HomeMy WebLinkAboutFIRE REVIEW - Palmer, Gene - Hidden Valley SubdivisionMemo
To: To Whom It May Concern
From: Chris Huskinson
Date: 05-27-01
Re: Plan Review for Hidden Valley Subdivision, Phase 3
Upon review of the drawing for the above mentioned project, the following items need
to be addressed:
1. Fire Hydrants: Fire Hydrants shall be provided so that they provide a minimum of 1,000
GPM with spacing to be a minimum of 500 feet between hydrants. (1997 UFC, Appendix III -
B)
A. Hydrants shall be clearly identified to prevent obstruction by parking and other
obstructions. (1997 UFC, Section 901.4.2)
2. Access: Fire department access (including installation of water hydrants) shall be installed
and made serviceable prior to and during the time of construction. (1997 UFC, Section
901.3)
These items need to be addressed prior to construction. If there are any questions please
contact me at the fire department.
Chris Huskinson, Fire Inspector
0 Page 1