HomeMy WebLinkAboutSHORT FORM - 05-00151 - Parkside Townhomes - Bldg 12,�1 Short Form Entire House Job: UNIT "Be Date: May 117 2005 BY: G M Robertson For. Parkside Apartments Rexburg Rexburg, I D Htg Cfg Outside db ("F) -fi 89 inside db (°F) 70 75 Design TD (°F) 76 14 Daily range _ M Inside humidify {%} - 50 Moisture difference (gr/lb) - -31 HEATING EQUIPMENT Make PAYNE HEATING Trade Payne Model PG8HAA036050* Efficiency 80 AFUE Heating input 50000 Heating output 40p00 Temperature rise 59 Actual air flow 733 Air flow factor a.027 Stafic pressure 0.50 Space thermostat ROOM NAME Btu h Btu h OF cfrn Gfm IBtu h in H2Q Htg load (Blah) Infiltration Method Construction quality Fireplaces SIMI31ified Average 4 COOLING EQUIPMENT Make Payne Trade Payne PA10 Cond PA10JA024-C Coil CK5A/CK5l3A024+TDR Efficiency 10 SEER Sensible cooling 154D0 Btuh Latent cooling 66 00 Btu h Total cooling Actual air flow Air flaw factar Stafic pressure Load sensible heat ratio CIg load (Btu h�) BATH 108 1643 1361 BEDROOM 2 130 2947 896 M CL 2T 0 D MASTER BEDROOM 187 5227 2592 U HALL 43 0 0 BEDROOM 3 117 1739 'i59 U STRS 40 0 0 DINING KITCHEN 165 7033 1537 UTIL 135 0 0 360 � PWDR STRS 28 0 0 36 0 0 LIVING RM 222 8302 3581 22 000 Btu h 733 cfm 0.068 cfmlBtuh 0.50 in H20 1.00 Htg AVF Clg AVF (Cfm) (cfrn) Printout certified by ACOA to meet all requirements of Man ual J 8th Ed. vv1-1 =Suite Res idenh al 6.0-08 RS R 41031 ACCK -mace nI s and Sett ingMG uy Robertwnft D cpajm n RKi DE UN IT B _rrp C ais - rientation 45 93 80 61 0 0 142 177 0 0 47 52 0 p 192 105 0 p 0 p 0 p 0 p 226 245 2006 -May -12 0:345 Page 1 Entire House Other equip loads Equip. @ 0.94 RSM Latent cooling TOTALS 26,891 1425 10726 262 10329 10329 Printout certified b y ACGA to meet all requirements of Man ual J 8#h Ed. N rI0htSC&t Rigft-SUReResidenfial6-O.O8RSR41031 ACACK C-00cuments and SelfingsGuy RobeftsonNy DocumentsVARKSIDE fT 13 733 733 733 733 2005-Mby - 12 06:34:35 Building Analysis Entire House Job: UNMU Date: May 11 , 2005 Robertson For-. Parkside Apartments Rexburg Rexburg, I d Location: Idaho FII, Elevation: Lattude- Outdoor: ID7 US 4741 ft O Dry bulb (OF) Daily range ('17) Wet bulb (°F) Wind speed (mph) Indoor. Heating Indoor temperature (°F) 70 Design TD (°F) 76 Relative humidity 50 H eat`tng Cooling$Mv�stu�e difference �rl�b} 61.5� 34� H � .1 of i tration: Simplified 60 Construction quality Average 'lS.D 7.5 Fireplaces D Cooling 75 14 50 -31.5 Component Btuhlff Btu %of load Walls 6.5 8234 29.1 Glazing 40.5 442 15.5 Doors 29.6 1245 4.4 Ceilings 2.3 158 5.2 Floors 1.3 834 2.9 Infiltration 3.8 5344 18.9 Ducts 5374 19.0 Piping 0 Q.0 Humidification p 0.0. Ventilation 1425 5.0 Adjustments -0 100.0 Total 28316 140.0 �aborr Component Btu h/ff Btu h % of load Walls 1.1 1 1372 12.5 Glazing 34.0 36971 33,61 Doors 7.2 303 2.8 Ceilings 1.4 934 8.5 Floors, 0.2 154 1.4 I nfiItration 0.4 5+D3 4_6 Ducts 3762 34.2 Ventilation 262 2.4 Intemal gains p 0.0 Blower Q 0.0 Adjustments a Total 10988 100.0 Overall U -value = 0.087 C]!u h/! L -OF Data entries checked_ AMNf%.fIrs -Suite ReSidanb al 6D.08 RSR41 W 1 Ce U nts and Settings\Guy RoDertsonWy Docuents ARKSME UNIT B.rrp Calc = MA Orientation 2005 -May -1 2 0614:36 Page 1 Component Constructions Entire House Job: UNIT" * Date: May 11, 2005 By: G M Robertson For.- Parkside Apartments Rexburg Rexburg, ID Lvcaiuvn: Idaho Falls, ID, US Elevation: 474' ft Latitude: 44"N Outdoor: Dry bulb (OF) Daily range (°F) Wet bulb (°F) Wind speed (mph) Heating 15.0 Cooling 89 34 H 60 7.5 Indoor; I ndoor tem pe ra tu re (° F) Design TD (°F) Relative humidity (%) Moisture difference (gr/lb) Infiltration: i Method Construction quality Fireplaces Construction descriptions or Walls 1 F -o : Wood stud frame} siding or stucoo, no board. insulation, R-21 CaVity insulation 1 - sw : Wood stud frame, siding or stucco naitsul' -1 cavity insulation, Parbfions (none) Windows 4 1 -tow: Opera ble, wood frame , r glass, . rl pane ' 1 D -c2{ Opera bit clear glass, wood frame, 2 pane Doors 11 O: 'mood door, solid core, no storm Ceilings 16A -38w- Ceiling under unvented attic} no radiant Barr, a woo shaky R-38 in cul . 1 d: Ceiling under vented aftic, nio radiantbarrierdark shingles, :- insulation ' n all n e S► S SW W all n W all n se S SW all n S all Heating 70 76 50 61.5 Simplified Average 0 Cooling 75 "14 60 -31.5 Area -value 1nl R Htg HTM Loss Cig HTM Gain 399 0.70 0.0 35.7 286 52-4 41 120 0.065 21.0 4.94 593 0.47 57 104 0.065 21.0 4.94 514 0.47 49 224 0.065 21. 