Loading...
HomeMy WebLinkAboutPLAN ANALYSIS - 00-00015 - 121 E Main St - Office RemodelProj ect Prof ect Address. CITY OF REXBURG ENGINEERING Pa Box 28a RExBURG, Io 83,440 (208)359-3020 Plan analysis based on the 1994 Uniform RU 11ding Code Number: 6/28/00 Name: Dance Studio 121 E. Main Occupancy: A3,B Constructions -N - Office Date: June 2, 2000 Contractor: Designer Engineer: Report BY: Chuck Chuck Hill Hill VAL EE NOSE: The code 'terns listed this report are not complete listing of all it code r it It is a guide tO Selected sections of the code# Report crated using Plan Portions f the material from she Uniform Building International Conference 41 intended t iii the 1994 Analyst software by b w & a. contained in this proqr-am are Code with the permission of of Building Officials. (719) 599-562 reproduced the L NAME ----------------- --------------------- occ MAX FLR AREAALLOWED RAT I O STATUS i Office --------- 1392 ----_---- Interior check only I Dance 1 l4Jor A3 k! 1 Interior c J i l 1 Total ' Floor 2784 Interior check only Page # 2 Code review for. Project Id.: Dance Studio - off -ice Address: 121 E. Main OTHER BUILDING ELEMENTS Table 6-A ELEMENT MATERIAL RATING NOTES Interior Bearing wall Any 0 hr Interior nonbrg wall Any 0 hr Structural Frame Any 0 hr Exterior Struct Frame Any 0 hr See footnote #1 Floor/Ceiling Assembly Any 0 hr See Footnote #11 Roof/Ceiling Assembly Any 0 hr Stairs Any None 0 FOOTNCTES. 1) Elements in an exterior wail located where openings are not permitted or where protection of openings i5 required, shall be protected agal-nst external fire exposure as requ2-red for exterior bearing wails or the structural framer whichever is greater, -- 1 1 The ceiling of the basement is required to be protected with I hr. fire - resistive construction aria doors to basements are required to be of 1 3/8 -inch thick S.C. wood or a 20 minute fire assembly. -- Sec. 712 DRAFT STOPS: I -t there is comhii-qf- -i h i I � m1baft Em ,.SEOps Coes, not exceed 69-- feet there is combustibleconstru'cti- M, on in the roof ilin n -n q CZ h 4- --,L I -I 4--1- 1- ./cel--- -. - - - - -- -I_ -1 draf t aceeci j.ruuu square feet and so thatthe horizontal dimengion bet' ween Sec Oues nor eXCeecl 6U teet, .1.2.2 4-1 h6bambm OCCUPANCY SEPARATIONS Table 3-B A3 -B Ohr Code review Project Td.: Address. 121 for: Dance Studio iII Office HEATING EQUIPMENT SEPARATION., NUMB FOR A3 OCCUPANCY MIN I hr. occupancy separation is required around rooms containing boiler or central heating unit greater than 400,000 BTU input* T- Sec. 302.5 EXITS FOR B OCCUPANCY HDWR I fir. occupancy separation is required around rooms containing boiler or central heaTa-ng unit greater than 0 BTU -- sec. 302.5 0.2 ADDITIONAL SEPARATIONS 1.fff refrigeratiLon machinery room shall be separated from the -remainder f the building as required for an H7 occupancy. regardless of area. horizontal occupancy separation may be limited to the actual floor area f the machinery rood. Structural supporting elements shall be protected for the type of construction only. - Sec. 2802 A hour separation SQL r J�. i iis required .l L Lan A3 occupancy. EXIT REQUIREMENTS: FL NAME NUMB SIN MIN PANIC RATEDDOOR NOTES OCC EXITS WIDTH HDWR CORRIDORSWING 1 Office 14 1 0.2 1.fff d l 1 Dance Floor 199 23*3 Yes N/A Out 4 'DOTAL 213 2 3.5 Yes Out In areas where 2 exits are required, the ml'.nimum separation i3 1/2 of the maximum diagonal of the area or floor. — Sec. 1003.3 When 2 t o go except exits are Tn ether for dead -I , exits must be arranged so that J_t is possible direction from any point in a corridor to a separate exit sada not exceeding 20 feet ire length., — Sec. 1005.5 Code review Project I. Address: 121 for: Dance Studio E. Main Office Exit signs arerequired from ali areas where 2 or exits Sec* 1013.1 Main exterior exit doors which obviously and clearly as exi is need be si when approved,. -- exce I Door swing is based on Sec. 1004.2 except as noted. Occupant load factor is basedn Table 10-A. 1 J� r t are L�U c.L �� CX.1L.J �� iasea on '-Ean-Le iU-x except as noted, r are required, Exit width is in feet and based on Sec_ 