Loading...
HomeMy WebLinkAboutREVIEWS - 00-00023 - Rexburg Airport - Hanger0 8/22/2000 Mike Bressler Teton West Construction R.O. Bax i22 Rexburg, ID 83440 Dear Mi�Ce: STATE OF IDAHO 12 North Genter Street Rexburg, Idaho 8344 Phone (208) 359-3020 fax �206.) 359-3022 e-mail rexburg@srv.net I have reviewed your plans for a hanger at the Rexburg Airport and have identified the fallowing discrepancies: 1. Show building entrances. Code requires that one wall have aperllng in each SQ' of wall length. 2. Structural designs use Wind Exposure Category `B" instead of Category "C" Have structural engineer determine if wind design speed of 90 m.p.h. versus SO m.p.h. will compensate. 3. Fff'ewalls Will need to be constructed on the North and South walls. Please provide details. 4. Address any issues presented by the Fire Department, If you have any questions please give me a call at 359-3020 ext. 314. Sincerely, Val Christensen Assistant Engineer cc: John Millar Dee Owens 'A: It P.O. Box 2 8 0 26 North Center Rexburg, Idaho 83440 (208) 359"--3010 1994 Uniform F3se Code Plan Review Building Name: Parkinson Hangar Building A�.dress : Airport Plan Date: 08-01-2000 Review Date: OS -29-2000 Stories: One Type of Const -ruction: II -N I occupancy Class 11f1c3t10T1 : 5-5 Existing Floor Are.a.v New Construction Floor Area: 3600 sq_._f't._ 1).Required Fire clow (Appendix III -A): 1, 500 9,2M 2) Water Supply (Article 9, Section 903) Required: Yes Fire Hydrant Location: 36Q Fire Hydrant Flows,. x,514 fro southwest an airport road m @ 2 0 1h Fire Flaw Test location: main airport entrance Fire Fl w Supp-1--L"'d B Fire Department Water Supply Acceptable: Yes Fire Hydrant Location Acceptable: des Water Supply comments. See attached cornments 3.)Fire Apparatus Access Roads (�rticle 9 Section 9O2) Required: No, access from taxiw� N/A 4) .Installation Of Portable Fire Extinguisher (Article 10 Section 1D02) Required: Yes Location Acceptable: Not shown Type Provided Acceptable,: Not shown Co=ents: -cares one x �� �-BC Plan Review Page 2 � } .Automatic Fire Exti'nguish-ing Systemsv. (ArtJ-c-]-e 10 Section 100.-3. Required: Type Of System Being Installed. No 6}.Standpipes {Article 10 Section ? } . Fire Alarm. Systems (Article 10 Pans As Submitted Are Acceptable: Plans Checked By: Dee Owens 1004) Required: No Section 1007)Requirede. No Yes Date: 08-29-20x0 ka wo ' # I l all 9- rs jj jp i #1 OWNI tLL � 2,614 c per ftA at zu PsL order to get. zlg)re we=, have line te vvuul,d, to loup mto a smcwhm lkpl4j� m , .. ma by Waftwaff Tm., ybe jr% bc of any Luxu=r help p1me let know. ISM W q 1997 UNIFOAM FIRE CODE TABLE A -HI -A-1 A IMMMUM REQUIREG FIRE FL CFW AND FLOW DURAMOR FOR BU�INGS MEAMjqwmtw� Typ A am-mll. ' 91 MW4M-1 I a 0-22.3700 0-1Z700 -8?200 2Z7C1, 30201-38,700 K901-121900 38170148,W 21,801-24 12�901-171400 4"1-597ow 4 1-77401-213L3UO 59,001-70p9W 70001,0-17M 39,701-47PIOD 25;f-501-30,100 837701-97,700, 477,101.54,9W 101-357200 971701-112, 700 -4 -54,901-63,400 112,7101-128,7M 635401-7-2,400 40,601-4C400 MM1-145�qoo 7.401 -I00--- 46,401-52500 &2,101-9Z40D 164�ZOI-1835400 92w401-1031100 .59:11101-66,OW 1839,401-2039*700 �� -73 " 00- 66,001 13 11491-1, 73;301-,-Rl!vloo 225XI-2479700 121VOI-139,400 247,701-271,200 1391401-15:2,600 89,201-97JOO 2717201-295,900 15Z601-166t,5W 97,701-106,500 295,901-Grcater 166!.501-Gmuer 125!o5UO of 125r501-1351,500 ff MPMEW m 145,.801-156,7oo ........ 