Loading...
HomeMy WebLinkAboutSHORT FORM - 05-00419 - 1144 Red Cedar Rd - New SFR MechanicalShort mrm Entire House For: Travis Wade Rexburg, Idaho 83440 Htg Clg Outside db ('F) -6 89 Inside db (°F) 70 75 Design TD (°F) 76 14 Daily range - H Inside humidity (%) 50 Moisture difference (gr/Ib) -31 Job: 1 Date: Sep 12, 2005 By: Blair Singleton 0500419 1 144 Crescent Dr - Mad. Co. Mcch. Infiltration Method Simplified Construction quality Average Fireplaces 0 HEATING EQUIPMENT COOLING EQUIPMENT Make AmStd Make AmStd Trade Freedom 90 Single Stage Trade Standard Model AUX080C942D' Cond 2A7B2030A1 Coil TXC042C4 Efficiency 92.1 AFUE Efficiency 11.5 SEER Heating input 80000 Btuh Sensible cooling 20860 Btuh Heating output 75000 Btuh Latent cooling 8940 Btuh Temperature rise 77 °F Total cooling 29800 Btuh Actual air flow 1051 cfm Actual air flow 1051 cfm Air flow factor 0.020 cfm/Btuh Air flow factor 0.053 cfm/Btuh Static pressure 0.10 in H2O Static pressure 0.10 in H2O Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area (ft') Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (cfm) Bed 187 3018 1400 61 74 Bonus 364 9602 2443 193 130 Bed 3 222 2711 423 54 22 bath 50 248 3 5 0 stairs 3 64 0 0 0 0 Bed 4 182 3371 1031 68 55 CIst.1 21 0 0 0 0 Clst.2 21 0 0 0 0 storage 175 0 0 0 0 Mas Bed 195 2975 2417 60 128 utility 48 1430 1376 29 73 Bath 1 53 626 160 13 8 Stairs 64 0 0 0 0 Family Room 502 7102 3958 142 210 Mach 49 0 0 0 0 Family Room 2 586 7573 748 152 40 hell i n7 n n n n Printout certified by ACCA to meet all requirements of Manual J 8th Ed. wnghtsoft RightSude Residentml6.0.02 RSR40615 MCA CAMy DowmeMslWrighmaR WAOTravis Wade 1.0p Cale = MJB Orientation = W OCT 2 8 2005 r 2005-Sep-13 00:17:13 Page i Bed 5 .r 182 3493 1035 70 55 Kitchen/Dining 319 4681 2467 94 131 WIC 48 0 0 0 0 Mas. Bath 120 2456 886 49 47 Bed 2 208 3119 1428 63 76 Stairs 2 52 0 0 0 0 closet 12 0 0 0 0 Entire House 3906 52407 19774 1051 1051 Other equip loads 9743 1795 Equip. @ 0.94 RSM 20275 Latent cooling 0 TOTALS 13906 ' 62150 ' 20275 ' 1051 ' 1051 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. wnghtsoft RightSuRe Residential6.0.02RSR40615 2005Sep-1300:17:13 .CCA CAMy Dmumenls\Wnghtsa6 HVAC\Travis Wade 1.up Calc = MJ8 Cdentation = W Page 2 Building Analysis Entire House Job: 1 `- Date: Sep 12, 2005 By: Blair Singleton Pro'ect Information For: Travis Wade Rexburg, Idaho 83440 Design Conditions Location: Indoor: Idaho Falls, ID US Indoor temperature (°F) Elevation: 4' 41 ft Latitude: 44°N Design TD (F) Relative humidity (%) Outdoor: Heating Cooling Moisture difference (grAb) Dry bulb (°F) -6 89 Infiltration: Daily range (°F) - 34 (H) Method Wet bulb (°) 60 Construction quality Wind speed (mph) 15.0 7.5 Fireplaces Component Btuh/ft2 Btuh % of load Walls 5.4 22756 36.6 Glazing 25.8 8013 12.9 Doors 27.4 2298 3.7 Ceilings 2.0 4229 6.8 Floors 2.1 4521 7.3 Infiltration 2.2 8034 12.9 Ducts 2557 4.1 Piping 0 0.0 Humidification 0 0.0 Ventilation 9743 15.7 Adjustments -0 Total 62150 100.0 Coolinq Component Btuh/ft2 Btuh % of load Walls 0.4 1687 7.8 Glazing 27.6 8564 39.7 Doors 6.7 559 2.6 Ceilings 1.1 2337 10.8 Floors 0.1 148 0.7 Infiltration 0.2 793 3.7 Ducts 986 4.6 Ventilation 1795 8.3 Internal gains 4700 21.8 Blower 0 0.0 AdJjustments 0 TOtal 21569 100.0 Overall U-value = 0.060 Btuh/ff`--°F Data entries checked. G w -- Heatinng 50 61.5 Simplified Average 0 Cooling 75 14 50 -31.5 wrnght50ft Righ4Suite Residential6.0.02RSR40615 2005.Sep-1300:17:13 ACO', C:1My Documents\Wdghtsoft HVAQTravis Wade t.rrp Calc = MJ8 Orientation = W Page 1 Component Constructions Job: 1 p Date: Sep 12, 2006 Entire House By: Blair Singleton For: Travis Wade Rexburg, Idaho 83440 Location: Indoor. Heating Cooling Idaho Falls, ID, US Indoor temperature (°F) 70 75 Elevation: 4741 ft Design TO (°F) 76 14 Latitude: 440N Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 61.5 -31.5 Dry bulb (°F) -6 89 Infiltration: Daily range�°F) - 34 (H) Method Simplified Wet bulb (° ) - 60 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U-value insult R Mg HTM Loss Gig HTM Gain (11') (eWnlfti'1-! (Il"FIBWh) (eWhMn (aWro (S MFI (Mh) Walls 15813-DwcA: Basement - 8" concrete, wood framing, interior finish, R-13 cavity, no hoard insulation, V 12E-Osw: Wood stud frame, siding or stucco, no board insulation, R-19 cavity insulation Partitions (none) Windows 61 A: vinyl clear low e, clear low-e; NFRC rated (SHGC=0.30) Doors 11 K0: Metal door, fiberglass core, with storm n 472 0.059 13.0 5.73 2706 0.12 55 e 496 0.059 13.0 5.78 2865 0.12 60 s 472 0.059 13.0 5.73 2706 0.12 55 w 464 0.059 13.0 5.69 2639 0.11 52 all 1904 0.059 13.0 5.73 10915 0.12 222 n 571 0.068 19.0 5.17 2948 0.64 365 ne 13 0.068 19.0 5.17 67 0.64 8 e 526 0.068 19.0 5.17 2718 0.64 336 se 13 0.068 19.0 5.17 65 0.64 8 s 584 0.068 19.0 5.17 3018 0.64 373 w 585 0.068 19.0 5.17 3023 0.64 374 all 2291 0.068 19.0 5.17 11841 0.64 1465 n 16 0.340 0.0 25.8 413 10.5 167 n 30 0.340 0.0 25.8 762 10.5 308 ne 10 0.340 0.0 25.8 248 23.0 220 e 104 0.340 0.0 25.8 2687 32.8 3415 se 10 0.340 0.0 25.8 258 29.1 291 s 16 0.340 0.0 25.8 413 18.3 292 s 16 0.340 0.0 25.8 413 18.3 292 w 32 0.340 0.0 25.8 827 32.8 1051 w 77 0.340 0.0 25.8 