4� 4 1107 0.47 106 1 -091 13.0 6.92 823 1.23 146 FUQI M1 13.0 6.92 1 770 1.23 314 16 0.091 110 43.3 112 1.23 20 14 OMI 13.0 . 1477 1.23 262 10 0.091 13.0 6.92 68 .23 12 416 0. 09.1 13.0 6.922877 1 245 1.23 1 1 031 0.091 13.0 7128 1.23 1266 32 0.470 0.0 35.7 1143 15.9 508 399 0.70 0.0 35.7 286 52-4 41 40 0.470 0.0 35.7 1 429 23.E 928 12 0.570 0.0 43.3 520 18.6 223 0.570 0.0 43.3 276 53.E 340 38 0.570 0.0 433 1625. 33,2 1244 13 0.570 0-0 43.3 552 53-3 680 69 0.570 0.0 43.3 2973 36.2 2487 1 0.390 0.0 29.6 622 7.22 152 1 0.390 0.0 29.6 622 7.22 152 42 0.390 0.0 29.6 1 245 7.22 303 247 ' 1 OM6 38.0 1.98 488 1.61 398 399 0.032 30.0 2.43 970 1.34 536 RiqWSuite Residential 6.0,08 RM41031 C:Doctjment s ar-rd S ett in \Guy Robertson" D0cum e nts VARKS I DE UN rr B.irrp C a Ic = Mj 8 0 ri n 2005- May - 12 06:34 -3 7 Page I Floors 19GI9cscp: Carpe#ed floor over tight enclosed crawl, R-19 blanket v -1 1 wall} `IFb g ht -Suite Resident[ al 6.0.08 RSR41,031 C.Mocuments and itin s\Guy RobertsonWy Documents FA I(DE LjNrr fCM 11 19.0 1.29 834 0.24 2005 -Mai'- 12 06.34:37 Rage 154 Project Summary Entire House Job: eT 'rB' Date: May 11 7 2005 B: G M Robertson For: Parkside Apartments Rexburg Rexburg, ID Weather: Winter Design Conditions Outside db -6 OF Inside db 70 OF Design Td 76 OF Heating summary Structure D UCIS Cent ra I vent (20 cfrn) Humidification Piping Equipment load Method Construction Fireplaces Infiltration quality Area (W) Volume (ff) Air changes/hour Equiv. AVF (cfm) 21517 5374 1425 Q D x$316 Heating 126B 10144 D.45 76 Idaho Falls, f Df U5 Summer Design Conditions Outside db gg OF Inside db 75 " F Design TD 14 °F Daily range y Relative humidity 50 o/a Moisture difference -31 gr/lb Sensible Cooling Equipment Load Sizing Btuh Structure 5964 Btuh cin Ducts 3762 Btu h Btu h Central vent (2D cfm} 2fi2 Stuh Btuh Blower 0 Btuh Btu h Stu h Use manufacturers data � Rate/swing multiplier 0.94 Equipment sensible lead 1Q329 Btuh Simplified Average D Co X268 10144 0.23 39 Heating Equipment Summary Make PAYNE HEATING Trade Payne Model PG8HAA036050* Efficiency Heating input Heating output Temperature nse Actual air flaw Air flow factor Static pressure Space thermostat so aFUE 5Q 000 Btuh 4000r0 Btuh 59 OF 733 cfrn 0.027 cfmlB#u h 0.50 in H20 Latent Coaling Equipmentpment Lord Sizing Struct -699 Btu h Ducts -98 Btu h Central vent (20 cfm} w365 Btu Equipment latent load 0 Btuh Equipment totai load 10329 Btuh Req. fotol capacity at 0.70 SHR 1.2 ton Cooling Equipment Summary Mike Payne Trade Bayne PA10 Cord PA10JA024-C Coil CK5A/CK58AO24+TDR Efficiency �� S-ensik�fe cval�ng 1500 Latent coaling 6600Totaf cooling �2O�Q Actual air flow 73� Air flow factor a.Ofi8 Stafiic pressure D.50 Load sensible heat ratio 1,00 Printout certified by RCCA to meet a!I requirements of Manual J 8th Ed, MP Rigtt-Sufte Residential 6.0.08 RSR41031 C:00cunients and SeftllngMGuy Robertson\My Documents FAR IDE UN :CT SEAR Stu h Btu h BfU i1 CfTi1 cfmlBtu h in H2O Page I d AED Assessment Entire House Joba. UNIT H Date: May 11, 2005 Robertson For: Parkside Apartments Rexburg Rexburg, I D Location: Idaho Falls, 1131 US Eievativn: 47 41 ft Latitude: "ON Outdoor: Heating Goofing Dry bulb (T) -6 89 Daily range ('17) - 34 � Wet bulb (°F) - 60 Wird speed (mph) 15.0- 'i.5 Indoor: Indvar temperature (OF) Design Td {°F} Relative humidity (%o} Moisture difference (gr/lb) Infiltration: H Method Construction quality Fire laces Heating 70 7s so 61_5 Simplified Average 0 Cooling 75 14 50 -31.5 A 5. 5 U. Hourly Glazing Load a f 1, %.? IV 11 1Z' 1 -14 1b fb 1 1 19 20 Hour of :day oe HOUdy i Avemg MaXiMUM hourly glazing toad exceeds average by 3G.9%. House does not have adequate exposurediversity (I�ED) based vn AEa fImi# Qf 30°/a. AED excursion: 28Z Btuh (PFG - I-WAFG) VV1 Ri g4-Su'Re Res iden i al 6.0,08 RSR41031 C"Documents and Setfings�Guy Pobertsonft 2005- May- 12 0,4:7 Right„ vVorksheet Entire House Job= UNIT'B' Date: May 11 , 2005 By: G M Robertson 1 Room name Ent re House BATH 2 Exposed wall 175.6 ft 9.0 ft 3 Cling height 8.p ft 8.0 ft heat/cool 4 Roomdmensions 12.0 x 9_0 ft 5 Room aria 1268_0 f? 108.0 ft' Ty Construction Ll -value Or FfTM Area (ff-) Load Area (MLoadnumber ($tuhlf#� °�) �Btuhlii�j or perimeter' �#t} (Btuh) or perimeter (f#) (Btuh) Heat Cool Grass WAIS Heat Cool Gross NIPIS Heat Cool' 6 VJV 12F�?sw 0.065 n 4.94 0.47 152 720 593 57 0 D D 0 4A1-2ow 0.a70 n 35.72 15.