HomeMy WebLinkAboutFIRE REVIEW - Reed, Glen - 450 S 4th W - Rezone from HBD to HDRREXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 11/00
Plan Review Review Date: 5-9-01
Building Name: Glen Reed Apartments
Building Address: 450 South Fourth West
Stories: 2 Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: 10,360 square feet
1).Required Fire Flow (Appendix III -A): 2,750 GPM
Comments: With fully sprinklered building the fire flow drops to
1500 GPM
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: 4th South/4th West
Fire Hydrant Flows: Existing OR
Fire Flow Test Location: 4th South/4th West
Fire Flow Supplied By: RMCFD
Other Approved Water Source:
Water Supply Acceptable: NO
Water Supply Comments: Need to add one hydrant on site
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: YES
Complete Road Acceptable: YES
1 ,f
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments:
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: Not shown
Comments: Provide 2A-10BC fire extinguishers and locations
9).Fire Alarm Systems (Article 10 Section 1007)Required: Smoke
detector system required
Fire Alarm System Acceptable: NO
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: NO
Plans Checked By: Chris Huskinson
Date: 05-09-01
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES
Please provide site plan for installation of new hydrant on
site, locations for fire extinguishers, and smoke detector system
installation.