1990 32.8 2528 all 310 0.340 0.0 25.8 8013 27.6 8564 e 42 0.360 0.0 27.4 1149 6.66 280 w 42 0.360 0.0 27.4 1149 6.66 280 all 84 0.360 0.0 27.4 2298 6.66 559 wnghtsofit Right-Sude Residential 6.0.02 RSR40615 2005-Sep-1300:17,13 ACCK C:1My Documents\Wrightsoft WAGTravis Wade 1.np Cab = MJ8 OnentaWn = W Page 1 Ceilirtgs 168-38ad: Ceiling under vented attic, no radhwooarrier, dark shingles, R-38 insulation Floors 21A-32c: Carpeted basement Floor, No insulation, V wide 20P-19c: Carpeted Floor over open crawl/garage, R-19 blanket insulation 19A-0bscp: Carpeted Floor over tight basement, No wall insul, No insul 2140 0.026 38.0 )%Wy 1.98 4229 1.09 2337 1734 0.020 0.0 1.52 2636 0.00 0 332 0.050 19.0 3.80 1262 0.10 33 74 0.295 0.0 8.42 623 1.55 115 wrrghtsoR RightSufte Residenta16.0.0213SR40615 2005Seµ1300:17:13 ACCh C:%My CocumentslWrightsoft WAC%Travis Wade 1.np Cab = MJ8 Orientation = W Page 2 Project: -Summary Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton Project Information For: Travis Wade Rexburg, Idaho 83440 Notes: Weather: Idaho Falls, ID, US Winter Design Conditions Outside db Inside db Design TD Summer Design Conditions -6 OF Outside db 70 OF Inside db 76 °F Design TD Daily range Relative humidity Moisture difference Heating Summary Structure 49850 Btuh Ducts 2557 cfm Central vent (139 cfm) 9743 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 62150 Btuh Infiltration Method Simplified Construction quality Average Fireplaces 0 Heating Cooling Area (fN) 390 3909 Volume (ft3) 24512 24512 Air changes/hour 0.28 0.15 Equiv. AVF (cfm) 114 61 Heating Equipment Summary Make AmStd Trade Freedom 90 Single Stage Model AUX080C942D' Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 92.1 AFUE 80000 Btuh 75000 Btuh 77 OF 1051 cfm 0.020 cfm/Btuh 0.10 in H2O 89 OF 75 OF 14 OF H 50 % -31 gr/lb Sensible Cooling Equipment Load Sizing Structure 18788 Btuh Ducts 986 Btuh Central vent (139 cfm) 1795 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.94 Equipment sensible load 20275 Btuh Latent Cooling Equipment Load Sizing Structure 898 Btuh Ducts -51 Btuh Central vent (139 cfm) -2495 Btuh Equipment latent load 0 Btuh Equipment total load 20275 Btuh Req. total capacity at 0.70 SHR 2.4 ton Cooling Equipment Summary Make AmStd Trade Standard Cond 2A7B2030A1 Coil TXC042C4 Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio Printout certified by ACCA to meet all requirements of Manual J 8th Ed. 11.5 SEER 20860 Btuh 8940 Btuh 29800 Btuh 1051 cfm 0.053 cfm/Btuh 0.10 in H2O 1.00 wnghtsofC Right-Sude Residentia160.02 RSR40615 2005-Sep-13 0017 13 C?'. C:Wy DocumentsMrightsofl HVAOTravis Wade 1 rip Calc = MJ8 Orientation = W Page 1 AED AMessment Entire House For: Travis Wade Rexburg, Idaho 83440 Location: Idaho Falls, ID, US Elevation: 4741 ft Latitude: 440N Outdoor: Heating Dry bulb (OF) -6 Daily range (OF) - Wet bulb (OF) - Wind speed (mph) 15.0 1 1 M y Job: 1 Date: Sep 12,2005 By: Blair Singleton Indoor: Indoor temperature (OF) Design TD (OF) Relative humidity (%) Cooling Moisture difference (gr/lb) 89 Infiltration: 34 ( H) Method 60 Construction quality 7.5 Fireplaces Test for Adequate Exposure Diversity Hourly Glazing Load Heating Cooling 70 75 76 14 50 50 61.5 -31.5 Simplified Average 0 0 Hour of Dav Four-y Average AES) t Maximum hourly glazing load exceeds average by 23.7%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh writs fit RightSuite Residenlu160.02RSR40615 2005Sep-13001713 ACCA Carty Documents\Wrightsoh HVAC\Travls Wade I.rrp Cale = MJ8 Onentahon = W Page 1 D ll="" n, Right- Norksheet Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton 1 Room name Entire House Bed 1 2 Exposed vadl 573.6 ft 39.0 It 3 Ceiling height 8.0 ft 8.0 ft healfcool 4 Room dimensions 1.0 x 187.0 ft 5 Room area 3906.0 W 187.0 W Ty Construction U-value Or HTM Area (ft-) Load Area (F) Load number (BluhVft F) or perimeter (ft) (Blob) or perimeter (ft) (Btuh) Heat Cool Gross NIPS Heat Caol Gross WP/S Heat Cool 6 V✓ 15813-0m-4 0.093 n 4.48 0.24 488 472 2706 55 0 0 0 0 �G B1A 0.340 n 25.84 10.46 16 0 413 167 0 0 0 0 12E-Osw 0.068 n 5.17 0.64 600 571 2948 365 120 120 620 77 LC 61A 0.340 n 25.84 10.46 30 0 762 308 0 0 0 0 11 W 12E-Om 0.068 no 5.17 0.64 23 13 67 8 0 0 0 0 �C 61A 0.340 ne 25.84 22.98 10 0 248 220 0 0 0 0 W 15813-0wc4 0.093 a 4.48 0.24 496 496 2865 60 0 0 0 0 12E-Osw 0.068 a 5.17 0.64 672 526 2718 336 0 0 0 0 Ij 61A 0.340 a 25.84 32.83 104 0 2687 3415 0 0 0 0 11K0 0.360 a 27.36 6.66 42 42 1149 280 0 0 0 0 12E-Osw 0.068 se 5.17 0.64 23 13 65 8 0 0 0 0 61A 0.340 as 25.84 29.05 10 0 258 291 0 0 0 0 Vy 15B13.Owc4 0.093 s 4.48 0.24 488 472 2706 55 0 0 0 0 t-C 61A 0.340 s 25.84 18.26 16 0 413 292 0 0 0 0 1p/ 12E-0sw 0.068 a 5.17 0.64 600 564 3018 373 88 8s 455 56 L--G 61A 0.34g s 25.84 18.26 16 0 413 292 0 0 0 0 W 15813-0wc4 0.093 w 4.48 0.24 496 464 2639 52 0 0 0 0 L-C 61A 0.340 w 25.84 32.83 32 0 827 1051 0 0 0 0 12E-0sw 0.068 w 5.17 0.64 704 585 3023 374 104 88 452 56 61A 0.340 w 25.84 32.83 77 0 1990 2528 17 0 426 542 11K0 0.360 w 27.36 6.66 42 42 1149 280 0 0 0 0 C 16B-38ad 0,026 - 1.98 1.09 2140 2140 4229 2337 187 187 370 204 F 21A-32c 0.020 - 1.52 0.00 1734 246 2636 0 0 0 0 0 F 20P-19c 0.050 - 3.80 