1003.2. Exit width is to be divided approximalLely equallyamong exits. Width shown for all areas is based on other exits, (0.2) Width shown for 1st floor is based on other exits (0.2) Width shown for other floors & basements is based on stairways. for the minimum width of doors,Sec. 1 For the minimum width of corridorsF see Sec. 1005.2 For the minimum width of stairways, see Sec. 1006.2 FOOTNOTES: 4) Panic hardware is based on Sec. 1016.4. See exception for main exit'in A-3 occupancies and churches* FLUSH AND SURFACE BOLA'S Manually operated edge or surface -mounted flush bolts and bolts ar� prohibited. When automatic flush leaf having the automatic Bush bolt shall not have a door surface -mounted hardware. The unlatching of any leaf steal require more than one operation. -- Sec. 1004 LOCKS AND LATCHES: All means of sates from which knowledge egress i r effort., LANDINGS AT DOORS doors shail be readily to be made without the Sec. 1004+ operable use of (0.3) surface the door .knob or not from the side key or special _L) is i-1 -Lanc inq shall be provideda ch side of doors. When access for persons with disabilities is required. shall not be more than 12 inch lower than the threslaold. When access is not required., the xiUM 2.3 1 inch, - Sec. 1004.9 - 2) Landings shall have a width riot less than the width of , he stairway or width of the doorway, whichever is the minimum length in the direction of exit travel is 44 inches. - Sec. 1004.10 - TRAVEL DISTANCE, 4 Code review f or: Page # 5 Prop ect Id. Dance Studio - Office Address: 121 E. Main BUILDING ACCESSIBILITY: 1) This building including e-ach tenant shall be provided with at least one entrance which complies with the accessible route provisions of CABO/ANSI A-117.1. At least 50 percent of ail entrances shall be accessible. -- Sec. 1103.2.3 2) When more that one exit is required from any accessible spacef each access,ible portion of the space shall be served by not less than two accessible means of egress. -- Sec. 1104.1.1 1 3) When an exit stairway is part o -lc an accessible means of egress, the stairway shall have a clear width of not less than 48 inches between the handrails. The Stairway shali either inn orpprat- e an area of refuge within an enlarged story -level landing or shall be accessed from an area of refuge. -- Sec. 1104.1.2 The area of refuge shall have dire -clt access to the stairway that serves it. -- Sec. 1104.2.1 4) Each area of refuge shall be sized to accommodate one wheelchair space not less than 30 inches by 48 inches for each 200 occupants, or portion thereof. -- Sec. 1104.2.3 5) If the area of refuge is not within the stairway, it shall be separated from the rest I of the story by a smoke barrier having at least a one- hour fire -resistance rating. Smoke barriers shall extend to the roof or floor deck above . Doors shat be smoke and draft control assemblies with a rating not less than 20 minutes. -- Sec. 1104.2.4 6) Two-way communications are required, --- Sec. 1104.2.5 7) Each area Must be identified by a sign stating AREA OF REFUGE and the international symbol of accessibility. 8) NOTE: Exit stairways, in bul'idings protected throughout by an approved automatic sprinkler system are NOT required to . incorporate an area of refuge. Sec. 1104-1.2 exception #2 AUTOMATIC SPRINKLER If openings are not is floor area more sprinkler system is a minimum dimension opening in every 50 NOTE.- Openings must SYSTEMS: Provided in each FA feet of exterior wall or there than 75 feet from an exterior opening, an automatic required. Sec. 904. 2.2 Note,.- Openings shali have of 30 inches. There must be at least 20 sq.ft. of lineal feet of wall. be entirely above the adjoining ground level. An automatic sprinkler system is required in enclosed usable areas above or below stairs,, -- sec. 904.2,3.4 Code review Project Id., Address: 121 for: Dance Studl4o E. Main - Office STANDPIPE REQUIREMENTS: There is no requirement for a standpipe. -- 'Table 9-A FOOTNOTES: 47 If the total occupant load for the building is greater than 1000, then a class IT standpipe with a hose is required. -- Table 9-A VENTILATION: All areas customarily occupied by humans ventilation by means of openable exterior less than 1/20 of the total floor area or P, mechan-ical1v operated ventilation system, Pr 4 shall be provided with naturai openings with an area of not shall be provided with a Such system shall be capable .