HomeMy WebLinkAboutPLAN ANALYSIS NORTHEAST ADDITION - 99-00010 - Upper Valley Industries - AdditionProject Project Address: City of Rexburg Building Department 12 North Center Street / P.O. Rexburg, Idaho 83440 (2 0 8) 3 5 9- 3 02 4 Box 280 Plan analysis based on the 1994 Uniform Building Cade Number : DevWk#2 Name : Deveopment TnTkshop 15 Forth end East Occupancy: F1, B, S1 Construction: iI-N Date: March 19, 1999 Northeast Addition NOTE-. The Code itpus 1 ; qfiPr� -;n complete It is a 4 1 Contractor Architect: Engineer Report By: report are not iiscing o� a1i possible code requirements guide to selected sections of the code. Report created using Flan Analyst software by b w L Portions of the material contained in this program from the Uniform Building Code with the permission International Conference of Building afficials. DIRECTIC]N BOUNDARY NORTH Property line BAST Property line SOUTH Separation wall WES'T' Separation wall Allowable area increase --- Sec. 505.1 SEPARATION AREA INCREASE 65.0 120.0 0.0 Feet 0.0 Feet 50.% for - Feet Feet I ntended to in the 1994 be a UBC. a. (719) 599-5622 are reproduced of the FIRE PRQTECTIflN 65.0 120.0 Feet Feet U.0 Feet 0.0 Feet open area on 2 sides . Code review Project Td.: Address: 15 for: Deveopment TvJkshap North end East I= Northeast Addition # a FL NAME OCC MAX FLR AREA ALLOWED RATIO STATUS ---------- — — — —---------- — ---- ------- ---------------------- 2 Of f icy TOTAL FOR FLUOR M Me 1 Woodworking Area F1 ok 1 Storage/Stock Room S1 ok TOTAL FOR FLOOR BUILDING '7'C7TAL 264 0.15 0.38 0.26 264 423 18000 264 18000 687 951 18000 0.15 0.38 0.26 18000 18000 18000 18000 -96000 0.15 0.15 0.24 0.15 0.38 0.26 The actual height of this building is 28. feet. The maximum height of the building is 55. feet. -- Table 5-B EX'z'ERI4R 1r�1ALL FIRE RATIIITGS AND OPENING PRQTEC'I'TC3N WIP-1-701a 0 reffilk we, For Bearing Nam -Bearing Occupancy Wall Wall F 1 0 hour 0 hour B 0 hour 0 hour SZ 0 hour 0 hour EAST For Bearing Non -Bearing Occupancy Wall mall F1 0 hour 0 hour B 0 hour 0 hour Si 0 hour 0 dour SOUTH Opening Protection Nene None None Opening Protection None None None: Construction Material Non -Comb Non -Comb Non -Comb Construction Material Nora -Comb Non -Comb Nan -Comb Parapet Required No No No Parapet Required No No No ok ok ok ok ok ok AREA SEPARATION WALL - See requirements listed later in this report. WEST AREA SEPARATION WALL - See requirements listed later in this report. None 3 I4 hour - - No fire projection - Openings are to be 50% of the area of requirements for open11 ings. protected with 3/4 hr fire the wall maximum. -- Table assemblies. 5 -At Code review Project Ick, . Address: 15 Not Allowed ELEMENT for Page # 3 Deveopment Wkshop Northeast Addition North 2nd East Footnote Maximum greater -- openings Interior Bearing Interior nonhrg Structural Frame Exterior Strutt Shaft Enclosure 11 5 & Sec, 5Q3.2,2 single window size is than 12 feet. -- Sec. are not permitted in OTHER BUDDING ELEMENTS wall wall Frame Floor/Ceiling Assembly Roof /Ceiling Assembly Stairs MATERIAL Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible Noncombustible 84 sq. ft. 713.8 this wali. Table 6-A RATING o hr 0 hr 0 hr 0 hr 1 hr 0 hr 0 hr with no TES See Footnote See footnote NOTE: See Section 711 for shaft enclosure exceptions. FOOTNOTES dimension MMI PON � } Elements in an exterior wall located where openings are not permitted or where protection of openings is required, shad be protected against external fire exposure as required for exterior bearing walls or the structural frame, whichever is greater. -- Table 6-A, footnote 5 } Nonloa.d-bearing walls within a tenant space that are not part of a 1 hr. corridor may he of a} Noncombustible (nonrated) material, b} Fire retardant- treated. wood c) One-hour construction (any material ) OCCUPANCY SEPARATI0NS -- Table 3-B Ohr Ohr Ohr Sec, 601. 5. 