CITY OF 'REXBURG
ENGINEERING
PO BOX 280
REXBURG . T D 8 3 4 4 0
(208)359-3020
Pian analysis based on
the 1994 Uniform Building Code
Number:
Name: Ashton Memorial
299 Technology may
Occupancy: B,E1
Construction: V -N
Date ;
Contractor:
Architect:
Engineer
Report By:
July 17, 2000
VAL CHRISTENSEN
NOTE: The code items listed in this report are not
complete listing of all possiLble code requirements
Tt is a guide to selected sections of the code.
11
intended to be a
in the 1994 UBC11v
Report created using Plan Analyst software
Portions of the material contained in this program are
from the Uniform Building Code with the permission of
International Conference of Building Officials .
DIRECT10N BOUNDARY
NORTH Property ii-ne
EAST Property line
SOUTH Buildinq
WEST Building
Allowable area increased
Sec. 505.1
FL NAME
of f ice
Kitchen
1 Class Room
TOTAL FOR FLOOR
BUILDING TOTAL
The allowed area for
NOTE.- Accessory area
-- Se%, -,-,o 504.3
PRAT ION
AREA INC'REASE
42.0 Feet
72.0 Feet
56.0 'Feet
dO.0 Feet
1:00.% for open
occ MAX FLR
E3,
B
El
the major use
cannot exceed
ex.c. I
(719) 599-5622
reproduced
the
FIRE PROTECTION
42 - 0 Feet
72.0 Feet
28.0 Fee -',---
20.0 Feet
area on 4
AREA ALLOWED RATIO STTOS
ok 988
16000
0,06
ok
ok 98
16000
0.01
ok
ok 647
18200
0.04
ok
1733
16756
0.1
ok
1733
16756
0.1
ok
was used for minor accessory areas.
the al -I. -owed area in Table 5-B 9
46
10
Code revlew
ProJect Id.:
Address: 299
for.,
Ashton memorial
Technology Way
Page # 2
The actual height of this building is 20. feet,
L
Themax' heiU
1 -mum ght of the bId' Table 5-B
I Ing rs 40. feet,,
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 5-A
NORTH
For R;nA-ri nn W -T P
Occupancy
B
El
EAST
For
Occupancy
B
El
SOUTH
For
Occupancy
B
El
WEST
For
Occupancy
B
El
Wall
0 hour
0 hour
Bearing
Wall
0 hour
0 hour
Bearing
Wail
0 hour
0 hour
Bearing
Wall
0 hour
0 hour
9
- ID t. -A CL _L
Wall
0 hour
0 hour
Non -Bearing
Wall
0 hour
0 hour
Non -Bearing
Wall
.0 hour
0 hour
Non -Bearing
Wall
0 hour
0 hour
opening Construction p...
Protection "rapet
None Material Required
Any No
None Any No
Opening Construction Para -pet
Protect'
None 3- on Material Requ-ired
Any No
None Any No
Opening Construction Parapet
Protect'
,iLon Material Required
None Any No
None Any No
Opening Construction Parapet
Protection Mat"eri ' Required
. a L
None Any NO
None Any No
,�� No fire protection requirements for
OTHER
ELEMENT
Interior Bearing wall
Interior nonbrg wall
Structural Frame
Exterior Strust Frame
Pioor/Ceiling Assembly
Roof/Ceiling Assembly
Stairs
BUILDING ELEMENTS
MATERIAL
Any
Any
Any
Any
Any
Any
Any
DRAFT STOPS:
If there is combustible
stops shall be installed
exceed 3,000 square feet
StOps does not exceed 60
Table 6-A
RATING
0
hr
0
hr
0
hr
0
hr
0
hr
0
hr
None
openings.
NOTES
construction in the roof/ceil Ing assembly,(jraft
so that the area of concealed space does not
and so that the hori
'zontal dimension between
feet, -- Sec. 708.3.1.2.2
Code review
Project Id.:
Address: 299,
for:
Ashton Memorial
Technology Way
EXIT REQUIREMENTS:
FL NAME
NUMB MIN
occ EXITS
Page � 3
MIN
PAN I C
RATED
DOOR NOTES
WIDTH
HDWR
CORRIDOR
SWING
I office 10 1 0.2 No N/A N/R
I Kitchen 0.0 No N/A N/R
I Class Room 32 1 0.5 No
TOTAL 42 2 0.7 No N/A N/R
In areas 'where 2 exits are requi-red,, the minimum separation 13 1/2 of
the maximum diagonal of the area or floor. -- Sec. 1003.3
1
Exit signs are required from all areas where 2 or ex'ts are required.
