Loading...
HomeMy WebLinkAboutMULT DOCS - 03-00045 - Jack In The Box - Restaurant - CopyTRANSMITTAL Date: July 24, 2003 To: Val Christensen City of Rexburg 12 North Center Street Rexburg, Idaho 83440 Re: Jack In The Box Rexburg, Idaho arc "low VW L L P 1630 5W Morrison Sof to 210 Portland, Oregon 97205 503.226.3617 phone 503.226.3715 fox Job: 0162 Enclosed i am sending you (2) copies of the revised drawings and this response letter to address your plan review comments dated 7/111Q3. Item 1. See the attached response and revised sheep DC -2 of the structural calculations from Lewis & Vanvleet, our structural engineer.. Item 2. Terry White of Harper Leavitt Engineering is preparing the flood certificate and will forward it to you directly. item 3. The aver -excavating, fill and compaction is currently taking place by the landlord. Inspection is being provided by Strata, the same company that prepared our sails repvrt. You can contact pan Item 4. uado at %Strata ZU0 q'i 10 8ZUU. See information and response from Larson Bin. ey Engineering, our Mechanical 1 Electrical engineers.Item 5. Seg the attached energy calculations from Larson Binkley, our Mechanical l Electrical engineers. Item 6. Per our conversation with the fire department the new fire hydrant to the North of our building will be in place prior to occupancy. We can use the existing hydrant to the East during construction. Please review and give me a call if you have any questions or need additions! information. We are hoping to pull our permit on Wednesday July 301h. Your efforts are greatly appreciated. Thanks again, Jeff W. Hammond Scott I Edwards Architecture JDL-i9-?0031�i0Vi LEW15 & VAN VLEET jr'Me.011 p UFLlI e a Irl rI5 c. van jpe .r p..e w dL 91 10WIS. P.12, 16, �0 P. OQ2,%003 July L412003 MEMORANDUM TO: Scott EdwardsArchitcetilre, LLP Ancntion: Jeff.119mmond ]FRONT: Gary J., Lewis, P.E. RE: Jack -In -The -Box, Rexburg, Idah0 In responsc to Item No. I of the City of Rexburg PjaLn Check Comments, we liad begun sur calculatians using Exposure 'B °wind when we rcccivc� � �����n�c to our �m�i1 to Rexburg requesting design criteria. That email noted that we should Ilse Exposure ' C' for the bLild'ng, v�a�uch we �l�en used. Weneglecied to ch�,n��c the rcfcrrz��c to Exposure '�3' in the wind ��l�u��t�on �n SI��et D�-�, but the C ad calculation below it has a 1.4Q factor added, Which madific:s Exposure: 'B' wind pressures to Exposure 'C'. Therefore, the calculations are X11 based on 90 mph wind Exposure 'C' Ioading. We liave attached a correuted-calculatioti-sIieetDC-Y?; W�apO1o91'2e-for-the�-error-and urge-you-to-c-azI -jl�y�u have any furtli-er questionst GJL:kme 14 consulting L=n fn 2r 10 0 w- � ferry f al , r -g !3CI USLID) EM -5-B505 phnrje 1511311319-S - 12118 rm LEW15 & VAN VLEET jr'Me.011 p UFLlI e a Irl rI5 c. van jpe .r p..e w dL 91 10WIS. P.12, 16, �0 P. OQ2,%003 July L412003 MEMORANDUM TO: Scott EdwardsArchitcetilre, LLP Ancntion: Jeff.119mmond ]FRONT: Gary J., Lewis, P.E. RE: Jack -In -The -Box, Rexburg, Idah0 In responsc to Item No. I of the City of Rexburg PjaLn Check Comments, we liad begun sur calculatians using Exposure 'B °wind when we rcccivc� � �����n�c to our �m�i1 to Rexburg requesting design criteria. That email noted that we should Ilse Exposure ' C' for the bLild'ng, v�a�uch we �l�en used. Weneglecied to ch�,n��c the rcfcrrz��c to Exposure '�3' in the wind ��l�u��t�on �n SI��et D�-�, but the C ad calculation below it has a 1.4Q factor added, Which madific:s Exposure: 'B' wind pressures to Exposure 'C'. Therefore, the calculations are X11 based on 90 mph wind Exposure 'C' Ioading. We liave attached a correuted-calculatioti-sIieetDC-Y?; W�apO1o91'2e-for-the�-error-and urge-you-to-c-azI -jl�y�u have any furtli-er questionst GJL:kme 14 consulting L=n fn 2r 10 0 w- � ferry f al , r -g !3CI USLID) EM -5-B505 phnrje 1511311319-S - 12118 rm II I.?.,0 consulting enginLmers IEl3 El S,vv _ t]ncnes FSU raacl tu'z1}1z1tiF,s W-09un 97062 Lz . Phone t c2l Des. lam m lIgnt Jc� No, I SOONER I VAN VLEET I In cair ptarated Date tv� el o_ Dc..2. . �` ' y h r*L �,i�ti �•#�.fr.A.ii' g��'h~��'; 31 �.e � � � � �ri I E� F iIF,. �P �I&F s �r�. ` } i 9 Y1 w I F IIr,F i 7Plr y�.