0.10 332 73 1262 33 0 0 0 0 F 19A-Obscp 0.295 8.42 1.55 74 18 623 115 0 0 0 0 6 c)AED excursion 0 167 Envelope loss/gain 41816 13295 2323 1102 12 a) Infiltration 8034 793 695 69 b) Room ventilation 1 0 0 0 0 13 Internal gains: Occupants ® 230 10 2300 1 230 Appliances ® 1200 2 2400 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -0 0 0 0 14 Subtotal 49M 18788 3018 1400 15 Duct loads 5% 5% 2557 986 0% 0% 0 0 Total room load 52407 19774 3018 1400 Air required (cfm) 1051 1051 61 74 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. wnghtsoflt Right -Suite ResWentia16,O.G2 RSR40615 2005-Sep-13 00:17:13 CAMy Documents\Wdghtsoft HVAC\Travis Wade Imp Calc = MJ6 Orientation = W Page 1 ' T, 11C Right-Q-Norksheet _ Job: 1 Entire House Date: Sep 12, 2005 By: Blair Singleton 1 Room name Bonus Bed 3 2 Exposed wall 80.0 8 33.0 0 3 Ceiling height 8.0 8 heat/cool 8.0 8 heaVccol 4 Room dimensions 26.0 x 14.0 8 1.0 x 222.0 0 5 Room area 364.0 0' 222.0 W Ty Construction 11-value Or HTM Area (8-) Load Area (W) Load number (BluhRR`F) (Btuh/0') or perimeter (0) (Bluh) or perimeter ((I) (Btuh) Heat I Cool Gross NIPS Heat Cool Gross WP/S Heat Cool 6 W 15813-OwcA 0.093 n 4.48 0.24 0 0 0 0 96 80 441 8 �G 61A 0.340 n 26.84 10.46 0 0 0 0 16 0 413 167 W, 12E-0sw 0.068 n 5.17 0.64 112 112 579 72 0 0 0 0 �--G 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 17 `C 12E-0sw 61A 0.068 0.340 ne ne 5.17 25.84 0.64 22.98 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 15B73-0wc4 0.093 a 4.48 0.24 0 0 0 0 168 168 970 20 y! 12E-0sw 0.068 a 5.17 0.64 208 208 1075 133 0 0 0 0 I --.G 61A 0.340 a 25.84 32.83 0 0 0 0 0 0 0 0 D iiKO 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 W/ 12E-0sw 0.068 se 5.17 0.64 0 0 0 0 0 0 0 0 �C 61A 0.340 se 25.84 29.05 0 0 0 0 0 0 0 0 lq/ 15B734)wc-4 0.093 s 4.48 0.24 0 0 0 0 0 0 0 0 Y-6 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 gyp/ 12E-0sw 0.068 s 5.17 0.64 112 96 496 61 0 0 0 0 L-C 61A 0.340 s 25.84 18.26 16 0 413 292 0 0 0 0 W 15B7&Owc4 0.093 w 4.48 0.24 0 0 0 0 0 0 0 0 Y-C 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 l9/ 12E-0sw 0.068 w 5.17 0.64 208 208 1075 133 0 0 0 0 FL-GD 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 11K0 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 168-38ad 0.026 - 1.98 1.09 364 364 719 397 0 0 0 0 F 21A-32c 0.020 - 1.52 0.00 0 0 0 0 2.22 33 337 0 F 20P-19c 0.050 - 3.80 0.10 332 73 1262 33 0 0 0 0 F 19A-Obscp 0.295 - 8.42 1.55 0 0 0 0 0 0 0 0 6 c) AED excursion -36 -37 Envelope loss/gain 6619 1086 2163 158 12 a) Infiltration 1426 141 294 29 b) Rcamventitation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 1 230 Appliances @ 1200 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 254 5 14 Subtotal 7045 1456 2711 423 15 Duct loads 36% 68% 2657 986 0% 0%1 0 0 Total room load 9602 2443 2711 423 Air required (ctm) 193 130 54 22 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. wrlgl'1t5oR RghtSuite Reeiden6al6.0.02RSR40615 2005-Sep-1300:17:13 ACCA C:1My Documents\Wrghtso8 HVAC\Travis Wade 1.np Cale = MJB Orientation = W Page 2 Right_ Worksheet Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton 1 Room name bath stairs 3 2 Exposed wall 0.0 It 4.0 R 3 Ceiling height 8.0 R heat/cool 8.0 ft heaUcool 4 Room dimensions 5.0 x 10.0 R 16.0 x 4.0 R 5 Room area 50.0 W 64.0 W Ty i Construction U-value Or HTM Area (ftj Load Area Load number (Btuh/R;°F) (Btuh/W) or perimeter (R) (Btub) or perimeter (fi) (Btuh) Heat I Cool Grass 14IP/S Heat Cool Gross N/P/S Heat Cool 6 W 15B13-0wc4 0.093 n 4.48 0.24 0 0 0 0 32 32 185 4 t-G 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 U+/ 12E-Osw O.D68 n 5.17 0.64 0 0 0 0 0 0 0 0 t-G 61A 0.340 n 25.84 10.46 D 0 0 0 0 0 0 0 11 T 12E-0sw 0.068 ne 5.17 0.64 D 0 0 0 0 0 0 0 t--G 61A 0.340 no 25.84 22.98 0 0 0 0 0 0 0 0 w 15813-0wc-4 0.093 a 4.48 0.24 0 0 0 0 0 0 0 0 12E-0sw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 Tj 61A 0.340 a 25.84 32.83 0 0 0 0 0 0 0 0 11 KO 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 t--G 12E-0sw D.068 se 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 se 25.84 29.05 0 0 0 0 0 0 0 0 W 15813-0wc-0 0.093 s 4.48 0.24 0 0 0 0 0 0 0 0 �C 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 �9/ 12E-0sw 0.068 a 6.17 0.64 0 0 0 0 0 0 0 0 L-C 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 Vy 15813-Owc-4 0.093 w 4.48 0.24 0 0 0 0 0 0 0 0 �C 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 ILZ12E-0sw 0.068 w 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 11 KO 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.98 1.09 0 0 0 0 0 0 0 0 F 21A-32c 0.020 - 1.52 0.00 50 0 76 0 64 4 97 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.42 1.55 0 0 0 0 0 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 76 0 282 3 12 a) Infiltration 0 0 36 4 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances @ 1200 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 172 3 -318 -7 14 Subtotal 248 3 0 0 15 Dud loads 0% 0% 0 0 0% 0% 0 0 Total room load 248 3 0 0 Air required (rim) 5 0 0 0 Printout Certified by ACCA to meet all requirements of Manual J 8th Ed. wr4ghtsof[ Right -Suite Residential6.0.02RSR40615 2005-Sep-1300:17:13 