April 8, 2004
Permit Numbers. 04 00112
Project Name:
Project Type:
Wingers Restaurant
Commercial New
Review Action
Review Item.�_. Actions Required for
Firs Department Review � ,
Required Fire Flow
Water Supply
Fire Access Roads
Other Comments
warm systems
Firs Extinguishers
Automiatc Fire Extinguishing Systems
Standpipes
Commercial hooking
Fire Department Siteplan Review 1 Approval
Parcel #'s
REQUIRED FIRE FLOW IS 1750 GPM/TWO
HOURS. WITH A FIRE HYDRANT WITHIN 500
FEET. /
000W 40 Y�w \j a-ird
7WPIF
OCCUPANCY REQUIRES A "K" TYPE FIRE
EXTINGUISHER MOUNTED IN KITCHEN
AREA IN ADDITION TO A MINIMUM OF
2A10BC FIRE EXTINGUISHERS MOUNTED
WITHIN TRAVEL DISTANCES.
OCCUPANCY REQUIRES A FIRE
SUPPRESSION SYSTEM IN THE EXHAUST
HOOD. SUBMITTALS., CONTRACTOR NAME
ADDRESS, AND TELEPHONE NUMBER
REQUIRED PRIOR TO BUILDING PERMIT
BEING ISSUED.
iliLe, � Cwc��„t s�e
E�14Vk dor t�i� P.�rr►�
B 14, L � � � ✓E,� SS�u e-.5
12 North Center Street
Rexburg, Idaho 8344
Phony: (2(7$) 359-3020
Fax (2D8} 359-3422
03/23/2004
03/23/2004
03(23/2004
03/23/2004
03/23/2004
03!23/2004
03/23/2004
03/23/2004
A
C]TY OF
[��EXBU
R,G.
N1 J'Y
April 29, 2,004
Permit Numbers. 04 00112
Proje;ct Name:
Project Type:
Review Item
Wingers Restaurant
Commercial New
Building Department Review
Accessibility Review
Height and Area Review
Complies with approved Site Rlan review
Building Code Fire Compliance Review
Building Type Compliance
Exiting review
Water and Sewer Service
Plumbing Sewer Drain Review
Plumbing Storm Drain Review
Mechanical Review
Interior Environment
Review Action
Actions Required for Approval
Accessible Parking signs are shown on page
A7.02 but not on site plan. Idenfify the location
on the site plan.
The code allows a VB building used as a
restuarant to be 6000 sq. ft. and this buidling is
about 360a. This building 'i's one story as
allowed by code.
A new site plan was provided. The previous
site pian did not match the building construction
plans. identify an site plan the location of the
handicap parking space signs.
The plansidentify open space around the
building. Exterior dire seperatian is not required.
Sprinklers are not required.
Building has been reviewed as Type VB non-
rated construction.
Provide panic hardware on egress doors as per
the 2000 International Building Code (113C)
Section 1003.3.1-9. Emergency lighting, is
required at exits as per !BC Section 1003.2.11.
The lighting plan on page E9.01 identifies
emergency lights in the restrooms and the
kitchen. Please identify in the dinging area.
Grease trap required to have 311 gent.
Wader softners recycling system requires floor
sink. Floor sink should not discharge into
grease interceptor. Discharge into sanitary
sewer.
Provide manufacture's certificate of compliance
for mechanical components as per !BC Section
1621.3.5
Provide the fame spread and srnvkedeveloped
index,of the interior paneling identified as "bead
12 Forth Center Street
Rexburg, fdaho 83440
Phone (248) 359-3020
Fax (208) 359-3022
04/21/2004
04/27/2004
Le l�iI�L!
04/27/2004
04/28/2004
04/28/2004
04/29/2004
04!29/2004
r
115
04/29/2004
04/29/2004
CITY Or
f 'EXBUPs..G.
NNIFRICA5.5 FAMILY COMMUNI FY
April 29, 2004
Permit Number: 04 00112
Project Name:
Project Type:
Revi-ewAtem
Wingers Restaurant
Commercial New
Plumbing Potable Water Review
Structural Review
Energy Conservation Compliance Review
Parcel #'s
Review Action
ions Required f
board" includ ing the paint -or 'finish associated
with it.
The plans an page S2.02 indicate that the
Contractor is to coordinate the placement
location and the weights of the HVAC roof units
with the joist manufacturer. Please provide the
engineering documentation for the joists.
Include the locations and the weights of the roof
units.
The foundation is, not designed as per local
requirements. The frost depth is a minimum of
36" deep. Please redesign the foundation
accordingly.
Provide lighting evaluation for the International
Energy Conservation Code (IECC)..
RO Box 280
12 North Gent r Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (20$) 359-3022
04/29/2004
04/29/2004
CITY OF
f EXBUP��G -
April 29, 2004
Permit Number: 04 00112
Project Name:
Wingers Restaurant
Project Type. Comm-erdal New
Review Item
Fire Department Review
Required Fire Flow
Other Comments
Fire Extinguishers
Automatic Fire Extingul'shing Systems
Alarm Systems
Standpipes
'mater Supply
Fire Access Rosas
Fire Department Siteplan Review 1 Approval
Commercial Cooking
Review Action
ions Ream
r Apmoval
REQUIRED FIRE FLOW IS 1750 GPM/TWO
HOURS WITH A FIRE HYDRANT WITHIN 500
FEET.
OCCUPANCY REQUIRES A "K" TYPE FIRE
EXTINGUISHER MOUNTED IN KITCHEN
AREA. IN ADDITION TO A MINIMUM OF
2A1013C FIRE EXTINGUISHERS MOUNTED
WITHIN TRAVEL DISTANCES.
Must install 3" Vent off of grease interceptor
New drawings submitted show change in
parking around structure. Please provide "No
Parking Fire Lane" signs and paint the curb red
in the front.
New drawings submitted show change in
parking around structure. Please provide "No
Parking Fire Lane" signs and paint the curb red
in front.
OCCUPANCY REQUIRES A FIRE
SUPPRESSION SYSTEM IN THE EXHAUST
HOOD. SUBMITTALS, CONTRACTOR NAME,
ADDRESS, AND TELEPHONE NUMBER
REQUIRED PRIOR TO BUILDING PERMIT
BEING ISSUED.
P-0 Box 280
12 North Center Street
Rexburg, Idaho 83444
Phone (248) 359-3020
Fax (208) 359-3022
Ap.proved
03/23/2004
03/23/2004
03/23/2004
03/23/2004
03/23/2004
03/23/2004
03/23/2004