� N i. PIy`.�.�r •�' yF lw4ii...a .1{. ►, ti r r ti';� r�'i i } h■, 1 �4%: 3 , ,,! 46P� ir�4ii 41 '� - il. # •�df' �, ii 4'i�'I 'i+4f #'L`,. � �iM�j. i4�i . F i. I ' 7&. 4"k e Yarv4-.r ar j_.a`4"q4"rr .1W.1r, V Tpr r 0 MCI . '31 c I , use ■ k �? 14't' cw Y 0. � I s Y P a 1 r Lz> I i P P-�-CrV Ur PEENED 90 1 F r �A s P r 1 1 �r ip, rd i 0 s-ui 41 MIN 1 e� q [i R _4 FSF Or 4 fi i P r CLSliAPW A6- W %J wSO Fm rzou ps p I G IA74rcp 1004 h I 1 r ' 1 1 r � t y � j P F .Y ■ � �.. �1 0.. I r Z �yl XOw 17 g + ye •JI - I 0 ■ 0 i 1W 11 W u I t i L r r r z III' ` 5 r Lr r� �-P ■ el Rn !� L F,ae "rAe�Lat. f La i S. 1.0 7—;x � i - r6-8 FS6,r ME—M cs:7 (=d>1=,,r A 0,77 S + 15 j L O. 17 S �Og r=rAIL. `T,+4rfp,5 LX= 1(vi lacy _S C1 E) 1u4 i� PSTV.- r lPeV-- [0.4s) W 1.4 [Cod ■ � { 11111 MMv• P ,,a 4h%], '�9 ±"#�..���.i •� 17��'. ry'''ii`��'�yl�+t'"'"r ���. ����� ; 5 a., rl i � � +■4 �1i� r.� 6S i � r� ��e�T' �pr�,► =� � l 9 +� � � .� Ll �� 4�+1 �� w •4 1 � ti �'�.^' �"'y �" �1'� f �•� e,1 -�� � �� Lwo x,�e ��,�, 1U�-Iq-)003�i00) II I.?.,0 consulting enginLmers IEl3 El S,vv _ t]ncnes FSU raacl tu'z1}1z1tiF,s W-09un 97062 Lz . Phone t c2l Des. lam m lIgnt Jc� No, I SOONER I VAN VLEET I In cair ptarated Date tv� el o_ Dc..2. . �` ' y h r*L �,i�ti �•#�.fr.A.ii' g��'h~��'; 31 �.e � � � � �ri I E� F iIF,. �P �I&F s �r�. ` } i 9 Y1 w I F IIr,F i 7Plr y�.� N i. PIy`.�.�r •�' yF lw4ii...a .1{. ►, ti r r ti';� r�'i i } h■, 1 �4%: 3 , ,,! 46P� ir�4ii 41 '� - il. # •�df' �, ii 4'i�'I 'i+4f #'L`,. � �iM�j. i4�i . F i. I ' 7&. 4"k e Yarv4-.r ar j_.a`4"q4"rr .1W.1r, V Tpr r 0 MCI . '31 c I , use ■ k �? 14't' cw Y 0. � I s Y P a 1 r Lz> I i P P-�-CrV Ur PEENED 90 1 F r �A s P r 1 1 �r ip, rd i 0 s-ui 41 MIN 1 e� q [i R _4 FSF Or 4 fi i P r CLSliAPW A6- W %J wSO Fm rzou ps p I G IA74rcp 1004 h I 1 r ' 1 1 r � t y � j P F .Y ■ � �.. �1 0.. I r Z �yl XOw 17 g + ye •JI - I 0 ■ 0 i 1W 11 W u I t i L r r r z III' ` 5 r Lr r� �-P ■ el Rn !� L F,ae "rAe�Lat. f La i S. 1.0 7—;x � i - r6-8 FS6,r ME—M cs:7 (=d>1=,,r A 0,77 S + 15 j L O. 17 S �Og r=rAIL. `T,+4rfp,5 LX= 1(vi lacy _S C1 E) 1u4 i� PSTV.- r lPeV-- [0.4s) W 1.4 [Cod ■ � { 11111 MMv• P ,,a 4h%], '�9 ±"#�..���.i •� 17��'. ry'''ii`��'�yl�+t'"'"r ���. ����� ; 5 a., rl i � � +■4 �1i� r.� 6S i � r� ��e�T' �pr�,► =� � l 9 +� � � .� Ll �� 4�+1 �� w •4 1 � ti �'�.^' �"'y �" �1'� f �•� e,1 -�� � �� Lwo x,�e ��,�, July 22, 2003 Val Christensen City of Rexburg P.O. Box 280 12 North Center Street Rexburg, Idaho RE: Jack -min -the -Box - Rexburg, Idaho Mr. Christensen, This letter shall serve as our response to your review comments for the referenced project. Item 4_ Submit manufacturer�s certificate of compliance for all components as per IBC Section 1621-15. Response. We added General Note 5 an Sheet M2,0 for mechanical system seismic restraints, and we modified Detail 21M4.0 to include seismic tie down restraints, Please reference Detail 1 1/P5.0 ter seismic restraints for the water heater. please refer to detail 3/E5.,O for light fixture seismic restraints. Item 5. Please provide energy calculations as per the 2000 Internationai Energy Conservation Code. Response: We have attached the required energy calculations. DC .: L01 r -1t Larson Binkiey, inc, 8900 State Line, Suite 150 • Leawood, Kansas 66206 ' Phone; (913) 383-2621 Wifh offices located in: Leawood, Kansas HEADQUARTERS • Albuquerque, New Mexico www,larsonbinkleycom • Fax: (913) 383-2831, Lighting Compliance Certificate 2000 IECC COMcheck-EZ Software Version 3.4 Release 2c Data filename: E-1Actjve\"00j\01200_ld.01\01200334.O1.CAL`JIB 012003;40Lcck Section 1: Project Information Prof e ct Name m r/ tr t r: Document Autlior.