$8 32 o 1143 508 a a o 0 12C-0sw 0.09 n 6.92 1.23 152 119 823 146 Q 4 0 Q '!D -chow 0.570 n 4.3.32 18_61 12 0 520 223 0 Q CI p 11 11 00 0.390 n 29.64 721 21 21 622 352 Q (l D 0 W 12C-0sw 0.091 e 6.92 1.23 256 256 1770 314 0 p 0 4 12C-Osw 0.091 se 6.92 1.23 23 96 112 20 0 0 0 D 1D-c2ow U_570 5e 43.32 53.33 6 Q 276 340 Q 0 D ❑ llj�f 12C-0Sw 0.091 5 6.92 1.23 272 214 7477 262 0 0 0 p I•---t� 1 o-c2cw 0.570 s 43.32 33,17 38 o 1.624 1244 o o o 0 L�r_a 11 bo 0.39:0 s 29.64 7.21 21 21 622 952 0 a a Q 12C-0sw 0-091 sw B_9� 'f,23 23 10 68 12 i} 0 Q p 1 Q-C2flNv 0.570 sw 43.32 53.33 13 i# 552 fib Q 0 0 Q 0 W 12F-(}sw (].065 w 4.54 0.47 104 104 514 49 0 0 0 D 12C-0sw 0.091 w 6.92 1.23 424 418 2877 511 72 64 443 79 4A1-2vw 0.470 w 35.72 52.43 8 0 288 419 8 0 286 418 C 96A -38w 0.026 -1-98 1.87 247 247 488 398 Q 0 0 Q C 46�3dac! 0.032 - 2.43 1.:4 399 399 970 536i08 108 263 145F 19C-19cscp 11049 - 1_29 o.24 mss 107 834 154 0 o a 0 s cj AEo excursion 282 188 Envelope tossfgain 16173 660 991 83'! 12 a} lnfilh'ation b} Room verttilatian � � �4 27D � 13 fntemal gain; Occupants @ 234 0 0 In Less exc#emal load AR�iar 1200 � � D Less transfer Q Q 0 0 Red istribi.rtion fl fl Q 0 14 Subtatai -0 D 50 26 15 Duct Icaads 215176964: 1314 883 25 54% 53i� 3762 25% 54% 328 477 Total roam Ind 26891 10726 1643 1361 Airrequirerf (c'fm) 733 733 1 45 93 Ae� Pdn to ut cerfified b y ACOA to meet all fNu ireme nts of Manual .18th BEd. �IVr:C�!`7tSQ'�C Right -Suite Residenfial5.0,08 RSR41031 C:IiJocumentS and Seltingscuy RoksertsanUufiy L]oc.umentsPARICSI E1E UNIT S.rrp Cade = M,18 Orientation 0s--1 2 0634`39 Page I Right-., 4Vorksheet Entire House ,fob: UNITS' Date: May 11 , 2005 : G M Robertson 1 Froom name BEDROOM 2 M CL Exposed wall 23.0 ft 3-0 ft 0 Ceil Ing height 8-0 ft he aticc6 8. 0 ft Room dimiom 10,0 x 13,0 ft 3.0 x 7.0 ft Room area 130.0 T 21.0 f Ty Can Stru dion U - value r HTM AreaP 1. o i Area f) Load. number (Btuh1f?--*F)(Stuhlffl nmeter (M (Btu r pe rimeter () (Btuh) Hat Cool Gross NIP/S beat Cool Gans NIP/S Heat Cool 1F-Os 0.065 n 4. 0.47 80 64 3160 0 0 0 1-2ow 0-470 n, 35.72 15-88 W. 12C-Os12C-Osw 0.091 n 6.92 1.23 0 0 0 0 0 a 0 0 1 D 0,570 n 43.32 18.61 0 0 0 0 0 11 11 DO 0.390 n 29,64 7,21 0 0 0 0 0 0 12 C-Osw 0.091 a &92'1.2 0 0 0 0 0 0 0 0 wt 12C -Dew 0.091 Se & 92 1.23 0 D 0 0 0 0 0 ID--c2cw 0.570 se 43M 53.3 0 0 0 0 0 0 0 0 1 0,091 S 6-921{2 0 0 0 0 24 24 166 2 ID -clow 0.570 s 4_ 33-17. 0 0 0 0 0 0 0 11 D0 0.390 s 29.64 7.21 0 0 0 0 01 01 0 0 1 Caw 0-091 Sw 6.92 1.23 0 G 0 0 0 0 0 0 1 Ch ow Or 57 0 sw 43.3253. 33, 0 0 0 0 0 0 0 0 1 F O, 06 5 w 4.94,0.47 104 104 514.0 0 0 Wh 1 0.091 w 0.92 1.2 0 0: 0 0 0 0 0 4A1-2cw 0.470 16A -38w 0,026 - 1.98 1.81 130 130 257 2100 0 0 01 1 B- 0 d 0.03 - 2.43 1. 0 0 0 0 21 21 51 28 F 19C-1 9CSCP 0.049 - 1.29 0.24 0 0 0 0, 6 1 8 1 D excursion Envelope losstga In 1658 516 225 56 12 a) Infi Itr tion Room venti-iation 0 66 91 01 0 13 Intema I gains pli es @ 1200 0 0 0i Less. tI r Less transfer Red ibi i+ 0 "� 0 0 1 not 0 0 -1-65 2358 581 0 0 314 % % 0, 0 Total room load A r ru ird . 7 896 so 1 Pfintout cerfified by ACOA to meet VIII requirements of Manual J 8th Ed. Kigtt-SudeResid' �ocu is and etting u Robert nDocu en%PA IDE UNIT B.rr� �I = ��� Orientation 00f - 1 0 --34.3a Page Right, 4Vorksheet Entire House Job: UNIT T' Dade: May I 1 9 2005 By: G M Robertson 1 Room name MASTER BEDROOM U HALL 2 expo sed vvatE 28-0 ft 0. a ft 3 Ceiling height 8. Q ft heat/cnoi 8.0 fthea#lcod 4 Room dirr►ensions 1.0 x 187.0 ft 1.0 x 43.Q ft 5 Roam area 18 7. 0 ft' 43.Q fig Ty Ccxnstrut#ion U -value Or HTM Area (ff) Load Area (f L2) Load Rur11bef (8tuh/ft22F). (13tuh/M or perimeter {f#} (6tuh) or perimeter (gkuh) Heat Cool Grass NI P1 S Heat Cool Gross NJP15 Heat Cool 6W. 12F-osw 0.065 n �. 0_47 a a o r� n a o 0 -4-94 4A'#-2ow 0.470- n 35.72 15.88 t} Q 0 p D 0 0 0 12c-asw 0_091 n 6.92 1.23 a o o a o a a Q 11. 11DO 0-390 n 29.64 7.21 0 D p U 0 0 0 D W 1 2G -05w 0.091 e 6.92 1.23 0 0 d 0 p Q 0 p WL 12c-nsw 0,091 se 6_92 1.23 a o 0 o a o 0 0 �---G '!D -claw 4.570 se 4.3.32 53.33 t? D 0 4 D 0 i? 0 W, 12G05w 0,091 s 6.92 1.23 128 1Q4 799 128 0 Q gyp. D f'^LJ 10-c2ow 0,570 s 43.32 33.17 24 o T040 796 a o o a 11 Do 0.390 s 29.64 7.21 o 0 0 0 o a o a 12C -05w t 0.091 sw 6.92 1.23 Q 0 Q 0 Q 0 0 D -G 1 D-c2ow 0.570 sw 43.32 53.33. 