-Lil ILCUILL UL _LJ UU01C zeet per minute ol outside aa'.r per occupant. ­ Sec.. 1202.2.1 WALL AND CEILLING FINISH: 1) Wall and ceiling finish materials Sec. 804.1 and Table 8 -Bo 2) Carpeting on the ce Imii I ng is spread rating, -- Sec. 804.2 required required to have a j) 'Ti1 waii coverings shall have_ Class I flame and shall be protected by automatic sprinklers acceptance criteria of U.B.C. Standard No. 8-2 INSULATION NOTES: 1. 3 J F tc) Comply With Class I flame spread or meet -- Sec 0 i insuiaTion material Including facings are requIred flame -spread rating of 25 or less and a maximum smoke unless it is in a concealed space and the facinn -lis in a wall or ceiling., -- Sec. 707.3 exc.2 2) Foam plastic insulations are required to be Protected. ADDITIONAL REQUIREMENTS: For A3 occupancy PLATFORM: 1) Permanent platfo =s shall be constructed for the building tVpe of construction, -- 9 rating. the 805 to have density contact a of 450 with -- Sec. 2602 of materials as required Sec. 405.2 unuer the plat corm is 11 used for any purpose (i inciuding storage) other than equipment wi-rng or piumbing, then the floor construction shall be not less than I hour fire reB-istive. -- pec. 4Ub.2 Code review Project I. Address.- 121 for Dance Studio E. Main Office For B occupancy Floor -1st Occupancy -Dance Floor when seats are not fixed, the capacity of this area is be posted at 199 occupants in a conspicuous place on an sign near the main exit . --- Sec. 1002.3 required to approved Code review Project id IV Address.- 121 Dance Studio E. MaJ'-n - Of f furca Page # 8 ACCESSIBLE FACILITIES: NOTE..* Except as noted, sect' i -on numbers listed below are from CABOMNSI A117.1 - 1992 WATER FOUNTAINS AND WATER COOLERS: At least 50 percent of drinking fountains, but not less than one, provided on every floor shall be accessible. -i- .. cc 1 units must comply with the following: 1) Spout is to be within 36 inches of the fioor. -- sec. 4-15.2.1 2) Spout arranged for paraliel approach shall be located 3 -inches maximum from the front edge. SPOuts of cantilevered units with knee and toe clearances shall be located 15 inches minimum from the vertical support and 5 inches maximum from the front edge, -- Sec. 4.15.2.2 r 3) Spouts shall prov-1de a flow of water 4 -inches height minimum. -- Sec. 4.15.2.3 4) Operable parts shall be located at or near the front edge of the unIt and shall comply with 4.25.4 -- sec. 4.15.3 5) A cantilevered unitI. f the vertical sup is required to extend 17 inches minimum from port. Clear knee space must provide a clear area of 8 inches in depth at 27 inched high and 11 7 minimum above the floor. -- Sec. 4.15.4,.,l inches at 9 inches 6) Forward approach unIts shall COMP-ly with 4.2. Units in alcoves shall coMply with 4.2.4.4. Units not having the necessary knee and 'Loe clearance or clear space under thern shali comply With 4. 2.4 and have a clear floor space- that allows a person in a wheelchair to make a parallel approach.. -- Sec. 4.15,4.2 TOILET FACILTTIES: 1) A 60 inch diameter unobstructed turning space is required 20-n the toilet room, -- sec. 4.16.3. 4.2*3 Fig. D4.2.3 2) Water closet shall be mounted adjacent to a side all or partition. The distance from theside wall or partito Ion to the centerline of the water closet shali be 18 in. Sec 4617.1 3) When the accessible water closet i3 not in a stall: The clear floor space shail be 48 In minimum -in front of the water closet and 42 in from the Center line of the water closet on the side not adjacent to the wall, -- Sec., .1 ,2 & Fig& .1 ,2 4) When the accessible water closet is in a stall - The stall shall be 60 in wide minimum and 56*in deep mini -MUM for wall hung water closets and59 in deep I inounted water closets, -- Sec. 4.18-3.1 M'nimum for fioor If the do -or swings into the stallf the requ-ired depth shall M be inch.by 