- Section 2: General Information u11d. Use Description by. - Activit -y - P Dininor Z:2 Kitchen Corridor, Restroom, Support Are 0 ffl C e Storage, Industrial and um—1 r ial Project Description (check one): New Construction Addition Jack the Box Larson Binkiev, Inc. �s LarsoninklInc. ActiVity Type Permit dumber Checked BylDate Floor Area 679 602 142 100 JPO Alteratioll ` Unconditioned Shell (File Affidavit) Section 3,*m Requirements Cheekli"st Z5 zn f I . Total actual watts .must be less thaii r equal to total X11 rtt Allowed Watt u ' li Y/�N 1 Z..'A p Exterior Lith 2. Efficacy greater than 4") lumens/W Exceptions: ad lightm'_g h .4 gh 11 � ,in �v fieat-ures L� lfi+"Y i+'i y,+ � �'4 s � T r UU11i�; signage _Lt r ,pec y &6nc'r; low-voltagelandscape lighting. .11 I uontrols,and Wl*ring -it coatrols for each space (switch/occup,,mcysensor) . -Exception: Areas that rust be continuouslyighted.' . Master switch athotel/motel guest room. r . Two switches or dimmer ~ onn light ivone niu m -race- An, occui)ant-sensin2 dev' The area is a corridor storao-e ice contTols the. area; r tr M' r lobby; Areas that mustlighted; 6.Photocell/astronomicalbtu �. � on or lights. Exceptions-,- Areas requ]'Tffig lightingdur 1.n daylight hours . Tandem wired one-lanip andthree-lamp do Electron*Ic high-fTequeacy ballasts; Luminaires nod on same switch Section 4: Compliancy Statement The proposed lighting design represented an this document is consistent with the buildnz plans, specification. and other calculations submitted with this permit a�aplication. The proposed hght'ng system has been designed to meetthe 2000 IECC, Chapter $, requirements in COMcheck--EZ Version ?.� Release Zc and to comply with the requixerienis anthe Requiremel-Its Checklist. mandatory r� I - Nees x A � '�•, T � k Fes • '7 3 Date } Lighting Application Worksheet 2000 IECC COMcheck-EZ Soffiva-re Version . Release S ed'i on 1: Allowed Lighting Power CaIcuiation 13 imna Allowance: Decorative .tiv / Fix. ID. G Kitchen Corridor, Restroom, Support Axea ffl C e Storaore Lndustrl'ai and CO=erclal r N J, I- Floor Area (ft2) 679 335{a} 602 142 100 520 C Total Allowed Warts (watts/ft2 1.4 I 2.2 0.8 1.5 1 i'Lrea claimea must not exceed the Illuminated area painted for thi's allowance type. (b) Allowance i or the actual wattage of the fixt-ures given in Section 2, whichever is less. Total 11 owe Watt Section 2: Actual Licy,hfing,Power Calculation Fixture Fixture Description ID Lam r tion Wtt crr � - err —_ _ e Fixture ElectronicA 2 x 4 fluorescent / 48 " TS "I W / Electronic 2 B 2 x 4 fluores c ent / 4 8 " T8 3 2W / D Sulfate mount fluorescent 48" Electronic Pendant mount fixture Twin Tube 13W / Electronic I K kitchen Hood liorht / Incandescent 1 Porcelam' Socket Incandescent 60W Desk light "' T8 32W/ Electronic None 02-1amp fluorescent " T8 W 1 c Allowed Watts X C 951 11 b 1 11 114 317X F f Fixture Fixtures Watt. (D x 18 62 1116 5 114 570 ? 62 124 7 16 11.2 5 100 544 60 60 X n2 32 4 52 ?48 Total Acttial Wats = 2762 Section 3: Compliance Calc y f I h ,,,a 1 l C 1 v e Tfla.-tits Total Ac-ikua7 j T K Watts '4 Hding LU 4 1 Vim LicIfing ]PASSES: Design 1",%betier than code Total Aliowed Watts = 317I Total Actual Watts = ? 7 6 2 Project Cazxiplzans:e = 409 Mechanical Compx�a�ce C'ert�ficaie 2000 IIECC CoMcheck-Ez Software Version 2.4 Release Zc Data fflename-. E-.�Active\200,-'\ol200-i34.01\01200-�'--'4.01,CAL\jj.B 0120033401.cck lection 1 : Project Information PrJet .m igner/Contractor: Des Document .author . Jack M the Box parsonink1 Inc. Larson Binkley, Inc. Section 2: general Information Building Location (for weather date Climate Zone: rteatin'c, Deoree Dai (base 65 degrees F)- Coolinc;Bore e Days(basegrees ' 41 Project Description (check our) New tin Addition Alteration Section 3: Mechanical Systems List Quantitv System TV, e & Desermfion HVAC AC t m �-ti� 15 Air -Cooled Condenser/ Sinale Zone Rexburg;, Idaho 1 869 Permit Number Checked %r)Date Unconditioned Shell (F1'ie Affidavit) Gas fill- Packaged Trni1 'itit F 7000 Btw1h17 HVAC System 1; .tin a : Central Furnace G / � cr• Rooftop Package, Un -t kBtu/h, A' -Cooled Condenser ` Sinale Zone Section 4: Requirements Checklist Bldg. r Use Requirements Specific To: HVAC System I - Newly purchased coo.ling ment meets the c1unaeffici�° requirements a It mated i r- - Requirements i To: HVAC I Newly purchased heatm-c, equipment assts the heatinor i re quirements 1' 2. Newly purchased1M,Y t meets the c001k2 efficiencyr * irements G eneric Requirements: Must be met by all Wstems to which the requirement I Load calculations per 1 997.Fundamentals [ ] � ' 1 tequipment d ui t _ F ice greater than needed to meet loads Exception.