i i i+ �e+i' a�T i •'i i Y a�°�i a `a { • i+psi _ - jl+P 12 min 305 mm (b) Plan � u p +'+ _ m'i'F • •u •'a _ 1'+' •�!'T� �{� {` • X4'4 Y'{ i��•a}ate L', 12min (a) Efevati"on (b) Plan (a) Elevation (b) Plan a X 2 min � mrn (a) Elevation (b) Plan 4LF�F4};i 12 min 305 mm 11 R. P 1 2 max 7-9 ILITy ACCESSIBILIT .,A Co 12 min 3C)5mm w_MF__l IN, i 1� 13os MM * Where space permits, extend grab tsar on transfer side. 36 max 91 5 MM TOILET. PAPER DISPENSER 95, li X E E E E CD M V) C%Q I Cn CO Co Cn TOILET. PAPER DISPENSER 95, li X v i OA as rn .41 13 z qo W1 M, J� C r ` v i OA as rn .41 13 z qo W1 M, J� C r G. M. ROBERT SON & A Guy M Robertson - owner 5550 Solitude L Idaho FaNs, Idaho $34Q6 (208) 522-7374 Office Quv&)dsif.com .doe Laird City Engineer City of Rexburg IZ North Center Street Rexburg Idaho 83440 RE: accidental financial FLP (Dentist Office on I s` North St.) Dear Mr. :: The following is a point by point r esponse to your letter dated March 25, 1999. I --- Corrected. See sheet SDI --- Corrected. See sheet SDI 3 --- Corrected. See sheet SDI 4 --- Corrected. See North & East elevations sheet A4, Stair Detail sheet Al 5 --- Corrected. See sheet SY71 -_- Corrected. 7 --- Corrected. dee sheet A3 8 --- I have discussed the egress situation with the owner of the property. Apparently, there is quite a lot of star -age required for this type of business. He ready his no intention of using the basement for any other purpose. 10 --- Corrected. Seg General Notes sheet A I I I --- Corrected. See General Notes sheet A2, 12 --- Corrected. See Details sheet A2 13 --- Corrected. See Interior handrail detail Sheet a5. The guardrail for the stairwell leading to the- basement he basement is actually a. 42" hig11 half wall. Thee is a note on Sheet A2 indicating the half wall. 14. --- Corrected. See. sheet