HomeMy WebLinkAboutCOMCHECK - 05-00142 - Madison Ridge Chiropractic - New Building0 5 0 Ol 4,0-)
Revised 6/8/()'-b-) NItalcl-
IS011 R, ge
C1 '11 1 ro
Mechanical ComPliance Certificate
2003 IECC
COMcheck E7 Software Version 3.4 Rel ease la
Data filem-une-. S:IDrawingsl2$0-Roderick1280.cek
Section 1: Proi e et Information
Project Naine: DR. RpDERICK
Designer/Contractor: JRW & ASSOCIATES
Document
Author --P
RICHARD
Section 2: General In formati o n
Building Locti (for weather data):
Climate Zone:
at i nor Degree r Days (base degrees F)-.
Cooling Degree Days (base 65 degrees F)-.
Pr i ect T
Section 3: Mechanical Systems e
OuantTW:
Z
nT)ti
Rexburg, Idaho
16
8693
143
New Construction
HVAC System L Heating: Central Fumace, Gas Cooling: Packaged T
n1nal Unit, Capacity 7000 Btulh.,
Air -Cooled CondenserSingle
HVAC System : Heating: Central Furnace Gas Cooling: Rooftop Packai t, Capacity >=90- <135
to/h,Air-Cooled Condenser Single Zone
Section 4 -*p Requirements Checklist
It
Dept.
Use
Requirements Specific To: HVAC Systern I
1. Equipment minimum efficiency:
l Packaged Tenninal DX Unit: Y 1.0 EER
[ ] � 2. Newly purchased coaling equipment mets the coaling eflciency requirements
i
� Requirements Specific To: HVAC System 2
[ ] + 1. Newly purchased heating equipment meets the heating efficiency requirements
[ J � 2. Equipment minimum efficiency:
�
Rooff op Package Unit: 10.1 EER
[ ] � 3 • Integrated air economizer required
Genetic u i n is : Must be met by all systems to which the requirement is applicable
f 1. Load calculations per 1997 ASHRAE Fundamentals
[ ] � 2. Plant equipment and system capacity no greater than needed to ineet loads
� - Exception: Standby equipment automatically of when primary system is aerating
f - Exception: Multiple units controlled to sequence operation as a function of load.
[ ] f 3. MInimuin one temperature control device per system
[ ] J 4. Minimum one humidity control devise per installed humidificationldehumidifcation system
[ ] J 5, Thermostatic controls has 5 deg. F deadband
� -Exception: Thermostats requiring manual changeover between heating and cooling
[ ] � 6. Automatic Controls: Setback to 53 dei. F (Meat) and 85 deg. F (C001); 7 -day clock,
� 2 -hour occupant override, 1 0 -hour backup
� -Exception: Continuously operating acnes
3 W Exception: 2 k'PV demand or less, submit calculations
[ ] � 7. Automatic shut-off damp ers on exhaust systems and supply systems with airflow >3,OOfl cin
[ � � S• Outside-air source for ventilation; systetn capable ofreducing SSA to required minimum
[ ] f }. R-5 supply and retum air duct insulation in unconditioned spaces
� R -S supply and return air duct insulation outside the building
j R-$ insulation between dints and the building exterior when ducts are part of building assembly
� - Exception: Ducts located within equipment
� - Exception: Ducts with interior and exterior temperature difFCrence not exceeding 15 deg. F.
[ ] [ 10. Ducts sealed - longitudinal sums on rigid ducts; transverse sew -ns an all ducts;
� UL 18 1 A or 18IB tapes and mastics
J -Exception: +ContinuousIy welded and licking -type longitudinal joints and seams on ducts
operating at static pressures less than 2 inches w.g. pressure classification
� ] � 11. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
[ ] � 12. Operation and maintenance manual provided to building; owner
[ ] � 13. Balancing devices provided in accordance with EMC G03. 15
[ ] j 14. Stair and elevator shaft vents are equipped with motorized dampers
Section 5: Compliance statement
The Proposed mechmucal design represented in this ocu t is consistent with the
other calculations submitted with this permit application. The proposed mechanical systems ha)w e been desicmed
the 2003 IECC requirements In C Mh`_Z Version 3.0 Release la and to Comply with the mandatory requirements in
the Requirements Checklist,
Principal Mechanical Designer -Name
itr
b
Date
Mechanical Requirements Descr01
iption
20+D3 IEC
C(]Mcheek-Ez Software Version 3.0 Release 1a
Data filenarne: S..\DraNvl'n.gs\280-Roden'ck\280.cck
the h1lowing list provides more detailed description of the requirements in Section, 4 of the Mechanical Compliance
Certificate.