- Standby OquiPment automatically when primary system ioperating - ti Multiple Mmit t" controlled 4 sequence rtlnfiunctFir, of load }munum one temperature control device per system munuin one humIdIty control nevi r m -stalled humidification/dehumidification+ 5. Thermostatic controls has 5 de cy. F deadband , Exception: Thennostats r u mamanual �� rte heat - ZD and coolm'g � ) ! 6. Autamatzc Controls Setback to Sa dei. F (heat) and 85 dei. F (cool); 7 -day cock 2M -hour � occupant averr�de, 1 0 -hour backup � -Exception: ContMuous'ly operating zones � - Exception: 2 kW demand ter less, submit calculations � } ( 7. Automatic shut-off dampers on exhaust systems and supply systems witii auEm�,, =3,Q�p �fr� $- Outside -air source for ventilation; system capable of reducing USA to required miniMuM C 1 � 9, R-5 supply and return au- duct insulation in unconditioned spaces j R-8 supply and return all duct insulation outside the buildL'na j R-8 insulation between dints and the buildm'cr exterior when ducts are part of a building assembly J - Exception: Ducts located within equipment j -Exception: Ducts with interior and exterior temperature difference not exceed.inIS deg. F. [ � � 10. Ducts sealed - longitudffial seas on rigid ducts; transverse seams on all ducts'�_' d UL I8 lA or 1$1B tapes and mastics [ ] � 11. Mechanical fasteners and sealants used to coanect ducts and air distribution equipment � ] � 12. Operation and maintenance manual provided to building owner [ ] ) 13. Balancing devices providedin accordance with IMC 606.15 Section 5: Compliance Statement The proposed mechanical design 4 �this document iconsistent with the b- uild cy - . Plans,specifications aTitercalculationsubmi with this permit application. T pr to meet the .M oposedha mechanical systemshave been d i d quiirements in -Zr .4 Release and tChecklist. comply withth-e . try requirements tRequirements Principal Mh n .I Desiorner-Name Date Mechanical Requirements Description 2000 JECC CflMcheck-E-Z Software Version 2.4 Release 2c Data filename,-, LActi�e'�20D3'�,41?�Q334.�I�,012�0334.QX.CALIJIB 01200-10401.cck The, followin�D list provides more detailed descxi�ti Certificate. on of the requi.Tements in Section 4 of the Mechalical Compliance Requirements �i To: HVAC System 2 T The specified cooling � �eut is Tsere Federal � �rTMm el Iciency requirements. -e etrequipment of this type can be assumed to meet or exceed ASHRAE go. I Code , ,moiffiteD,.,-ateeryraments for - ent ieiii selected ger � rewire r 1�di�� ��� � � tens er� � kB-t�..�/ or e i the allows integated economizer mate. Ansimultaneous operation outdoor -air and mechanical �fi '4� � 1y �4 r Requirements Specific To: HVAC System 1 1. The specified heating equipment is capered by Federal minimum efficiency requirements. New equipment of this hype can be assumed to meet or exceed. ASCE 9Q.1 Code requirements for equipment efficiency. 2. The specified coolina equipment is covered by Federal minimum eff ciency requirements_ New equipment of this type can be assumed to meet or exceed ASHRAE 90.1 Code requirements dor equipment efficiency. Generic . ye1 t�i require�n��t i1icabli. esi. e t or and cooling loadsfor" ' theEast ulProcedures• T • chaMers7°Handbook equivalent � tie � - -___,sem :iA 7ffrki, � tiJ4 4-91_L "? J. 1. v v %. d C u, 1[ aiii fir umcmazion Procedure. -All equipment and systems must be sized to be nO greater than e ede d to meet calculated ulte loads. A s'nale piece of cqu' ger t r t het . . cling must satisfy thisrir� ns. Ity for one - for the other f�nction as small as possible., within. available equipment optio - Exception.