HomeMy WebLinkAboutREVIEW - 00-00010 - Ricks College (BYUI) - Radio Station/Graphic ServicesMarch 3, 2000
RulonNeilsen
Ricks College Physical Plant
Rexburg, ID 83440
Deer Rulon,,
NATE OF IDAHQ
, Box 280
12 North Center Street
Rexburg, ftlaha $3440
Phony (208) 359-3020
fax (2O8) 359-3022
e-mail rexburg@srv.nefi
I have reviewed the drawing for the KFJC building and have identified the following
discrepancies:
1. The handicapped ramp to the parking lot is steeper than the maximum allowed
slope of 1: 12 (as per ICGANSI A 1
2. The curb at handicap ramp must also be configured for a maxxmum 1: 12 Slope 12
(as per ICC/ANSI A1 171-1998).
3. The 5/8" type X drywall at the ceilings of the Vestibule (room. 10 1), ReceptOF
ion
(room 102), Cart Storage (room 108), Hallway (room 123), Hallway (room 12._91)
and Hallway (room 1.30) must be doubled (as per Section 1005.7 1994 UBC).
4. Door # 07 (entry into Graphics area) must be a 20 minute fire rated door (as per
Section 1005.8 1994 UBC).
5. Draft stop in attic required (as per Section 708.3.1-2.2 1994 UBC).
6. Show trash receptacle.
7. Rexburg Madison County Fire Department has. identified some problems that need
to be addressed. I have attached a copy of their fmd*
ngs to thisletterM
Please make the necessary changes to the pian and return two copies to me at pity Half.
Thank you for your cooperation in this matter. If you have any questions Blease gimme m- e a call at
3 5 9- 3 020 ext. 3 14.
SM'cerely.,
Val Christensen
Assistant engineer
cc: Dere Owens
Joe Laird
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Cede
Plan Review
Building Name: Risks College
Studic for
Building Address& East Viking Drive
Plan Date: .02714-00 1
Review Date. 03/08/00
Mmv
KRIC & Graphic Services
Stories: One Tyke of Construction: V -N
Occupancy Classif ica-U-ion:
New Construction Floor Area:
3, 800
Existing E'laar Area: N/A
Square. Feet
1) Required Fire Flow (Appendix III -A) ; 1, 750 gpm
2) .Water Suppler (Article
9',
Section
9a3) Required: Yes
Fire Hydrant Location: 385'
west of
parkin lot entrance
Fire Hydrant Flows: Okay
Water Supply Acceptable: Yes
Fire Hydrant Location Acceptable. No
Water 5uppiy Comments:
of the new. building_.
You will need to add a -fire hydrant in front
3.) Fire apparatus Access Roads (Article 9 Section 9Q2)
Required: Yes Complete Road Acceptable.,
Comments : Access
.-ilot
will be from Viking Drive
Yes
and entrances to the
4) Access Roads and dater Supply, Including Fire Hydrants Are
Required To Be Installed And Made 5erv�.ceable Prior �o And During
T�me Of Construction (Article 9 Section 901.3) Yes
S).Installatior� Of Portable Fire Extinguisher (Article 10 Section
1 2 Required :� Loci
} Yes
flan
Page
Review
2
Type Provided Acceptable: Yes
6) .Automatic Fire Extinguishing Systems: Article 10 Section 1003
Required: No
7).Ferre Alarm Systems (Article
Type Of System Required -a.,
Nome
10 Section ?007}Required: Na
Type Of System Being Provided: Automat'
y i c & Manual
Fire Alarm System Acceptable -. No
r
Comments: I will need the following information before
installation. 1001.3 Plans. Completeplans and specifications for
fire alarm systems; fire -extinguishing systems, including
automatic sprinklers and wet dry standpipes; halon systems and
other special types of automatic fire-extingu.ishing systems;
OF
basement pipe inlets; and other fire -protection systems and
appurtenances thereto shall be submitted to the fire department
for review and approval prior to system installation. Plans and
specifications for fire alarm systems shall inclu+de,,but not be
limited to, a floor plan; location of all alarm --initiating and
alarm -signaling devices; alarm control- and trouble -signaling
equipment; annunciation; power connection* battery calculations;
conductor type and sizes; voltage drop calculations- and
L
manufacturer, model numbers and listing information for all
equipment, devices and materials.
The horn/strobe spacing needs to he adjusted in the hallways. The
hallways are over 30" and would require two strobes,, bar placing
them at the end of the hallway so they would be visible from both
direction You would only need to add one. The three restroom
would require strobes be. installed. Strobes are required in any
co=on use this
I was unsure on some of the rooms if they would
fall in th--Ls category,
Plans
As Submitted
Are
Acceptable:
Plans
Checked By:
Dee
Owens_
Please furnish comm, ents hack
manner: New dire aia--v-
I L -m Plan -
Yes with attached corrections
to the plan
and location
Date.- 03-08-00
reviewer in the
of new fire h
f ollowing
dram