Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
PROJECT SUMMARY - 05-00139 - 578 Golden Willow Dr - New SFR
Mike Wood Heating Cooling Project summary Entire House Job: #1 Date: May 04, 2005 B: Mike Wood For: Ryan Durfee Rexburg, ID. 83448 Phone: 313-0228 Notes.- spec home 1 i! Durfee SFR - 1180 Arctic'Willow Weather.- Winter Design Conditions outside db -6 OF Inside db 72 OF Design TD 78 OF Heating Summary Structure Ducts Central gent (76 cfm) Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces Idaho Falls, ID, US Summer Design Conditions Outside db 89 ° F Inside db 75 °F Design T❑ 14 OF Daily range H cfm/Btuh Relative Humidity 50 p/o Moisture difference -31 gr/lb Sensible Cooling Equipment Load Sizing 40496 Btuh Structure 13120 Btuh 14354 cfm Ducts 9923 Btuh 5453 Btuh Central vent (76 cfm) 979 Btuh 0 Btuh Blower [J Btuh 0 Btuh 60303 Btuh Use manufacturer's data n Rate/swing multiplier 0,94 Equipment sensible load 225$4 Btuh Area (ft2) Heti n 298-6 Volume (W) 23888 Air changes/hour 0.32 Equiv. AVF ( 127 Simplified Average a Cvaiin 2989 23888 Q_1fi 64 Heating Equipment Summary Make AmStd Trade Freedom 90 Single Stage Madel AL#X080C342Q* Efficiency 92.1 AFUE Heating input 80000 Btuh Heating output 75000 Btuh Temperature rise 74 -OF Actual air flow 1095 cfm Air flaw factor 0.020 cfm/Btuh Static pressure 0.00 in H20 Spare thermostat Latent Cooling Equipment Load Sizing Structure Ducts Centrad vend (76 cfm) Equipment latent load -1140 Btuh -285 Btuh -1360 Btuh o Stun Equipment total load 22580 Btuh Req. total capacity at 0.74 SHR 2.7 ton Cooling Equipment Summary Make Trade Cond C0,11 Efficiency Sensible cooling Latent cooling Total cooling Actual air flaw Air flow factor Static pressure Load sensible heat ratio Printout certified by ACCA to meet all requirements of Manual J 8th Ed. ,• VVr-1 t lila-Suite Residential 6.0.02 RSR40535 P roje t . rrp )c = MA Orientation 0 EER 0 Btuh o Btuh 0 Btuh 1095 cfm 0.048 cfm/Btuh 0.00 in H2O 1.00 2005 -May -04 20.-5125 Page 1 Mike Wood Hewing &Cooling AED Assessment Entire House. Job: #1 Date; May 04, 2005 BY: Mice Wood For: Ryan Durfee Rexburg, ID. 83448 Phone: 313-228 Location: Idaho Falls, ID, US Elevation: 4741 ft latitude: 44°Af outdoor: Dry bulb .(°F) Daily range (°F) Vliet bulb (°F) Wind speed (mph) Heating -6 15.0 Cooling 89 34 60 7.5 Indoor: Indoor temperature (°F) Design TD (T) Relative humidity (°/a) Moisture difference (gr/lb) Infiltration: H) Method Construction quality Fireplaces Heating 72 78 50 66. 1 Simplified Average 0 Cooling 75 14 50 W31.5 ll pal 12.0( 11.00 1030C 9.oc 830C 7,00 6,00 5.00 4.00 3100 2100 1,00 Hourly Glazing Load oe Hourty IV i r -12 13 14 15 16 17 18 19 20 Hour of Day Average ED limit Maximum hourly glazing load exceeds average by 28.4°l0. House has adequate exposure diversify (AED), based on AED limit of 30%. AED excursion: d Btuh Vviri0htsc> Right -Suite Residential 6.0,02 RSR40535 Proj _up Calc = Mia orientation 2005 -May -0 20:51:25 piagc 1 Mi. ke WDed Heating & Cud] rig R ght-,.., Norksheet Job: #1 Entire use Date: May 04, 2005 Bs Mike Wood 1 Room name Entire House garage Exposed wall 376.4 ft 92.0 ft Ceiling height 8.5 ft d 10.0 u n ndit.. 4 Froom dimer ion 24.0 x 39-o ft Room area 3922.0 ft2 916.07- TY Construction U -value Or HTIV1 Area (W) Load number (Btuh/f Z -'F Btu 2 or perimeter () Btuh) or perimeter (ft) (Etuh H eat cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 128-Obw 0.097 n T57. 