0 a D D 4 fl 0 D W 12 F-0sw 0.065 w 4.94 0.47 0 Q (i 0 U 0 0 0 W. - 12 C-0sw 0.091 w 6.92 1.23 96 96 664 118 0 0 D 0 '---G 4A1-2aw C 0.470 w 35.72 52_43 0 D Q D Q 0 0 4 16A -38w 0.026 - 1_98 t69 0 o a a o a o p C 16&30ad F 19C-19cscp 0.032 0.049 - - 2.43 1.29 1_34 0.24 187 18 187 455 251 43 43 105 58 3 23 4 Q p 0 Q 6 cj AE excursion 181 -3 Envelope loss/gain 2941 1478 105 55 92 a) Infiltration b) Ream venfilaiior, 85� p � � �Q 13 In Lama) gaj-na Occupants @ 230 fl �P��ances (g 1��p � 0 1 Less external load a1 0 Less transfer 0 d fl 0 RE(iIS�[bUtE0f1 � � 0 (} 14 Subtc�al 430 125 -405 -55 15 ❑tit 14ads 4'f 83 9683 0 0 25% 54% 1o45 sos 25% 54% a 0 Total raa„ load Airrequired (cfm) s227 2592 942 177 00 Printout certified by ACCAmeet all Muirements `L i 94 -SUS Res id nfi of 6 D,08 RS R 41031 CADocuments and SettinqsoGuy RobertsonWy DocumentsFARKSWE UNFrB.rrp Calc=mj8 Orientation 2005 -Flay- 12 06:34:39 Page Right,q.o Worksheet Job: UNIT '13' Entire Nouse gate: May 11, 2005 By: G M Robertson 1 Rom name 13ED Ips 11 T Ceiling height .0 ft he' 4 Room iimen .ice 13.0 ft 4.0 X 10_ ft Room are: 117.0 ff Ty Constniction LI -value Or HTM Area Lo ad Area (fl?) Load numb uh/f -"F (Bt u ) or perimeter (ft) (Btuh) or pe6meter ft 13tu Heat Cool Gross WKS Het Cool Gross NIPIS Tat Cool 6 Vr_..G 12F-Os12F-Osw 0. n 4. 0.47 72 56 277 4A1-2cw 0.470 ri 35,72 15.8 16 0 572 254 0 0 0 0 W. 12C-Osw 0.01 n _9 1.23 0 0 0. 0 01 1D 0-570 n 43,32 18.61 0 0 0 0 0 0 0 0 Y—G 1 0.091 se 6,92 1.23 0 0 0 0 0 1 0.570 Se 43-32 53.33 0 0 0 0 W. 1 0.091 S 6.92 1.23 0 0 10 0 0 1D -clow 0.570 sw 43-3253,33 0: 0 0 0 0 0 0 1 Caw 0.091 1 0 0 0 0 16A -38w 0.06 - 1.98 1.61 117. 117 231 189 16 B-0 ad 0.032 - 2.43 1_:4 0 0 0 0 40 40 97 54 D excursion - - Envelope loss/gain 1079 447 97 51 12 a) Infihration b) Room ventilation 274 26 0 0 0 0 0 0 13 Inte ma I g an s, erupt (g 230 ppliames (p 120001 Less exteFnal load 0 0 1 0 14 Subtotal 20' - -1 15 Duct lids 1392" 493 0 0 % % 348 266 25% % 0 Tota roorn load A r requ it d frim 1739 759 0 47 52 o 0 Pn'n to ut certified ACCAto ret all requ ire Ri !t -Suite Residential 6.0.08 R 8410 1 CADocuments and Setting \ pry Robertsons Do um entsTARKS SDE UN IT B -rrp C a1c _ Mja Orientat ion 2005 -May -1 2 06.34.39 a Righttij Worksheet Entire House Jy UNIT 'B' Date: May 11, 2006 B-. G M Aeon I Room name KiTCHEN DINING 2 Exposed wall 28.0 ft S.0 ft 3 Ceiling freight 8-U ft heaticoc�# 8.0 ft heaticod 4 Room dimensions 15.0 x 11.0 ft 15.4 x 9.0 ft 5 Room area 165.0 fF 135_U ftp Ty Canstmctivn U-value'Or FtTM Area {f�} Load Area �wmbet (Btuh/ff-DF} {Btuhl or ft�j perime#er (ft} �Btuh} or perim�er {fid} {Etu�h) Heat Cool Gross NIPIS Heat 11 1� Cool Grass NI PIS Heat Cool 6� 12 F -05w b.06�� 4.9a fl.47 Q U D Q Q 04A1 -tow 0.470 n 3572 15.88 U l 0 ( Q Q U'2C-0sw 0.�5'n 6.92 1.23 120 87 602 147 ] 0p9D-C2ow C5f0 r 43.32 18$1 12 4 520 23 11 DO Q 0 . . 7.21 21 21 622 152 i 0 p 0W 12C -?5v 099 e 6.92 12 4 p D {aV12C-0sw0.091. se 692 1.23 0 a D p Q a Q 41D-c2aw 4.570 se 43.32 53.33 { J U Q p p 0 4 92C -05w 0.091 s 6.92 1_23 4 p U 0 0 0 0 0 ID-c2ow 0,570 s 43.3 33.17 0 0 0 U 0 0 D 0 11 oo 0_390 s 29.64 7.21 a o o Q o n 0 Q t -G. 12c-0sw 0_091 Sw s_92 1.23 o 0 o a o o 0. o 10-c2aw O. 570 5w 43.32 53.33 0 o o a o o a 0 w 12F 0.065 w 4.9a o.a� a � s� a Q o � o W,L-G 12c-Osw a.as1 w s.sz 1.23 ss ss ros jos 72 72 ass ss 4A9 -2ow 0.470 w 35.72 52_43 a a o 0 a o o fl C 16A -38w 4.028 - 1.9$ 1.61 0 ❑ 0 0 [} D 0 D C 16B-30ad 0_032 - 2_43 1.34 0 0 Q 0 Q C3 0 D F 19G-19CSc�7 {7_QA�S - x.29 0.2� 'ffi5 26 213 39 '135 9 174 32 6 c} AE D Baca, rsion _32 7 Envelope foss/gain 2566 597 672 '114 12 a) infiltration b} Room verrtilation 79a 70 274 ZS a 0 93 lntema#gams Occupants @ 230 fl 0 0 Appliances @ 1200 �g U Less e�ckerr�al load o 0 0Less transfer' 0 0 p 0 Redistribution 220 327 0 0 14 Subtotal -94fi -140 115 Duct f Dads 5627 ggg Q 0 25% 54°fo 1405 539 25% 5A°/n 0 [} Total room load Airrequired (cim) 7033 1537 D D 192 105 0 0 Pnntout cerfified by ACOA to meet all requirements of Manual J 8th Ed. ,.'►- w�r'�gF-7tSOft RigFt-Suite Res Wen tia# 6.0.48 RSR41E731 C:ICTocuments and SettingslGuy RabertsonWly ilocul'rtentslPARKSff3E UNIT B.rrp Calc = M.18 orientation 205 -May -12 06:34:39 Pale 5 i RmIghtmi vVorksheet Entire House Job: UNIT Date: May 11, 2005 Robertson 1 Room name UTIL PWDR 2 Exposed wall '[3.0 #t 7.0 ft 3 Ceiling height 8.(] ft heat/cool 8.4 ft heaticooi 4 Room dimensions 4.0 x 9_0 ft 4_0 x 7.0 ft 5 Rao m area 36. Q W 28.0 ft' Ty Construction U -value Or HTM Area Load Area (ft) Load number (BtLihIff-'F) (Btu h /fF) or perimeter (#t) (Btuh) or perimeter(ft} (Btuh) Heat Coot Gross N1PlS Heat Cook Gross IdlP1S Heat Coal fi W '�2F-0sw 0.066n4.94 0.47 U C1 00 0 {� 0 D �� 4AI-2ow 0.470 n 35.72 15.88 0 0 Q o 4 0 fl D wl 'i 2 C-0sw 0.091 n 6.92 1.23 32 32 221 39 Q Q 0 0 1 D -chow �_�7Q n 43.32 18.61 a a 0 0 Q 0 0 0 1 '! 