We have reviewed the final pians for the sub building and have only the following requested
change to the Plans.-
---
Install Exit S1* gns in the basement'
n accordance with Sections 1012 and 1013 of the UBC.
Very tru
JOSEP
CITY ENGINEER & BUILDING OFFICIAL
Ricks college
Physical Plant Building
.Attn. Ruyan Nielsen
i I r�.�• r��r iy
STATE OF IDAHO
RE: Remodel 16 East Main (Old Sandra & Co. Bldg.)
Dear Rulon,
P.O. Box 280
12 North Center Sheet
Rexburg, Idaho 8344
Phone (248) 359-3020
Fax {208} 359-3022
e-mail rexburg@srv.ne#
July 17, 2000
Vire have reviewed the final plans fox the sub bufldi'.ng an i have only the following requested
change to the Plans:
1 --- Install Exit Signs in the basement in accordance with S ections 10 12 and 10 13 of the U -B C �
Very tru
JOSEP
CITY ENGINEER & BUILDING OFFICIAL
97 11 aP Ihb
May.'30, 2000
kicks College
Physical Plant Bull&ng
At-tn. Rulon Nielsen
RE.: Remodel 16 East Main (Old Sandra & Co. Bldg.)
Dear Rulon-,
P.O. Box 280
12 Nprth Center Strut
Rexburg, Idaho 83440
fgptl ��9 ) U11 UL�
Fax (208) 359-3022
e-mail rexburg9sr'v_net
We have review your preln'='
ary plans for the subject building. Attached is a copy° of the computer
analysis for your infonnation. The main points of discussion ars the following"
1 --- Due to the ocLupant load being over 5 0.. Classrooms 103 and I44 each need two separate e?dts. Y
used 20 sq. ft./ occupant for these classrooms. (See Table 110-A) Also see UBC Sec. 1004.2.4 for
separation of exits.
? --- The ceiling floor assembly beh-veen the basement and the 1ST floor needs to have a 1 hour axe rate.
(UBC Sec. 71.2) The columns holding up the I5` floor also need to have a one-hour fire rating. We
realize that this should have been done many years ago to meet previ*ous odes, but the first floor, use
charging ftom a Class B to an A3 (man -v students) makes this needed fire rating even more critical.
3 --- There needs to be 2 emits from the basement as per UBC Sic. 1004 ?-3 .2. UBC Sec. 9(}4.2.2 alio
requires two exits from the basement or an automatic sprinkling system is required. The e�sting
stairways are not located close enough to the exterior wail to exactly meet this requirement, but'vVith a one-
hour corridor (or ane -hour Tabby) connecting the stair to the exterior doer their would meet the intent of this
section. There would need to be afire-rated char and enclosure for the back stairs plus acne-hour rated
corridor from the top of the stairs to the e_yterior door.
4 --- We, would encourage ��ou to try to find some way to make the back entrance handicapped accessible.
A handicapped stalk could be created near the back door. Parking is eery limited ire. front along Main St.
and There are no handicapped ramps at the curblinc in the viciniNr of the builcHng entrance,
Ven; truly F r
JOSEPH A. LAIRD, P E
CITY ENGINEER & BUILDING OFFICIAL