Loading...
HomeMy WebLinkAboutCOMCHECK - 05-00142 - Madison Ridge Chiropractic - New Building0 5 0 Ol 4,0-) Revised 6/8/()'-b-) NItalcl- IS011 R, ge C1 '11 1 ro Mechanical ComPliance Certificate 2003 IECC COMcheck E7 Software Version 3.4 Rel ease la Data filem-une-. S:IDrawingsl2$0-Roderick1280.cek Section 1: Proi e et Information Project Naine: DR. RpDERICK Designer/Contractor: JRW & ASSOCIATES Document Author --P RICHARD Section 2: General In formati o n Building Locti (for weather data): Climate Zone: at i nor Degree r Days (base degrees F)-. Cooling Degree Days (base 65 degrees F)-. Pr i ect T Section 3: Mechanical Systems e OuantTW: Z nT)ti Rexburg, Idaho 16 8693 143 New Construction HVAC System L Heating: Central Fumace, Gas Cooling: Packaged T n1nal Unit, Capacity 7000 Btulh., Air -Cooled CondenserSingle HVAC System : Heating: Central Furnace Gas Cooling: Rooftop Packai t, Capacity >=90- <135 to/h,Air-Cooled Condenser Single Zone Section 4 -*p Requirements Checklist It Dept. Use Requirements Specific To: HVAC Systern I 1. Equipment minimum efficiency: l Packaged Tenninal DX Unit: Y 1.0 EER [ ] � 2. Newly purchased coaling equipment mets the coaling eflciency requirements i � Requirements Specific To: HVAC System 2 [ ] + 1. Newly purchased heating equipment meets the heating efficiency requirements [ J � 2. Equipment minimum efficiency: � Rooff op Package Unit: 10.1 EER [ ] � 3 • Integrated air economizer required Genetic u i n is : Must be met by all systems to which the requirement is applicable f 1. Load calculations per 1997 ASHRAE Fundamentals [ ] � 2. Plant equipment and system capacity no greater than needed to ineet loads � - Exception: Standby equipment automatically of when primary system is aerating f - Exception: Multiple units controlled to sequence operation as a function of load. [ ] f 3. MInimuin one temperature control device per system [ ] J 4. Minimum one humidity control devise per installed humidificationldehumidifcation system [ ] J 5, Thermostatic controls has 5 deg. F deadband � -Exception: Thermostats requiring manual changeover between heating and cooling [ ] � 6. Automatic Controls: Setback to 53 dei. F (Meat) and 85 deg. F (C001); 7 -day clock, � 2 -hour occupant override, 1 0 -hour backup � -Exception: Continuously operating acnes 3 W Exception: 2 k'PV demand or less, submit calculations [ ] � 7. Automatic shut-off damp ers on exhaust systems and supply systems with airflow >3,OOfl cin [ � � S• Outside-air source for ventilation; systetn capable ofreducing SSA to required minimum [ ] f }. R-5 supply and retum air duct insulation in unconditioned spaces � R -S supply and return air duct insulation outside the building j R-$ insulation between dints and the building exterior when ducts are part of building assembly � - Exception: Ducts located within equipment � - Exception: Ducts with interior and exterior temperature difFCrence not exceeding 15 deg. F. [ ] [ 10. Ducts sealed - longitudinal sums on rigid ducts; transverse sew -ns an all ducts; � UL 18 1 A or 18IB tapes and mastics J -Exception: +ContinuousIy welded and licking -type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g. pressure classification � ] � 11. Mechanical fasteners and sealants used to connect ducts and air distribution equipment [ ] � 12. Operation and maintenance manual provided to building; owner [ ] � 13. Balancing devices provided in accordance with EMC G03. 15 [ ] j 14. Stair and elevator shaft vents are equipped with motorized dampers Section 5: Compliance statement The Proposed mechmucal design represented in this ocu t is consistent with the other calculations submitted with this permit application. The proposed mechanical systems ha)w e been desicmed the 2003 IECC requirements In C Mh`_Z Version 3.0 Release la and to Comply with the mandatory requirements in the Requirements Checklist, Principal Mechanical Designer -Name itr b Date Mechanical Requirements Descr01 iption 20+D3 IEC C(]Mcheek-Ez Software Version 3.0 Release 1a Data filenarne: S..\DraNvl'n.gs\280-Roden'ck\280.cck the h1lowing list provides more detailed description of the requirements in Section, 4 of the Mechanical Compliance Certificate. Reqa firemen is Specific To: HVAC System I I. The spedfledti and/or cooling equipment i coveredb . t inn efficiency.