2.1 1 Code review Project Id.: Address: 15 for; Deveopment Wkshop North 2nd East HEATING EQUIPMENT SEPARATION: FOR F I OCCUPANCY: A 1 hr. bailer --- Sec . occupancy or central 3D2.5 FOR B OCCUPANCY0 A 1 hr. boiler -- pec. FOR S1 A 1 hr. boiler -- Sec. occupancy or Central 302.5 OCCUPANCY4P occupancy or central 302.5 separa ti on is heating unit separation is heating unit separation is heating unit ADDITIONAL SEPARATIONS: North-east Addition required around roams containing a greater than 400,000 BTU input. required around rooms containing a greater than 400,000 BTU input. required around rooms containing a greater than 400,000 BTU input., A refrigeration machinery room shall b of the bu 10 1ding as required for an H7 horizontal occupancy separation may be area of the machinery roam. Structural protected for the type of construction A 1 hour separation is required from a FOR F1 OCCUPANCY: Woodworking areas with a floor separated from other areas by -- Table 3-B, footnote #6 e separated from the remainder occupancy regardless of area. A limited to the actual floor supporting elements shall be only. -- Sec. 28Q2 n. F1 occupancy. area greater than one haus occupancy 2,500 Sq.ft. must be separation construction. EDIT REQUTREMENTS: FL NAMENUN�B Mid MIN PANIC RATED DOOR NOTES C CC EXITS TnTID'z'H HDWR Ct7RRIDrJR ,SWING 2 Of f ice 26 1 0.4 No No NIR. 9 TOTAL 26 2 0.7 No No N/R 1 1 Woodworking Area 21 1 0.4 Na No NIR 1 Storage/Stack Room 9 1 0.2 No No N/R TOTAL 30 2 0.5 Na des NIR Code review Project Id. 15 for: Deveopment Wkshop North 2nd East Page Northeast Addition # 5 Rated Corridors are to have 1 hr, fire protection on both sides of walls and ceiling. -- Sec. 1005.7 Door openings are required to be protected 3 with 2 0 minute assemblies, -- Sec. 1D05.8.1 Window openings are required to be protected with labeled 3I4 hour assemblies. -- Sec, 1005.8,2 Elevators opening into a rued corridor shall be provided with an elevator lobby at each floor containing a rate. corridor. -- Sec. 1005.10 Walls and openings between the corridor and the elevator lobby are required to be per sections 1045.7 and 1005.8 above. In areas where 2 exits are required, the minimum separation is 112 0f the maximum diagonal of the area or floor, -- pec, 1003.3 When 2 to go except exits are in either f or dead required, exits must be arranged so that direction from any point in, a corridor to ends not exceeding 20 feet in length.. --- Emit signs are required from all areas where 2 or --- Sec. 1013.1 it is possible a separate emit, Sec. 1005.5 exits are required. Main exterior exit doors which obviously and clearly as exits need not be signed when approved. -- exp. 1 Door serving is based on Sec. 1Q04.2 except as noted. Occupant load factor is based on Table 1Q -A. Z) S uabt-Du U11 ".L'aD1e 1u --x except as Hated. Exit width is in feet and based on Sec. 1003.2. identifiable �,� �k, �,� U.� V �U�u a.Pprox�rr�aLely squally among exits. Width shown for all areas is }used on other exits. (Q,2) Width shown for 1st floor is based on other exits. (a. 2) Width shown for other floors & basements is based on stairways. For the minimum width of doors, see Sec. 10a4. 5 For the minimum width of corridors, see Sec. 1005.2 For the minimum width of stairways, see Sec, 1006.2 (0.3) B Cade review Project Id.: Address 15 FOOTNOTES: far: Deveopment Wkshop North 2nd fast Page Northeast Addition Ulme l� The second float is required to h1 c! i n r-, '__Vave 2 exits when the o�c�.pant load - — - u11 �U ��,t�Ed ��U sprin.►�ler system and an automatic smoke-d�tectinn system is installed within the corridor, and actuation of any detector shall activate alarms is all areas served by the corridor, the corridor need not be rated if the occupant load is less than 1a0. -- Sec. 1005.7 exc. 5 FLUSH AND SURFACE BELTS Manually operated edge or surface -mounted flush bolts and bolts are prohibited. When automatic flush bolts are used, leaf having the automatic flush bolt shall not have a door surface -mounted hardware. The unlatching of any leaf shall require more than one operation, -._ Sec 1004.3 LACKS AND LATCHES; Ail means of earesc,- frim which knowledge Key -locking consists of egress i� r effort. hardware a single doers shall be readily to be made without the -- Sec. 10D4.3 operable use of a may _L ILLU_I_t'�q bec. luu'�.l door or pair exc. 9} If this entire sfin�-�f 1-,�C _----- -, - — - u11 �U ��,t�Ed ��U sprin.