HomeMy WebLinkAboutREVIEWS - 00-00004 - Ricks College (BYUI) - David O McKay LibraryBRUCE SUTHERLAND
MAYOR
ROSE BLEY
CLERK
RICHARD HORNER
FR EAS URER & F1NANGIAL 0FRCER
Mr. Bob Niblett
Nielson -Bodily & Assoc.
990 John Adams Parkway
P.O. Box 2212
Idaho Falls,, ID 83403-2212
RE: Remodel fast & West Wings
David 0. McKay Library
Ricks College
STATE of iaAHo
November 29, 1999
" I A" 0 t
12 NORTH CENTER STREFT
REXBURG, IDAHO 8344
PHONE (208) 359-3020
FAX (208) 359-3022
The City of Rexburg has reviewed the plans for the subject project and has the following
comments:
1 ---- An analysis of the building sire indicates that the actual buildi'ng sire of the West Wigg of
the building is larger than the allowable building size for an unsprin.kled, Type 11- 1 hr. building.
The actual building sire hof the three floors of the Nest Wing) is approximately i9,600 sq. fit.,
while the allowable area for a Type H-1hr. building is 72,00d sq. fit. (See. attached capes of
computer analysis afWest and East Wings.) The meas of the stairs, rest rooms, etc. can not b e
deducted from the area of the building. The number of people that mai be in these accessory
areas can he deducted from the total number of people calculated fior the building, but the actual
sq. ft. area of these accessary areas cannot be deducted from the total building area.
it is my understanding that the installation of a sprinkling system ire the West ming is one of the
,AlLCnic7.tc L31dS in }iC>lu CiJilLTciC:t. With thc Izig1i fuel load m -id largc ntunUcr of people in the
building, we. would highly encourage you to made the installation of a sprinkling system your
highest pri'ority.
Note that Table 9A, kine 5 indicates that the West Wing needs to have a Class II Standpipe and
hese if it does not have a sprinkling system.
2 --- All EXITS needemergency exit illumination as required in 94UBC Sec. 1012.2 - Separate
Sources of -Power. I didn't see this called for -in the electri'cai plans.,
3 --- Sht. A62--- Dimensions are not given for the drawing showing the Handicapped Stall for
the Fast Wing Second Floor, Large Scale Toilet Room. Clearance di'mensions should be at
D-oor swing Out.
4 --- Sht. A2. i & A22 -_. It mould be beneficial to enlarge Door E I 46A s it more nearly
approximates the width of Hallway 146, The size of t��s southwe�� exit system meds -to more
nearly approximate the size of the northerly main exit system.
I struggle with what to suggest regarding Doors El 50A and E266A that are a part of -the arca
Separation Wall separatilia the East and West Wings of the Library. Technically bath doors
should swing out in both directions so that people madly exiting either the East Wing or the- West
Wing don't get mashed up against a dosed door that only swings toward the exiting crowd. To
find out how others have solved this problem, I called 1CB0 Headquarters to ask their experts
how they ustially see this type of situation handled. They said they usually gee two separate
doors at such locations, with one door marked EXIT which opens outward handling traffic in one
direction and a second door (adjacent to the first) that is marked. EXIT an the other side and
which opens outward in the other direction fliereby handling traffic in the opposing direction. I
think this is the best solution, if you have the room to do it. If you don't have enough room, the
door svving �h� way you .ave �t �s probably the best way to �o. i would sill mark tne ciaor as an
EXIT for people going from the West Wing to the Easy Wing.
Also, be sure there are large
handles
an
the west side of the
doors
and that the wards "FIRE DOOR
- PULL TO OPEN"' are
written
(in
large letters) on the
back (west)
side of the doors when they
are in the cloyed position..
If you can use the two :E.YZT door salution(one door dor each direction) it would be good to put
and F 15 EXIT sign in the corridor near the men's rest xoorri (W 14 8) (and an F 8 at the entrance to
Room WI 23) and in Corridor W242 (and an F8 at the entrance to Roam W232). If you don't
use this solution, it is probably best to leave the advance EXIT signing the may you have shown
ii.
S --- Sht. E2. I --- Cin the .First Level Easy, it would be good to put an F 15 EDIT sign in the
corridor in brant of Group Study Pim �;1. 3 � paxn��ng towards the north exit.
6 --- Sht. X2.2 ---Y On the Second Levu East, you use an F 15 EDIT sign above Stairs E 17 S.
It would seem desirable is also use an F 15 EXIT sign above Stairs E 165 as it would show up
better.
This has been a rather "hurried" review of the plans.
you.regarding them.
Very truly you
,4s,
JOSEPH A. LAIRD, P.E.
CITY ENGINEER & BUILDING OFFICIAL
If we find any other items we will contact
2
CABG/ANSI Al 17.1-1992
A rei Pa"%/ 10 V" ;V-% ALTERNATE DOOR
r.
c.
it
54 min
1370
56 min (WALL -MOUNTED W,C.)