- The equi I pment wid/or system capicicitv may be, greater than calculated loads for standby purpo,ses. Standby equipment gut be automaticaliv ee tr Iled tbe e the rime equipment e r er system T per tinct' r equipmentEXCtD,Pti011 d. MUftlple UnitS of the same type whose combined capacities exceed the calculated load .r allowed it they are ie����� ireT Operation units as the load increases ordecreases. . Each heating or e T stem .s ervi zone .et .have its own temperature control device. • - ter Trust it N humidity control device. r Thermos tats control1mg both. heat-cr and e ing rust be e bie r� mt iri . temcool' � e�ree ' feu store h re n I4 iprovided). Exception: Deadband capability is not ire ie terr.tt does not e ilie� e eheati_n,,,_,, . automatic changeover and el 6. The system or zone eltrl mutbe a procrrammablei r enn stat r ter automatic control meeting followling er teri --capable o ett cg temperaturede Z:Iroe ��, .tdegree dug heating.dsetting up to 85 ing autmt Te.TT setti-ng back or :u,� down systemsdura unoccupied ehoursdifferent se.edie have eeTble 2 -hour occupant erried) have a batteback- C) � w capable t .prog-ranunedsetT� s for at least 10 hours without power. - Exception. A setback r shutoff control is not reg uire .0 thermostats �7+,�yy �,. qa�.• �that control s ate lli�'vUously-.!'.r that ope- Fxcp : A setback or shutoff coutrois l rhr less. not required � n systems with total ever demand of 2 W (6,826 7. Outdoor-airui-V systems with design it rates >3,000 of outdoor air all exhaust systems mustedampers that are automatically ally ei sed while the equipment ` 8. Te - �� t er�.tTrT, system must su .�i outside en "]at- r re u re . q _ b Ti ter the tem tT n I Me ch an e.tTi�tirT �e� � designed;�� �� .� �Te�. e. t ss app �quantities- r utu r- ,rre �eed . i In r r 'levels 1. stem mustbe capable � � required �ee�.� t��e 9. reducing outdoor -air flow t the minimum reuse levels. . ducts t be ffisulated to ° i tie iT�r�ier rem Tr ducts ' r conditioned ne tr Veteuner�Ttioned e(spaceseitier ted nor t . Te rr�ust l-�d TtT� TUni o .�� . Unconditionedfficlude attic -S,. .. crawl spaces., unheated d b se ents and unIleated i t e. Suppiy and 10. 1 X. 12. 13* return au ducts and plenums must be iz1sulated to a minimum of R -S when located outside the buildi-ag.c) When ducts are located within exterior components (e, or., floors or roofs}, m�nYmum R -S insulation is required only between the duct and the building exterior. Exception', Duct insulation is not required on ducts located within. equipment. - Exception: Duct insulation is not required when the design temperature difference bet�veen the interior and exterior of the duct or plenum does not exceed 1 S de.c.)-ree F. All joints, Joncritudinal and transverse seams, and connections in ductwork mush be securely sealed using weldments; mechanical fasteners withseals, ffaskets, or mastics; mesh and mastic sealing systems; or gapes. Tares and mastics must be listed and labeled in accordance with UL 181A or UL 181B.- Mechanical fasteners and seals, mastics, or �asl�ets must be used when connectins ducts to fans and Other air Y equipment, includ�n.g multiple -zone ierm�nal units. Operation and maintenance documentation must be provided to the owner that includes at least the following znformatian:a} ee�uipmeni capacity (input and output) and required maintenance actiozzsb} equipment operation and maintenance manualsc) HVAC system control maintenance and calibration information, including wiring diagrams, schematics, ar�d canira1 sequence descriptions; desired or field -determined sit points must be permanently recorded on control drawuags, at control devices, oz-, for dia�tal control systems, in pxa�rammin.g comrx�entsd} complete narrative of how each system is intended to operate. Each sup �►ly aix c�ut�et or di�fizs�r ar�d each zone terminal device (such as VAV or mixing fax) must have its own balancing device, Acceptable balancing devices include adjustable dampers located within t��e ductwork, terminal devices, and supply au diffusers. Aug 07 03 10: p7a Aug OZ 03 10: 30at j ni- Aug. 5. ?0H Scott I edwards Stet const architect 5032263715 503 2S7 0309 no= 1M CITY of AExauAG 8UiLDING INSPECTION SEQUENCE Type of [n:,pEctipns: For on -Sits GOrlStrijr_linn, from time to time the building official, upon r+otn- atior from the holder hu��r or h,b dyent, shall make or cause to b d'0 any nCco ,nary i��peCfi�+�:; �nc� �ha�l �X�he�' approve that portion of the construction as completed or shelf notify .0 the permit hofder or his agent wherein the same fails to conVly