- Packaged Temiinal DX Unit: 11.0,EER . ool r�equipment i cove Federal it i can be assumed to meet or exceed ASHRAE 90.1 Code requirements dor equipment Requ i semen ts S p i fie T: HVAC System . I. The specified heating equipment is covered by Federal minimum efficiency fequirements.- can be aSSUrned to meet or exceed ASHRAE 90.1 Code requi'renleilts for equipment eEciency. The specified heating and/or cooling e4quipment is coveredby . HRAE 90.1 Code and must meet the Elowing minimum efficiency: Roofop Package Unit: 10. 1 EER 3. An i4ntegrated air a onomizr is required r ind � ideal cooling systems ovcr 65 kBtu/h in the selected climate. Ali integrated economizer allows simultaneous operation of outdoor -air an.d meani.1 cooling. Gen enc Requirements. Must be met by all systems to which the requirement is applicable I. Design, heating and cooling loads for the building must be detemilned using procedures equivalent to those in Chapters 27 and 28 of the ASH -RAE Handbook ofFundamentals or an approved equivalent calculation procedure. 2. All equipment and systems must be sized to be no greater than needed to meet calculated Loads. A singly piece of equipment pmvidina bath heating and cooling must satisfy this provision for one function with the capaczty fDr the other function as small as passible, within available equipment options_ - Exception: The equipment and/or system capacity may be greater than calculated loads fc)r standby purposes. Standby equipment, must be automatically controlled to be offwhcn the primary equipment and/or system 'is operating. - Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are allowed if they ars provided with controls to sequence operation oftbe units as the load increases or decreases. 3. Each heating or cooling system serving a single gone must have its own temperature control device. 4. Each humidification system must have its awn humidity control device. S. Thermostats controlling both heatina and cooling must be capable ofmaint�i�ling a S degree F deadband �a rangy of temperature where no heating or cooling is provided). - EXCeptlptl: Deadban.d capability ss nit required i f the thermostat dogs not ha�o-e automatic changeaver cap abiXity between hating and cooling. 6. The system or zone control must be a programmable themiostat or other automatic control mefollowingting the capable ofsetting back temperature to SS degree F during heating and setting up to $S degree F daring coolingb) capable of automatically setting back or shutting down Systems dUfing Ur10CGupiEd hours using 7 d1fei'eilt day schedulesc) have an accessible 2 -hour occupant vveirided} have a battery hack -up capable of maintaining programmed settings for at last 10 hours without power. - Exception: A setback or shutoff control is not required on theimastats that control systems serving areas that operate continuously. - Exception : A setback or shutafcontrol is not required on systerns with taut energy demand oft kW (6,$26 Btu/h) or Tess. T. outdoor -air supply systems with design ..rflow rates o f outdoor air and all exhaust systems mut d -n erg that are automatically while the equipment i. s not operating. . The system mut -supple outside roti l tion air as required bar Chapter 4 of the Intemational MechaniM Code. If the Velifflation systern 's designed to supply outdoor -air quantities exceeding minimum required levels, the system must be capable of reducing outdoor -air ff ow to the minimum required levels. 9. Air ducts must be insulated to the foliowing leWels:a} supply and return air ducts for conditioned air located 'in unconditioned spaces (spaces neither heated nor cooled) must be insulated With a minimum of R-5. Uncond'fioned I. 1 1 spaces include attics, crawl spaces, unheated basements, and unheated orarkws.b) Supply and return air ducts and Plenums must be insulated to a minimum of R-8 when located outside the building.c) When ducts are located within exterior components (e.g., floors or roofs), minimum R-8 insulation is required only between the duct and the, building exterior. - Exception. Duct insulation is not required on ducts located