Reqa firemen is Specific To: HVAC System I
I. The spedfledti and/or cooling equipment i coveredb .
t
inn efficiency.- Packaged Temiinal DX Unit: 11.0,EER
. ool r�equipment i cove Federal it i
can be assumed to meet or exceed ASHRAE 90.1 Code requirements dor equipment
Requ i semen ts S p i fie T: HVAC System .
I. The specified heating equipment is covered by Federal minimum efficiency fequirements.-
can be aSSUrned to meet or exceed ASHRAE 90.1 Code requi'renleilts for equipment eEciency. The specified heating and/or cooling e4quipment is coveredby .
HRAE 90.1 Code and must meet the Elowing
minimum efficiency: Roofop Package Unit: 10. 1 EER
3. An i4ntegrated air a onomizr is required r ind � ideal cooling systems ovcr 65 kBtu/h in the selected climate. Ali
integrated economizer allows simultaneous
operation of outdoor -air an.d meani.1 cooling.
Gen enc Requirements. Must be met by all systems to which the requirement is applicable
I. Design, heating and cooling loads for the building must be detemilned using procedures equivalent to those in
Chapters 27 and 28 of the ASH -RAE Handbook ofFundamentals or an approved equivalent calculation procedure.
2. All equipment and systems must be sized to be no greater than needed to meet calculated Loads. A singly piece of
equipment pmvidina bath heating and cooling must satisfy this provision for one function with the capaczty fDr the
other function as small as passible, within available equipment options_
- Exception: The equipment and/or system capacity may be greater than calculated loads fc)r standby purposes.
Standby equipment, must be automatically controlled to be offwhcn the primary equipment and/or system 'is operating.
- Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are
allowed if they ars provided with controls to sequence operation oftbe units as the load increases or decreases.
3. Each heating or cooling system serving a single gone must have its own temperature control device.
4. Each humidification system must have its awn humidity control device.
S. Thermostats controlling both heatina and cooling must be capable ofmaint�i�ling a S degree F deadband �a rangy of
temperature where no heating or cooling is provided).
- EXCeptlptl: Deadban.d capability ss nit required i f the thermostat dogs not ha�o-e automatic changeaver cap abiXity
between hating and cooling.
6. The system or zone control must be a programmable themiostat or other automatic control mefollowingting the
capable ofsetting back temperature to SS degree F during heating and setting up to $S degree F daring
coolingb) capable of automatically setting back or shutting down Systems dUfing Ur10CGupiEd hours using 7 d1fei'eilt
day schedulesc) have an accessible 2 -hour occupant vveirided} have a battery hack -up capable of maintaining
programmed settings for at last 10 hours without power.
- Exception: A setback or shutoff control is not required on theimastats that control systems serving areas that operate
continuously.
- Exception : A setback or shutafcontrol is not required on systerns with taut energy demand oft kW (6,$26 Btu/h)
or Tess.
T. outdoor -air supply systems with design ..rflow rates o f outdoor air
and all exhaust systems mut
d -n erg that are automatically while the equipment i. s not operating.
. The system mut -supple outside roti l tion air as required bar Chapter 4 of the Intemational MechaniM Code. If the
Velifflation systern 's designed to supply outdoor -air quantities exceeding minimum required levels, the system must
be capable of reducing outdoor -air ff ow to the minimum required levels.
9. Air ducts must be insulated to the foliowing leWels:a} supply and return air ducts for conditioned air located 'in
unconditioned spaces (spaces neither heated nor cooled) must be insulated With a minimum of R-5. Uncond'fioned
I. 1 1
spaces include attics, crawl spaces, unheated basements, and unheated orarkws.b) Supply and return air ducts and
Plenums must be insulated to a minimum of R-8 when located outside the building.c) When ducts are located within
exterior components (e.g., floors or roofs), minimum R-8 insulation is required only between the duct and the,
building exterior.
- Exception. Duct insulation is not required on ducts located within equipment.
- Exception: Duct 'insulation is not required when the design temperature d $erence between the interior and exterior of
the duct or plenum does not exceed 15 degree F.
10. All joints, longitudinal and transverse seams, and connections in ductwork must be securely sealed using weldments;
mechanical fasteners with seals, gaskets, or mastics, mesh and mastic sealing systems; or tapes. Tapes and mastics
must be listed and labeled in accordance with LTL 18 1 A or LTL 1$1B.
- Exception: Continuously welded and locking -type longitudinal Joints and seams on ducts operating at static
pressures less than 2 inches w. g. pressure classification.
11 Mechanical fistenm and seals, mastics, or gaskets must be used when connecting ducts to fans and other air
distribution equipment, including ncluding multiple -zone terminal units.
