Loading...
HomeMy WebLinkAboutREVIEW - 00-00010 - Ricks College (BYUI) - Radio Station/Graphic ServicesMarch 3, 2000 RulonNeilsen Ricks College Physical Plant Rexburg, ID 83440 Deer Rulon,, NATE OF IDAHQ , Box 280 12 North Center Street Rexburg, ftlaha $3440 Phony (208) 359-3020 fax (2O8) 359-3022 e-mail rexburg@srv.nefi I have reviewed the drawing for the KFJC building and have identified the following discrepancies: 1. The handicapped ramp to the parking lot is steeper than the maximum allowed slope of 1: 12 (as per ICGANSI A 1 2. The curb at handicap ramp must also be configured for a maxxmum 1: 12 Slope 12 (as per ICC/ANSI A1 171-1998). 3. The 5/8" type X drywall at the ceilings of the Vestibule (room. 10 1), ReceptOF ion (room 102), Cart Storage (room 108), Hallway (room 123), Hallway (room 12._91) and Hallway (room 1.30) must be doubled (as per Section 1005.7 1994 UBC). 4. Door # 07 (entry into Graphics area) must be a 20 minute fire rated door (as per Section 1005.8 1994 UBC). 5. Draft stop in attic required (as per Section 708.3.1-2.2 1994 UBC). 6. Show trash receptacle. 7. Rexburg Madison County Fire Department has. identified some problems that need to be addressed. I have attached a copy of their fmd* ngs to thisletterM Please make the necessary changes to the pian and return two copies to me at pity Half. Thank you for your cooperation in this matter. If you have any questions Blease gimme m- e a call at 3 5 9- 3 020 ext. 3 14. SM'cerely., Val Christensen Assistant engineer cc: Dere Owens Joe Laird P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Cede Plan Review Building Name: Risks College Studic for Building Address& East Viking Drive Plan Date: .02714-00 1 Review Date. 03/08/00 Mmv KRIC & Graphic Services Stories: One Tyke of Construction: V -N Occupancy Classif ica-U-ion: New Construction Floor Area: 3, 800 Existing E'laar Area: N/A Square. Feet 1) Required Fire Flow (Appendix III -A) ; 1, 750 gpm 2) .Water Suppler (Article 9', Section 9a3) Required: Yes Fire Hydrant Location: 385' west of parkin lot entrance Fire Hydrant Flows: Okay Water Supply Acceptable: Yes Fire Hydrant Location Acceptable. No Water 5uppiy Comments: of the new. building_. You will need to add a -fire hydrant in front 3.) Fire apparatus Access Roads (Article 9 Section 9Q2) Required: Yes Complete Road Acceptable., Comments : Access .-ilot will be from Viking Drive Yes and entrances to the 4) Access Roads and dater Supply, Including Fire Hydrants Are Required To Be Installed And Made 5erv�.ceable Prior �o And During T�me Of Construction (Article 9 Section 901.3) Yes S).Installatior� Of Portable Fire Extinguisher (Article 10 Section 1 2 Required :� Loci } Yes flan Page Review 2 Type Provided Acceptable: Yes 6) .Automatic Fire Extinguishing Systems: Article 10 Section 1003 Required: No 7).Ferre Alarm Systems (Article Type Of System Required -a., Nome 10 Section ?007}Required: Na Type Of System Being Provided: Automat' y i c & Manual Fire Alarm System Acceptable -. No r Comments: I will need the following information before installation. 1001.3 Plans. Completeplans and specifications for fire alarm systems; fire -extinguishing systems, including automatic sprinklers and wet dry standpipes; halon systems and other special types of automatic fire-extingu.ishing systems; OF basement pipe inlets; and other fire -protection systems and appurtenances thereto shall be submitted to the fire department for review and approval prior to system installation. Plans and specifications for fire alarm systems shall inclu+de,,but not be limited to, a floor plan; location of all alarm --initiating and alarm -signaling devices; alarm control- and trouble -signaling equipment; annunciation; power connection* battery calculations; conductor type and sizes; voltage drop calculations- and L manufacturer, model numbers and listing information for all equipment, devices and materials. The horn/strobe spacing needs to he adjusted in the hallways. The hallways are over 30" and would require two strobes,, bar placing them at the end of the hallway so they would be visible from both direction You would only need to add one. The three restroom would require strobes be. installed. Strobes are required in any co=on use this I was unsure on some of the rooms if they would fall in th--Ls category, Plans As Submitted Are Acceptable: Plans Checked By: Dee Owens_ Please furnish comm, ents hack manner: New dire aia--v- I L -m Plan - Yes with attached corrections to the plan and location Date.- 03-08-00 reviewer in the of new fire h f ollowing dram