-- Sec. 1013.1
Main exterior exit doors which obviously and clearly are identifiable
as exits need not be signed when approved. -- exc. I
Door ;ming is based on Sec. 1004.2 except as noted.
Occupant load factor is based on Table 10-A.
Number of exits is based on Table 10,A except as noted.
Exit width is in feet and based on Sec.. 1*003.2,
Exit width a -s to be diLvid-ed approxi -mately equally among exits,
Width shown for all areas is based on other exits. (0.2)
Width ohown for 1st floor is based on other exits. (0.2)
Widt�i shown for other floors & basements i5 based on stal
For the minimum width of doors, see Sec. 1004.6 2-rways. (0.3)
For the Tninimum width of corridors, see Sec. 1005.2
For the minimum w-idth of sta'
-Lrwaysf see Sec. 1006.2
FOOTNOTES:
FLUSH AND SURFACE BOLTS -
0
Manually operated edge or surface -mounted flush bolts
it are prohibited. When automatic flush bolts are
leaf having the automatic flush boit shail not have
surface mounted hardware. The unlatching of any leaf
require more than one operationO -- Sec. 1004.3
on
and
used
door
shall
surface
door
knob or
not
Code review for:
0
ProDect 1d.: Ashton Memorial
Address: 299 Technology way
Page # 4
LOCKS AND LATCHES:
All means of egress doors shall be readily openable from the Side
from which egress is to be made without. the use, of a key or special
knowledge or effort, -- Sec. 1004.3
Key -locking hardware may be used on the main exit when the main exit
consists of a single door or pair of doors if there is a sign stating
THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS. When unlocked,
door(s) Iftust swing without operation of any latching device.
RAMP REQUIREMENTS:
1) The mini -mum width is 44 'Inches. If a ramp serves an occupant load of
49 or, less, it may be 36 'Inches wide. If the ramp is serving a high
occupant load, check exit table above for required width.
-- Sec. 10-07.2
2) If the ramp is part of the accessible route, the maximum siope is
1: 12. All other ramps may have a slope of 1: 8 or less..
-- sec. 1007.3
3) When the siope is greater than 1:15, landings shall be provided at
the top, bottom and for each 5 feet of rise. Top- landings and
f
I_ntermediate iandings shall b.e at least 5 feet in the direction of
travel. Landings at the bottom of ramps shall be at least 6 feet 'in
the direction of travel, -- Sec. 1007.4
4) Handrails shall be per stair requirements,, -- sec. 1007.5
5) The surface shall be roughened or shall be of slip -resistant
Materials. -- Sec. 1007.7
LANDINGS AT DOORS:
1) A floor or landing shall be provided on each side of doors. When
access for persons with disabilities is required, the floor or landing
shall not be more than 1/2 inch lower than the thresbold. When access
A
is not required, themax-
-IMUM is I inch,, -- Sec. 1004.9
2) Landings shall have a width not less than the width of the stairway
or wi.dth of the doorway, whichever is the greater. The minimum
-1. 1 -- Sec. 1004.10
length in the direction of exit travel Ls 44 'nches.
0
Code review
Project Id.*
Address: 299
for., 0
Ashton Memorial
Technciogy'day
Page 4 5
BUILDING ACCESSIBILITY:
J1
1) This building g each tenant shall be provided w'th at least
one entrance which complies with the accessibie route provisions of
CABO/AtiSI A117.1. At ileast 50 percent of ali entrances shall be
accessible. -- Sec. 1103.2.3
2) When more that one ex't is required from any accessible space, each
accessible portion of the space shal i be served by not less than two
accessi
*ble means of egress Sec. '1104.1.1
3) When an exit stairway 'is part Of an acces-s-l"ble means of egress,, the
stairway shall have a clear width of not less than 48 'inches between
the handrails. The stairway shali either incorporate an area of refur,_TE,,3
within an enlarged story -level ianding or shall be accessed from
an area of refuge. -- sec, 11,04-1.2
The area of refuge shall have direct access to the stairway tha'L'- serves
sec* 1104.2.1
4) Each area of refuge shall be sized to accommodate one wheelchair space
not- 1P_<:zq th_-)n -qn I I'll
_L11
imcnes for each 200 occupants, or
portion
thereof. -- Sec.