42 (1065) rn-in 1420
LATCH APPROACH 59 min {rLO0R-MOUNTED VV,C.)
T
ONLY., OTHER 1500
APPROACHES 48 �'
Y
Fig. B4. 18-3.1 id's,
Wheekbair Accessible Toilet StaHs
Door Swing Out LF.��,4
min
__v. 1420
59 min
1 500
(raj End of Row
VVALL -IVI UU N I t U W.C.)
(FLOOR -MOUNTED W.C.)
Firs. B4. 1 8.3.2
Wheelchair Accessible Toilet Stalls -
Door Swing In
WE
W
0
November 29,1999
Payne Engineering
107 South 18'' Ave.
� kfi�, ft 1 ro
, Idaho 83201
To Wham It May Conce
t
I have reviewed the plans for the fire warm system for the Ricks College Library
remodel and came up with the following items that need to be addressed:
Basement Level West:
Test Center Lobby W10 inadequate strobe coverage. NFPA 72 Sec. 6-4.4.1.2
Test Center
W24 inadequate strobe
coverage. NFPA
72 Sec. 6-4.4.1.2
Mechanical
Room W25 inadequate
strobe coverage.
NFPA 72 Sec.
6-4.4.1.2
Room W46 strobe east end needs to be visible from Hall W50. NFPA 72 Sec. 6-
4.4.2.2
Vestibule W51 should have a null station. UFC 1007.3.3.1
If any of th
e unexcavated area is to be used for storage, it W-111
with horn/strobes.
First Level West:
UFC Sec. 1007.33,14
need to be covered
Reference Area/Computer Reference W1 15 inadequate strobe coverage. NEPA
72 Sic. 6-4.4.. 1 .2
Office VII'f 38 move horn/strobe to east wail.
Staging W 122 move to
Computer Research; 1N
4.4.1.2
NFPA 72 Sec.. 6-4.4.2.2
hall wall. NFPA 72 Sec. 6-4,.4.2.2
111 E inadequate strobe coverage.
NFPA 72 Sec. 6-
Area
between Computer Reference W115 and Circulation W1 19 inadequate strobe
coverage. :NFPA 72 Sec.. 6-4.4.1.2
Stairs W1 51 inadequate strobe coverage.
NFPA 72 Sec. 6-4.4.2.2
TV Viewing W 12 3 inadequate strobe coverage.
NFPA 72 Sec. 6-4.4.1.2
- Page Z
group Study 1 1 1 1 I C inadequate stro be coverage.
Second Level West-,
November 30. 1999
NFPA 72 Sec. 6-4.4
12
Study/Stacks W240 Computer Research W240 inadequate strobe coverage. NFPA
72 Sec. 6-4.4.1.2
Special' Collections
11'V'230 inadequa#e strobe coverage.
Special W230E inadequate strobe coverage.
Cataloging W 224 inadequate strobe coverage,
Notebook Conn
NFPA
72 Sec. 6-4.4.1.2
NFPA 72 Sec. 6-4.4
NFPA 72 Sec. 6-4.4
ect W223 inadequate strobe coverage. NEPA 72 Sec. 6-4.4.1.2
Corridor W242 inadequate strobe coverage. NFPA 72 Sec. 6-4.4.2.2
Stairs W255 inadequate strobe coverage. NFPA 72 Sec. 6-4-4-2-2
Third Level West.-
Computer Area W308 Inadequate strobe coverage. NEPA 72 pec. 6-4.4.1.2
Stairs W302 inadequate strobe coverage. NFPA 72 Sec. 6-4,4.2.2
Hall W377 inadequate strobe coverage. NFPA 72 Sec. 6-4.4.2.2
Media Lab Stock Room W358 inadequate strobe coverage. NFPA 72 Sec. 6-
4.4.1.2
Corridor W376 -W378 inadequate strobe coverage. NFPA 72 Sec.. 6-4.4.2.2
Corridor W381 inadequate strobe coverage. NFPA 72 Sec. 6-4.4.2-2
Audio/Visual W324 inadequate strobe coverage. NFPA 72 Sec. 6-4.4.1.2
Audio/Visuall Storage W322 inadequate strobe coverage. NFPA 72 Sec. 6-
4.4.1.2
Self Serve
Video
Editing W357A W315-cV inadequate strobe coverage. NFPA 72
Sec. 6-4.4.1.2
First Level East.-
Computer Area E 150 istrode coverage. N SPA 72 See. 6-4.4.1.2
Mechanical E752 inadequate strobe coverage. NFPA 72 Sec,. 64_4.'1.2
Faculty Research E102B inadequate strobe coverage. NFPA 72 Sec. 6-4.4.1.2
* Page 3
November 30, 1999
Hallway between Circulation E 172 to Stacks Q -Z E 120 inadequate strobe coverage.