0.46 742 532 2663 160 390 180 0 L -D 11FO O2801 n 21 -a4 5-18 210 210 0 0 210. 210 0 0 T --G 12B-,Dbw 0.097 ne 7-57 0.46 34 28 214 13 0 0 0 0 2A- ov 0.550 ne 42- .74 6 0 243 254 0 0 0 0 11W 1 B -o bw 0.097 e 7-57, 0.46 832 759 3927 237 240 240 0 0 2A-2o2A-2ov 0.550 a 42,90 64-78' 52 0 2231 3369 0 11 FO 0.28 21.84 5.18 21 21 459 109 0 0 0 12B- 0.097 se 7.57 0.4 34 25 189 11 0 0 0 0 .2 - ov 0.550 se 42.90 57-09 0 386 514 0 0 0 0 W. +1 B -O b ` OM7 s 7.57 0.46 674 650 4540 274 50 L -G 2A-2ov 0.550 s 4M 3.x.14 24 W. 12B-Obw 0.097 046 880 755 4139 E:D 2A -2o 0-550 w 42.90 64.7 8 , 104 0 3089 4664 11 FO 0.280 w 21.84 5-18 21 1 459 109 0 0 0 0 P 12C-Osw 0.091 - 7.10 0.33 272. 272 1931 89 0 0 0 0 1 13 a OM -2 - 1.72 0.92 2452 2452 2.601 1401 936 936 F 21 A -20t 0.027 - 211 0.00 2462 253 X214 0 936 92 0 0 ED excursion Envelope loss/gait 1 1 1 2295 0 1 a Infiltration 9184 824 0 0 b) Room ventifation 0 0 13 Int mal gains- Occupants 230 0 _ 0 0 Appliances g 1200 01 01 01 0 u Less extemal load 0 Less transfer 0 F i-zitn butt D -0 0 14 u btot) 40496 13120 15 but Ind .� .� � 76% 14354 9923' 92 0% 0 %0 Total room load 54850 23043 Air r u red ofm) 1 1095 0 Printout certified by ACOA to meet all requirements of Manual J 8th Y Project . rrp a I c = IIII'.� rlent tlor = - - :2 Page I M I ke Wood Heating Cool I rig Right-,, Worksheet Job: #1 Entire House Date` May 04, 2005 B: Mike Wood 1 Room name m ech Expos wall . Ceiling height Froom dr'r an ion .0 x 10.0 ft 9.0 5 Room area 70-0 ft2 90.0 ft2 Ty Construction LI -value Or HTM Arent r _ Loyd Area (f Load number Btuh� F (E to h/ ) or penmeter Bh or perimeter (ft) Btuh) Heat Cool Gross N/PP Heat Cool Gross N/P/S Heat CSI 1 B -O 0.0 n T57 0.46 80 80 605 36 0 0 -L-D11 F0 0.280 n 21.84 5.18 0 0 0 0 0 T ---G2A-2ov 0.550 ne 42-90 44-74 0 0 0 0 0 0, 0 01 12B-Obw U97 ne 7-57 0.46 0 0, 0 0 0 0 0 11 1 B-ob 0.007 e 7.57 0-46 56 56. 424 26 72 721 545 2A -2o 0.550 e 4Z90 64.78 01 0 0 0 0, 0 0 0 11 FO 0.280 a 21.8 5.18 0 0 0 0 0 0 1 B 0 0.007 'e -7 0.46 0 0 0 0 0 0 0 T—G 2A- ov 0.550 se 42.0 57.09 0 0 0 0 0 0 0 0 W, +1 -0 bar O,097 s 7-57 0,46 0 0 0 0 0 0 0 L—G 2A-2ov 0.550 S 42.90 35.14 0 ID 0 0 0 0 0 0 12B-obw 0.097 w 7-5 0.40 0 0 0 0 0 0 0 E64-78, 0 0 0 0 0 0 0 0 0 +11F 0.200 w 2184 5.18 0, 0 0 0 0 0 0 0 P 12C-Osw 0.001 - 7.10 0.33 0 0 0 0 0 0. 