12. Operation and maintenance documentation must be provided to the owner that includes at least the following
infon-nation:a) equipment capacity (input and output) and required maintenmice actionsb) equipment operation and
D d.
maintenance manlialse HVAC system control maintenance and -calibration in�rmation, including wiring diagrw-ns,
Schematics., and control sequence descriptions, desired or field-deterrnined set points must be pen-naneutly recorded on
control drawings, at control devices, or, for digital control systems in programm'
ing commented) complete nanative
of how each system is intended to operate.
13. Each supply air outlet or difuser and each zone terminal device (such as VAV or mixing box) must have its own
balancing device. Acceptable balancing devises include adjustable dampers located within the ductwork, terminal
devices., and supply air diffisers..
14. Stai'r and elevator shaft vents must be equipped )ATI'th motorized dampers capable ofbeing automatically closed during
normal building operation and interlocked to open as required by Ere and smoke detection systems. All gravity
outdoor air supply and exhaust hoods, vents, and ventilators must be equipped with motorized dampers that will
automatically shut when the spaces served are not in use.
Exceptions:
- Gravity (non -tom t fi dampers are acceptable, in buildings less than three Stones in height above grade..
- Ventilation systems serving unconditioned spaces.
May--
L*Ighting Compliance Certificate
2001 IECC
COMcheck-F.7 Softw-are Version 2.4 ease
Data
2b
Data filename: Ulidtled
Section Ida? Pra,�ec� informa�ivn
Project Name:
DeSi9Wr/GDntMctor-
Docffwnt
Author:
Section 2: General Inforn ation
Building Use Description by.
Building T
Medical and Clinical C,arc
JRW cYz Assoc Madisoll Ridge (.'.hiro
New Office For Dar. Rodenck
Fayv.e Engineedng Inc.
Mike Pay -m
Mav 0
Whole Building I'Ve
IN
M'%. ;. a
4326.
Pr Dtscri pEian {chick one):
Constniction Audition Ait�ra�ionUncAUnconditioned SheZx (File Ai�daVit)
�ev�
Secti"on 3-6a Requ�rernen#s Checklist
Interior LlghfingO
Taal actual wets must be less than or equal to tote allowed watts
Allowed Watts Actual Watts Compfies(Y/N)
6922
6143
Exterior Lighting
2. Efficacy greater than 451unen51W
Exceptlnns:
YES
c
Specialized lighting highlighting features of historic tuildings; signage; safety or security lighting;
low-voltagc landscape fighting-
Controls,
Switching, and Wiring
3. ln&Tcndent cntrols for each spm (switchJoccupancy sensor).
Exception: Areas that must be continuously bighted.
4. Master switch at entry to hQtellmote1 guest roast.
S. Two sr"'tches or dimmer in each space to provide unffnrtrt light reductiolt capability.
Exceptions_
Only one lumninaire ire space; An or.cupar,t-senskng dice c�antrols the area;
The area is a carnidor, storage, restroom, or lobb�-; Arm that must be continuously lighted -
Areas greater than 2541 sq.ft.
6.. Photocell/astwnormcal finw switch an exterior lights.
M - M
Lighting Application Worksheet
2001 IECC
COMc-heck-EfZ Software Version 2.4 Release 2b
Section I *a Allowed Lighting Power Calculation
0
Mcdical and Clinical Care
Section 2.v Actual Lighting Power Calculation
M
Floor
c
Total
Allowed
Watts
U
4326 1.6
Allowed
Warts
(B x 0
6922
ion Allowed Wafts = 6922
A B C D E F
Fixture Future Description 1 Lamps/ # of Fixture
ID LAM P!Ion I Wattafac Per Lam 1 Ballast- Fixture Fixtures Watt,(DEl
F1 3 damp recesmd fluor. 1 48" T:9 32W / Elertrnnic 3 49 95 4655
F2 21amp over mirror fluor, 148" TS 32W / Electronic 2 3 bl 183
F4 Recessed shover light / 1TWAffidescent 73W 1 1 ?:5 ?S
FS 2 lamp open strip fluor. 148" TS 321 1 Electronic 2 7 61 427
F6 Dark mam light / Incandescent 1 St} W 1 2 150 300
F7 Bark raarn waming light 1 Incandescent 25W 1 1 25 25
F8 D=rdtive wall sconce /Triple 4 -pin 13W !Electronic 2 3 26 78
FIO R=ssed can light ! Incandcscent I oow 1 4
ToW Ac Watts = 6143
Sect*I
On 3: Compliance Calculation
If the Total Allowed Waits nU.�us the Total Actual Ff'aits ister 4M*% aar eq to zero,, tbuilding complies.