NFPA 72 Sec. 6-4.4.1.2
mop Afgn Elio OR8 Ron of gfoo 1noggQUgto gt1080 00V@1�09. PA 71 9@c. 6-
4.4.1.2
Group Study E136 inadequate strobe coverage. NFPA723ec.64.4.1.2
Second Level fast:
Group Study E246, E248, E250, E252, E254, E256, E258, E214, E216, E224, E226,
and E228 inadequate strobe coverage. UFC Sec. 1007-3.3-3.4
Study E242 Study/Stacks E266 inadequate strobe coverage. NFPA 72 Sec. 6-
4.4.1.2
Math Lab E202 inadequate strobe coverage.
NFPA 72 Sec. 6-4.4.1.2
Tutoring E206 inadequate strobe coverage. NFPA 72 Sec. 6-4.4,1,2
Hall E207 inadequate strobe coverage. NFPA 72 Sec. 6-4.4.2.2
Train/Tutor E230C inadequate strobe coverage. NFPA 72 Sec. 6-4.4.1.2
Hallway off Train/Tutor E230C inadequate strobe coverage. NFPA 72 Sec. 6-
4.4.2.2
Reading LabE230 inadequate strobe coverage. NFPA 72 Sec. 6-4.4.1.2
The following Uniform Fire Code sect -ions ars included for your reference:
1007'.3,3,1 Manual fire alarm boxes. When a manual fire alarm system is required,
manual fire alarm boxes shall be distributed throughout so that they are readily
accessible, unobstructed, and ars located in the normal path of exit travel from the
area and as follows:
1. At every exit from every level,.
2-Additionalfire alarm boxes shad be located so that travel distance to the nearest
box dies not exceed 2a0 feet (S0 960 mm).
When fire alarm systems are not monitored, an approved permanent sign that reads
LOCAL ALARM ONLY -CALL FIRE DEPARTMENT shall be installed adjacent to
each manual fire alarm box.
EXCEPTION: SeParate signs need not be,provided when the manufacturer has
permanently provided this information on the manual fire alarm box
1007.3.3.3..3 Aud'Ibility. The alarm signal shall be a distinctive sound which is not
used for any other purpose other than the fire alarm. Alarm-signaling devices shall
produce a sound that exceeds the prevailing equivalent sound level in the room or
space by 15 decibels minimum, or exceeds any maximum sound leve! with a
duration of 30 seconds minimum by 5 decibels minimum, whichever is louder. Sound
levels dor alarm signals shall be 120 decibels maximum.
r
246 Chapter 61, Notification Appliances for dire Alarm Systems
64=1 There are two methods of visible si nalin Thes
methods in which the messy c)t notification
condition is n d by d'rest viewing
illuminat-
ingappliance or by means of illumination n f the urroundi.
area.
NOTEE One method of deternnining compliance with Section 6-4
is that the product be listed in Rccordance
Standard for Safety Signaling a vices for the Hearing Impaired.'
641 Light Pulse Characteristics. The flash rate shall
not exceed two flashes per second (2 Hz) nor be less than
one flash every second (I Hz) throughout the listed voltage
rage of the appliance.
64n2ml
maximum pulse duration shall be 0.2second with
percent. The pulse duration i
defined as the time interval between initial and final f nth` �f
1 ,percent of maximum l*
The light intensity of a pulsed source may be graphed
as a bell-shaped cuzve. The duration of thepulse is
measured beginning at the point when the upward side
of the curve exceeds 10 percent of the maximum inten-
sity to the paint where the downward side of the curve
drops below 10 percent of the maximum intensity.
6411 The light source calor shatl be clear or nominal white
and shall not exceed 1000 candela (cd) effective intensity).
Source Untertsity is a measure of the light output of the
appliance. The unit of measure is the candela (cd). ('This
unit was formerly called "candlepower." There is a one -
to -Dile relationship between candela and candlepow�r. }
As you move away from any fight source, its zl�umina.-
tiOn decreases. Illumination is measured in units of
lumens 0M) per square meter (also called ug"), or
lumens per square foot. (Formerly; the unit used to
describe illumination was the " foot -can.dl e." One foot-
candle equals ozie lumen per square foot, One lumen per
square meter equals {x.926 foot-candles.)
Because strobe lights flash for a very brief ptriod of
time, the perceived brightness can vary depending on the
actual peak source strength and duration of the flash.
One appliance might r. each a beak intensity of 1(]00
candelas in 0.1 seconds while another might reach 750
candelas in Q.2 seconds. Neverthelessthe human eye
IIIight perceive both as being equalIv bri'ght- A mathe-
matical relationship is used to relate the perceived
brightness of a strobe dight to that of a constan�.ly burn-
ing light. The result is called the effective intensiry
(candela, effectzve or cd, ef£.).