with tNs code. I . LA,rOUi: LU[ cot-nersstaked, staking in place for building, pi'ior tb extovation: 2. F00TING: Comrnonly made after poles or piers are set or trenches or easement areas are excavated.. Forms and h4rizvnlai reinforcing tied in place,, YeCttCBl ieIT110rcuig CU4 and on jorb Si'Ee of tied in in piac,`e_ 3. FOJNo,aTQN INSPECTION: The foundation [nspacfion shall inetuded excavations for thickener] :ilaw .intended for the support of bearing wafts, RartitiQns, siruMural supports. or equipment and special requirements for wood foundations. All forms and reinforcing steel, etc,, Ghali be in placc, 4. PLI WRING. MECHANICAL AND FLE-GTAICAL Rough inspection: Gommonly made prior lo covering or concealment. before fixtures are set, and prior to framing inspecl,c4n. 5. TRUSS INSPECTION. - Inspections & lrusses. b_ %HAMS iNSP�'CTIC]N: Communly made atter the roal, all fEanfling. fi.estvlVing, drafistvpping and braclng are in plate and aver the plumbing, mechaniGal and eleGiriCal rough in.SpeGtivnS are approved. (Electrica [ performed through State of Idaho Bectrical Bureau) T LAI'H AND/OR WALLBOAHU INSNtC_1-I0N: Commonly made alter all lathing andlor wallboard interior is an place, but . before any plaster Is applied, or before waflbpard jtxinm and faslener5 are taped and fin(shed. 8. FWAL PLUMBING AND HEATING INSPECTION: All systems in place, fixtures sit, ready far pcwpancy y. SIDEWALK iNS,PECTION�: Aher forms are Sgt, prier to placing concrete. 10_ FtN a L INSPECTION,.- Commonly NsPECTlON,: Commpnly made after the building is Completed and ready Ior occupan4'y 1 I.. 0G�`3"'UPANCY PERMIT; .Issued when, on final: inSpeCtion, buildirtg is reedy to occupy_ 1?. 0714FR INSPEC11QNS: In addition to the caped in,SpeC#ions above, the building cknpadmerr# may maks or require any ether inspections to ascertain compliance with this cad¢ and other favus enforced by the building depailmen't. INSPECTION CMID The permit ha►Ider or his agent shall pest the inspection record Uri the joky site in an accessible and conspi..'uvus place to allow the building official to make the reqL�red entries. The recgrd shall be maintained by the permit holder until the final 'inspection has been made and approved. I have reaG Me above and will comply in my requests for inspections by q1VI"ng 24 HOUR NOTICE prior toy inSpeCtiOnS to be pude- Electrical- :356-48building' 359,--,,3020 ex 341 Or 313 Plumbing] '159- a 59-3034 S`gnaturol � ` oate� A00 7 1 -e ■.... rM • • — • 1 PIf I NAME: WENDY'S RESTAURANT ACCT 134430 PHONE: 000 3569667 SERVICE: 545 PI 2ND E ROUTE 82030 CLASS/UPdITS: B 001 BILLING: BOX 639 BLDG #: LABEL CODE: FLAG: CITYIST: REXBURG[ IDAHOZIP: E3440 0000 MAIL CODE/ROUTE: C 03 OWNERIP4 MURPHY & ROBISON BUS. SCHED/UNITS: 20 001 BILLINS TYPE: EXPIRE MONTH: 00 DEPOSIT DATE,* 000000 AMOUNT: 00000 Moved In/Out: 010998 000000 F9=RFAD HISTORY -----------USAGE HISTORY ----- WATER SIZE SCHED MOYR READS Y/N 57- 0302 261 0802 98- 0103 #1: Ol 60 02 0000 0119'0 01363 282 0902 23i 0902 48— 0203 #2: 00 00 49 0000 00000 00000 58 0502 132 1002 48— 0303 #3: 00 60 49 0000 00000 00000 236 0602 48— 1102 323 0903 E ST: 00055 X; READ DATES: 05 1 33 06173 221 0702 48— 1202 45 0503 SEWER SCHED: 02 EQ USERS,<XX,X,,>: 000 BIN #f MTWTFSS DAY; ALL 0 0 GARBAGE SCHED: 04 SIZE: 3YD ROUTEff: 01 0 2020220 SEQ#: 415 000 000 OTHER CGDE: AMOUNT: EXPIRE MO/YR: 0000 DESC: Hi Water: 30 Hi Sewer; 60 CHARGES I TRANSACTIONS I WATER: 5157 TOTAL DUE: AMOUNT DATE AMOUNT DATE CODE J SEWER: 12870 I CURRENT: 56427- 55167 0103 57-1-67- 01093 ROA I GARBAGE: 38400 I OVER 30: 56427 55167 0203 � 55167- 02103 ROA � OTHER: I OVER 600 55167 0303 55167- 03073 ROA SVC HG* I NOTICE 4,1/ DT; 00000 58255 0403 5.5167- 04073 ROA I MAN CHG:.0I TYPE/TERM DT00000 56A27 0503 � 58265- 05083 ROA I MAN C _R I SHUTOFF TIME: 00 <CMD 6> HIST 56427- 06053 ROA TOTAL: 5642 1 SECURE: MAI Meter Date 5/13/03 9/17/03 10/16/02 9/17/02 8/14/02 7/15/02 6/18/02 5/15/02 4/10/02 10/16/01 9/18/01 8/14/01 7/16/01 6/15/01 5/14/01 Meter Read History Customer: 13443-k WENDY'S RESTAURANT Meter 1 1196 1151 828 696 459 198 9977 9741 9583 9401 9304 5053 8818 8661 8466 Usage 45 323 132 237 261 