167.1901-179,400 Af 179v44)1 -191.94W B L91,401-Gmmff 1TYP" Of Oxsuuctkm we basedupon tk Biidding CDdc 2MCaSUred a, 2a pSi (137.9 kpa). SCr 6.p APP MdX MSA. L SeCt,on 2 A is TVGv 53,901-779M 9,80-1-12,600 12,601-15,400 155401-49�4W I -- 18,401-21ksm 21180125,900 25t%1i2900 29,301-335500 33P501 -3729W 37,901-42,700 '-p- 427-701-477-700 475701-53,000 97;901-106718W IMI- 113,201-121.,300 121JOI-1299600 1.2,95601-13893M :1 , Fil 1- 91 T"o Vv lK 9.179 *r L fl�376 3,601-4,WO 7m rZ—IWO 65,201-71700 2,2M 7.701.9w4OO 500 RM W --- 3,250 31,750 20!0601,Z3,.,3M =Wpm 237 -VI -26,300 41250 267301-29,300 41500 29,301-3Z600 43750, 32,001-36:pOM 5-tooD "7601-43� "00 4a.P401-47-1400 5�750 47F401 - 51,5M 6!lt000 6,250 6!9500 1- -61,750 X1,750 645,801-69�600 69w6Ol-74!00 71.250 "74$601-7%M 0 D T750 p 3 0 E I UNIFORM FIRE CODE APPENDIX Itl-B SEGT101d I —SCOPE Ith Fire. &ants hyshaff be provided in aw=&nce W" Appendix Id for the protcrAion of buffdings� or portions of buflidinp, here- after cCwftn&e& SE Ok CATION Fire hydrants is be pmvided aion ireqw- ed &e appwatm ac� cess raads anJ adjac,=t public streets, SECTION 3 — NUMBER OF FIRE HYDRANTS Thr. minim= number of fim hydmis available to a NMding &ball not be less than that listed 'M' Table A-Iff-13-1. The number of 15re hydrants available to a complex or Subdivision shaR not be- less than that doennined by spacmg reqw-ements listed in Table A -M -B.4 when applied to fire appanim access mads and *PIM enm ter public stiectsftom which fune, operadow could be conducted. 1� 0 ftlZi�ff'ip. A :. -L is x3. fac UrAlL ft or hms 27OW-2,250 0 3tOOO 3r5OD4001W 47500-SvOW sr" 6,,Offl 6r5W710DO 7,5W or mme 4 5 6 6 7 8 or mor0 oil SLI I A Cal 0 LN- L of f i(i4sti 'MV,+ H t 410 1 q. "1 .7111 lb I=' d not .4-0 Ly, SECTION 4 -w­m CONSIDERATION OF DOSTING FIRE HYDRAAlTS W, Exisfmg fire hydrants obsftets are allowed to be con&dw ered as w0able- Existing fire hydr"Is on adjamat properties sha-H not be consWered available unk*s fffe apparAw access roa& extend between properties amd cawments are established to prevent obstruction of suchro&k SE ON 5 — DISTRIBUTION OF FIRE HYDRANTS Tie average spacing between fire hydrants shaU not exceed that lisWd m* Table A -M -B- I E EXCEPMN: The chief may accept a defic-tency of up to 10 ?er- cent Wbare, cxishIf" E= hydrant& provift all or it penion-nxpd=d fut hyftnt servkt- Regard1cm of the average spadnX fn hydhnts sW be iomtW such that aff points on str=ts ;&=ss roa4s adiwent to a buildw b mg are within the dis=ces Hsted in Table A -IN -B-1. T .V: . 7 q TVT fff "iii` — 0 L JL NFL L AL L, :500 2.50 450 450 225 4 350 210 300 IM 150 i