NATIONAL FERE ALARM CODE .HANDBOOK
64 3
p iance hotometrics.. 'risible notification
antes used i ti Pli rode shall be located so that the`a
operatina effect of the a lance can be seen by the intended
viewers and shall be of a type, s,ize, intensity, and numb .
that the viewer can discern whenthey have ° r
regardless of theviewer'orientation.In the same manner that Y
.gnats produced by audiblenotification appliances must be clearly heard, signals
:
produced by visible notification c must alsoclearly seen
t regard to the viewer position4a
within the protected area.
:I-:
ApplianceLocation. Wt0 app f
ances shall
have their bottoms at h ights
less than 80 in. ( and no areater
rri).ell-
.,
aliances shali be instalJed per Table .a
Eti Appliances installed in sleeping°
COMPly with 6-4.4-3.
In. ra4rn.s with sufficient ceiling height, the bottom of
a wall-mountedviszble notification appliance must beat
Ieast 6 feet 8 inches (2 m) above the floor, but not more
than 8 feet X2.4 mj above the floor. The exception refers
to 6-4.4.1'3' for the location of cQmbl-nation units within
sleeping areas. If the linear dirnensl'on of a sleeping F
room exceeds :1 6 feet, 6-4.4.3.2 requires a combination
audible/visible notification appla�nce to be located
within 16 feet (4.87 111) of the pillm�v
The minimum mounting height is intended to locaM4.
appliances so they are riot blacked by common furnish-
ings or equipment. The maximum mounting is impor-
tant because the iIlumi.naric3n from a visible appliance
reduces drastically with distance and angle fzorn a iiori-
zonta plane through the appliance, dor this reason, wail
mounted appiiances are 11'mited to 96 'inches (2.44 m}
above the flo or. Ceiling mounting is permitted, howrn,-cr,
tie apph"aizces must be specifically I'sted for cell'
ng y,
mounting.
64AMI * Spacing in Roams.
A "�`4.4.1 Areas large enough to exceed the rectangular
dimensions given in Figures A-6-4.4.1 (a.), (b), and (c) require
additional appliances. Often, proper placement of appliances
can be facilitated by breaking down the area into rnuItipie
squares and dimensions that fit most appropriately (see
Figures A-6-4.4.1 (a), (b), (c), and Mi. An area 40 ft X12.2 m�
wide and74 ft (22.6 m) long can be covered wi wo 60 -cd
appliances. Irregular areas reed more careful planning to
maks car#airs th,at a# least onc 15 -cd aPpliarioe is installed for
each 20 -fit x 20 -ft (6.09-m x 6.09-m) area.
k;
P.
�a
rpt7
SrL•
0.
41
0
10 ft
40 #t {12,2 rr►}
1
22 ft(6.7 m)
loft
(3.1 )
I j Incorrect
GQ i# (12.2 rn) I I
30 ft (9.1 rn)
\LI
vin�_ J
30 fit (9,1 m} y
s
Figure A -6-4.4.7{a} Irregular area spacing.
These figures were added to avoid rnisizzterpretation
of the text. Fzgure A -6-4.4.1(a) demonstrates how a non -
square or nonrectangular room can lie fitted into the
spacing allocation of Tables 6-4.4.1(a) and (b). Figure
A -6-4.4.1(b) demonstrates how to divide a roam or
area into smaller areas to enable the use of lower inten-
sity lights. Figures A-6-4.4. I (c) and (d) show the correct
and incorrect placement of multiple visible notificatzDn
appliances in a xoom.
6'4.4.1 .1 Spacing shelf be in accordance with Figure
6-4.4.1.1 and Tables 6-4,4.1.1(a) and (b). The separation
between appliances shaft not exceed 140 ft ('30 m).
Vis'l-ble notification is antes shall be installed in accor-
dance
with Taale 6-4.4-1.1 (a), using one of the following:
(a)* A singlevisible notification appliance; or
(b) Two visible notification appilancer, located an opposite
galls; or
64 Visible Characteristics, Public Mode
247
. --40 ft (12.2 rte) 0 ft i. 1 m),74 ft (22.6 m) --
e
t: Broken lines represent imaginary waI I.
Figure A-6-4.4. 1Spacing of wall -mounted visible appliancesi
r00 7.
(c)* In rooms 80 ft x 80 #f (24.4 m x 24.4 m) or greater,
where here are more than two appliances in any field of view,
they shall be spaced a minimum of 55 ft (16.76 m) from each
other; or
(d) More than two visible notification'appliances that flash
in synch ronization..
Figure A -6-4.4.1(c) Room spacing ll tion -correct.