19 DO 0-390' n 29.64 7.21 D 0 0 4 0 0 0 p W 12C -05w 11.091 e 6.92 1.23 72 72 498 88 56 56 387 69 T -G 12C-Osw 0.091 se 6.92 1.23 0 0 0 0 0 0 0 'lD-c2ow, 0.570 Se 43.32 53.33 0 0 0 0 Q 0 0 D 'E 2 Caw 0.091 s 6.92 1.23 0 0 0 d 0 ti 0 D 1-c2vw a_sra s 43.32 33-17 o a o 0 o a o 0 11 DO 0_390 s 29.64 7.21 o a o 0 0 0 o a L� 12C-0Sw 0.091 sw 6.92 1.23 Q Q p p 0 0 0 0 1 Q-c2aw 0-570 sw 43.32 53.33 a a a o v o 0 0 W 12F-0sw 0.065 w 4.94 0.47 0 o a a a a o v 12C-0sw 0.091 w 6.92 1.23 0 (} b D 0 0 D d 4A1-2aw 0.470- W 35.72 52.43 Q 0 0 D D 0 0 0 C 16A -38w +0.026 - 1.9$ 1.61 0 0 [] 4 0 0 0 D G 16B-30ad 0.032 - 2.43 1.34 D d D D 0 0 0 0 F 19C-19CSCp 0.049 - 1.29 0.24 36 13 46 9 28 7 36 7 6 c) AE D excxi r5 -Ion $ Envelope loss/gain 766 128 423 71 12 a) Infilfraticxn 395 37 b) Room ve213 20 r�tila[itxi ° ° a o 13 fn�mal gains Occupants@ 230 o 0 O ext Appliances @ 9200 0 0 � 1 1 0 Less erna! bad� 0 Less transfer Q U Redistribution 0 a 0 +0 114 Subtotal -1161 -166 $36 -91 15 Duct wads a 0 o 0 25°Io 54% 0 0 25% 54°lo 0 p Tial room load Air required [cpm} � Q o a 0 D Pdntaut certified bY AGFA to meet all requirements of Manual J 8th Ed. Right -Suite Res idential6.a.D8 RSR47031 C;l€]acuments and Setting5lGuy RobertsanlMy i}ocumenisVARKSEI7E UNIT B.rrp Calc = M.lB Orientation 2405 -May -1206:34:39 Page 6 A`! Job: NIT "B :{. s Date Entire HouseMay 2005 , _-. Robertson 1 Room name `TRS UVING Exposed wdl 9.0 ft 39.6 ft ei1'rr g he igh t 8_0 ft heat/cool 8,0 ftheat/cool Room dimensions 4.0 x 9-0 ft 1.0 x 222.0 ft Room area 36.0 22 2. 0 ff Conistrudion TY U -value Or HTM Area W) Low Area. T) toad number I (Btuh/ft22F)i(ice or peftetier (ft) (Btuh) or Perimeter Btu Heat Coo I dross N/PIS Heat Cool Grp N/P/S Heat Coo 6 VL_�G 1 Few n 4a94 . r 0 0 0 0 0 0 zW, 1 0.091 n 6.92 1. 0 0 I' - O. C n 4. 18.61 0 0 0 0 0 0, 0 0 w 1 Caw O. 091 e -6-92 1.23 72 72 498 88 56 56 387 69 t_6 12C-12C-0sw 0,091 se, 6-921.23 0 G 0 0 23 16 1121 ID -c 0.57 43.32 53_33 0 0 0 0 6 0 276 340 W. 12C-Nw 3.091 S 6,92 1.23 0 0 3 0 120 86 591 105 ID-c2ow 0.570 s 43.32 33.17 0 0 0 14 0 586 448 11 Do 0.390 s 29.64 7,21 0 0 3 0 21 21 622 152 1[ ,570 sw 43.32 53,33 0 0 0 0 13 0 552 680 W, 12C-Osw 0.091 w 6M1.23 0 0 0 96 96 6654 118 .1- 10.470 1 0.0 - 1.98 1.61 3 0 0 0 0. 010 0 1--30 0.032 - 2.43 1.34 0 0 0 0. 0 3 F 1 1 c O.049 1.29 0.24 36 9 46 9 222 40 287 53 D excu is ion Envelope loss/gain 544 1 41 2024 �1 a) In fi I�atic�n b) Room ventilation 274 26 �1 114 0 13 1n terra I gainsnt 10 Less til I 0 Less transfer 0 0 0 Red i Sti bution e 0 0 0 14 Subtotal -818 -117 1291. 187 15 Duct Iced s 25%, 0 6643. 2325 °o 0 0 % 54 % 16 Total room load 01 Air required 8302 3581 1 226 245 Printout certified by ACCA t meet all re quir ements Iii -.its Res idnti al 6,0.08 RSR41031 ACC :'�f u rpt and Ring ' u o r t n' o en# F I IDE UN r B.rr is = - - 1 06:34 Short rorm Entire House JON: UNIT "N Date: May I I x 20 0 B: G M Robeson For: Parkside Apartment Rexburg Rexburg, ! D nay c:[g outside db (°F) -6 gg Inside db {°F} 70 ?5 Design TD (°F) 76 �q. Daily range _ H Inside humidity (%) _ 50 Moisture difference (gr/lb) - _31 Method Construction quality Fireplaces Infiltration Sfmpl�fied Average Q HEATING EQUIPMENT Make PAYNE HEATING Trade Payne Model PG8HAA036050* Efficiency 80 AFUE Heating input 50000 Heating output 40000 Temperature rrse 58 Actual air flaw 74.,p Air flow factor 0.028 Stafic pressure p �p Space thermc)stat 0 ROOM NAME BEDROOM BATH M CL MASTER BEDROOM CL U HALL U STRS KITCHEN DINING UTIL PWDR STRS LIVING RM Area (ft2) COOLING EQUIPMENT Make Payne Trade Payne PA10 Cond Pg1Cl.iq024..0 Coil PFlMNB024 Efficiency Btuh Sensible cooling Btu h Latent cooling °F Total coaling cTm Actual air flaw cfim/Btu h Air flow factor in N20 Matic pressure Load sensible heat ratio 169 81 21 151 39 43 40 132 108 36 Htg load (Blah) 5803 1394 Q 61 �0 4 Q 0 6076 0 0 0 0 7336 C19 load (13tuh) 10 SEER 15540 Btu 6660 Btu 22200 Btu h 740 cfrn 0.073 cfrn/Blah 0.5-0 in H2O 1.p0 fl Htg AVFI C1g AVF (arn) (0m) 9 8621 1637 1 36 4'f � 38 30 0 o 0 2815 169 los 0 fl Q 0 0 o ° o 0 1453 168 106 0 p a a Q o 0 0 0 a a 0 3575 2�� 261 Printout certified b y ACCA to meet SII requirements of Manual .f 8th Ed. . ,.- vvrights<3ft Ri gff-SU fte fees id nti al 6.0-08 RS R 41031 CA C-00cuments and Robertsonft DocumentsWARKS11DE x'005 -May- 12 (1.-46:1 Fuge 1 Entire House Other equip loads Equip. a[7 0.94 RSM Latent cooling TOTALS 1070 26828 1207 10121 222 9723 9723 Printout certified b y ALGA to meet all requirements of Manual J 8#h fid. VVIrI4ghtSC>ft RIck-Uit Res identi aI 6.0.08 RSR41 031 )OCAZ�k CIDOC u wents and S eft ings rusu y Robert n" D ocum ents VARKSIDE UN rT A-rrp C aIC = W 8 Orientation 740 740 740 4 005 -May - 12 06:48:° Building Analysis Entire House Job: UNIT `A! Date: May 11, 2005 Robertson For.