within equipment. - Exception: Duct 'insulation is not required when the design temperature d $erence between the interior and exterior of the duct or plenum does not exceed 15 degree F. 10. All joints, longitudinal and transverse seams, and connections in ductwork must be securely sealed using weldments; mechanical fasteners with seals, gaskets, or mastics, mesh and mastic sealing systems; or tapes. Tapes and mastics must be listed and labeled in accordance with LTL 18 1 A or LTL 1$1B. - Exception: Continuously welded and locking -type longitudinal Joints and seams on ducts operating at static pressures less than 2 inches w. g. pressure classification. 11 Mechanical fistenm and seals, mastics, or gaskets must be used when connecting ducts to fans and other air distribution equipment, including ncluding multiple -zone terminal units. 12. Operation and maintenance documentation must be provided to the owner that includes at least the following infon-nation:a) equipment capacity (input and output) and required maintenmice actionsb) equipment operation and D d. maintenance manlialse HVAC system control maintenance and -calibration in�rmation, including wiring diagrw-ns, Schematics., and control sequence descriptions, desired or field-deterrnined set points must be pen-naneutly recorded on control drawings, at control devices, or, for digital control systems in programm' ing commented) complete nanative of how each system is intended to operate. 13. Each supply air outlet or difuser and each zone terminal device (such as VAV or mixing box) must have its own balancing device. Acceptable balancing devises include adjustable dampers located within the ductwork, terminal devices., and supply air diffisers.. 14. Stai'r and elevator shaft vents must be equipped )ATI'th motorized dampers capable ofbeing automatically closed during normal building operation and interlocked to open as required by Ere and smoke detection systems. All gravity outdoor air supply and exhaust hoods, vents, and ventilators must be equipped with motorized dampers that will automatically shut when the spaces served are not in use. Exceptions: - Gravity (non -tom t fi dampers are acceptable, in buildings less than three Stones in height above grade.. - Ventilation systems serving unconditioned spaces. May-- L*Ighting Compliance Certificate 2001 IECC COMcheck-F.7 Softw-are Version 2.4 ease Data 2b Data filename: Ulidtled Section Ida? Pra,�ec� informa�ivn Project Name: DeSi9Wr/GDntMctor- Docffwnt Author: Section 2: General Inforn ation Building Use Description by. Building T Medical and Clinical C,arc JRW cYz Assoc Madisoll Ridge (.'.hiro New Office For Dar. Rodenck Fayv.e Engineedng Inc. Mike Pay -m Mav 0 Whole Building I'Ve IN M'%. ;. a 4326. Pr Dtscri pEian {chick one): Constniction Audition Ait�ra�ionUncAUnconditioned SheZx (File Ai�daVit) �ev� Secti"on 3-6a Requ�rernen#s Checklist Interior LlghfingO Taal actual wets must be less than or equal to tote allowed watts Allowed Watts Actual Watts Compfies(Y/N) 6922 6143 Exterior Lighting 2. Efficacy greater than 451unen51W Exceptlnns: YES c Specialized lighting highlighting features of historic tuildings; signage; safety or security lighting; low-voltagc landscape fighting- Controls, Switching, and Wiring 3. ln&Tcndent cntrols for each spm (switchJoccupancy sensor). Exception: Areas that must be continuously bighted. 4. Master switch at entry to hQtellmote1 guest roast. S. Two sr"'tches or dimmer in each space to provide unffnrtrt light reductiolt capability. Exceptions_ Only one lumninaire ire space; An or.cupar,t-senskng dice c�antrols the area; The area is a carnidor, storage, restroom, or lobb�-; Arm that must be continuously lighted - Areas greater than 2541 sq.ft. 6.. Photocell/astwnormcal finw switch an exterior lights. M - M Lighting Application Worksheet 2001 IECC COMc-heck-EfZ Software Version 2.4 Release 2b Section I *a Allowed Lighting Power Calculation 0 Mcdical and Clinical Care Section 2.v Actual Lighting Power Calculation M Floor c Total Allowed Watts U 4326 1.6 Allowed Warts (B x 0 6922 ion Allowed Wafts = 6922 A B C D E F Fixture Future Description 1 Lamps/ # of Fixture ID LAM P!Ion I Wattafac Per Lam 1 Ballast- Fixture Fixtures Watt,(DEl F1 3 damp recesmd fluor. 