NATIONAL FIRE ALARM CODE HANDSOOK
248 Chapter fi: Notification Appliances for Fire Alarm Systems
Table 4.4.1.1 Room Spacing for
Wall-MountedVisible din
Minimum Required Light Output, Candela (cid) (Effective Intensity)
Two Lights per Four Lights per
One Light Ravm (Located on Room One Light
Maximum Room Size Per Roam D j}poSE#e VllalIs) per Wall)
jet} (M) (cd) (cd) (cd)
20
x
20
30
x
30
40x40
1
12:2
0
X
50
60x60
X 15.2
95
0
x
70
80
X
80
0
X
90
100
X
100
110X110
1
12:2
120X120
60
30
130X130
X 15.2
95
N/A: Not allowable.
.1
X 6A
1
Spacing for Ceiling -Mounted
9.14
x 9,14
30
1
12:2
x 12.2
60
30
15.2
X 15.2
95
60
18.3 X1 .
21.3 x 21.3
24.4 X 24.4
27.4 x 27.4
30.5 X 30.5
33.5x33.5
36.6x36.6
39.6 x 39.6
135
185
240
305
375
455
540
635
X-6-4.4.1 .1 (a) iA design that delivers 0.0375 lumenS/f t
(0.4037 lumens/ effective intensity to all occupied aces
= ■ 1 y
where visible t�f !cation required T considered to meet the
minimum light intensity requirements of this paragraph.
A-6-4.4.1
focus-
ing capabilfty of the human eye, specified as 120 degrees in
the ES Handbook. The apex of this eagle is the viewer's
eye. In girder to ensure compliance with the requirements of
6-4-4.1.1 , this angle shouid be increased to approxrmately
135 degrees..
Able appliance improperly located
Visible appliance 30 cd
A.
r
30 ft (g, j m)
Visible appliance 30 cd
30 ft (9,1 m)
a
-50 ft (1,x.2 m)
e
Figure A-6-4.4. 1(d) Poom spacing ll do '
NATIONAL FIRE ALARM CODE HANDE300K
95
95
135
185
240
240
305
375
Table 6-4.4.1.1
b
Room
Spacing for Ceiling -Mounted
Visible
Appliances
Minimum
Required
Light Output,
Candela
(cd)
(EffectiveIntensity)
Maximum
Maximum Room
Ceiling
Size
Height
One Light
tt(m)(ft)
(M)
(cd)
0
X
20
6.1
x.
1
10
3.05
1
30
x
30
9.14
x
9.14
10
3.05
30
40
X
40
12.2
x
12.2
10
3.05
60
50
X
50
15.2
x
15.2
10
3.05
95
20
x
20
6,1
X
6. 1
20
13.1
30
50
x
50
15.2
x
152
20
6.1
11
20
x
20
6.1
X
6. 1.
30
9.14
55
40
x
40
12.2
12.2
0
9A4
11
50
x
50
15.2
x
15.2
30
9.14
150
OTE I : Where ceiling heights exceed 30 ft 1 , visible signal-
ing appliances shall be suspended at or below,30 ft .1 rwall-
mounted in accordance with Table - .4.1.1 (a.).
NOTE 2, Table -4.4.1.1(b) is based on locating the visiblei n l -
I g appliance - ,t the center of the ro rn. Where
'It is not located at the
center of the room, the effective intensity () shall be determined b
doubling the distance from the appliance to the farthest wail to obtain
L
he maxim= room size.
�a
ler
]ht
ht
The 1.996 edition of this Cade has been modified to
reduce the chanes that strobe lights will induce epileptic
seizures in persons with photosensitive epilepsy. The flash
rate has been adjusted so that one, or even two appliances
not flashing in unison can not produce a flash rate that is
considered dangerous. If two or more appliances can be
Viewed at the same time, they must either be synchronized
or located far enough apart so that their intensity at the
viewer's location is low enough to be considered safe.
Visible signaling is a eery complex typic. For this
reason, the Code presents prescriptive requirements
rather than the performance requirements, such as those
for audible signaling. In essence, the bode provides
preset designs that can be used for a variety of actual
field conditions requiring these devices. The prescriptive
requirements contained in the Code are based, in part,
an extensive tests performed by Underwriters Laborato-
ries,
Inc.,. Northbrook) IL.
6M,4K4411 .2 Where j
guration 'is not square, the
square room size that entirely encompasses the room or
subdMdes the room into multiple squares shall be used.
Figure 6-4.x. 1,1 and Tables 6-4.4. 1. 1 (a) and (b) help
to ensure that a sufficient number of properly -sized visi-
ble notification appliances ars installed in each protected
space to provide complete coverage. The ked to proper
coverage in irregular spaces is to divide the space into a
series of squares and provide proper coverage for each
square as if at were an independent space.
6=4.4.2*
Spacing in rri I r .