1104.2.3
If the
area of refuGe is
rint-
Within r
*3 CX-L-LWC1yf _LU snaii De separated
from the rest of -the story by a smoke barrier having at li:��ast a one-
hour fire -resistance rating. Smoke barriers shall extend to the roof or
floor deck above. Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes. -- Sec. 1104.2.4
P
6) Two-way communications are required., -- Sec. 1104.2.5
7) Each area must be ident]A'ed by -a '
I sign stating AREA OF REFUGE and the
international symbol of accessibility.
8)
NOTE :Exio
it stairways In bu.11dings protected throughout by an approved,
automatl.c 5prinkler system are NOT required to 'incorporate an area of
refuge. -- Sec. 1104-1.2 exception #2
ROOFING REQUIREMENTS:
1) The roofing on this
Cedar or redwood shake
accordance with Section
-- Exception 2
building is required to
shingles and #1 shingies
1504.5, special -Purpose
4) :)ee section 1,L)04 and ICBG research reports
be Class C.
constructed
Roofs may be
-- Table 15-A
in
used
for requirements,
STANDPIPE REQUIREMENTS:
M
There is no requi-rement for a standpipe. Table 9,A
FOOTNOTES:
Code review
7
Prod Id.-,
Address 299
VENTILATION:
for:
Ashton. Memorial
Technology Way
All meas customarily Occupied by humans shah be provided with natural.
ventilation by means of openable exterior oveninas with An Arc�A nf ne,+
fess than 1/2Q of the total f1cor
mechanically operated ventilation
of supplying a minimum of 15 cubic
occupant. -- Sec, 1202.2.1
WALL AND CEILING FINISH
I
area or shall be provided with a
system. Such system shall be capable
feet per minute of outside air per
a -L -L ana cj--L-meq-il materials
SeCV 804.1 and Table S -B.
2) Carpeting on the ceiiing i
spread rating. -- Sec. 804.2
T
required to C01RPiy with
required to have a Classl awe
ie3xLj-ie wa.ii coverings shall have Class I flame
and shah be protected by automaticspr-inklers
acceptance criteria of U.B.C. Standard No. 8-2
spread
or meet
-- Sec V
rating,
the
805
46
4
Code review for:
Project id.0,. Ashton Memorial
Address: 299 Technoiogy Way
Page # 7
ACCESSIBLE FACILITIES:
NOTE: Except as noted, section numbers listed below are from
CAB O/ANSI P.117.1 , 1992
WATER FOUNTAINS AND WATER COOLERS:
At least 5.0 percent o. -L';7 drinking fountains, but not legs than one,
0
P ov-id
ed on every floor shall be accessibie, -- UBC Sec. 1105.4.1
Accessible units must comply with the following:
1) spout is to be Within 36 'Inches of the floor. -- sec. 4.15.2.1
2) Spout arranged for parallel approach shah be located 3 inches
maximum from the front edge. SPOuts of cantilevered units with
knee and toe clearances, shall be located 15 -inches minimum from
the -vertical support and 5 inches maximum from the front edge..
-� Sec. 4.15.2.2
3) Spouts shall Provide a flow o]ff water 4 inches height minimum.
-- Sec,,. 4.15.2.3
4) Operable parts shad be located at or near the front edge of the
unit and shall comply with 4.25.4 -- sec. 4.15.3
5) A cantilevered unit is required to extend 17 inches minimum from
the vert icca:11 support. Clear knee space must provide a clear area
of 8 inches 'in depth at 27 inches high and 1 11 inche3 at 9 inches
a V
m-ini-mum above the floor.., -- sec. 4.15.4.1
6) Forward approach units shall comply with 4.2. Unaw-ts in alcoves
shall comply with 4.2.4.4. Units not having the necessary knee
and toe clearance or clear space under them shail cOmPly with
4..2.4 and have a clear floor space that allows a person 'in a
wheelchair to make a parallel approach. sec. 4,15.4.2
TOILET FACILITIES: 1
1 V
) A 60 'nch diameter unobstructed turning space 'i's required in
the toilet room. -- Sec. 4.16.3, 4,2.3
2) Water closet shali be mounted adjacent to a side wall or
partition. The distance from the side wall or partition to the
centerline of the water closet shall be 18 i -n. Sec. 4,,17.1
3) When the accts siblf.,--n water closet i's not "V
in a stall.,
The clear floor space shall be 48 in minimum in front
of the water closet and 42 in from the center line of the
water closet on the side not adjacent to the wall,
-� Sec., 4.17.2 & Fig. B4.17*2
4) When the accessible water closet is in a stail:
The stall shall be 60 in wide minimum and 56 in deep minimum
for wall hung water clos-ets and 59 in deep minimum for floor
mounted water ciosets, -- Sec. 4.18.3.1
If the door swings into the s -tail, the required depth shall
be increased by 36 inches in-ini-mum,
Fig. B4.18,3,1
5) The bars are to be 33 to 36 inche8 above the floor and shall
be Provided on the rear wall and on the Side wall closest to
the water closet., -- sec. 4.24.2.2 & Pi
and B4,18,3,1 -1gs. B4.17.3f B4.17.4
a) Side grab bar is required to start within 12 inches of the
backwail and extend to 5.4 inches frcm the back wall. �The
G
I
Code review
Project Id.