MCA CAMy Documets\Wri nghtsoft HVAWravis Wade 1.np Cale - MJB Orientation = W Page 3 Right-w Worksheet Entire House Job: 1 Date: Sep 12, 2006 By: Blair Singleton 1 Room name Bed 4 Clsl. 1 2 Exposed well 38.0 fl 7.0 8 3 Ceiling height 8.0 0 heat/cool 8.0 6 heallcool 4 Room dimensions 13.0 x 14.0 8 7.0 x 3.0 8 5 Room area 182.0 P 21.0 W Ty Construction U-value Or FfTivl Area (" Load Area (it-) Load number (Btuh/IP--°F) (BfuhMt� or perimeter (it) (Btuh) or perimeter (it) (Bluh) Heat Cool Gross l4/P/S Heat Cool Gross t4/P/S Heal Cool 6 W 15813-Owc-4 0.093 n 4.48 0.24 112 112 647 14 0 0 0 0 I-G 61A 0.340 n 25A4 10.46 0 0 0 0 0 0 0 0 y/ 12E-Osw 0.068 n 6.17 0.64 0 0 0 0 0 0 0 0 Y_G 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 11 W 12E-0sw 0.068 no 5.17 0.64 0 0 0 0 0 0 0 0 �C 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 15813-0wc4 0.093 a 4.48 024 0 0 0 0 0 0 0 0 4y 12E-0Ow 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 IL�D, 61A 0.340 a 25.84 32.83 0 0 0 0 0 0 0 0 11K0 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 19/ 12E-0sw 0.068 as 5.17 0.64 O 0 0 0 0 0 0 0 __G 61A 0.340 se 25.84 29.05 0 0 0 0 0 0 0 0 tR/ 15B13.0wc-0 0.093 s 4.48 0.24 88 88 508 11 0 0 0 0 _f 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 12E-OSW 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 s 25.84 1826 0 0 0 0 0 0 0 0 1pr 15813-0wc4 0.093 w 4AS 024 IN as 488 9 56 56 323 7 --G 61A 0.340 w 25.84 32.83 16 0 413 525 0 0 0 0 Vy 12E-0sw 0.068 w 5.17 0.64 0 0 0 0 0 0 0 0 _`(D` 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 11K0 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 168-38ad 0.026 - 1.98 1.09 0 0 0 0 0 0 0 0 F 21A-32c 0.020 - 1.52 0.00 182 38 277 0 21 7 32 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-Ob5cp 0.295 - 8.42 1.55 0 0 0 0 0 0 0 0 6 c) AED excursion 192 -1 Envelope loss/gain 2333 751 355 6 12 a) Infiltration 339 33 62 6 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances @ 12DO 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 700 17 418 -12 14 Subtotal 3371 1031 0 0 15 1 Duct loads 0% 0% 01 0 0% 0%1 0 0 Total room load 3371 1031 1 0 0 Air required (rim) 68 55 1 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. w111­44_=Jhtsoft Right -Suite Residential 6.0.02 RSR40615 2005Sep-13 00:17:13 ^MCA C:\My Documents\Wrightsoe HVAC\Travis Wade 1.np Calc = MJ8 Orientation = W Page 4 Right-w-Worksheet Entire House Date: Sep 12,2005 By: Blair Singleton 1 Room name Clst. 2 storage 2 Exposed wall 7.0 it 15.0 it 3 Ceiling height 8.0 it heat/cool 8.0 6 heat/cool 4 Room dimensions 7.0 x 3.0 it 1.0 x 175.0 it 5 Room area 21 D ft2 175.0 it' Ty Construction U-value Or HTM Area #F) Load Area (it-) Load number (BluhMF_.F) (BtuhV) or perimeter (it) (Btuh) or perimeter (it) (Btuh) Heat I Cool Gross WP/S Heat Cool Grass hgP/S Heat Cocl 6 Vy 15B13-0wc-0 0.093 n 4.48 0.24 0 0 0 0 0 0 0 0 l-6 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 V+l 12E-Osw 0.068 n 5.17 0.64 0 0 0 0 0 0 0 0 �-C 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 1 i 12E-0sw 0.068 no 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 15613-0wc41 0.093 a 4.48 0.24 0 0 0 0 0 0 0 0 Vj/ 12E-0sw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 �L1D2 61A 0.340 a 25.84 32.83 0 0 0 0 0 0 0 0 11 K0 0.360 a 27.36 B.66 0 0 0 0 0 0 0 0 YN 12E-0sw 0.068 se 5.17 0.64 0 0 0 0 0 0 0 0 --G 61A 0.340 as 25.84 29.05 0 0 0 0 0 0 0 0 W 15B13-Owcd 0.093 s 4.48 0.24 0 0 0 0 120 120 693 15 �--G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 ILG12E-0ew 0.068 a 6.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 W 15B13-0wc-0 0.093 w 4.48 0.24 56 56 323 7 0 0 0 0 t-G 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 Vj/ 12E-0sw 0.068 w 5A7 0.64 0 0 0 0 0 0 0 0 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 tF----GD 11K0 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.98 1.09 0 0 0 0 0 0 0 0 F 21A-32c 0.020 - 1.52 0.00 21 7 32 0 175 15 266 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.42 1.55 0 0 0 0 0 0 0 0 6 c) AED excursion _1 .2 Envelope losstgain 355 6 959 12 12 a) Infiltration 62 6 134 13 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances @ 1200 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -1093 -25 14 Subtotal 0 0 0 15 Dud loads 0% 0% 0 0 0% 0% 0 Total room load 0 0 0 1000 Air required(cfm) 0 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. C^M Dgme t \Wnghtsoh HVAMTravl s2005Sep-t3 00: Wade imp Calc - MJ6 Orientation = W age 5 Job: 1 E"I--,r"'° Li Righ._, Worksheet Entire House Date: Sep 12, 2005 By: Blair Singleton 1 Room name Mas Bed utility 2 Exposed wall 27.0 ft 8.0 ft 3 Ceiling height 8.0 ft hest/cool 8.0 ft heat/cool 4 Room dimensions 13.0 x 15.0 ft 8.0 x 6.0 it 5 Room area 195.0 it, 48.0 W Ty Construction U-value Or HTM Area (ft2) Load Area (ft) Load number I (BtuhflR-'F) or perimeter (R) (Btuh) or perimeter (ft) (Btuh) Heal Cool Gross WP/S Heat Coal Gross WP/S Heat Cool 6 V1/ 15813-Owc-0 0.093 n 4.48 0.24 0 0 0 0 0 0 0 0 L--G 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 W, 12E-Osw 0.068 n 5.17 0.64 112 112 579 72 0 0 0 0 LG 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 11 W 12E-0sw 0.068 ne 5.17 0.64 0 0 