164.4=21 Table E-4.4.2.1 shadl appy to corridors not
exceeding 20 ft (6.1 m) in width. For corridors greater than 20,
ft (6.1 m) wide, refer to Figure 6-4.4.1.E and Tables 6-
4.4. 1.1 (a) and (b). ire a corridor application, visible appliances
shall be rated not less than 15 cd.
a
The ince � 1 T ii ci r 1�, n r . ��,
l ppl
ances located 111 corridors (less than 20 feet Wide
r
stringent than for those in rooms. It is recognized that
person in a corridor 'is usually movie and alert. Because
the t are usually alert, fewer appliances are
required, which results in greater spacing m long cor'
6-4.4-2.2 The visible appliances shall be located no more
than 15 ft X4,57 mj from the end of the corridor with a separa-
tion no greater than 100 ft (3[}.4 m) between appliances. Where
there l's an interruption of the concentrated viewing path, such
as a dire door, an elevation change, or any other ubstruction,
the area sha#I be considered as a separate corridor.
O-4 VIIS'16le 8karacterlistlics, RU61'ic Mode
P
r
A A
20 ftrn
j
0 ftM)i
40 f
(12.2 m) i
(15.2 )
_oft l
(6.1 m)
r30 ft - 1
(.1 )
40 tt
(12.2
1 �
0 ft
(1.)
Note: Figure 6- . .1.1 is based on locating the visible signalingappliance
at the halfway distance of the longest wall. In square rooms with
appliances not centered or nonsquare rooms, the effective intensity (cd)
from one «s bl signaling pplia shall be d t r fined by Maximurn
room size dimensions obtained elther by measuring the distance to the
farthest wall or by doubling the distance to the farthest adjacerit wall,
whichever is greater, as shown in Tab[e 64.4.1.1Tab[(a).
Figure -+. 1F 1 Room spacing for wall - Lit visible
appliances..
E
N
rZ
4f
Ln
100 ft .. . _
Visible
ice
T
0 ft .1 )
Pour -6-4.4.2 Corridor and elevator area sDac;na allocation.
NATIONALFIRE ALARM CODE HANDBOOK
rr
A
ler
]ht
ht
The 1.996 edition of this Cade has been modified to
reduce the chanes that strobe lights will induce epileptic
seizures in persons with photosensitive epilepsy. The flash
rate has been adjusted so that one, or even two appliances
not flashing in unison can not produce a flash rate that is
considered dangerous. If two or more appliances can be
Viewed at the same time, they must either be synchronized
or located far enough apart so that their intensity at the
viewer's location is low enough to be considered safe.
Visible signaling is a eery complex typic. For this
reason, the Code presents prescriptive requirements
rather than the performance requirements, such as those
for audible signaling. In essence, the bode provides
preset designs that can be used for a variety of actual
field conditions requiring these devices. The prescriptive
requirements contained in the Code are based, in part,
an extensive tests performed by Underwriters Laborato-
ries,
Inc.,. Northbrook) IL.
6M,4K4411 .2 Where j
guration 'is not square, the
square room size that entirely encompasses the room or
subdMdes the room into multiple squares shall be used.
Figure 6-4.x. 1,1 and Tables 6-4.4. 1. 1 (a) and (b) help
to ensure that a sufficient number of properly -sized visi-
ble notification appliances ars installed in each protected
space to provide complete coverage. The ked to proper
coverage in irregular spaces is to divide the space into a
series of squares and provide proper coverage for each
square as if at were an independent space.
6=4.4.2*
Spacing in rri I r .
164.4=21 Table E-4.4.2.1 shadl appy to corridors not
exceeding 20 ft (6.1 m) in width. For corridors greater than 20,
ft (6.1 m) wide, refer to Figure 6-4.4.1.E and Tables 6-
4.4. 1.1 (a) and (b). ire a corridor application, visible appliances
shall be rated not less than 15 cd.
a
The ince � 1 T ii ci r 1�, n r . ��,
l ppl
ances located 111 corridors (less than 20 feet Wide
r
stringent than for those in rooms. It is recognized that
person in a corridor 'is usually movie and alert. Because
the t are usually alert, fewer appliances are
required, which results in greater spacing m long cor'
6-4.4-2.2 The visible appliances shall be located no more
than 15 ft X4,57 mj from the end of the corridor with a separa-
tion no greater than 100 ft (3[}.4 m) between appliances. Where
there l's an interruption of the concentrated viewing path, such
as a dire door, an elevation change, or any other ubstruction,
the area sha#I be considered as a separate corridor.
O-4 VIIS'16le 8karacterlistlics, RU61'ic Mode
P
r
A A
20 ftrn
j
0 ftM)i
40 f
(12.2 m) i
(15.2 )
_oft l
(6.1 m)
r30 ft - 1
(.1 )
40 tt
(12.2
1 �
0 ft
(1.)
Note: Figure 6- . .1.1 is based on locating the visible signalingappliance
at the halfway distance of the longest wall. In square rooms with
appliances not centered or nonsquare rooms, the effective intensity (cd)
from one «s bl signaling pplia shall be d t r fined by Maximurn
room size dimensions obtained elther by measuring the distance to the
farthest wall or by doubling the distance to the farthest adjacerit wall,
whichever is greater, as shown in Tab[e 64.4.1.1Tab[(a).
