Loading...
HomeMy WebLinkAboutFIRE REVIEW - Larsen, Kelton - Brighton Townhomes - 242 W 6th S - Site PlaniP.O. Box 280 ll m/ J?V x l (l li y 12 North Center Street 0 // Rexburg, Idaho 83440 STATE OF IDAHO Phone (208) 359.3020 Fax (208) 359-3022 e-mall rexburg@srv.net TO: TO WHOM IT MAY CONCERN FROM: CHRIS HUSKINSON, FIRE INSPECTOR DATE: APRIL 14, 2003 RE: BRIGHTON TOWNHOUSES TO WHOM IT MAY CONCERN: Upon review of the site plan drawings submitted the following items need to be addressed: 1. Drawing is inaccurate, property due east of proposed project belongs to Shelbourne Apartments LLC, not Grandview Townhouse Subdivision. 2. WATER SUPPLY: This proposed project shows two hydrants of which only one appears to be accessible. The east hydrant is located on the adjacent property that is currently marginally acceptable for the existing facility. 3. ACCESS: The north parking lot is approximately 458 feet long without provisions for a fire apparatus turn -around. Code states anything in excess of 150 feet shall have means to turn apparatus around. 4. The areas adjacent to the buildings and along the north side without any parking spaces shall be marked with "No Parking, Fire Lane" in addition to having the curbs painted red and maintained. 5. FIRE SUPPRESSION SYSTEM: Plans indicate buildings to be in excess of 5,000 square feet which requires a complete fire sprinkler system according to Rexburg City Ordinance. Additional plans are required to complete an accurate plan review of this project. If there are any questions please feel free to contact me. Chris Huskinson Fire Inspector 359-3010