- Parkside Apartment Rexburg Rexburg, J D Idaho Fila Elevation: Latitude: Outdoor: Or US 4741 ft 44°N ury bulb (OF) Daily range {°F} Wet bulb (°F) Wind speed {mph} Heating -fi 15.0 Cooling 89 34 60 7.5 H ) maoor: Indoor temperature {°F} Design TQ (°F) Relative humidity (0o)Mo€s#ure difference grlib} infiltration; Method Construction quality Fireplaces Heati ng 70 7s Simplified Avenge 0 Coaling 75 14 50 -31.5 Overall U -value = 0.091 Btuhlft2- �F �a Data entries checked. AV5K W%f E-1 LLJ n 1USC3 i -Suite Res idenfi al 6.0.08 RSR41031 ;VOCUMEn# sand S ett ings�uy Robertn MY D ocu rn DE LIN IT A.rrp ail =Orientation 2005=Mays-1 06 81-1 Page 1 Component Constructions Entire House Job: N IST Date: May 11, 2005 B: G M Robeson For.- Parkside Apartments Rexburg Rexburg, ID Lvcaxion; Idaho Falls, ID, US E I evation 4741 ft Latitude: 44.°N Outdoor: Dry bulb (°F) Daily range (°F) Wet bulb (°F) Wind speed (mph) Cooling 89 34 ( H 60 7.5 Construction descriptions Walls 1 - : Wood stud frame, siding or stucoo,no board insulation, R-13 cavity 1n Parti ons {Wane} Windows I 0-c2 : Op era b , dear glass. wood frame, 2 pane Doors 11 DO: Wood d oor, solid core, no storm Ceilings 1 -d: Ceiling uncle r vented attic, no radiant .farrier, dark sly ingIe 5 R-30 in SuI atio n Floors 1 C-1 9cscp : Carpeted fIcor over tight en do sed crawl, -11 warfl R-19 blanket Indoor: I ndoar temperatu re (° F) Design TD {°F} Relative humidity Moisture difference (gr/lb) Infiltration: } Method Construction quality Fireplaces Simplified Average 0 Coolin, 75 14 50 -3"x_5 Or Area -value tui R Htg HTM Loss Cig HTMfn 6 710 Se () ( --F) (-¢Flh) (BW (Ruh) (2) (h) n 199 0.0911 13.0 43.E 1376 1.23 244 Sw 528 0.091 13.0 . 552 53.3680 Se 16 0.091 13.0 6.92 112 123 20 n 166 0.091 13-0 6.92 1145 1,23 203 sw 10 0.091 13.0 6.92 68 1.23 1 all 528 0.091 13.0 6.92 3652 1.23 649 all 1447 0.091 13.0 6.92 10006 1.23 1777 n 36 O.570 0r043.3 1560 18.6 6 710 Se 6 0.570 0.0 43.3 276 53.3 3 S 38 0.570 0.0 43.E 1 625 33.2 1 244 Sw 1 .570 0.0 43.3 552 53.3680 all 93 0.57043.3 4013 31.7 2934 n 21 0.390 0.0 29.6 622 7.22 152 1 0.390 0.0 29.6 622 7.22 152 all 42 0.390 0.01 245 7.22 303 558 032 MO 2.43 1 357 1.34 750 558 0.049 19.0 1.29 720 0.24 133 A�� VV1-10htSACVft Rgft-Su Res idental 6.0.08 RSR410,31 G.'Vocuments and Settings\Guys RobertsonNy DocumentsVPARKSIDEEM IT A.rrp Calc = PAJ8 Orientation 2005 -May -120648-18 Page I ba Project Summary Entire House Job: UNIT W Date: May 119 2005 B Robeson For: Parkside Apartments Rexburg Rexburg, I D Weather: Idaho Falls, ID, US Winter Design Conditions Summer Design Conditions db Outside db � Inside db �� °F Inside db $9 OF Design TD 76 °F *F Design TD 14 OF Daily range H Relative humidity 50 % Moisture difference -37 r/lb Heating Summary Structure 21849 Btuh Ducts 49 79 Orn Central vent X17 cfmj 1207 Btuh Humidification p gbh Piping 0 Btuh Equipment load 28035 Btuh Method Construction Fireplaces 1-nf i1tration quality Area (ftx} Volume (f?) Air- changes/hour Equiv. AVF (cfm) Hea1�� 8560 0.45 64 Simplified Average D Cooling 10i� 8550 D.23 33 Heating equipment Summery Make PAYNE HEATING Trade Payne Model PG8HAA036050* Efficiency Heating input Heating output Temperature nose Actual air flow Air flow factor Static pressure space thermostat 8[7 AFUE 50000 Btuh 40D00 Btuh 58 OF ago cfm 0.028 ctmiBtun 0.50 in H2O Sensible fooling Equipment Load Sizing Structure = Oa 0�..�. Ducts Cen(cfrn) Blower lJse manufacturer's data Ratelswing multiplier Equipment sensible load .LU n 34 97 Btu h 222 Btuh 0 Btuh 0.94 9723 Btu h Latent C ling Equipment Load Sizing Structure Ducts -93 Btu l� Central vent {17 cfrn} -309 Btuh Equipment latent load 0 Btuh Equipment total lead 9723 Btuh Req. total capacity at Q.70 SHR 'i.Z ton Cooling Equipment Summary Make Payne Trade Payne PA10 Cord PA 1 0 JA024-C Cali PF'(MNB024 Efficiency 10 Sensible coaling 15540 Latent cooling 6660 Total coaling 22200 Acfuai air flow 740 Air flow factor Q.073 Stabc pressure 0.50 Load sensible heat ratio 1.00 - - Printout certified by RCCA to meetall requirements of Manual J 8#h Ed. pjgft_SudePZesidenbal6.C.O8RSR41031 GADocun-ents and Selflnuyftbertsonft DocumentsPARKsIDE SEER Btu Btuh Btu h cfrn CTM/Btuh in CH2O 00 M - 12 06:48:1 AED Assessment Entire House For: Parkside Apartments Rexburg Rexburg, Id Location: Idaho Falls, 1D, US Efevatian: 47 ft Latitude: 44°N Outdoor: Heating Dry bulb (°F) ..6 Daily range (°F) - Wei bulky (OF) - Wind speed (mph) 15_Q Cooling 8.9 34 60 7.5 indoor: Indoor temperature{pF3 Design TID (°F) Relative humidity (4/0) Moisture difference (gr/lb) Infiltration: H) Method Construc i'on quality Fireplaces Hourly Glazing Load Job: UNIT * Date: May 11, 2005 B- G M Robertson Heati ng 70 76 so 61.,5 Simplified Average 0 Hour of Day Average D fimit Maximum houdy glazing loaf exceeds average by 38.2%, House does not have adequate exposure diversity'AP �ased on AED I MR of 30 Yo. AED excursion: 3a3 Btuh (PFG - 1,3*AFG) v r 1ohtsc:x-Vt Rj 9It-Su its: Res ide #i a# -.0 D8 RS R 41031 ACOk C:Uocuments and Seftings\Guy Robertsonft DocumentsPARKSIDE U r iT A..rrp Calc = Orientation Coolina 75 14 50 X1.5 2005 -May -1 2 06:4818 Page I 5x500 5,000 4x500 4,000 Jc 31500- 3100& 2.,500- 25000- 11500- 1r -i i i o` Cooling 8.9 34 60 7.5 indoor: Indoor temperature{pF3 Design TID (°F) Relative humidity (4/0) Moisture difference (gr/lb) Infiltration: H) Method Construc i'on quality Fireplaces Hourly Glazing Load Job: UNIT * Date: May 11, 2005 B- G M Robertson Heati ng 70 76 so 61.,5 Simplified Average 0 Hour of Day Average D fimit Maximum houdy glazing loaf exceeds average by 38.2%, House does not have adequate exposure diversity'AP �ased on AED I MR of 30 Yo. AED excursion: 3a3 Btuh (PFG - 1,3*AFG) v r 1ohtsc:x-Vt Rj 9It-Su its: Res ide #i a# -.0 D8 RS R 41031 ACOk C:Uocuments and Seftings\Guy Robertsonft DocumentsPARKSIDE U r iT A..rrp Calc = Orientation Coolina 75 14 50 X1.5 2005 -May -1 2 06:4818 Page I b .-04 N Righ�„Worksheet Entire House Job: UNIT Eft Date: may 11 � 2005 By: G M Robertson Phntout certified b ACOA to meet all r ft-Sufte Residential 6-0-08 R5R41031 CADOcuments and Selt ingsGuy Robertsonft DocumentMPARKSf DE UN rr uIrements of Manual J 8th Ed MMMMWIMM A.r-rp Gait = Mj8 Orientation 2-005- Ma y - 12 06--48:19 Page 2 Right Worksheet Job.- NIT 'A' i '.date: May 11 2005 Entire Rouge By: G M Robertson Nntout cerfified, by ACCAto meet all r2quirements C - Documents and et hgM uy ober mon Do m :�tS �,RKIDE UNC , 1 - Pa ' Right -.a Worksheet .yob: UNIT 'Ay Entire House date: May 91, 2005 By: G M Robertson 1 Room name MASTER BEDROOM COB ing helight RooRoom area d i o . 0 ft t/ m �-� ��,� fit _0 x 1.0 ft 7 151 390 ff TY Contnuton U-vtal r HTM Area 1 A� LOW Area O uh/ - F (fituh/f) or pe 6 ) (Bf uh) or pe riet r ft Load Rtuh) Heat Cool Gross N/P18 Heat COW Gross N/P/S H eat Cool 61 12 Caw 0.091 n 6.92 1.23 0 0 Q 4 16629 T 11 LSO � 0 11 1 -� 1 104 1 128 L—G 1 D-c2cw 091 x.92 1.23 0 0 0 0 W. 12C4)sw 0570 se 43.32 53.3 0 0 0 11 ID 0.390 s 29.E 7.21 0 t—G 1 x.570 5_3 0 0 0 0 0. 0 C 16B -Wad 0.091 w 6-92 1-23 96. 96 664 118 19C-19CSCP OM2 - 2,43 1-34 15.1 151 367 203 39 39 95 52 c) AE D excu rs ion EEnvelope lossigain 236 -3 m 2624! 1452 988 0 1 IrefT i b Rom ventilation. 570 365 3 0 0 � 0 1 rr f in Occupants pi� @ 1200 0 0 L � r`r l I 0 Less transfer 0 0 0 RedlsMtUbn 0 0 0 01 14 Su btotal 1789 337 -1353 -242 15 Duct Ids 498. 1421 Tutaf room load - i r requ i rel arn61-20 2815 1 P nI n to ut cerlified b ACCA to meet alI r2qu Ire . lUs. 19t Ri 9Iht-Suite Res Id eff al 6,0.05 RSR 410,31 rets WARKS I DE UN IT A.gip C a Ic = Ori fitat io n 12 06:48 ,1 Page I ,-1 Right -j Worksheet Entire House Job: UNIT W Date! May 11, 2005 By . G M Robertson 1 Room name U HALL U STRS 21 Exposed wall 4. 0 ft 1 10.0 ft 3 Ceiling he igh t 8.0 ft teat/00(A 8. 0 ft heater4 Room dimensions 1.0 x 43. 0 ft 4.0 x 10-D ft 5 Room area 43 - 0 T 40 - 0 W TY Construction U -value Or HT M Area I ; ff) Load Area Load number F(Btiuh/fF-"F) (Btuhlff) or pefirneter (ft) (13tuh) or Perim eter (ft) (Btuh) "P Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12C-osw 0- 091 n 6,92 1,23 0 0 0 0 0 0 01 0 1D -c2 - IF3 Cw 0.570 n 43.32 18.61 0 Or 0 0 0 0 0 0 ---D - I I [Do 0.390 n 29.64 7.21 0 0 0 a 0 0 0 0 w 12C-Osw 0. 091 e 6.92 1.23 32 32 221 39 so 80 553 98 11 W. 12C-Osw 0-091 se 6.92 1-23 0 0 0 0. 0 L --G 1 D-c2cw 0. 57 0 se 43.32 53,33 0 W 0 0 0 0 12C-Osw 0.091 S 6.92 123 0 0 0 0 0 0 0 0 1D-c2cw 0-570 s 43-32 33,17 0 0 0 0 0 0 0 0 `t1 DO 0-390 S 29-64 7,21: 0 n r 12C-Osw 0.091 Sw 6.92 0 0 0 01 0 0 V 123' G. 0 0 0 0 0 0 0 ..-G ID-c2ow M70 sw 4:3.32 53.33 0 0 0 0 0 0 0 0 W. w 12C-Osw 0,091 w 6,92 1.23 0 0 0 0 0 0 0 0 C 16 B-30 ad 0.032 - 2.43' 134 43 43 106 58 40 40 97 54 F 19C-19cscp 0.049 - 1y 0.24 0 0 0 0 0 0 0 c).AED excursim -2 Envelope loss/gain 326 96 651 150 12 a) in fi Itration b) Room verdjjat�on 91 9. 