HomeMy WebLinkAboutSTAFF REVIEWS - 05-00480 - Pinnacle Security - Remodel3/1/2006 Scott Spaulding Design Intelli-gence 103 7 Erickson Drive Rexburg, Idaho 8344a Dear Scott, CITY EXBLaG Americas Family Community I have reviewed the Pinnacale drawings that you have provided me and have identified the following discrepancies: 1. The total occlipant number for the upstairs i's greater than 99 and therefore two sets of stars at least 44" wide are required for egress. 2. Provide details thatidentify how the requirements of SBC See ion 704.1 1 Will be met. 3. The 2 -hour dears at the firewall must be self closing. Identify an the plans. 4. If building is not sprinklered, the maximum length of a dead. end hallway is 20' as per IBC Section 10 16.3. Nuke the necessary changes to the plans. S. Are new footings required for the added floor loads? Do the walls that are supporting the new floats have footings Winder.hem? If so, are they sized adequately for the added loads? Provide details and calculations. 6. How is the HVAC being handled. Provide details. 7. Please respond to the requested review actions that were submztted by the Fire Department Review (attached). Please return two segs of revised plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 ext. 324. Val Christensen Building Official cc Brad Johnson Josh,Stoddard Val Christensen Bu-ildingOficial 19 E. Main Rexburg ID 83440 P. 0. Box 280 vale @rexhurg. arg wwiv.rexbmtX. or Phone . 3020 .t. ' Rax(206)359.3022 ITY OF EXBURG _--_C)W- Amefica� Family Community February 1, 2006 Permit Number: 05 00480 Project Name: Project Type: Review Item Review Action Pinnacle Security Remodel commercial Remodel Building Department Review Interior Environment Complies with approved Site Plan Review Accessibility Review Exiting Review Building Code Fire Compliance Review Structural Review Height and Area Review Building Type Compliance Mechanical Review _ Actions Required for Approqal Wall and ceiling finishes must meet the requirements of Section 803 of the IBC. Adding 15% to the occupancy of the building requires a new site plan be submitted. An accessible women's restroom is required on the ground floor. The men's restroom must be made to be accessible. Provide details. The West and center stairways must be a minimum of 44" wide. Identify location of exit signs and emergency exit lights. Identify two new doors to the nursery as per !BC Table 1014.1. Entry doors at amain entrance must swing in the direction of travel as per IBC Section 1008.1.2'. Building must be sprinklered. Adding the additional space to the upstairs and changing the occupancy of the building requires that the building meet the requirements of the 2003 International Building Code (113C). Windows are not allowed on the South wail due to the location of the property line. Provide structural details and calculations. Idenfify,joist size and spacing. The struetural engineer must identify haw all Loads will be bandied. They include but are not limited to footings for the new bearing walls that have been created and existing wall seismic considerations from adding a new floor diaphram. Provide details stamped by a licensed professional. Area does not meet the requirements of the code unless sprinklers are provided. Building is V13 or VA identify new HVAC at the new offices and other spaces. RO Box 280 19 E. Main St. Rexburg, Who $3440 Phase (2(}8) 359-3020 Fax (208) 359-3022 W-, 0 fl!"T = 02/01/2006 CIT 1 0 F EXB TJRG- -C)QV---- A March 1, 2006 Permit Number: 05 00480 Project Name: Project Type: R eview Action Pinnacle Security Remodel Commercial Remodel Review Item .. .. ..... ....:.. ....... Firl .. iw ................ Required Fire Flow '"mater Supply Automatic Fire Extinguishing Systems Standpipes Fire cress Roads Fire Exfinguishers Commercial Cooking Alarm Systems ether Comments Parcel #'s RPRRXB 103 745 10 bg RO Box 280 19 F Mair St. Rexburg, Idaho $344 Phone (2Q8) 359-3020 Fax (208) 3593022 Actions Reqmu re�lfo r Ap pTova l —Anproved REQUIRED FIRE FLOW BASED ON APPROXIMATELY 24,000 SQUARE FEET TYPE IV IS 2750 GPM/TWO HOURS. ESTABLISHED WITH EXISTING HYDRANTS NOT REQUIRED NOT REQUIRED ESTABLISHED FIRE EXTINGUISHERS NOT NOTED ON SUBMITTED PLANS, PLEASE PROVIDE MORE INFORMATION. PLANS INDICATE A KITCHEN AREA. PLEASE PROVIDE MORE DETAILS. AREA MAY REQUIRE A HOOD SYSTEM WITH FIRE SUPPRESSION. MANUAL FIRE ALARM SYSTEM REQUIRED AS OCCUPANCY LIMIT ON UPPER FLOOR EXCEEDS 700 PERSONS. (IFC SECTION 907.2.2) PLEASE PROVIDE PLANS AND/OR A LETTER OF INTENT FROM A LICENSED FIRE ALARM COMPANY. PLEASE PROVIDE DETAILS ON SWIMMING POOL OPERATIONS (CHEMICAL USAGE, HEATING, ETC.)PLEASE PROVIDE MORE DETAILS ON NOTED ITEMS. IF THERE ARE ANY QUESTIONS PLEASE CONTACT CHRIS AT 705-1312 OR BRAD AT 716-1321. 