HomeMy WebLinkAboutREVIEW RESPONSES - 05-00380 - Rexburg Surgical CenterRexburg Surgery Center
Review Response
PLANNING STAFF REVIEW
Exterior modifications will be made to comply with design standards as per
discussion with Kurt Hibbert.
BUILDING DEPARTMENT REVIEW
Accessibility Review: * One handicap parking space has been
added. Storage and lockers will be accessible
as per IBC section 1109.8.
Exiting Review: * Door 55 has been modified to comply.
* The laundry room exterior door is not an exit.
The existing plan exceeds the IBC exiting
requirements. See attached drawing.
Structural Review: * See attached structural calculations. All
other items acknowledged.
Miscellaneous: * Weep holes & flashing will be provided.
* Flood Elevation Certification will be provided.
* See attached mechanical engineers
response.
* Operating room will be shielded for C-Arm
use. Shielding requirements will be provided.
Building Code Fire Compliance Review:
* Sheet A1.5 shows the locations of required
draft stops. The 1 hour smoke barrier is also a
draft stop.
* Manufactures information will be provided
during submittal process.
* Penetrations through type V-A construction
walls are not required to be protected unless
required by location to property line.
FIRE DEPARTMENT REVIEW
Additional Comments: * Medical gas room will meet section 3006.
Automatic Fire Extinguishing Systems:
* GEM State was the low bidder. A letter on
intent shall be provided after contracts are
signed.
Alarm Systems: * A letter will be provided.
Other Comments: * The two HVAC units that exceed 2000 CFM
have duct detectors on them.
* Lock box will be provided.
OCT-28-2005 12:06PM FROM -ENGINEERED SYSTEMS
208-233-0529 T-353 P.001/001 F-933
M
October 28, 2005
Mr. Johnny Watson
JRW & Associates
1152 Bond Avenue
Rexburg, Idaho 83440
Re: kexburg Surgical Center.
Dear Johnny,
16�
Engineered S7 stemmsAssocialesq Inc.
MECHANICAL -ELECTRICAL - ENGINEERING
315 W. CENTER, POCATELLO, IDAHO 83204
TELEPHONE - 208-233-0501
FAX - 208-233-0529
D. SUDWEEKS, P.E.
R. RICE, P. E.
In response to the City of Rexburg review comments concerning the required plumbing fixtures
on the subject job I offer the following:
1. This is a private facility - therefore separate finale/female toilet rooms are not required
as per 2902.2 exception 1.
2. The IBC square footage building occupancy load is 106 persons (however, there will
never be that many people in the building at one time). Assuming 53 male and 53
female - Table 2902.1 would require one toilet/25 employees and one toilet/75
visitors, We have 6 toilets which meets these requirements.
Feel free to call if you have further questions.
Sincerely,
IENGFgFFRED SYSTEMS ASSOCIATES, INC.
(79ie4ian�'
Dwayne dweeks
kl
1 �
•
MEMBER ACEC
CITY 0P
1
REXBURG
Ow
Amed.1 r. 11y Community
June 21, 2006
Review Action
Permit Number: 05 00380
Project Name: Surgical Center (Bldg.)
Project Type: Commercial New
RO Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item
Actions Required for Approval
Approved
that is less safe than the space that you are
already in. Please make the necessary
changes.
Structural Review
Provide seismic calculations. Include detailed
10/31/2005
design of canopy for seismic with snow loads.
Make sure to use Use Group IV. The sturctural
calculations are missing pages 17 thru 33 (all of
the lateral and foundation design). Industrial
washers and dryers require special connection,
please provide. Structural observations are
required as per IBC Section 1709. Provide
special inspections for bolting and any field
welding. Fasteners iused in treated woods
must be stainless steel or hot dipped.
Building Code Fire Compliance Review The IBC Analysis on the front page of the
10/31/2005
building plans identifies that draft stops are
identified on page A1.6. The smoke barrier is
the only draft stop identified. Draft stops are
required every 3000 sq. ft. Provide
manufacture's literature to identify Class B
Rating for the asphalt shingles. Provide details
for penetrations through rated exterior walls and
ceiling. (dryer duct as one example).