0 0 0 0 0 0 �G 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 15813-0wc4 0.093 a 4.48 0,24 0 0 0 0 0 0 0 0 0.068 a 5.17 0.64 104 56 289 36 0 0 0 0 t12E-0sw 61A 0.340 a 25.84 32.83 48 0 1240 1576 0 0 0 0 -GD 11K0 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 1W 12E-0sw 0.068 as 5.17 0.64 0 0 0 0 0 0 0 0 t--G 61A 0.340 se 25,84 29.05 0 0 0 0 a 0 0 0 Yy 15813-Owc-4 0.093 s 4.48 0.24 0 0 0 0 0 0 0 0 I--G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 'q/ 12E-0sw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 i--G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 yI 15B13-0wc-0 0.093 w 4.48 0.24 0 0 0 0 0 0 0 0 L-0 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 lt/ 12E4sw 0.068 w 5.17 0.64 0 0 0 0 64 43 222 27 F--G 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 L--D 11K0 0.360 w 27.36 6.66 0 0 0 0 21 21 575 140 C 16B-38ad 0.026 - 1.98 1.09 195 195 385 213 48 48 95 52 F 21A-32c 0.020 - 1.52 0.00 0 0 0 0 0 0 0 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 8.42 1.55 0 0 0 0 0 0 0 0 6 c) AED excursion 13 -117 Envelope loss/gain 2494 19091 892 103 12 a) Infiltration 481 48 143 14 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances@ 1200 0 0 1 1200 Less external load 0 0 0 0 Lass transfer 0 0 0 0 Redistribution 0 0 396 59 14 Subtotal 2975 2417 1430 1376 15 Duct loads 0% 0% 0 0 0% 0% 0 0 Total room load 2975 2417 1430 1376 Air required (cfin) 60 12a 29 73 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. �wr>,ghCsoR Right -Suite Residen8a16.0.02RSR40615 2005Sep-1300:17:13 C:1My Documents\Wrightsoft HVAC\Travis Wade 1.np Calc = MJ8 Orientabon = W page 6 Right-aJVorksheet Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton 1 Room name Bath 1 Stairs 2 Exposed wall 5.0 0 4.0 It 3 Ceiling height 8.0 0 heat/000l 8.0 A heat/cool 4 Room dimensions 1.0 x 53.0 0 16.0 x 4.0 it 5 Room area 53.0 W 64.0 0' Ty Constmotion U-value Or HTM Area (ft-) Load Area (ft) Load number I (Btuh1t'-F) (BtuW or perimeter (it) (Btuh) or perimeter (it) (Blob) Heat I Cool Gross NIPIS Heat Cool Gross NIPIS Heat Cool 6 W, 15813-Owc4 0.093 n 4.48 0.24 0 0 0 0 0 0 0 0 I-O 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 V� 12E-Osw 0.068 n 6.17 0.64 40 36 183 23 32 32 165 20 L-G 61A 0.340 n 25.84 10.46 5 0 116 47 0 0 0 0 11 1f/ 12E-0sw 0.068 ne 5.17 0.64 0 0 0 0 0 0 0 0 L-G 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 15B13-0wc4 0.093 a 4.48 0.24 0 0 0 0 0 0 0 O 12E-Osw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 Tj 61A 0.340 a 26.84 32.83 0 0 0 0 0 0 0 0 11 KO 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 as 5.17 0.64 0 0 0 0 0 0 0 0 �G 61A 0.340 as 25.84 29.05 0 0 0 0 0 0 0 0 Y15B13 -0wc4 0.093 s 4.48 0.24 0 0 0 0 0 0 0 0 �C 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 gyp/ 12E-0sw 0.068 s 5.17 0.64 0 0 0 0 0 0 0 0 L-C 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 15B13-Owc-4 0.093 w 4.48 0.24 0 0 0 0 0 0 0 0 81A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 1ql 12E-0sw 0.068 w 5.17 0.64 0 0 0 0 0 0 0 0 FLED 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 11K0 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 1619J8ad 0.026 - 1.98 1.09 53 53 105 58 64 64 126 70 F 21A-32c 0.020 - 1.52 0.00 0 0 0 0 0 0 0 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.42 1.55 0 0 O 0 0 0 0 0 6 c) AED excursion -11 -g Envelope loss/gain 404 117 292 82 12 a) Infiltration 89 9 71 7 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances @ 1200 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 132 34 -30 -89 14 Subtotal 626 160 0 0 15 Dud loads 0% 0% 0 0 01 0% 0 0 Total room load 626 160 0 0 Air required (dm) 13 e 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. we-4ghtsolRt Right -Suite Residentia16.0.02RSR40615 2005Sep-1300:17:13 ��A C:\My Documents\Wnghtsoft HVAMTravis Wade t.np Calc = MJ8 Orientation = W Page 7 Righ- Worksheet Job: 1 Entire House Date: Sep 12, 2005 By: Blair Singleton 1 Room name Family Room Mach 2 Exposed wall 53.0 8 14.0 ft 3 Ceiling height 8.0 It heal/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 502.0 ft 7.0 x 7.0 ft 5 Room area 502.0 W 49.0 ft' Ty Construction LI-value Or HTM Area (1112) Load Area (S) Load number I (BtuhM2--OF) (Bluh/ftD or perimeter (R) (Blob) or perimeter (ft) (Btuh) Heat I Cool Gross I WP/S Heat I Cod Gross N/P/S Heat Cool 6 N/L wc 15813-04 0.093 n 4A8 0.24 0 0 0 0 0 0 0 0 C 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 0.068 n 5.17 0.64 96 71 367 45 0 0 0 0 t12E-0sw -G 61A 0.340 n 25.84 10.46 25 0 646 261 0 0 0 0 11 1p� 12E-0sw 0.068 ne 5.17 0.64 0 0 0 0 0 0 0 0 t-G 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 15813-0wc4 0.093 a 4.48 0.24 0 0 0 0 0 0 0 0 0.068 a 5.17 0.64 216 176 910 112 0 0 0 0 t12E-0sw 1' 61A 0.340 a 25.84 32.83 40 0 1034 1313 0 0 0 0 -D 11KO 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 l9/ 12E-0sw OA68 se 5.17 0.64 0 0 0 0 0 0 0 0 _G 61A 0.340 se 25.54 29.05 0 0 0 0 0 0 0 0 Yy 15813-0wo4 0.093 s 4.48 0.24 0 0 0 0 56 56 323 7 �G 61A 0.340 s 26.84 18.26 0 0 0 0 0 0 0 0 �q/ 12E-0sw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 I_f 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 0.093 w 4.48 0.24 0 0 0 0 