Figure -+. 1F 1 Room spacing for wall - Lit visible
appliances..
E
N
rZ
4f
Ln
100 ft .. . _
Visible
ice
T
0 ft .1 )
Pour -6-4.4.2 Corridor and elevator area sDac;na allocation.
NATIONALFIRE ALARM CODE HANDBOOK
250 Chapter fi:
Notification Appliances for Fera Alarm Systems
Table 6-4.4.2.E Corridor Spacing for Visffile Appliances
QQrridor Length
Minimum Number of
15 -cd Visible
(f t). (M)
Ujoliancam_q Regciirecf
0
- L
1
-130
131
—230
23 1
- 330
1
—430
43 1
- 530
0-9.14
1
9.45-39.6
39.93
70,E L 100.
100.9 -J 131.1
131.4 -161 .
6-4. 4. 3 * Sleeping Areas,
A=6-4.4-3 Effective intensity is the convennimethod of
equating the brightness of a flashirg light to that of
a steady -
burning light as seen by a human observer.
effec-
five intensity are expressed in candelas. For exam
flash-
ing light that has an effective intensity of 15 cardelas
J1F{ }', the
same apparent brightness to an observer as a 15 -candela
steady-burningsteady-burning light source.
64m4mll Combination smoky detectors and visible appli-
ances shall be installed in accordance with the applicable
requirements of Chapter 6, Chapter 2, and Chapter 5.
This requirement reinforces the detector coverage
requirements of Chapters Z and 5, as well as those of this
Chapter While not expixcitly mentioned in 6-4.4.3.1,
smoke warms da have integral notification appliances,
and these appliances should conform to the require
znents of this chapter,
6-4.4-3.2 Table 4.4.3.E shall ap ly0 Sieg in
g areas
having no 1�near dimension greater than 16 ft (4.87 m). For
larger rooms, the visible notification
located within 16 ft (4.87 f the pillow,
In order to offset the obscuration effect of smoke near
the ceiling, it vvas determined that a value of X77 cd ;.s
required when the notification appliance is located
within 24 inches (610 mm) of the cefling, and a ❑aluOf
110 cd is sufficient when the distance is greater than 24
inches (61Q mm},
64AA T
Where visible appPances are require
of one appliance shall be instafled in the concentrated ,
ew-
erg path such as might be experienced in such areas as.
classrooms r theater stages.
NATIONAL FIRE ALARM CODE HANDBOOK
_ t
Table f-4.4.3.2 Effective inte-nsity Requirements for
Sleeping Area 6
Visible Ngtitica#yen APP11rarl.ce
Dista rtce #torn Ceiling to Top of dens Intensity 6'
Greater than or equal to 24 in. (610 mm) 110 cd
Less than 24 gin. (6� 4 mm) 177 cd
6-5 Visible Characteristj S, iva e ode. Visible it
used in the private mode shall be adequate for their Intended
purpose.
Visible notification appliances in the private mode are
almost always used in conjunction with an audible nati,
fiction. appliance to calf the viewer's attention to the
visible appliance. Many visible appliances in the private
mode provide annunciated information that helps
viewer to locate the smixce of an alazrn, supervisory, or
trouble signal,
6m6 Su
,pplementary Visl e Signa ing , w 16. A suppl
nt r iib pl n i intended n �
t� �r-n rpt an audible
r visible signal,
m�sifiA supplementary � �npance :s not
intended to serve as ons of the requut.red visible notiifica-
tian:3ppl.zan.ces. Examples include non -required remote
annunciators, or non-regm.red flash-
ing lights located in
a gward's OF office maintenance office.
6"6 .-1 A supplementary visible appliance shall comply with
its marked rated performance.
Recognizing that tb.is appliance is not satisfying ,I
requirement, but is Providing a supplemental function, this
subsection makes it mandatory that the appliance function
as inarked mid rated. This requirement discourages manu-
facturers from overrating the marking, which might not be
detected since the appliances are supplementary, and gives
the authority having jurisdiction a basis for verifying tie
performance of such appliances.
6-6.2 Supplementary visible notification aplian�es shad
be permitted to be located less than 80 in. (2'
m) above the
floor.
Because such an appliance is supplementary, it need
1-1nt n}eet the mandatary height requirement for visible
appliances.
6 -
BRUCE SUTHERLAUD
MAYOR
ROSE BAG LEY
CLERK
RICHARD H NE
TREASURER & FINANVAL OF-RCER
Nielson, Bodily & Associates
900 John Adams Parkway
P.O. Box 2212
Idaho Falls, Idaho 83403
STATE IDAHO
November 4,, 1999
RE: Remodel of Library East & 'West Wings C Ricks College
Dear Sir,
12 NORTH CENTER STREET
REXSIlRG, IDAHO 8340
PHONE (208) 359-3020
FAX (2q8) 359-3422
I sent a copy of your "Prelzminary-Development StageI plans dor the subject building remodeIing
to our Fire Marshall for his,preliminary comments.