Address: 299
fog,
.,
Ashton Memorial
Technology way
minimum length of the bay _
Figs. B4.17.3 and B4.18.3.1
Sec. 4.17.4.1 &
b.) The rear bar shall be 24 "in ungini , centered on the
water closet. Where space permits, the bar shall be 36 in
long minimum, with the additional length providedt
transfer side, -- Sec. 4.17.4.2 & Figs. 134.17.3,
and B4.18.3.1
6) The top. f the seat on the water closet is requa-red to be 17
to 19 inches above the floor., i- Sec. 4.17.3
7) Accessible urinals shall be of the stall
the rim at 17Inches maximum above t -- sec. 4.19.2
8) A clear area of 30 X 48 'Inchesi '
mum is required 'in front
of the urinal. Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 *
nches apart
MIRIMUMO -- Sec
. 4.19.3
9) Accessible lavatories shall be mounted with the rim 34 inches
maximumabove the f1oorand a clearance of 29 inches rrLin,imum
from the floor to the bottom the fry
nt edge of the apron.
-- Sec. 4.20.2.1 & Fig* B4*2o*3*1
10) It shall extend 17 inches m*n'I imum
from the wall. The clear knee
-pace shall be 8 inches in depth minimum at 27 inches mlnimum
above the floor and 11 'aches in depth minimum
above the floor. The the overflow shall be ignored when
Checking the clearances, -- Sec. 4.20.3.1 & Fig. B4.20-3.1
11) A clear floor space of 30 X 48 inches minimum shall be Prov Ided
in front of the iavatory and shall extend 19 'Inches maximum
zinger the lavatory, -- Sec. 4.20.3.
1 ) Water supply and drain under lavatories shall be
insulated or otherwise treated to protect against contact,
-- sec. 4.20.4
13) The bottomof m'
'}
equired to be within 38 -inches of
the float. Sec. 4.16.6 & Fig. B4.20A.1
Code reView
Project I.
Address: 299
for
AshtonMemorial
Technology way
GLAZING REQUIREMENTS
All glazing in hazardous
giazlng materia.. -- Sec.
CRAWLS PACS RE11REMF
I T� t*T t
locations is required to be of safety
r -k
24Q6.1 & 2406.4
_J_�t ii -means r in
exterior walls. Opening ll id
1 square foot for each 150 � feet E
n crawl space.
Openings shall distributed t two opposite sides and be located
E
-cornersas tical. �--� Sec. 2317.7
Note Vert openings may reduced t 1096 of the above if grou-nd
surface area covered with roved .
the
building official approves..
2) Provide 18 -inch by 24 -inch access opening t the crawl
Opening
i located thecrawl ace Sec T
Unless t F
Sueu as an approves wood of natural resistance
to decay or treated wood, the minimum clearance between exposed earth
ciearance to beams and
girders is 12 'aches_ -- see. 2317#
ATTIC REQUIREMENTS:
1) Provide an access to all attic areas with a clear height of 30 inches
or more. The minimum size 'I's 22 inches by 30 E _nchesv There rqust be 30
inches or more Clear height above the
attic2) Provide ventilation in all attic areas. The net free vent area isto be not less than I square foot for each 150 square feet of
area. The vent area may be 1/300 if at least 50.% of the requ'red
ventliaLi
.ng area iS Provided by ventilators located in the upper
porIE-J.on of the attic. The upper ventilators