0112812006 01/28/20-06 01 /28/2006 01/28/2006 01/28/2006 0 til ITT REXBURG March 2, 2006 Permit Number: 06 00103 Project Norrie: Project Type: Review Action Pinnacle Security -Site Plan Site Plan Review Review Item Building De�ra�ttnen� Revir Number of Parking Spaces Fire Separation Parking Configurative Plumbing Review Miscellaneous Snow Storage Parcel #'s RPRRXB 103 745 10 Avt_i�ons Require -d for A rov Parking meets requirements as long as the exercise space is used as accessory to the business portion of the building. If used other than described above, then more parking may need to be provided. An easement on the property adjacent on the North side has been provided to allow window in the North wall of the. building. The ADA van parking space requires 8wide loading space adjacen# to it. Replace the landscape strip between the curb and the sidewalk. This area has been hard surfaced in the past and should be restored to a landscape area. The snow storage identified for the front parking lot does meet the 10% requirement. R Box 280 1Main St. Rexburg, Idaho 8344 Phone (2Q8) 359-3020 Fax (2Q$) 359-3422 A130m)ved 03/01/2006 03/01/2006 REVD jx-L)LTRG QV February 1, 2006 0 ReviewActoon Permit Number: 05 00480 Project Name: Pinnacle Security Remodel Project type: Commercial Remodel Review Item Miscellaneous Parcel #!'s RPRRXR10374510 ActionsRe�c aired for Ap.Vroval P.0 Box 280 19 E. Main St. Rexburg, Idaho 8344 Phone {20$} 359-3020 Fax (2Q8) 3593022 Plumbing fixtures must meet the requirements of !BG Section 29Q2. Provide a new yet of drawings that are stamped by a licensed professional. . a ,,. I TY OF REXBURG Apnmcals Family Communily March 22, 2006 bg Permit Number: 05 00480 Project Name: Project Type: Review Item Review Action Pinnacle Security Remodel Commercial Remodel Building Department Review Interior Environment Complies with approved Site Flom Review Accessibility Review Exiting Review Building Code Fire Compliance Review Structural Review Height and Area Review Building Type Compliance Mechanical Review Actions lReq-qtred Wolf and ceiling finishes must meet the requirements of Section 8Q3 of the IBC. Adding 151J/0 to the occupancy of the building requires a new site plan be submitted. An accessible women's restroom is required on the ground floor. The men's restroom must be made to be accessible. Provide details. The West and center stairways must be d-' minimum of 44" wide. Identify location of exit signs and emergency exit lights. Identify two new doors to the nursery as per IBC Table� 1D14.1. Entry doors at main entrance must swing in the direction of trace! as per IBC Section 1008.1.2. V0AJLC- P-0 Box 280 19 E. Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (2p8) 359-3022 02/0 Building must be sprinkfered. Adding the additional space to the upstairs and changing the occupancy of the building requires that the building meet the requirements of the 2003 ,,o' International Building Cade (113C). Windows are not allowed on the South wall due fn the l location of the property line. Provide structural details and calculations. Identify joist size and spacing. The structural engineer must identify how all loads will be handled. They include but are not limited to footings for the new bearing walls that have been created and existing wall seismic considerations from adding a new floor diaphram. Provide details stamped by a V licensed professional- Area does not meet the requirements of the code unless sprinklers are provided. Building is VB or VA DfC r1e, i P 0 /0 Lo; OeV fIx�ir'rc� P66t cr��yy�E Identify new HVAC at the new offices and othPr spaces. I 1_4 I TY OF I�EXBURG - - - Americ : � family Comm t4 n ily March 22, 2006 0 Permit Number: 05 00480 Project Name: Project Type; review Item Review Action Pinnacle Security Remodel Commercial Remodel Fire, Department Review Required Fire Flow Water Supply Automatic Fire Extinguishing Systems Standpipes Fire Access Roads Fire Extinguishers Commercial Cooking Alarm Systems Other Comments Parcel #`s RPRRYB 1 X3745 I .0 Actions Required fo Val REQUIRED FIRE FLOW BASED ON APPROXIMATELY 24,000 SQUARE FEET TYPE IV IS 2750 GPM/TWO HOURS. ESTABLISHED WITH EXISTING HYDRANTS NOT REQUIRED NOT REQUIRED ESTABLISHED FIRE EXTINGUISHERS NOT NOTED ON SUBMITTED PLANS, PLEASE PROVIDE MORE INFORMATION. P.0 Box 280 19 E. Main St. Rexburg, Idaho 83440 Phone (2Q$) 359-3020 Fax (208) 359-3022 Aroved . A 01/28/2006 01/28/2006 01/28/2006 01/28/2006 01/28/2006 PLANS INDICATE A KITCHEN AREA. PLEASE /J�� �,�n PROVIDE MORE DETAILS. AREA MAY REQUIRE A HOOD SYSTEM WITH FIRE SUPPRESSION. MANUAL FIRE ALARM SYSTEM REQUIRED ��NNAG G� ro AS OCCUPANCY LIMIT ON UPPER FLOOR V 10� t�7F�K EXCEEDS 100 PERSONS. (IFC SECTION °� tu• TIFE /S 907.2.2) PLEASE PROVIDE PLANS AND/ORA PC01**#ft*i/ k VC,. ,_ .n LETTER OF INTENT FROM A LICENSED, FIRE ALARM COMPANY. PLEASE PROVIDE DETAILS ON SWIMMING POOL OPERATIONS (CHEMICAL USAGE, HEATING, ETC.)PLEASE PROVIDE MORE DETAILS, ON NOTED ITEMS. IF THERE ARE ANY QUESTIONS PLEASE CONTACT CHRIS AT 705-1312 QR BRAD AT 716-1321. G� ryryL Y ? 2 pb _ -- I TY 0 F EX -B URG CW-------- t U o March 22, 2006 Permit Number: Project Name: Project Type: Review Item Miscellaneous 10 Review Action 0500480 Pinnacle Security Remodel Commercial Remodel .. _ Actions Re rovall Plumbing fixtures must meet the requirements of IBS Section 2902. Provide a new set of drawings that are stamped by a licensed professional. Parcel #'s RPRRXB 103745 10 P.O Box 280 19 E. Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (2(78} 359-3022