►�ler system and an automatic smoke-d�tectinn system is installed within the corridor, and actuation of any detector shall activate alarms is all areas served by the corridor, the corridor need not be rated if the occupant load is less than 1a0. -- Sec. 1005.7 exc. 5 FLUSH AND SURFACE BELTS Manually operated edge or surface -mounted flush bolts and bolts are prohibited. When automatic flush bolts are used, leaf having the automatic flush bolt shall not have a door surface -mounted hardware. The unlatching of any leaf shall require more than one operation, -._ Sec 1004.3 LACKS AND LATCHES; Ail means of earesc,- frim which knowledge Key -locking consists of egress i� r effort. hardware a single doers shall be readily to be made without the -- Sec. 10D4.3 operable use of a may be used an the main door or pair of doors if surface the door knob or not from the side key or special exit when the main exit THIS DOOR MUST REMAIN UNLOCKED DUPING SUSI�rTESS�HUURS1��a sign stating rt1�.�t ��„�l�g �,,l�t�iQut operation of any latching device��l����d door (s) , enc. LANDINGS AT noaRs: 1} A floor or landing shall be provided on each side of doors.. When access for persons with disabilities is required. the floor or landing shall not be more than 1/z inch lower than the threshold.. When access is not require., the maximum is I inch. -- Sec. 10Q4.9 2) Landings shall have a width not less than the width of the stairway or width of the doorway, whichever is the greater. The minimum length in the direction of exit travel is 44 inches. -- Sec. 1(]Q4.10 TRAVEL, DISTANCE: The maximum travel distance in this building is lSa feet_ -- Sec_ 1003.4 Codi review Project Id,: Address; 15 for; Deveopment Wkshop North 2nd Eases Northeast Addition BUILDTNG ACCESSIBILITY: 1} This building including each tenant one entrance which comm i Ps w i t --h t-}-,� 2) r -M shall be nrnvi c]c�rl CA.BO/ANSI A117.1. At least 50 percent accessible. -- Sec. 1103.2.3 accessible route of all entrances with at least provisions of shall be wnen more tnat one exit is required from any accessible spice, each accessible portion of the space shall be served by not leis than two accessible means of egress. -- Sec. 11Q4.1.1 3 } when an exit stairway is part of an accessible means of egress, the stairway shah have a clear width of not less than 48 inches between the handrails. The stairway shall either incorporate an area of refuge within an enlarged story -level handing or shall be accessed from an area of refuge, -- Sec. 1104.1.Z The area of refuge shall have direct access to the stairway that serves it. -- Sem, 1104.2.1 4 } Each area of refuge shall be sized to accommodate one wheelchair space not less than 30 inches by 48 inches for each 200 occupants, or portion thereof. -- Seg. 11x4.2.3 5} If the area of refuges is not within the stairway, it shall be separated from the rest of the story by a smoke barrier having at least a one- hour fire -resistance rating. Smoke barriers small extend to the roof or floor deck above. Doors shall be smoke and draft control assemblies with a rating not less than 20 minutes. -- Sec. 1104.2,4 6) Two-way communications are required. -- Sec. 1104.x.5 7} Each area must be identified by a sigma stating AREA OF REFUGE and the international symbol of accessibility. S} NOTE: Exit stairways in buildings protected throughout by an approved automatic sprinkler system are NOT required to incorporate an, area of refuge. -T Sec. 1104,1.2 exception 42 ROOF'ING REQUIREMENTS 1} The roofing on this building is required to be Class B or better. -- Table 15-A 2) See section 1504 and ICSO research reports for requirements. Code review Project Id.. . Address: 15 AUTOMATIC for: Deveopment Wkshop North end East SPRINKLER SYSTEMS: If openings are not is floor area more sprinkler system is minimum .ire i n open-ing in every 50 Northeast Addition provided in each 50 feed of exterior walk or there than 75 feet from an exterior opening, an automatic required. -- Seg. 904.x.2 Note: openings shall have of 30 inches, There must be at least 20 sq.ft. of