9779- 236 58 282 97 251 235 157 195 63 Meter 2 Usage Meter 3 Usage Total Usage 45 323 132 2 37 261 9779- 238 58 28P 97 2 5'1 2 36 15'7 195 63 ACCT: 134430 NAME; WENDY'S RESTAUPN,.,,ZUTT ROUTE: 82030 SERVICE ADDR: 545 N 2ND E DATE CODE AMOUNT WATER SEWER GARBAGE 06%05/2003 ROA 56427- u i / J1 / LUVJ 05/08/2003 ROA 09/30/2003 04/ 07/2003 ROA 03/31/2003 1260 03/07/2003 ROA 02/28/2003 02/10/2063 ROA 01/31/2003 01/09/2-003 ROA 01/01/2003 BCH 12/31/2002 12/09/2002 ROA 11/3Q/2002 11/07/2002 ROA 10/31/2002 IO/17/2Q02 ROA 1-0/11/2002 ROA 10/11/2002 ROA RE FE -GUST SCRN �b4L/ 5157 58265- 58265 7198 55167- 55167 5318 55167- 55167 5318 55167- 55167 5318 57167- 2000 55167 5318 55167- 55107 5318 59678- 59678 9829 117143- 5.9277 59277- FlO/Fll-NEXT/P 12870 12667 1,1449 11449 11449 11499 11449 11449 REV ACCT 38400 38900 38400 384 00 38400 38400 38400 38900 IN/OUT: 1/09/1998 TELEPHONE: 3569667 OTHER BALANCE F24-PREV SCRN WENDY'S RE 0 56427 WENDY'S RE 1838- 56427 WENDY'S RE 1260 � 56427 WENDY'S RE 1260 0564Z 7 WENDY'S RE 1260 � 56427 WENDY'S RE 740- WENDY'S RE 1260 0 56427 WENDY'S RE 1.260 0 5 64 2 7 WENDY'S RE 3251- 0 56427 WENDY'S RE 60716- WENDY'S RE 1439- WENDY'S RE 60716- ENTER-MORE HI5T ACCT: 134430 NAME; WENDY'S ROUTE; 92030 SERVICE ADDR: DATE1CODAMOUNT WATER 09T3-012002 � 65143 15168 05/10/2002 ROA 66432- 09/O1/2002 GBS 52000 08/31/2002 66432 16 75 7 OR/12/2002 ROA 64284- u7/31/2002 64284 14,609 07/08/2002 RCA 65089- 06/30/2002 65085 15414 06/05/2002 ROA 55530- 05/31/2002 55530 5855 05/10/2002 ROA 52455— U4/JU/ZUU2 �2455 2580 04/08/2002 ROA 57277- 03/31/2002 RE 57277 5802 03/07/2002 ROA 57277- 02/28/2G02 RE 57277 5802 02/08/2602 ROA 5727V- 01/31/2002 RE 58427 57277 5802 01/11/2002 ROA 59277- 12/31/2001 BCH 2000 FE -BUST SCRN FIO/Fll-NEXT/P RESTAURANT 545 N 2ND E SEWER GARBAGE 11275 38400 11275 38400 11275 38400 11275 38400 11275 38400 11475 38400 13075 38400 13075 38400 13075 38400 11V OUT: 1/09/1998 TELEPHONE: 3569667 OTHER BALANCE 0 FT_7na REV ACCT F24 -PREY SCH 0 0 C I 0 WENDY'S WENDY'S WENDY I S WENDY' S WENDY'S WENDY'S WENDY'S WENDY'S WENDY' S 0 WENDY I S WENDY'S ENTER -MORE RE 2728 - RE 49272 115709 RE 51420 115704 RE 50615 115704 RE 60179 115704 RE 63249 1157 04 RE 58427 115704 RE 58927 115704 RE 58427 115704 RE 56427 RE 58427 HI ST NAME: ARBYS ACCT 135980 PHONE: 000 3591345 SERVICE: 478 td 2ND E ROUTE 83990 CLASS/UNITS: B 001 3ILLItdG: PASCO-PE IN^ 27220 N 5000 E BLDG #: LABEL CODE: FLAG: CI'^'Y,ST: SUGAR CITY, IDAHC 7IP: 83448 C000 MAIL CODE/ROUTE: ROS OWNER: <MIKE �t'ITHERS 356-5821 9 0FF 7/99 BUS. SCNED/UNITS: 20 001 BILLING TYPE: EXPIRE MONTH: 00 DEPOSIT DATE: 01309,14ILMOUNT: 27500 Moved In/Out: 013094 000000 F9 -READ HISTORY------ ----USAGE HISTORY ------ WATER SIZE SCHED MOYR READS YIN 42- 0302 29 0802 25- 0103 #1: 00 75 01 0000 06196 06227 142 0402 31 0902 25- 0203 #2: 00 00 49 0000 00000 00000 28 0502 25 1=002 25- 0303 #3: 00 GO 49 0000 00000 00:000 29 0602 25- 1162 141 0403 EST: 00024 X: RKAD DATES: 05133 05173 28 0702 25- 11202 19 0503 SEWER SCHED: 26 EQ USERS<XX,X>- 000 BIN ff MTWTFSS DAY: ALL 2 0 GARBAGE SCHED: 04 SIZE: 3YD ROUTH: 03 0 0101010 SEQ#: 396 265 00,0 OTHER CODE: L31 AMOUNT: 14793 EXPIRE MO/YR: 0000 DESC: LID 31 CHG Hi Water: 60 Hi Sewer: CHARGES TRANSACTIONS AMOUNT DATE AMOUNT DATE CODE 40863 0103 42'264- 02043 ROA 40863 0203 46863- 02213 ROP. 40264 03,03 40863- 03263 ROA 39578 0403 40264- 05083 ROA 39739 0503 I 39578- 05273 ROA <CMD 6> HISm I 397,39- 06113 ROA WATER: SEWER: GARBAGE: OTHER: SVC CHG: MAN CH G: MAN C R: TOTAL: 1923 TOTAL DUE: 8623 CURRENT: 39739- 19400 OVER 30; 39739 14793 I OVER 60: I NOTICE #/ DT: 2 07182 TYPE TERM DT - 0 D 08062 SHUTOFF TIME: 00 39739RESECU: Meter Locations rfl: INSID$ #2: #3: Date 5/13; 03 9/17/03 10/16/02 9/17/02 8/14/02 7/15/02 6/18/02 5/15/02 4/10/02 10/16/01 9/18/01 S/14/O1 7/16/01 6/15/01 5/14/01 Meter Reaci Customer: BUILDING meter 2 Usage 6196 19 6177 141 6036 25 6011 31 5 9 8 0 29 5951 28 5923 29 5 8 9 4 28 5366 142 5724 27 5697 35 5662 35 5627 33 5594 28 5506 25 13 5 9 8 * History ARBY'S Meter 2 Usage Meter 3 Usage Total Usage 19 141 25 31 29 28 25 28 142 27 35 35 33 2B 25 0 AC -CT: 135980 NAME; ARBY'S ROU'S'E: 