56 56 323 7 t15813-0wc-4 _G 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 12E-0sw 0.068 w 5.17 0.64 112 47 243 30 0 0 0 0 61A 0.340 w 25.64 32.83 44 0 1137 1445 0 0 0 0 110 0.360 w 27.36 6.66 21 21 575 140 0 0 0 0 C 16B-38ad 0.026 - 1.98 1.09 502 502 992 548 0 0 0 0 F 21A-32c 0.020 - 1.52 0.00 0 0 0 0 49 14 74 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - 8.42 1.55 0 0 0 0 0 0 0 0 6 c)AED excursion -327 -2 Envelope loss/gain 5902 3568 721 11 12 a) Infiltration 945 93 125 12 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances @ 1200 0 0 0 0 Less external load 0 0 0 0 Lass transfer 0 0 0 0 Redistribution 255 67 -846 -24 14 Subtotal 7102 3958 0 0 15 Duct loads 1 0% 0% 0 0 0% 0% 0 0 Total room load 7102 3958 0 0 Air required (cfm) 142 210 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed wragflt5oft Right -Suite Residential 6.0.02 RSR40615 2005-Sep-1300:17:13 '�-� C:Vdy Documents\Wright"It HVAC\Travis Wade Imp Cale = MJ8 Orientation = W Page 8 Right-s 1Norksheet Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton 1 Room name Family Room 2 hall 2 Exposed wall 84.0 It 6.0 It 3 Ceiling height 8.0 it heat/cool 8.0 It heaUcool 4 Room dimensions 1.0 x 586.0 fl 1.0 x 182.0 It 5 Room area 586.0 fl2 182.0 fl2 Ty Construction U-value Or HTM Area (1`12) Load Area (fl2) Load number I (Btuh/fl?'F) (Btuht" or perimeter (fl) (Blob) or perimeter (fl) (etuh) Heat Cool Gross WKS Heat Cool Gross 14IPIS Heat Cool 6 W 15613-Owc-0 0.093 n 4.48 0.24 112 112 647 14 48 48 277 6 1--G 61A 0.340 n 25.64 10.46 0 0 0 0 0 0 0 0 _ V+l 12E-Osw 0.068 n 5.17 0.64 0 0 0 0 0 0 0 0 Y-C 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 11 12E-Osw 0.068 ne 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 1512113-Owc-4 0.093 a 4.48 0.24 328 328 1895 40 0 0 0 0 W 12E-Osw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 a 25.84 32.83 0 0 0 0 0 0 0 0 11---GD 11K0 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 12E-0sw 0.068 as 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 se 25.84 29.05 0 0 0 0 0 0 0 0 T-G 15B13-0wcA 0.093 s 4.48 0.24 112 96 534 10 0 0 0 0 61A 0.340 s 25.84 18.26 16 0 413 292 0 0 0 0 1q/ 12E-Osw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 L-G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 Vy 158134)wc-4 0.093 w 4.48 0.24 120 120 693 15 0 0 0 0 L-C 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 Vj! 12E-Osw 0.068 w 5.17 0.64 0 0 0 0 0 0 0 0 II---.OG 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 11K0 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.98 1.09 0 0 0 0 0 0 0 0 F 21A-32c 0.020 - 1.62 0.00 586 84 891 0 182 6 277 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-0b5cp 0.295 - 8.42 1.55 0 0 0 0 0 0 0 0 6 c) AED excursion 31 -1 Envelope losstgain 5073 400 554 5 12 a) Infiltration 749 74 53 5 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances ® 1200 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 1752 44 -607 -10 14 Subtotal 7573 748 0 0 15 Duct loads 0% 0% 0 0 0% 0% 0 0 Total room load 7573 748 0 0 Air required (cfm) 152 40 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. wrr ghlatsoft Right -Suite Residential 6.0.02 RSR40615 2005Sep-1300:17:13 ,4CCh C Wy DocumentslWnghtsofl HVAC\Travis Wade t.np Calc = MA Onenlat,on = W Page 9 Righ- Worksheet Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton 1 Room name Bed 5 Kitchen/Dining 2 Exposed wall 38.0 It 17.6 It 3 Ceiling height 8.0 ft heat/aool 8.0 ft heeUcool 4 Room dimensions 13.0 x 14.0 ft 1.0 x 319.0 It 5 Room area 182.0 ft' 319.0 ft' Ty Construction U-value Or HTM Area (112) toad Area (ft-) Load number I (Btuh81? °F) (Btuh/fl-) or perimeter (fl) (Bluh) or perimeter (ft) (Btuh) Heat I Cool Gross NIPS Heat Cool Gross HIPIS Heat Cool 6 Vy 15813-0wc4 0.093 n 4.48 0.24 88 88 508 11 0 0 0 0 �3 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 l� 12E-Osw 0.068 n 5.17 0.64 0 0 0 0 0 0 0 0 I-C 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 11 Tq/ 12E-0sw 0.068 ne 5.17 0.64 0 0 0 0 23 13 67 8 `C 61A 0.340 ne 25.84 22.98 0 0 0 0 10 0 246 220 W 15813-OwcA 0.093 a 4.48 0.24 0 0 0 0 0 0 0 0 V�! 12E-0sw 0.068 a 5.17 0.64 0 0 0 0 80 38 196 24 I-- 61A 0.340 a 25.84 32.83 0 0 0 0 0 0 0 0 I 9 11 KO 0.360 a 27.36 6.66 0 0 0 0 42 42 1149 280 1W 12E-0sw 0.068 as 6.17 0.64 0 0 0 0 23 13 65 a T-f 61A 0.340 se 25.84 29.05 0 0 0 0 10 0 258 291 19/ 15813-Owc-4 0.093 s 4.48 0.24 112 112 647 14 0 0 0 0 L-G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 gyp/ 12E-Osw 0.068 s 5.17 0.64 0 0 0 0 0 0 0 0 LG 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 y/ 15813-Dwc-4 0.093 w 4.48 0.24 104 88 488 9 0 0 0 0 LG 61A 0.340 w 25.84 32.83 16 0 413 525 0 0 0 0 12E-0sw 0.068 w 5.17 0.64 0 0 0 0 16 16 83 10 Ti 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 11KO 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 168-38ad 0.026 - 1.98 1.09 0 0 0 0 319 319 630 348 F 21A-32c 0.020 - 1.52 0.00 182 38 277 0 0 0 0 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 8.42 1.55 0 0 0 0 22 1 185 34 6 c) AED excursion 192 -190 Envelope loss/gain 2333 751 2883 1034 12 a) Infiltration 339 33 315 31 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants 230 1 230 0 