1 48" T:9 32W / Elertrnnic 3 49 95 4655 F2 21amp over mirror fluor, 148" TS 32W / Electronic 2 3 bl 183 F4 Recessed shover light / 1TWAffidescent 73W 1 1 ?:5 ?S FS 2 lamp open strip fluor. 148" TS 321 1 Electronic 2 7 61 427 F6 Dark mam light / Incandescent 1 St} W 1 2 150 300 F7 Bark raarn waming light 1 Incandescent 25W 1 1 25 25 F8 D=rdtive wall sconce /Triple 4 -pin 13W !Electronic 2 3 26 78 FIO R=ssed can light ! Incandcscent I oow 1 4 ToW Ac Watts = 6143 Sect*I On 3: Compliance Calculation If the Total Allowed Waits nU.�us the Total Actual Ff'aits ister 4M*% aar eq to zero,, tbuilding complies. Lighting PASSES: Design I I °/abetter than code TataF Allowed Watts = b922 TOtal Act watts = 6143 Project Compliance = 779 P_03 May -04-05 08:44A Exceptions: Areasrequinng lighting during daylight Tan&^m wird one -lamp and #hum.-Jamp ballasted lun P,`xceptiorrs: Electronic hours rte, high -frequency ballasts; Lvminaires tkot on same switch Sntion 4: Compiiance Statement The proposed lighting design reptmnt+ed in this document is consistent with Ede building plans, specifications and other calctilatians sutsrnitted w�t-h this pert application. The proposW lighting system has been designed to meet the 2001 ECC rqut'remen#s in COMcbeck-.EZ Version 2.4 Release 2b and to cIDmp�► with the �naz�datory requirements in the Requirements Checklisti, SE 9 igner--Nanie P-02 0500142 JRW c�c Assoc Madison'RI"dge CJuro Envelope Compliance Certificate 2001 IECC CQiVlcheck-EZ Software Version 3.0 Release 2 Data filename: C:1Prograzn Fz1eslCheckICQMcheck-EZl280.cck Section 1: Project Information Project Nam e.- Designer/Contractor: Document Author: DR. RODERICK JRW &ASSOCIATES RICHARD Section 2: General Information Building cat n (fir weather data): Cli• t Zone: Heating Degree Days (base 65 degrees F}: Coaling Degree Days (base 65 degrees F)-, Project Type: Window / Wall Ratio. - N .4 -dW Medical and Clinical Care Seection 3: Requirements Checklist Rexburg, Idaho 15 8693 143 New Construction x.31 4712 Air Leakage, Component Certificatioirt, and Vapor Retarder Requ- irements ed By/Date I. All points and penetrations are caulked, gasketed., weather-stripped, or othezwise sealed. 2. Windows, doors, and skylights certified as meeting leakage requirements. 3. Component R -values & U -Tars labeled as certified. Climate -Specific Requirements Na.e4.;rtj n Roof 1: All -Wood Joist/ Rater/T rus S WEST ELEVATION: Wood Frame, Any S,paclng W indow 1: Meth Frame with Thermal $reak:Double Pare with Lew -E Other, SHGC 0.87 EAST ELEVATION: Woad Frame, Any Spacing Window 2: Metal Frame with Thffrnal Break. -Double Pane with Low -E Tinted., SHGC 0.58 NORT11 ELEVATION: Wood Frame, Any Spacing Window 3; Metal Frame with 'Thermal Break:Double Pane with Low_E Cher, SHGC 0.59 Window 4.- Metal Frame with Thermal Break -.Double Pane with Low -E Other, SHGC 0.59, PF 0.68 SOUTH WALL: Woad Frame, Any Spacing Window 5: Metal Frame with Thermal Break:Dauble Pane with Low -E Tinted, SHGC 0.58, PF Q.68 EAST DOOR.- Glass, Other, SHGC 0,59, PF 4.68 SOUTH DOOR: Glass, Tinted, SHGC 4.59, PF 4.68 Basement Wall 1: Solid Concrete or Masonry > g', Furring: Wood, Wall Ht 1 Q.4, depth B.G. 9.6 Floor 1: All -Wood Joist/Truss Gross Area or Cavity Cont& Proposed Budget Perimeter R -V R -Value U -Fox jL-Factor 3133 38.0 0.0 0.028 0.047 627 19.0 0.0 0.068 0.067 1 --- --- 0.330 0.520 627 19.-0 . . 067 288 --- --- 0.330 0.520 704 19.0 U.0 0.08 0.067 96 --- -- 0.330 0.520 704 19.0 0.0 0.068 0.067 95 --- --- 0.330 0.520 21 --- --- 0.420 0.520 32 --- --- 0.920 4.524 1680 15.0 0.0 0.093 0.041 3133 38,0 0.0 0. 027' 0.040 (a) Budget -factors are used for softwarelig.e calcul ti . requirernents. � ve 1 ode FAS S ES: Design 17% bitter than code Section 46* Compliance, Statement The proposed envelope design representedin this document is consistent with the building glans, specifcations and other calculations submitted with this permit application. The proposed envelope system has beerx designed to meet the 2401 IE C, Chapter 8,requirements in CQMcheck-EZ Version 3.0 Release 2 and to campy with the mandatory requirements .in the Requirements Checklist,, PhYcipal Envelope Designer -Name Si RM