Lighting PASSES: Design I I °/abetter than code
TataF Allowed Watts = b922
TOtal Act watts = 6143
Project Compliance = 779
P_03
May -04-05 08:44A
Exceptions: Areasrequinng lighting during daylight
Tan&^m wird one -lamp and #hum.-Jamp ballasted lun
P,`xceptiorrs:
Electronic
hours
rte,
high -frequency ballasts; Lvminaires tkot on same switch
Sntion 4: Compiiance Statement
The proposed lighting design reptmnt+ed in this document is consistent with Ede building plans, specifications and
other calctilatians sutsrnitted w�t-h this pert application. The proposW lighting system has been designed to meet
the 2001 ECC rqut'remen#s in COMcbeck-.EZ Version 2.4 Release 2b and to cIDmp�► with the �naz�datory
requirements in the Requirements Checklisti,
SE
9
igner--Nanie
P-02
0500142
JRW c�c Assoc Madison'RI"dge CJuro
Envelope Compliance Certificate
2001 IECC
CQiVlcheck-EZ Software Version 3.0 Release 2
Data filename: C:1Prograzn Fz1eslCheckICQMcheck-EZl280.cck
Section 1: Project Information
Project Nam
e.-
Designer/Contractor:
Document Author:
DR. RODERICK
JRW &ASSOCIATES
RICHARD
Section 2: General Information
Building cat n (fir weather data):
Cli•
t Zone:
Heating Degree Days (base 65 degrees F}:
Coaling Degree Days (base 65 degrees F)-,
Project Type:
Window / Wall Ratio. -
N .4
-dW
Medical and Clinical Care
Seection 3: Requirements Checklist
Rexburg, Idaho
15
8693
143
New Construction
x.31
4712
Air Leakage, Component Certificatioirt, and Vapor Retarder Requ-
irements
ed By/Date
I.
All points and penetrations are caulked, gasketed., weather-stripped, or othezwise sealed.
2. Windows, doors, and skylights certified as meeting leakage requirements.
3. Component R -values & U -Tars labeled as certified.
Climate -Specific Requirements
Na.e4.;rtj n
Roof 1: All -Wood Joist/ Rater/T rus S
WEST ELEVATION: Wood Frame, Any S,paclng
W indow 1:
Meth Frame with Thermal $reak:Double Pare with Lew -E
Other, SHGC 0.87
EAST ELEVATION: Woad Frame, Any Spacing
Window 2:
Metal Frame with Thffrnal Break. -Double Pane with Low -E
Tinted., SHGC 0.58
NORT11 ELEVATION: Wood Frame, Any Spacing
Window 3;
Metal Frame with 'Thermal Break:Double Pane with Low_E
Cher, SHGC 0.59
Window 4.-
Metal
Frame with Thermal Break -.Double Pane with Low -E
Other, SHGC 0.59, PF 0.68
SOUTH WALL: Woad Frame, Any Spacing
Window 5:
Metal Frame with Thermal Break:Dauble Pane with Low -E
Tinted, SHGC 0.58, PF Q.68
EAST DOOR.- Glass, Other, SHGC 0,59, PF 4.68
SOUTH DOOR: Glass, Tinted, SHGC 4.59, PF 4.68
Basement Wall 1: Solid Concrete or Masonry > g',
Furring: Wood, Wall Ht 1 Q.4, depth B.G. 9.6
Floor 1: All -Wood Joist/Truss
Gross
Area or Cavity Cont&
Proposed Budget
Perimeter R -V R -Value U -Fox jL-Factor
3133
38.0
0.0
0.028
0.047
627
19.0
0.0
0.068
0.067
1 --- --- 0.330 0.520
627 19.-0 . . 067
288 --- --- 0.330 0.520
704 19.0 U.0 0.08 0.067
96 --- -- 0.330 0.520
704 19.0 0.0 0.068 0.067
95 --- --- 0.330 0.520
21 --- --- 0.420 0.520
32 --- --- 0.920 4.524
1680
15.0
0.0
0.093
0.041
3133
38,0
0.0
0. 027'
0.040
(a) Budget -factors are used for softwarelig.e calcul ti .
requirernents.
� ve 1 ode FAS S ES: Design 17% bitter than code
Section 46* Compliance, Statement
The proposed envelope design representedin this document is consistent with the building glans, specifcations and other
calculations submitted with this permit application. The proposed envelope system has beerx designed to meet the 2401
IE C, Chapter 8,requirements in CQMcheck-EZ Version 3.0 Release 2 and to campy with the mandatory requirements
.in the Requirements Checklist,,
PhYcipal Envelope Designer -Name
Si
RM