have finished
the review
of your drawings for the New Melalue ca Capt Center in Rexburg
and have
'Identified the
following
discrepancies:
1. Show dumpster location with proper screening on plot pian.
2. Identify compact parkmg spaces on Northeast gide of parking lot to keep fire
ena3ne isle at least 20' wide.
3. Provide Fire Department with items requested as per the attached document.
4. Satisfy requirements from the State Electrical Inspector.
Thank you for your patience. Please. come into City Hall and we will. issue a building
pernut based on the above itemsbemg completed. If you have any questions please give me a call
at 359-320 ext 314..
Sincerely,
Val Christensen
Assistant Engineer
cc: John MiUar
Joe Laird
Dee Owens
A
REXBURG MADISON
COUNTY FIRE PARTMENT
P. 0. Box 2 8 0
26 North Center
Rexburg, I 83440
(208) 359-3010
Fire Plan Date: 09--"01-00
1994 UnIfor Ere Code
Plan Review Review Date: 14&-02--40
Building Name : Mela,leleuca Inc. Call Center
Building Address -. lc ---,:.7 West Main
L
Stories: One
OccupancyC1.assification:
Type of Construction: V -N
A -3y B1, Mr_ S-1
3r
Existing Floor Area: 2_3,434
New Construction Floor Area.
N/A
1).Required Fire Flow (Appendix III -A): 4
anm far automatic fire sprinkler system
250 gpm,
reduced to 1, 504
2).Water Supply (Article 9, Section 903) Required: Yes
Fire Hydrant Location: 50 W. Main, 1't W. -and Main
Water Supply Acceptable: Yes
Fire Hydrant Location Acceptable : Yes
Water Supply Comments
stem
3 ) .Fire Apparatus Access- loads (Article 9 Section 902 )
Required.* Yes
4 ) . Installation
Acceptable: Yes
Of Portable Fire Extinguisher
sect -!On 1002) R�:qulred: Yes
-, 1.1
Location Acceptable: Not shown
Type Provided Acceptable : Not_ shown
(Article 10
Cmm Minimum 2-A '-,.O-BC within 75 feet travel
5-01) Automatic i .ext irigui-51'ri-iy.ms: (Art-icle 10
lection
1003
Required:
Yes
Tyke
Of
System.
Being
Installed;
Existing
wet
system. -- System
m� s � be
changed
to
cover
the remodel
Sprinkler System Monitoring
1003.3) Required: Yes
re aired
6} .Firms Alarm. Systems
Required (Article 10
Ccmme-n-ts-* Flow and
Section
tamDer monitorin
(Art-I"cle 1❑ Secy I on 1007)Requiredo. No
'hype Of System Being Provided: Manual
Items needin
i-d,dresse-4
WM
fire
alarm
stem*
Install annunciator Tanel at front entrance
Add horn strobe south wall in sales area
Cover unfinished area with horn strobes
Move pull station to south emit
move horn strobe to renter of south wall
Install outside weather raof horn
Tamper and flow switches re uire manitQrin
Candela rating on some strobes need to be
at le'ast
I need the submittals and voltage drop calculations
Plans As Submitted Are Acceptable: Yes
are addressed
Plans Checked
By: Dee Owens
Date:
rovided
30 not 15
highlighted items
1-0--02-00