Waste Water Application
\
Miscellaneous
Provide weepholes and flashing at bottom of
masonry. Provide flood elevation certification.
The number of toilet and sink fixtures does not
` )
meet the requirements of Section 2902 of the
IBC. Also, seperate sex facilities are required.
Please identify on plans. Will there be an x-ray
area? If so, please provide the shielding plans
and the manufacturer's literature for the
equipment.
Waste Water Grease Trap Form
CITY OF
REXBURG
CW
America's Family Community
June 21, 2006
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Review Action Fax (208) 359-3022
Permit Number: 05 00380
Project Name: Surgical Center (Bldg.)
Project Type: Commercial New
Review Item Actions Required for Approval Approved
Additional Comments Medical gas room is required to have special
enclosure in sprinklered building.See section
3006 of The International Fire Code 2003
addition.
Required Fire Flow Building is required to have a minimum fire flow
of 1.500 gpm for 2 hour with full fire suppression
system.
Water Supply Established
Fire Access Roads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Standpipes
Commercial Cooking
Alarm Systems
Other Comments
See site plan review.
Install all extinguishers as shown on plans.
Extinguishers are requied to be a Minimum of
2A10BC.
Letter of intent is required from a licensed
sprinkler contractor. Pains must be approved
by the state Fire Marshall and a approved set of
plans provided to the fire inspector before any
part of the fire suppression system is installed.
N/A
N/A
Please have any alarm contractor submit a
letter of intent. Contractor needs to submit a set
of alarm plans for approval before installing
system.
Special requirements for duct detectors
installation in HVAC units over 2000 CFM. Duct
detectors can be deleted if all portions of the
building are covered by smoke detectors and
are connected to the fire alarm system.
Lock box required for this occupancy. Forms
available at the fire station.
10/25/2005
10/25/2005
10/25/2005
10/25/2005
10/25/2005
10/25/2005
10/25/2005
10/25/2005
10/25/2005
10/25/2005
CITY OF
REXBURG
cr.
AmMmk Family Cornmuni y
June 21, 2006
Review Action
Permit Number: 05 00380
Project Name: Surgical Center (Bldg.)
Project Type: Commercial New
me
RO Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
Building Department Review r
Energy Conservation Compliance Review An energy review has been submitted. 10/21/2005
Complies with approved Site Plan Review Site plan has been reviewed.
Height and Area Review Meets code requirements
Mechanical Review Roof HVAC units must be connected as per
Section 1621 of the IBC.
Building Type Compliance Building is Type VA.
Water and Sewer Service
Plumbing Sewer Drain Review
Plumbing Storm Drain Review
Plumbing Potable Water Review
Accessibility Review
Interior Environment
Exiting Review
All plumbing services are required to be tested
and inspected before covering.
All Drains are to be installed according to Plans
provided. All drains are to be installed according
to the Uniform Plumbing Code.
All storm drains are to be installed according to
Chapter 11 of the Uniform Plumbing Code. All
storm drains are required to be tested and
inspected beofre covering.
10/2112005
10/21 /2005
10/21 /2005
10/21 /2005
10/25/2005
10/25/2005
10/25/2005
All water lines are required to be installed 10/25/2005
according to the Uniform Plumbing Code. All
water lines are required to be tested and
inspected before covering.
/10% of hospital out patient parking is required to 10/31/2005
be designed as handicapped. 5 handicapped
spaces are required. Storage and lockers must
be accessible as per IBC Section 1109.8.
10/31/2005
The configuration of the doors at the patient exit 10/31/2005
do not meet the requirements of Section
\� 1008.1.7 of the 2003 International Building Code
(IBC). The exiting for the portion of the building
on the South side of the smoke partion can not
exit through the laundry room. Two exits are
required from the hall. The code does not allow
you to enter a space that is part of your exiting