lineal feet of wall. An automatic sprinkler system is required in woodworking areas when the floor area greater than 2,50a sq.ft. -- Sem. 3Q6.8 STANDPIPE REQUIREMEN'T'S There is no requirement FOOTNOTES: for a standpipe. VENTILATIQN All areas customarily occupied by humans ventilation by means of operable exterior less than 1/20 of the total floor mechanically operated ventilation of supplying a minimum of 15 cubic occupant, -- - Sec. 1202.2,.1 area or system, -- Table 9-A shall be provided with natural openings with an area of not shall be provided with a Such system shall be capable zeez per minute of outside air per WALL AND CEILING FINISH l} mall and ceiling finish materials are required Sec. 804.1 and Table 8-B. 2} Carpeting on the ceiling is required to have a spread rating. --- Sec, 804.2 3} Textile wall coverings shall have Class I flame and shall be protected by automatic sprinklers acceptance criteria of U.B.C. Standard No. 8-2 to comply with Class I spread. or meet -- Sec. INSi1LATI4N NOTES 1} All insulation material including facings are required flame -spread rating of 25 or less and a maximum smoke -- Sec. 707.3 2) Foam plastic insulations are required to be protected, flame rating. the 805 to have a density of 450. Sec. 2602 Code review Project 1. Address 15 for; Deveopment Cnikshop Northeast Addition North 2nd East ADDITTONAL REQUIREMENTS; For F1 occupancy Equipment, machinery or appliances which generate finely divided combustible waste or which use finely divided combustible material shall be equipped with an approved methal of collection and removal. -- Sem. 30-6.8 For B occupancy For Sl occupancy ACCESSIBLE FACILITIES; NATE; Except as noted, section numbers listed below are from CABG/ANSI X117.1 - 1992 WATER FOUNTAINS AND CATER COOLERS: At least 50 percent of drinking fountains, but not less than ane, prov-idedon every floor shall be accessible. -- UBC Sec. 11D5,4,1 Accessible units must comply with the following: 1) Spout is to be within 36 inches of the floor, -- Sic. 4,15.2,1 2} Spout arranged for parallel approach shall be located 3 inches maximum from the front edge. Spouts of cantilevered units with knee and toe clearances shall be located 15 inches minimum from the vertical support and 5 inches maximum from the front edcre_ oil -- Sec. 4.15.2.2 Spouts shall provide a flow of water 4 'inches height minimum, -- Sec. 4,15.2.3 4) Operable parts unit and shall 5} A cantilevered shall be locatip-(9 at Comply unit is with x.25,4 required to r near -- Sec. extend the front x.15.3 17 inches �.11E,- ACL u�cct-L suppor--c. k-:lear Knee space must provide of 8 inches in depth at 27 inches high and ll inches minimum above the floor. -- Sec_ 4.15.4.1 6)- Forward approach units shall comply with 4.2. shall comply with 4.2.4.4. Units not having Units the edge of the minimums from a clear area at 9 inches in alcoves necessary knee it Code vi Project Id. :. Address 15 for. Deveopment Wkshop North 2nd East Northeast Addition and toe clearance or dear spare under them shah Comply with. 4.2.4 and have a dear floor space that allows a person in a wiLeelch.air to mare a parallel approach. --- Sec. 4.15.4.2 TOILET FACILITIES: 1} A 60 inch diameter unobstructed turning space is required in the toilet room. -- Sec. 4.16_3, 4.2.3 & Fig_ F34.2.3 2} Water closet shall be mounted adjacent to a side wail or partition. The distance from the sides wall or partition to the centerline of the water closet shall be 18 in. Sec. 4.17..1 3 } When the accessible water closet is not in a shall The clear floor space shall be 48 in minimum in front of the water closet and 42 in from the center line of the mater closet on the side not adjacent to the wall. -- Sec. 4.17.2 & Fig. 54.17.E 4} When the accessible water closet is in a stall: The stall shah be 60 in wide minimum and 56 in deep minimum fog walk hung water closets and 59 in deep minimum for floor mounted water closets. -- Sec. 4.18.3.1 If the door springs into the stall, the required depth shall be increased by 36 inches minimum. -- Sec. 4.18.3.2 & Fig. B4.18.3.1 5} the bars are to be 33 to 36 inches above the