Attached 'is a copy of his letter comments. You can mach him, Fire Marshall Dee Owens Cc
359-3010., if you would like to talk to hirn regarding his comments.
JOSEPH A. LAIRD, P.E.
CITY ENGINEER
Yom:
From.
Date:
Jaye Laird
Dee Owens
11/02/99
Re: Ricks College Library Remodel
1 reviewed the plans for remodeling the Library and came up with the following items
that f would like to see addressed:
Fire department access to this building is eery poor. i would like to sit down with the
College and see if we could come up with some type of solution to this problem. This
is not the only building that we have problems with as far as firs department access.
1s the fire alarm system in the building going to be upgraded in the remodel, if it is i
will need to review the plans?
0 'age 1
e;W(Eu N
o
ism
March 10., 2000
Rulon NeRsen
Ricks College Physical Plant
Rexburg, ID 83440
Dear Rulon,
STATS OF IDA I O
R . Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (2081 359-3020
Fax (2U8) 359-3022
e-maik rexburg@srv.net
doe Laird reviewed the plans and specifications for the David 0_ McKay Library ren�ode1.
I have attached to this letter the origu��a.I requests for p�Ian correct�a�s that were sent to Bob
Niblett ofNielsan-Bodily & Assoc.. Please make the necessary changes to the plans andreturn
two copes to me at City Halt. Tharp you for your cooperation in this matter. If you have Iv
questio-ns please give me a, call at 359-302D
Sm'cerely'
I � /
Val Christensen
Assistant Engineer
ext. 3 14.
Mr. Bob Nibiett
Nielson -Bodily & Assoc;ates
990 John Adams Parkway
P.O.Box 2212,.,
Idaho Falls, Idaho 8_3403
RE:
Renovate Library East & West Wings
Picks College, Rexburg, Idaho
Dear Mr. Nzblett,
STATE OF IDAHO
M17
dw
12 North Center Street
Rexburg, Idaho 834410
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexbutg@srv.net
June 21:, 1999
We have reviewed the very prelim�nazy drawings of the subject buzld7ng renovation that youdeft S
and the accompanying Library Feasxbi�x�y Study.
We are particularly concerned that the suggested structural improvements to the East Wing Building
be accomplished as we see this buildi'ng's inability to meet the seismic requirements as a very
hazardous situation that really needs to be corrected.
00
The West Win� Building is rated as Type 1�-1hx construction throughout so all new partitions
hallways etc. will have to meet Type IIr113r. requirements.
box the top of the corridors in with IT-Ihr, ceifing con It is my understanding that you will
construction. The corridor arrang,ement
etc. that you show on the plans all appears acceptable,
T
die note the inclusion of the 2 -hr. Area Separation Wall between the, two buildings which
is needed.
We also note the EXIT lighting, emergency lightincy, Fire Alarm System anHar�dicapped
accessibility improvements that are included.
We concur with the direction in Which You appear to be headed..
Thank you for the opportunity to have this advance preliminary look at whatare oupro�os�n�the Library Building.Y for
Very truly Y qffirs
JOSEPH'A, LAIRD, - P.E.`
CITY ENGINEER &BUILDING OFFICIAL
10 September 1919191
Mr. Joe Laird
City Engin,eer & Building Official
P.O. Box 280
72 North Center Street
Rexburg, Idaho 83460
Re: Smith Building Remodel --
Ricks College
Dear Mr. Laird:
P.A.
I appreciated the opportunity to meet with you concerning the above referenced project lash
week. The following is a summary of theitems that we discussed during hat meeting.
The stairs are not enclosed. You would like to gee the rear (east) stairs enclosed.
The existing building is not fire sprinklered, Fire sprinklers are not a part o
Perhaps they can be added at some time in the future.
You, requested copies of the design submittals " along the way".
You also requested a ropy of the code review when it is complete.
f this project.
Seismic upgrade of the structure is not a past of this projea. As we have surveyed the
------
build',ng, we have found no evidence of undue cracking or settlement.
We discussed the areas th
to conform to the code.
at are to be remodeled and that the newly remodeled areas need
l again thank you for your time. �
do all we can with the approval a
conformance.
Randy K. Haye
S2 AIA
a
Ne will endeavor to keep you up to date with the project and
f the Owner to bring the Smith Building nearer to Codi
cc: Wayne Clark, RicklMvReO HAVES • SHROPSHIRE
Paul W. Jensen, A1A 9 Randy K. Hayes,, AIA 9 R. Keeven Shropshire, AIS
208/23,2-1223 a 125 N., Garfield * Pocatello, Idaho 83204
FAX 2081232-1226 'D -ta ll jhsarchftemstatemet