36 inches minimum. Fig. B4.18$*1 The bars are to. be 33 to 36 inches- above the fioor and 3hall be provl 4ded on the rear wall and on the Side wall closest. to the water closet, -- Sec. 4.24.2.2 & Figs. IB4.17.3r B4.17.4 and B4.18.3.1 a) Sade grab bar is required to start with"n 12 inches of the backwall and extend to 54 inches from the back wall. (The minimum lh of the bar is 42 in) -- Code review Project Id.: Address; 121 for,, Dance Studio E. Main - Of f ice Figs. B4.17-3 and E34,18.3.1 b) The rear bar shall be 24 in long minimum, centered on the water cioset. Where space permits, the bar shall be 36 in long minimum, with the additional length provided on the transfer side., -- Sec. 4.17.A -.L.2 & Figs. B4*17.3f B4.17.4 and B4.18.3.1 6) The top of the seat on the water closet is required to be 17 to 19 inches above the floor. -- sec. 4.17.3 & Fig, B4.17-3 7) Accessible urinais shall be of the stall type or wali hung with the rim at 17 inches maximum above the floor.. -- sec. 4. 19.2 8) A clear area of 30 X 48 inches minimum is required in front of the urinal. Privacy shields shall not extend beyond the front edge of the urinal rim, unless they are 30 inches apart minimum* -- Sec. 4.19.3 9) Accessible lavatories shall be mounted with the rim 34 -inches maximum above the fioor and a clearance of 29 inches minimum from the floor to the bottom of the front edge of the apron, -- Sec. 4.20-2.1 & Fig. B4.20.3.1 10) It shall extend 17 inched minimum from the wall. The clear knee space shall be 8 inches in depth minimum at 27 inches minimum above the floor and 11 inches in depth minimum at 9 in minirnum above the floor. The dip of the overflow shall be 'ignored when checking the clearances. -- sec. 4.20.3.1 & Fig. B4o2O.3.1 1 ) A clear floor space of 30 X 48 inchesmin' imum shall be provided in front of the lavatory and shall extend 19 inches maximum under the iavatory, -- See. 4.20.3.2 & Fig. B4.20.3.2 12) Water supply anddra--in pipes under lavatories shall be L' insulated or o-�-herw-J-se treated to protect ains Sec. 4.20.4 ag t contact. 13) The bottom of mirror i's required to be w�"Lthin 38 inches of the floor dip -- Sec. 4.1 6.6 & Fig,* B4.20 -3.i Code review Project I. Address: 121 f or: Dance Studio E. Main I Of f -ice GLAZING REQUIREMENTS All glazing ire hazardous -locations is required to be of safety glazing material,. -- sec. 2406.3 & 2406.4 Locations: 1) Glazing in iiigress and egre3s doors except jalousies. 2) Glazing in fixed and sliding panels of sliding door assenblies and panels in swinging doors other, than wardrobe doors. 3) Glazing in storm doors. 4) Glazing in all unframed swinging doors. 5) Glazing -in doors and enclosures fffor hot tubs, whirlpools, saunas, steam roomsf bathtubs and showers. Glazing in any portion of a bulldIng wall enclosing these compartments where the bottom ex osi:,q edge of the glazing *s less than 60 inches above a standing surface and drain inlet. 6) Glazing 'n fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24 -inch arc of e-ither vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is -less than 60 inches walking surface . K-OLi ove e 7) Glazing in an ind-1vidual fixed or operable panel, other than those locations described 'in iteras 5 and 6 abovef than meets all of the following conditions, A. Exposed area of an individual pane greater than 9 sauare fee+ - B. Exposed bottom edge less than 18 inches above'the fl"Loor. C. Exposed top edge greater than 36 inches above the floor. D. One olc- more waiking surfaces within 36 inches horizoTitaily of the plane of the glazing. 8) Glazing in railings regairdless of he.ight above a walking surface, Included are structural baluster panels and nonstructural in -fill panels. 9 Glazing in walls and fences used as the barrier for indoor and outdoor swimming pools and spas when the bottom edges is iess than 60 inches above the pooi side and the glazing is within 5 feet of the pool or spa deck area. 10) Glazing in walls enclosing stairway landings or within 5 feet of then bottom and top of sta r irways where the bottom edge is less than 60 inches above the walking surface,