HomeMy WebLinkAboutREVIEW RESPONSES - 05-00380 - Rexburg Surgical CenterRexburg Surgery Center Review Response PLANNING STAFF REVIEW Exterior modifications will be made to comply with design standards as per discussion with Kurt Hibbert. BUILDING DEPARTMENT REVIEW Accessibility Review: * One handicap parking space has been added. Storage and lockers will be accessible as per IBC section 1109.8. Exiting Review: * Door 55 has been modified to comply. * The laundry room exterior door is not an exit. The existing plan exceeds the IBC exiting requirements. See attached drawing. Structural Review: * See attached structural calculations. All other items acknowledged. Miscellaneous: * Weep holes & flashing will be provided. * Flood Elevation Certification will be provided. * See attached mechanical engineers response. * Operating room will be shielded for C-Arm use. Shielding requirements will be provided. Building Code Fire Compliance Review: * Sheet A1.5 shows the locations of required draft stops. The 1 hour smoke barrier is also a draft stop. * Manufactures information will be provided during submittal process. * Penetrations through type V-A construction walls are not required to be protected unless required by location to property line. FIRE DEPARTMENT REVIEW Additional Comments: * Medical gas room will meet section 3006. Automatic Fire Extinguishing Systems: * GEM State was the low bidder. A letter on intent shall be provided after contracts are signed. Alarm Systems: * A letter will be provided. Other Comments: * The two HVAC units that exceed 2000 CFM have duct detectors on them. * Lock box will be provided. OCT-28-2005 12:06PM FROM -ENGINEERED SYSTEMS 208-233-0529 T-353 P.001/001 F-933 M October 28, 2005 Mr. Johnny Watson JRW & Associates 1152 Bond Avenue Rexburg, Idaho 83440 Re: kexburg Surgical Center. Dear Johnny, 16� Engineered S7 stemmsAssocialesq Inc. MECHANICAL -ELECTRICAL - ENGINEERING 315 W. CENTER, POCATELLO, IDAHO 83204 TELEPHONE - 208-233-0501 FAX - 208-233-0529 D. SUDWEEKS, P.E. R. RICE, P. E. In response to the City of Rexburg review comments concerning the required plumbing fixtures on the subject job I offer the following: 1. This is a private facility - therefore separate finale/female toilet rooms are not required as per 2902.2 exception 1. 2. The IBC square footage building occupancy load is 106 persons (however, there will never be that many people in the building at one time). Assuming 53 male and 53 female - Table 2902.1 would require one toilet/25 employees and one toilet/75 visitors, We have 6 toilets which meets these requirements. Feel free to call if you have further questions. Sincerely, IENGFgFFRED SYSTEMS ASSOCIATES, INC. (79ie4ian�' Dwayne dweeks kl 1 � • MEMBER ACEC CITY 0P 1 REXBURG Ow Amed.1 r. 11y Community June 21, 2006 Review Action Permit Number: 05 00380 Project Name: Surgical Center (Bldg.) Project Type: Commercial New RO Box 280 19 E Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 Review Item Actions Required for Approval Approved that is less safe than the space that you are already in. Please make the necessary changes. Structural Review Provide seismic calculations. Include detailed 10/31/2005 design of canopy for seismic with snow loads. Make sure to use Use Group IV. The sturctural calculations are missing pages 17 thru 33 (all of the lateral and foundation design). Industrial washers and dryers require special connection, please provide. Structural observations are required as per IBC Section 1709. Provide special inspections for bolting and any field welding. Fasteners iused in treated woods must be stainless steel or hot dipped. Building Code Fire Compliance Review The IBC Analysis on the front page of the 10/31/2005 building plans identifies that draft stops are identified on page A1.6. The smoke barrier is the only draft stop identified. Draft stops are required every 3000 sq. ft. Provide manufacture's literature to identify Class B Rating for the asphalt shingles. Provide details for penetrations through rated exterior walls and ceiling. (dryer duct as one example). Waste Water Application \ Miscellaneous Provide weepholes and flashing at bottom of masonry. Provide flood elevation certification. The number of toilet and sink fixtures does not ` ) meet the requirements of Section 2902 of the IBC. Also, seperate sex facilities are required. Please identify on plans. Will there be an x-ray area? If so, please provide the shielding plans and the manufacturer's literature for the equipment. Waste Water Grease Trap Form CITY OF REXBURG CW America's Family Community June 21, 2006 P.O Box 280 19 E Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Review Action Fax (208) 359-3022 Permit Number: 05 00380 Project Name: Surgical Center (Bldg.) Project Type: Commercial New Review Item Actions Required for Approval Approved Additional Comments Medical gas room is required to have special enclosure in sprinklered building.See section 3006 of The International Fire Code 2003 addition. Required Fire Flow Building is required to have a minimum fire flow of 1.500 gpm for 2 hour with full fire suppression system. Water Supply Established Fire Access Roads Fire Extinguishers Automatic Fire Extinguishing Systems Standpipes Commercial Cooking Alarm Systems Other Comments See site plan review. Install all extinguishers as shown on plans. Extinguishers are requied to be a Minimum of 2A10BC. Letter of intent is required from a licensed sprinkler contractor. Pains must be approved by the state Fire Marshall and a approved set of plans provided to the fire inspector before any part of the fire suppression system is installed. N/A N/A Please have any alarm contractor submit a letter of intent. Contractor needs to submit a set of alarm plans for approval before installing system. Special requirements for duct detectors installation in HVAC units over 2000 CFM. Duct detectors can be deleted if all portions of the building are covered by smoke detectors and are connected to the fire alarm system. Lock box required for this occupancy. Forms available at the fire station. 10/25/2005 10/25/2005 10/25/2005 10/25/2005 10/25/2005 10/25/2005 10/25/2005 10/25/2005 10/25/2005 10/25/2005 CITY OF REXBURG cr. AmMmk Family Cornmuni y June 21, 2006 Review Action Permit Number: 05 00380 Project Name: Surgical Center (Bldg.) Project Type: Commercial New me RO Box 280 19 E Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 Review Item Actions Required for Approval Approved Building Department Review r Energy Conservation Compliance Review An energy review has been submitted. 10/21/2005 Complies with approved Site Plan Review Site plan has been reviewed. Height and Area Review Meets code requirements Mechanical Review Roof HVAC units must be connected as per Section 1621 of the IBC. Building Type Compliance Building is Type VA. Water and Sewer Service Plumbing Sewer Drain Review Plumbing Storm Drain Review Plumbing Potable Water Review Accessibility Review Interior Environment Exiting Review All plumbing services are required to be tested and inspected before covering. All Drains are to be installed according to Plans provided. All drains are to be installed according to the Uniform Plumbing Code. All storm drains are to be installed according to Chapter 11 of the Uniform Plumbing Code. All storm drains are required to be tested and inspected beofre covering. 10/2112005 10/21 /2005 10/21 /2005 10/21 /2005 10/25/2005 10/25/2005 10/25/2005 All water lines are required to be installed 10/25/2005 according to the Uniform Plumbing Code. All water lines are required to be tested and inspected before covering. /10% of hospital out patient parking is required to 10/31/2005 be designed as handicapped. 5 handicapped spaces are required. Storage and lockers must be accessible as per IBC Section 1109.8. 10/31/2005 The configuration of the doors at the patient exit 10/31/2005 do not meet the requirements of Section \� 1008.1.7 of the 2003 International Building Code (IBC). The exiting for the portion of the building on the South side of the smoke partion can not exit through the laundry room. Two exits are required from the hall. The code does not allow you to enter a space that is part of your exiting