0 Appliances 1200 0 0 1 1200 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 822 21 1483 202 14 Subtotal 3493 1035 4681 2467 15 Duct loads 0% 0% 0 0 0% 0% 0 0 Total room load 1 3493 1035 4681 2467 Air required (rim)1 70 55 94 131 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. .Ya(A, we-�gf CS<>flt Right -Suite Residentia16.0.02 RSR40615 2005-Sep-13 00:17:13 C:\My Documents\Wdghtsoft HVAC\Travis Wade Imp Cato = MJ8 Odema8on = W Page 10 Right a-Worksheet Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton i Room name WIC Mas. Bath 2 Exposed wall 14.0 it 23.0 ft 3 Ceiling height 8.0 0 heal/cool 8.0 ft heat/cool 4 Room dimensions 8.0 x 6.0 ft &0 x 15.0 ft 5 Room area 48.0 ft2 120.0 ft2 Ty Construction UJ Iue Or HTM Area (112) Load Area (ft) Load number (Bluh/ft?'F) (BtuMF) or perimeter (ft) (Bluh) or perimeter (fl) (Bluh) Heat I Cool Gmss WP/S Heat Cool Grass l41P/S Heat Cool 6 W 15B13-0wcA 0.093 n 4.48 0.24 0 0 0 0 0 0 0 0 I-O 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 yl 12E-0sw 0.068 n 5.17 0.64 0 0 0 0 0 0 0 0 Y-C 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 11 l9/ 12E-Ow 0.D68 ne 5.17 0.64 0 0 0 0 0 0 D 0 LC 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 15613-0wc-4 0.093 a 4.48 0.24 0 0 0 0 0 0 0 0 y! 12E-O w 0.068 a 5.17 0.64 0 0 0 0 64 48 248 31 IL-.-GD 61A 0.340 a 25.84 32.83 0 0 0 0 16 0 413 525 11 KO 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 W/ 12E-0sw O.8 D6 se 5.17 0.64 0 0 0 0 0 0 0 0 �-G 61A 0.340 se 25.84 29.05 0 0 0 0 0 0 0 0 W/ 15B113-0wc-4 0.093 s 4.48 0.24 0 0 0 0 0 0 0 0 L-G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 gyp/L-- 12E-0ew 0.068 a 5.17 0.64 48 48 248 31 120 120 620 77 G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 Yy 15B13-0wc-4 0.093 w 4.48 0.24 0 0 0 0 0 0 0 0 �C 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 V)! 12E-0sw 0.068 w 5.17 0.64 64 64 331 41 0 0 0 0 IL-GD 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 11K0 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 166-38ad 0.026 - 1.98 1.09 48 48 95 52 120 120 237 131 F 21A-32c 0.020 - 1.52 0.00 0 0 0 0 0 0 0 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.42 1.55 0 0 0 0 0 0 0 0 6 c) AED excursion -12 4 Envelope loss/gain 674 112 1519 768 12 a) Infiltration 250 25 410 40 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances @ 1200 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -923 -137 528 78 14 Subtotal 0 0 2456 886 1151 Dud loads 0% 0% 0 0 0% 0% 0 0 Total room load 0 0 2449 847 Air required (cfm) 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. AC�A wa7gh1M0Tt Right Suite Residential 6.0.02 RSR40615 2005-Sep-1300:17:13 C9My Documents\Wrightsofl HVAC1Travis Wade 1.rrp Calc = MJ8 Odentation = W Page 11 Job: 1 J f' "�I " Right,a, Worksheet Entire House Date: Sep 12, 2005 By: Blair Singleton 1 Room name Bed 2 Stairs 2 2 Exposed wall 40.0 It 17.0 It 3 Ceiling height 8.0 ft heaVcool 8.0 It heallcool 4 Room dimensions 13.0 x 16.0 It 4.0 x 13.0 It 5 Room area 208.0 ft2 52.0 fF Ty Construction U-value Or HTM Area (ft) Load Area (III Load number I (Btuhtft2--°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP/S Heal Cool Gross WP/S Heat Cad 6 N/ 15B13-Om-4 0.093 n 4.48 0.24 0 0 0 0 0 0 0 0 �13 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 _ Uy 12E-0sw 0.068 n 5.17 0.64 88 88 455 56 0 0 0 0 --G 61A 0.340 n 25.84 10.46 0 0 0 0 0 0 0 0 11 12E-0sw 0.068 no 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 ne 25.84 22.98 0 0 0 0 0 0 0 0 W 15BI3-Owc-4 0.093 a 4.48 0.24 0 0 0 0 0 0 0 0 Vy 12E4)sw 0.068 a 5.17 0.64 0 0 0 0 0 0 0 0 61A 0.340 a 25.84 32.83 0 0 0 0 0 0 0 0 111(0 0.360 a 27.36 6.66 0 0 0 0 0 0 0 0 l4/ 12E-Osw 0.068 se 5.17 0.64 0 0 0 0 0 0 0 0 -G 61A 0.340 se 25.84 29.05 0 0 0 0 0 0 0 0 W/ 15813-0wc4 0.093 s 4.48 0.24 0 0 0 0 0 0 0 0 t-C 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 1Q/ 12E-0sw 0.068 s 6.17 0.64 128 128 662 82 104 104 537 66 I---G 61A 0.340 s 25.84 18.26 0 0 0 0 0 0 0 0 1y 15813-Owc-4 0.093 w 4.48 0.24 0 0 0 0 0 0 0 0 �C 61A 0.340 w 25.84 32.83 0 0 0 0 0 0 0 0 12E-0sw 0.068 w 5.17 0.64 104 88 452 56 32 32 165 20 61A 0.340 w 25.84 32.83 17 0 426 542 0 0 0 0 11KO 0.360 w 27.36 6.66 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.98 1.09 208 208 411 227 20 20 40 22 F 21A-32c 0.020 - 1.52 0.00 0 0 0 0 0 0 0 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.42 1.55 0 0 0 0 52 17 438 81 6 c) AED excursion 165 -18 Envelope loss/gain 2406 1127 1180 172 12 a) Infiltration 713 70 303 30 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances @ 1200 0 0 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -1483 -202 14 Subtotal 3119 1428 0 0 15 Duct loads ow. 0 0 0% 0', 0 0 Toroom load 3119 1428 0 0 Air required(ofm) 63 76 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. I..: kwr7ghC50ft Right -Suite ResidenBal B.0.02RSR40615 20D5.Sep-1300:17:13 C:\My Documents\Wrightsoft HVAC\Travis Wade t.np Cale = MJB Onentaton = W Pape 12 Right-sJVorksheet Entire House Job: 1 Date: Sep 12, 2005 By: Blair Singleton 1 Room name closet 2 Exposed wall 0.0 ft 3 Ceiling height 8.0 ft heavcool 4 Room dimensions 4.0 x 3.0 ft 5 Room area 12.0 ft Ty Construction U-value Or HTM Area (ft.) Load Area Load number I (Blutuli °F) (Btutdft-) or perimeter (ft) (Blob) or perimeter Heat Cool Gross WP/S Heat Cool Grass WP/S Heat Cool 6 W i5B13-0wc-4 0.093 n 4.48 0.24 0 0 0 0 �C y/ 61A 12E-Osw 0.340 0.068 n n 26.84 5.17 10.46 0.64 0 0 0 0 0 0 0 0 I-G 61A 0.340 n 25.84 10.46 0 0 0 0 11 lQ/ 12E-Osw 0.068 ne 5.17 0.64 0 0 0 0 �--!' 