HomeMy WebLinkAboutREVIEWS - 02-00051 - Pioneer Farm EquipmentAugust 19, 2002 Mr. Val Christensen Engineering wept. City of Rexburg 12 N. Censer Street Rexburg, ID 83440 Dewar Mr. Chri*sfensen: I was contacted this morning by M�'. Mike $ress�er of SteeiVision Cons#ruet�on concerning a deviation from the foundation drawings which I prepared for the Pioneer Equipment building being built in Rexburg. The deviation, as I understand, is as follows: Page 4 of the foundation details (Column Foundation for Framelines 2 thru 5, Except.'E & 4E) shows 4 continuous 45 bars going around the anchor bolts and across the bu'Id"'�g to the opposite co1�.�rnn foundation. The detail shows these �bays below the 5'" slab and below the top two #3 ties in the pier. fix. Bressler stated �ha� the bars were placed such that the pop two #5 bars are actually above the top tie and the second two #S bars are approximately 3" below the fop wies. In addition the contractoused #� ties instead of #-3 ties. This deviation does not create any problems. As long as the tap tie is n.e"r the fop of the #5 vertical bars (w10thin 2-3 "), and the other 3 ties are spaced throughout the height of the pier, these should be adequate lateral strength for the, pies. in fact, having the #5 cross -die bays near the top of the pier is desirable. Use of #4 ties is also acceptable. Please contact me if you have any questions, Sincerely, Brent G. Harris, P.E. 190""' West 190 South Rexburg, ID 8 3 44 0 Telephone: 208-.'--)'56-6397 rIr STATE. OF IDAHO P,I BOX 280 12 North Caster Street Four, Idaho 83440 Phone (208) 359.3020 Fax (208) 359-3022 e-mail rexbur�i ill [ I d.�] w s 91a1?40? Scott Spauldm'g Design Intelligence 1.3"S E Main Rexburg, Idaho 83440 Deas Scott, I have reviewed the Pioneer ]P_,quipmeiat drawmgs that you have provided me and have identified the follo�g discrepancies: 1. The ADA parking requirements requ0 ire two handicapped spaces when 26 parking spaces are provicled. 2. Please obta�. a development ac2reement from the City, dee John Millar the Public'Works Director regarding this issue. 3. The Sales Room (Equipment and Parts Display) exztmg does not meet the fz diagonal rule for exit separation. Exit signs ars required in this room as well as the Parts Storage doom. Please identify on plans. 4. Are all doors between the H-4 occupancy and the rest sof the building I rated assemblies? �. ��Jl,l���� Allj��lL1.4iU�1.4J U1�' i�i��',,r+�u iii ffi"gharm"u��itii`� �eiu 'v►a�,ius. Who will be perfor these m*spections`? Please provide us information regarding frequency of inspection and any details associated with these in4L spections. 6. The Fire Department has reviewed the plans. I have attached a copy of there report. Please provide the necessary information they have requested. Pleaseretum two AL. e T is iffi Let �����f � 1L46,2LA fLifther assistance. If vou have any Qu 4W V -, . give me a call at 359�3020ext 324, smo'cerely" Val Christensen Building Official cc Cahn Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P -a 4. Box,, 28� 26 North Center 113murul Idea 91440 (208) 359-301 Q 1997 Unifo Firms Code Plate Review Building Name . PIONEER EQUIFMEi�TT Plar3 Date: 8pwd2 0-DZ Review Date: 8-24-02 -Building Address: 1500 WEST, REXBURG Stories : ONE Type of construction: Occupancy Classification: B, Mo S-2. H-4 �tl New Construction Floor Area: APPROXINATELY 18, 000 SQUARE FEES' 1) Required Fire Flow (Appendix IIi-A): 3500 GPM/THREE HOURS Comments: FIRE FLOW REDUCED TO 1500 GPM AS THE FACILITY IS TO BE EQUIPPED WITH AN AUTOMATIC FIRE SPRINKLER SYSTEM. 2} .Water Supply (Article 91 Section 903) Requited: YES Fire Hydrant Location.: EXTSTINGI AND PROPOSED ONE NEW ON SITS Fire Hydrant Flows.* EXISTING QDAY Fire Flow Test Location: 1500 WEST Fire Flow Supplied By.: FD Other Approved Water Source,-, NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable.- YDS Water Suppler comments. 'ONE 3.)Ficre Apparatus .Access Roads (Article 9 Section 902) Required : YDS Acceptable; Width} X Turning Rad]L: X Cl -. X Complete Riad Acceptable: Length: X surzace Grade : X Vehicle Vertical : X Turn Arounds: X YES a 4) -Access Roads and Water Supply.' Includilng Fire Hydrants Are Required To Be Installed. And Made serviceable Prior To And During Time Of Ca�struction (Article 9 SecE l on 901*3) : YES Co=ents: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5�.Installation Of Portables Fire Extinguisher(Art'I cle 10 Section 10 0Z ) Required* YES Location .Accep�.able : NOT SHOWN Type Provided Acceptable.: NST SHOW Comments: PROVIDE MINIMUM SIZE 2AIOBC FIRE EXTINGUISHERS THROUGHOUT BUILDING 0 6) -Automatic Fire EXtinguishing Systems -4h, {Article 10 Section 1003 Required. YES Type Of System Being Installed: WET Sprinkler system Monitoring Required (Article 10 Section -003.3) Required..; YES Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments : B�.Ventilating Hand And Duct Fare Extinguishing System (Article 10 -mequired,. Automatic Fuel. Shutoff Shown ,ioype Being Provided, (Article 10 Section 1006.2.4) Portable Fire Extinguisher Shawn Comments (Article 10 section 1006.2.7): 9 } ,Fire A-larm. Systems%����ri�l� 10 Secf-ion _11.007)Required 4ES Type 0f System Required: Manual: Automatic: X Both: Type of system Bei Typem Provided,* Manual: Automatic. Both o Components Of System Shawn; Smoke Detectors; Heat Detectors: Manual Pull Station; Sounding Devices: Visual Devices: Doter Holders: eruct Detectors: Flaw Alarm: Sprinkler Valve Monitorin: Fire alarm System Acceptable: ND Comments: FIRE PROVIDE PLANS ALARM SYSTEM REQUIRED AS PER 1997 UFC. PLEASE SHAT INCLE�E FARM COMN.TROL AM- TRnTT-RT.-W CTr-1TTT T1TI1 POWER c'nNvRrmTnWr loin 6N ftq-J I I I I H CONDUCTOR TYPE AND SIZES, VOLTAGE DROPCALCULATION. S Y MANUFACTURERS , MOa�L NUMBERS AND LISTING INFORMATION P8R 26tTT1PMnXTr DEVICES Arra MATERIALS. 10) Other Corrections That Are Requ ti k- ti ired By special Occupancy or �U11ulL1lUus: rLl�ASE AUL3HESS ALL ITEMS LISTED. Plans As submitted Are Acceptable: Na Plans Checked By: CHRIS Hi7SKINSON Date: 8-24-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: x New Plans: X