HomeMy WebLinkAboutREVIEW - 01-00046 - Greenbrier Association Apartments - 9 Units1
P.O. Box 2 8 0
2 6 North Center
Rexburg, Idaho 83440
(20 8) 359-3 Q10
1997 Unif orm Fire Code
Plan Review
Building Name: Avonlea Apartments 2
Building Address: Second West and Thud South
Plan Date.: 6-01
Review Date:12/11/01
Stories:
2,5
Type
of
Construction: V -N
0ccupancy
Classification:
R
Existing Floor Area: N/A.
New Construction Floor Area: Approximately 1d,500 square
4,800 sq. feet per floor
1) Required Fire Flow (Appendix III -A) : 1750 GPM/2 Hours
Comments. Flog may be reduced by ug
automatic sprinkler system is installed
2) Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location:
Fire Hydrant Flows: OK
Fire Flow Test Location:
Second West ,
Fire Flow Supplied By: FD
Sarre
Other Approved dater Source: done
Water Supply Acceptable � YES
Firms Hydrant Location Acceptable: YES
Water Supply Comments.: N/A
Third South
3..)Fi'Ire Apparatus Access Roado (Article 9 Section 902)
Required: YES
feet/
approvec
Acceptable: Width: YES
Turning Radius:
Clearance' oK
Length: OK Surface:
OK Grade: OK
Turn Arounds: bK
Complete Road Acceptable: YES
Vehicle vertical: OK
4 } .Access Roads and dater Suppler, Including Fire Hydrants Are
Required
To Be Installed And MadeSeryiceable
Prior To
And During
Time Of
installed
Construction (Article
PRIOR to construction a
9 Section 901.3);
STOP WORK vrder will
YDS , if
be issued.
5} . Installation Of Portable Fire Extinguisher
1002) Required: YES Location Acceptable:
(Article 10 Section
Not Shown
Tvpe Provided Acceptable: Plans state 2A-10BC in each unit
Comments: none
6) .Automatic Fire Extinguishing Systems: (Article
Required; NCS Type Of System Being Installed:
10 Section 1003
sprinkler System Monitoring Required (.Article 10 Section 1003.3)
Required: Comments:
7} .Fire
Alarm
Systems �Article 10
Section 1007)
Required.& YES
Type Of
System
Required: Manual.
Automatic:
YES Both:
Type Of System Being Provided: Manual: Automatic:
Components Of System Shown; Smoke Detectors.* Not Shown,
Manual Pull Station:
YES
Sounding Devices
Both:
required
S Visual Devi
Sprinkler Valve Monitoring: Fire Alarm System. Acceptable,: NQ
not
Comments: Planrs did shover horn/strob.es in each handicap units .
Smoke detectors and H/S units shad be hardwired together so they
will all go into ala= mode is one is actinrated. Although not
required, battery back-up to the H/S units beneficial
a
Plans As Submitted Are Acceptable:
Plans Checked By
Please furnish
follawing
Chris Huskinson
co=ent s back
manner Written Co=ents,:
YES
RE
Date: 1
the plan
New Plans:
2/11/01
reviewer in
M