floor and shall be provided on the rear wall and an the side wall closest to Code review Project Id. . Address: 15 for.: Deveapment Wkshop North 2nd East Page # 11 Northeast Addition the water closet. -- Sec. 4.24.2.2 & Figs. B4.17.31 84.17.4 and 84.18.3.1 a} Side grab bar is required to start �,�rithin 12 inches of the backwall and extend to 54 inches from the back wall. (The minimum length of the bar is 42 ice) ---- Sec. 4.17.4.1 & Figs. 84.17.3 and B4.18.3.1 b} The rear bar shall be, 24 in long minimum, centered on the water closet. Where space permits, the bar shall be 36 in hong minimum, with the additional length provided. an the transfer sides, -- Sec. 4.17.4.2 & Figs. 84.17.3, B4.17.4 and B4.18.3.1 6} The top of the seat on the water closet is required to be 17 to 19 inches above the floor. -- Sec. 4.17.3 & Fig. B4.17.3 7} Accessible urinals shall be of the stall type or wall hung with the rim at 17 inches maximum above the floor, --- Sec.. 4.19.2 $} A clear area of 30 X 48 inches minimum is required in front of the urinal. Privacy shields shall not extend beyond the front edge of the urinal rim, unless they are 30 inches apart minimum. Sec. 4.19.3 9} Accessible lavatories shall be mounted with the rim 34 inches maximum above the floor and a clearance of 29 inches minimum from the floor to the bottom of the front edge of the apron . -- Sec. 4.20,2.1 & Fig. B4.20.3.1 107 It shall extend 17 inches minimum from the wail. The clear knee. space shall be 8 inches in depth minimum at 27 inches minimum above the floor and 11 inches in depth minimum at 9 in minimum above the floor. The dip of the overflew shall be ignored when checking the clearances. -- Sec. 4.2D.3.1 & Fig. B4.20.3.1 11) A clear floor space of 30 X 48 inches minimum shall be provided in front of the lavatory and shall extend 19 inches maximum tender the lavatory. -- Sec. 4.20.3.2 & Fig. B4.20.3,2 12y Water supply and drain pipes under lavatories shall be insulated or otherwise treated to protect against contact. -- Sec. 4.20.4 13) The bottom of mirror is required to be within 38 inches of the floor. -- - Sec. 4.16.6 & Fig. B4.20.3.1 Code review Project Id.: Address: 15 for. Deveopment Wkshop North 2nd East GLAZING REQUIREMENTS Northeast Addit11 ion All glazing in hazardous locations is r-equireci to be of safety glazing material. -- Sec, 2406.3 & 2406.4 Locations: 1 } Glazing in ingress and. EgrE'S5 doors except jalousies. 2} Glazing in fixed and sliding panels of sliding door assemblies and panels in swinging doors other than wardrobe doors. 3} Glazing in storm doors. 4} Glazing in all unframed swinging doors. 5) Glazing in doors and enclosures for riot tubs, whirlpools, saunas, steam rooms, bathtubs and showers. Glazing in any portion of a building wall enclosing these compartments where the bottom exposed edge of the glazing is less than 50 inches above a standing surface and drain inlet. 67 Glazing in firmed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24 --inch arc of either vertical edge of the door in a closed position and were the bottom exposed edge of the glazing is les, than 60 inches above the walking surface. 7} Glazing in an individual fixed or operable panel, other than those locations described in items 5 and 6 above, than meets all of the following conditions: A. Exposed area of an individual pane greater than 9 square feet. B. Exposed bottom edge less than 18 inches above the floor. C. Exposed top edge grater than 36 inches above the floor. D. One or more walking surfaces within 36 inches horizontally of the plane of the glazing. S) Glazing in railings regardless of height above a walking surface. Included are structural baluster panels and nonstructural in -dill panels. 9) Glazing in walls and fences used as the barrier for indoor and outdoor swimming pools and spas when the bottom edges is less than 50 inches above the pool side and the glaring is within 5 feet of the pool or spa deck area. 10} Glazing in walls enclosing stairway landings or within 5 feet of then bottom and fop of stairways where the bottom edge is less than 50 inches above the walking surface.