228 2111 01 0 0 0 13 Irma I gahs Occupants g 230 0 0 0 App12nces Q 1200 0 0 Less e)dem.1 load 0 0 0 0 0 Less transfer 0' 0 Redistibution 0 0 0 14 SU btotal -417 -104 -879 -171 .15 Duct Ioads 23% 53% 0 70 0 0 0 0 23% 53% G 0 Total room load 0 01 0 Air requjred MM) 0 0 Frit ACOA to meet VIII ru i reme nts of Man ual J 8t h Ed. lt!S- C> -ft F?j gtt -Suite Res iden t a) 6.0-08 RS R41031 2005 -May -1 2 06A&19 C.'Oocufmnts andetti , Snqs�Guy Robertsonft CocumentsVARKSIDE UNIT A.rrp Calc = MJ8 Orientation Page 4 Right"'q4 Worksheet Job.- UNIT "N Entire House Date: May 17, 2005 By: G M Robertson 1 Room name i DINING 21 Exposed wall 23. 0 ft al Ing height . ft 1_0 x 11.0�1_� .� ftp Room 132.0 TY Construction U -value Or HT I Area (Btuh/ft2-9F)i �Load ------ numberr Perimeter f(f?) Load Rtuh) or PeTimeter ft ( tui) Heat C001 Gross N/P/S Heat Coo I Grms NIPISH ea t Coo I 1-Os0.091 n 1.23 96 63 436 77 0 0 0-570 n 43.3 18-131 1 0 520 22 3 0 01 0 w 12C-0sw 0-390 n 29.c>4 7-21 21 21 622 152 0 0 0 0. 0 0 0 W 0 0 0 0.570 sw 43.32 53.33 0 0 a 0 0 0 0 C 1613-30ad 0.091 w 6-92 1.23 88 88 609 108' 72 72 498 88 0.032 - 2.43 134 0 0 0 0 0 0 0, E D excu ri- on Envelope lossigain 2357 584r:1 ' 112 12 a) In h Oration b) Room ventilation 49 2051 0 0ccup ant s. p 23 Appliances 1200 U0 Less externo l load 0 0 InG Less transfer ,� Fled: abi t ion] 0 0 � 1 Subtotal 2067 115 Duct I oads 4948 951 43 -1 32 % % 11 % % Total room load Air ru cfm6076.1453 0 168 106 01 0 Ott cerfified by ACOA to meet all r u i reme- nts of Manual i 8t h Ed. rr� Ri ll -Suite Residential 6.0.0 103 -Vra 2105 -May -1 06A8 1fa t o u r nft t #F.IT I � Orientation Page 5 Right-.. Worksheet Entire House Job` UNIT W Date. May! 1$ 2005 By: G M Robeson 'I Roam name UTIL PWC7R 2 Exposed wall 13.0 ft 7.0 ft 3 C61ing height 8_� ft heatlood 8.0 ft heat/cool 4 Roo mdimen sices 4.0 x 9.0 ft 4.a x 7.0 ft 5 Roam area 36-0 ff 2$ _ 0 ##2 Ty Construction U -value HTM Area �� (�] LO Arm load number (BtuhJfF-'F) (Btuh Iff) or perimeter (ft) (Muh) or perimeter (ft) (duh) Hest cool Gross NIPIS Heat Cool Gross NIPfS Hest Cool 612G-0sw 0.09 r� � 6.92 1.23 32 32 221 39 0 0 0 D T---nG 1 D-C2oiw 0.570 n 43.32 18.61 D p 0 fl 0 0 0 0 11 DQ 0.390 n 29.64 7.21 0 0 0 D 0 D 0 D W 12C -%w 0.091 e 6-92 1,23 72 72 498 88 56 56 387 69 11 W 12G-0sw 0.091 se 6.92 1.23 0 f] 0 0 0 0 0 Q "IO-c2ow 0.570 se 43.32 53.33 ❑ 0 Q U 0 Q 0 0 0-09112C-OSW ❑_�1 s 6.92 1.23 0 0 0 0 0p 0 0 � �D2aw 0.570 s 43.32 33-17 a o 0 0 o a o 0 11 QO 0-390 s 29.64 7.21 d 0 p 00 0 0 0 w 12 G-0sw 0,091 Sw 6.92 1.23 Q D 0 D 0 D Q 0 1 G 1 d-c2aw 0,570 sw 43.32 53.33 D Q 0 0 Q Q Q p V11 12C-0sw 0.094 w E_92 1.23 fl d D D 0 0 0 0 C 16B-30ad 0.032 - 2_43 1.34 0 Q p Q 0 a Q Q F 19G-19CscP 0.049 - 1.29 0_24 36 13 45 9 28 r 36 7 B c) AES excursion 2 -1 Envelope loss/gain 766 934 423 74 12 a} Inff It-ation b) Room ventilation�0 �� 16�0 15 93�ntiemal gains: QGCuparlts @ 230 Q 0 Q D Less external load pPf�iances @ 12D0 a Q 0 p Less transfer � 0 0 fl R� 15tFT b€1fIOC1 � � 0. Q 14 Subtotal -1os2 -152 -583 -89 15 Duct loads 0 0 0 0 23°l0 53°/n 0 p 23% 53c/o 0 0 Total room load Air required (cfm) 01 0; 0 D Printout certified by RCCA to meet all requirements of Manual J 8#h fid. �- v�rr�C�hrtsC�� RigF#-Suite Residential 6.0.08 RSR44031 C:1[lacumentsand SetungslGuy RohertsonlM}r ClocurflentsWA.RKSiUE UNETA.rrp Cali= M.i8 Orientation 2005-May-1206�48:19 Page 6 Right ---j Worksheet Entire House Job: UNIT W Date: May 11, 2005 Robertson 1 Room n arae STRS LIVING R Ceiling height 8.0 ft � _ 4 Roo m d i men i 4.0 x 9-c ft 1.0 Rom area . 0 f 1_ 0 ff Ty Construdion LI -Value Or HTM Are n l bar(BtuhJfF2F)L M Load or rime r ) Btuh or Heat Cool Gross N/PIS Heat cool Gross N/P/S bleat cool 6 Ve 1 . 0.091 n 6.92 1.23 0 0 0.570 n 43 18.61 0 0 - 1100 -390 n 29.64 7.21 0' 0 0 11 W. 12C-0sw 69 1 112 2D 1 M91 s 6.92 1.23 0 0 0 0 96 62 425 76 0 ET1 D- 0.570 s 43-32 33.17 0 0 0 0 14 11 Do 0 585 448 1 21 622 152 12C -Nva 0. 1 6.92 1.23 0 0 0 1D -570 �. �.3 0 0 0 23 1 1 13 01 552 680 �1 B- 0.032. -- .x.43 1-34 0: 0 96 � 11.E 14 34 19 19C-119C-19CSCP 0.049 - 1.29 0.24 3 9 46 9 1 86 37 240 44 D excursion -1 104 Fn ele Imstga in 544 96 3967 2080 1 b) Room ventilation 205 19 836 0 0' 13 Inte ma I g a n Occupants (P 230 Appliances 1200 0 Less external load 0 Less transfer 0 0 0 Red ism but ion 0 14 Subtotal -750 -115 1171 181 15 Duct, i oad s 0 01 5975 234 23%-53% 23% % 1362 1235 local room loan{ A r ru i r3575] 0 0 2021261 Fri t ut certified �Y-ACCA to meet all requirements of Manual J 8th Ed'. i It -Suite Res ifi al B -G.08 RSR41031 A400.k CADoc unients and Settingsl uy Robert sonNy Dow mencs P I DE UNIT A.rrp Calc=mj8 Orientation 2005 -May -1206A819 Page