83990 SERVICE ADDR: SATE CODE PMOUNT WATER 06%11/2003 RDA 397 3 9- UJ/ 1)1/ LUV.S 8623 05/27/2003 R OA 05/08/2003 ROA 04/30/2003 14793 03/31/2003 8820 03/26/2003 ROA 02/28/2003 02/21/2003 ROA 02/04/2003 ROA 01/31/200-3 01/01/200"-)"' BCH 12/31/2002 12/23/2002 ROA I2/02/2002 ROA 11/30/2002 10/31/2002 ROA 10/31/2002 10/04/2002 ROA 10/02/2002 ROA H-CUST SCRN 'JN /j9 395111 40264 40863- 408-63 40863- 42264- 40863 2 0 0 0 40264 40254- 40863- 40269 41045- 40863 4 0 9 3 7- 40937 F10/F11-NEXT/PREY ACCT IN/C)UIJL: 1/30/1994 478 N 2ND F, TELEPHONE: SEWER GARBAGE OTHER ARBY'S 1923 8623 14400 14793 1762 8623 14400 14 93 2295 8826 14406 14793 2245 8820 14400 ?5392 2245 8826 19400 15392 2245 8826 19406 14793 2245 8826 14400 14 79 3 2245 8 8 2 6 14400 15392 F24-PREV SCRN ARBY'S ARBY'S ARBY'S ARBY'S ARBY'S ARBY'S ARBY'S ARBY'S ARBY'S AR$Y'S ARBY'S 3591345 BALANCE I 39739 161 40103- 525- 39739 1129- 39739 1124- 93388- 2525- 525- 39139 525- 41388- 1124- 42169- 1306- 42243- 1306- ENTER-MORE HIST ACCT -1- 1-305980 NAME: ARBY'S ROU'�'E: b3490 SERVICE ADDR: SATE CODE AMOUNT 1C%02/2302 ROA 40937- 09/30/2002 2406 41045 08/31/2002 40937 08/19/2002 ROA 40883- 07/31/2002 40883 0 7 / 2 5 / 2 0 0 2 ROA 4093']- 07/18/2002 ROA 40883- 06/30/2002 40937 05/31/2002 40883 05/30/2002 ROA 35728- 04/30/2002 ROA 45035- 09/30/2002 35728 03/31/2002 45035 03/26/2002 ROA 95035- 03/21/2G02 ROA 45035- G2/28/2G02 45035 02/05/2002 ROA S0834- 01/31/2CO2 4 5 n 3 5 12/31/2001 BCH 2600 12/31/2001 48834 WATER rb-�,us1 sctuv r'lU/F11-NEXT 478 N SEWER IN/OUT: 1/30/1994 2ND E TELEPHONE: GARBAGE OTHER 2568 868 5 14400 15392 15392 2460 868514400 2406 SCRN ENTER -MORE 15392 I'll 2406 8685 14400 15392 2460 86E5 8685 15392 19900 12085 15392 2406 SCRN ENTER -MORE 8685 14400 15392 2749- 86E5 14400 15392 3158 12085 14400 15,392 3158 12085 14400 15392 3158 12085 14400 15 3G 2 ARBY'S ABBY' S ARBY'S ARBY'S ARBY'S ARBY'S ARBY'SARBY'S ARBY'S 3158 12085 14400 19191 /PREY ACCT F24-PREV SCRN ENTER -MORE 3591345 BALANCE 83180- 42135- 1198- 42081- 1198- 42135- 83018- 92081- 1198- 36926- 81961- 46233- 1198- 46233- 91268- 46233- 97067- 52032- 50032- 1198- HIST Transmission Result Roport(MemoryTX) (Aug. 7. 2003 9 56A } � 2� Date/Time: Aug. r. 2003 9:55AM Oro in FUM"O: — 2 0 11 ! 2 A �- - I'" � 11�11 e m Y T Rqsult MemorvTx) 91503226311F� RP,aon f oar e r o r fE- 1) Hang VP o r I i n f I E-3) No answer E ) R 1i F]uU,M1'Mg Permit Valuzuon Fe,% ev"M . Jeck in me Box OftYof o � drV o�� Con�rn�r�,� A 12 N � t- i; _ . tires �a I'LlJ4al, yw• POSF'4, M L 2 irzK L _erg c : 'M 357 L.� 4d t -� u' �,y ��� �� C Wmxmy1 HWOttti �' '[.�, 4147 1 CC41'.�i TAX =L74�• $3,4ms Find a ` 7=—;:; +_ U� - Iad gq J-!�}'ly,�.iq ry�.��•,p7■.+�, a 7 TIF r7 Ft 4~ = '�fM PIM cm*&uc!$n VMm Fa dm F�►at 'fi'1 rAid Fra Per V 500 TOO Sol 2,OX WO 2.001 25. L 1.4a low ,01 50,OMJ�1 _ * f 0.10 low .DO7 100.030 7-00%J imu Ino,901 jl�,?6 SWIM 03-7v� Sim law! • ADI 1.4300. 3233.75 4.7S Iwo 1 m i , 6=75 3�- 1 t TO&A MOMing P=rait Fee_ E[14Mb nP1!f7# j &ftr" & Mm I.:QfE M 1jg MYL bnr Uyore! qFf Mbxvs :OminWr Fee'.. Rate Re -r dirt UAM Fc c DM BUM F : Tit PMS Ftom it Fein_ #'trrrbr =i� 11PiT 21100; 1 KOOD mm 2.0% $00MI ;MMa 2236,00 UfW% 1 TW Pkwy 13.f �e �1r PermA � Ad�orral �!l7r rr fi rLi$ .#ritio4a [I7�i Mtt' i' '-I" Mr Piirit $P firr $iA .E fer- $?D Mm & Lid 32M 1r r a 9- 0 D) 25it-mer C110 V,6 IH im svm 0 M25 2 -OU k!V ER *ft WeffFiS � ��� �17L71r F1ff��Inti.,p "€� O7-rCtn*&cW $1-11W,00 C�)rnffbertu �FmTmfy Hntr )' x.00 0 • ( F &srdy 1' .1 $235.i1D 1 t+ -c Frut FrOtq p- $I.?-M erfru 1~ 912M Totaff Wah-r t o Paras smas ci ( Rug. P g ( s ) I I : 2 2AM ) e ;3 U ti on n e c t i an COOWSCUO Type Gast Sq F1 P MMT. $JD. I? 3] S1 M.57101 12Z If ;1. 01.17 Feft �7C1.OD Si S.1 O,4L.r JO -00 SM 307.00 � #�.�] +@� ou WA $�0r y_s�,y� -� . ry0 74 -.14 $11 W- x•30 =,014 -3 x_30 ,�� S•�.�. ice'.' .W _ . tires 35-34T-1D •�_����- , 00 357 •r.: t Ito nUVL $3,4ms P MMT. $JD. I? 3] S1 M.57101 12Z If ;1. 01.17 Feft �7C1.OD Si S.1 O,4L.r JO -00 SM 307.00 � #�.�] +@� ou WA $�0r y_s�,y� -� . ry0 74 -.14 $11 W- x•30 =,014 -3 x_30 -f0 .W $0-134-346--W 35-34T-1D DU , 00 357 Ito FA2 $3,4ms TOM AN Fma-1 $6.0sam Page fiat Son t