61A 0.340 ne 25.84 22.98 0 0 0 0 W 15B13-0wc-4 0.093 a 4.48 0.24 0 0 0 0 0.068 a 5.17 0.64 0 0 0 0 t12E-Osw 1Da 61A 0.340 a 25.84 32.83 0 0 0 0 11K0 0.360 a 27.36 6.66 0 0 0 0 Iq/ 12E-Osw 0.068 se 5.17 0.64 0 0 0 0 t--G 61A 0.340 se 25.84 29.05 0 0 0 0 W 15813-Owe< 0.093 s 4.48 0.24 0 0 0 0 �--G 61A 0.340 s 25.84 18.26 0 0 0 0 �qI 12E-0sw 0.068 a 5.17 0.64 0 0 0 0 L-G 61A 0.340 s 25.84 18.26 0 0 0 0 W, 15B13-Owc-4 0.093 w 4.48 0.24 0 0 0 0 --C 61A 0.340 w 25.84 32.63 0 0 0 0 12E-0sw 0.068 w 5.17 0.64 0 0 0 0 61A 0.340 w 25.84 32,83 0 0 0 0 11K0 0.360 w 27.36 6.66 0 0 0 0 C 16B-38ad 0.026 - 1.98 1.09 12 12 24 13 F 21A-32c 0.020 - 1.52 0.00 0 0 0 0 F 20P-19c 0.050 - 3.80 0.10 0 0 0 0 F 19A-Obscp 0.295 - 8.42 1.55 0 0 0 0 6 c) AED excursion .1 Envelope loss/gain 24 12 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances @ 1200 0 0 Less external load 0 0 Less transfer 0 0 Redistribution -yq -1 14 Subtotal 0 0 15 Duct loads 0% 0% 0 0 Total room load 0 0 Air required (cfm) 0 0 Printout certified by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft Right -Suite Residential 6.0.02 RSR40615 2005-Sep-13 00:17:13 .9C�A C:\My Documents\Wrighlsoft HVAC\Travis Wade Imp Cato = MA Orientation = W Page 13 Main Floor Job #: 1 Performed by Blair Singleton for: Travis Wade Rexburg, Idaho 83440 Scale: 1 : 116 Page 1 Right -Suite Residential 6.0.02 RSR40615 2005-Sep-13 00:17:48 C Wy Documents\Wrightsoft F Basement Job #: 1 Performed by Blair Singleton for: Travis Wade Rexburg, Idaho 83440 Scale: 1 : 116 Page 2 Right -Suite Residential 6.0.02 RSR40615 2005-Sep-13 00:17:48 DocumentslWrightsofl HVAC\... Bonus u .I,.. L, I I6er��s I i Job #: 1 Scale: 1 : 116 Performed by Blair Singleton for: Page 3 Travis Wade Right -Suite Residential 6.0.02 RSR40615 2005-Sep-13 00:17:49 Rexburg, Idaho 83440 C:\My Documents\Wrightsoft HVAC\... Duct System Summary Entire House Project Information For: Travis Wade Rexburg, Idaho 83440 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.10 in H2O 0.00 in H2O 0.10 in H2O 0.04 / 0.06 in H2O 0.012 in/100ft 1051 cfm KEflmii Job: 1 Date: Sep 12, 2005 By: Blair Singleton Cooling 0.10 in H2O 0.00 in H2O 0.10 in H2O 0.04 / 0.06 in H2O 0.012 in/100ft 1051 cfm Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) Rect Size (in) Duct Mal Actual Ln (ft) F1g.Egv Ln (ft) Trunk Bed 1 c 1400 61 74 0.012 6 Ox 0 VIFx 78.0 250.0 st4 Bonus -A h 4801 96 65 0.013 6 Ox 0 VIFx 10.0 295.0 st6 Bonus h 4801 96 65 0.012 6 Ox 0 VIFx 19.0 295.0 st5 Bed 3 h 2711 54 22 0.013 6 Ox 0 VIFx 80.0 220.0 st4 bath h 248 5 0 0.012 6 Ox 0 VIFx 52.0 265.0 st4 Bed 4 h 3371 68 55 0.013 6 Ox 0 VIFx 80.0 230.0 st4 Mas Bed c 2417 60 128 0.015 6 Ox 0 VIFx 26.0 225.0 St4 utility c 1376 29 73 0.017 6 Ox 0 VIFx 10.0 225.0 st4 Bath 1 h 626 13 8 0.012 6 Ox 0 VIFx 59.0 255.0 st4 Family Room c 1979 71 105 0.012 6 Ox 0 VIFx 61.0 265.0 st4 Family Rao. -A c 1979 71 105 0.012 6 Ox 0 VIFx 77.0 240.0 St4 Family Room 2 h 3787 76 20 0.015 6 Ox 0 VIFx 21.0 240.0 st2 Family Room 2-A h 3787 76 20 0.015 6 Ox 0 VIFx 29.0 225.0 st4 Bed 5 h 3493 70 55 0.015 6 Ox 0 VIFx 50.0 210.0 st4 KitcherVDining c 1233 47 66 0.016 6 Ox 0 VIFx 27.0 215.0 st4 Kdchen/Dining-A c 1233 47 66 0.017 6 Ox 0 VIFx 26.0 200.0 St4 Mas. Bath h 2456 49 47 0.021 6 Ox O VIFx 15.0 170.0 St2 Bad 2 c 1428 63 76 0.016 6 Ox 0 VIFx 52.0 190.0 st4 wnghtsoft RightSuite RftWerroa16.0.02 RSR40615 2005Seµ1300:17:30 )CGA C:1My DocumentsMrightsoft HVACITravis Wade i." Calc = MJ8 Orientation = W Page 1 Supply Trunk Detail Table Trunk Htg Cig Design Veloc Diam Rect Duct Duct Name Type (cfm) (cfm) FIR (fpm) (in) Size (in) Material Trunk st5 Peak AVF 96 65 0.012 866 6 8 x 2 ShtMetl st3 st6 Peak AVF 96 65 0.013 866 6 8 x 2 ShtMetl st3 st2 Peak AVF 125 67 0.015 1127 6 8 x 2 ShtMetl st3 Peak AVF 193 130 0.012 866 7 8 x 4 ShtMetl st4 Peak AVF 733 854 0.012 769 14 8 x 20 ShtMetl Return Branch Detail Table Name Grill Size (in) Htg (cfm) Cig (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (n) RectSize (in) Stud/Joist Opening (m) Duct Matl Trunk rb2 Ox0 193 130 288.0 0.021 552 8 0x 0 ShMt rt1 rb5 Ox0 144 75 401.0 0.015 454 6 14x3.25 10x5 SJSp rt2 rb1 Ox0 167 268 349.0 0.018 425 8 2-143.25 2-10x9 SJSp rt2 rb4 Ox0 140 196 177.0 0.035 310 8 2-14x3.25 2-10x9 SJSp r12 rb3 Ox0 202 284 517.0 0.012 450 8 2-14x3.25 2-10x9 SJSp rt2 rb8 0x 0 59 23 461.0 0.013 188 6 14x3.25 10x5 SJSp rt2 rb7 Ox0 76 20 513.0 0.012 240 6 14x3.25 1Ox5 SJSp rt2 rb6 Ox0 70 55 256.0 0.024 222 6 14x3.25 1Ox5 SJSp rt2 Return Trunk Detail Table Trunk Htg Cig Design Veloc Diam Rect Duct Duct Name Type (cfm) (cfm) FIR (fpm) (in) S,izf(i Material Trunk rt1 Peak AVF 193 130 0.021 552 8 0 ShtMetl rt2 Peak AVF 858 921 0.012 553 18 8 30 ShtMetl wrrghtsoft RightSuite Residential6.0.02RSR40615 20055ep 1300:17:30 ACC4 C9My CocumentsSWnghtsoft HVAC\Travis Wade 1.rrp Cak = MJ8 Orientation = W Page 2