0 1 Bad 0.02 1.72 0-92 0 0 0I D; 0 0 0 0 F 1►. -0t 0.027 - 2.11 0.00 70 17 147 0 00 100 0 ED er-i Envelope Ic ain 1 1 1 ) Infiltration b) Room ventilation 549 49 2911 26 0 0 13 Inte al gains: Occupants Q 230 D 0 ppfiances 1200 0 0 Less extern a l load 0 Less transfer 0 I 0 0 0 0 r1��n��tir� -1 � -0 �1 Subtotal 1015 15 Duct loads 0 0 2040 0 0 % % ' 723 75 Total room load Airequires cfm 0" 0' 2763 17 0 0 55 8 Printout certified by ACOA to asst all r u i r a nt f Manual VVr-j -tRight-Suite Right—SuiteResidential 0,0.02 RSR40535 ProjectZrrp Calc = lVj8 Orientation = W . 005- Ma -04 20-51:2 Fuge Mike Wood Heating & C-Dali rig Rightm.. iVrs Job: #1 Emire House Date: , Br Miked 21 Room name bed Exposed wal I �11. 27.0ft ilTrig h igbt . 1t h:a cmJ _0 ft heat/cool Room area 154,0 ft2 182.0 T TY Construction U- aloe Or HTIVI Area (2 re ft Load A number (B.tuF�/� �' -°F� ���ft2�ir� �r ter � � LO�� Heat Cool Gross /PIS Heat Cool Gross N/PIS IS ` Heat Cool 0W. 12B-obw 0.097 n 7.57 GA6. 0 0 0 - L—D. 1 1 FO 0.280 n 21.04 5_18 0 0 0 0 0 0 0 0. T__6 12B-Obw 0.097 ne 7.57 0.46 0 0 0 0 0 0 0 0 2A- oar 0.550 ne 42-90 44-74 0 0 0 0 0 0 0 0 11 LG 1 -O b 0.007 e T57 0,46 88 72 545 33 104 104 787 47 2A- ov 0.550 a 42.90 64.78 16. 0 686 1037 0 0 0 0 11F0 0.280 e 21_84 5-18 0 0 0 0 0 0 0 0 VIV 12B-Obw 0,097 se 7.57 0.40 0 0 0 0 0 0 0.550 se 42.90 57.09 0 0 0 0 0 0 0 0 VIV L—G 1 -o b � 097 s 7_ 0-46 0 0 0 0 11 0. 726 44 2A-2ov 0.550 1213-0bw 0.097 w 7.57 0.40 0 0 0 0 0 0 0 2A-2ov 0.550 w 42.190 04.78 0 0. 0 0 0 0 0 0 11FO 0280 w 21.84 5.1.E 0 0 0 0 0 0 0 0 P 12C-Osw 0.001 r 7,10 0-33 0 0 01 0 0 0 0 0 10Bad 0,022 - 1.72 0.92 0 0 0 0 0 0 0 0 F 21A -20t 0.027 - 2.11 0.00 1541 11 324 0 182 27 383 0 :ED excursion Envelope Iossigair 15 00 2583 040 12 a Infiftration 355. Room ventilation 872 7 0 0 0 0 13 Internal gal res_ Oocupants (P 230 0 0 AppliancesQ �1 X00 0 � 0 Lesst rrr�� load � 0 Less transfer 0 0 0 0 Ilitrlbutrn 0 0 0 0 14 Subtotaj 00 0 49 0 15 Duct loads 2000 1000 3.03 724 1 242 548 Tot) room load Air required (.fm) 0 1�' '1 4745 1272 54 84 95 00 Printout certified by ACOA t0 meet all requirements xfvrl hits<D Right -Suite Residential 6.0.02 ,ra= -� 2005-May-04 20--51-25 Page MIke Wood Hpat Ing & Cmtin-9 Right=*., Worksheet Job: #1 Entire House Date. May 04, 2005 : Mike o d 1 Froom name Exposed wall beth bed rrrm. Ceiling height 10.0 ft ft, 2&0 ft 4 Flom dimans on _0 heat/cool 8_0 ft heat/cool Room a x'0.0 .0 f�2 10..0 1 . 0 x 14.0 ft 196-0� ft Ty Construction U -value Or HTM area (2) Load Area Load number(Btu hJf 2 -'DF (BtuF t2) or perimeter () (13tuh) orpe meter(ft) (Btuh Heat Cool Gross N/P/S Heat Cool rosy N/P/S Heat Cool 1213-0bw L11F 0.097 n 7.57 0.46 0 0 - 0.280 n 21.8 5.18 0 0 0 .0 0 0 0 0 1 -Ob T 0.097 rye 7.57 O.46 0 0 0 0 0 -G 2A-2ov 0.550 ne 42.90 44,74 0. 0 a 0 0 0 0 0 1 213 -ober 0.097 7.57 0.46 0 0 0 0. 0 0 2A-2ov 0.550 e 42M 64-78 0 0 0 1 1 F 12B-obw 0.280 e 0.097 se 21�84 7_57 5�18 0-46 0 0 0 0 0 0 L --G ov 0.55 0 0. 0 0 0 vhv 12B -obi' 0.097 s 7.57 0.46 80 80 605 36 11.E 112 847 1 ►- ov W. 1213 0 bw 0.550 s 0.097 42.90 35.14 0.46 0 0 0 0 0 0 0 0 0 0 0 .A-2ov O�550 w 42.91D 64.78 0 0 0 0 112 1. 96 0 726 686 44 1037 .L::�G 11FO P 0.280 w 21.84 5-18 0 0 ID 0 0 0 0 0 1 O 1 -d 0.091 -- 0.022 - 7.10 1.72 0.33 0.92 0 0 0 0 0 0 0 F 21A -20t 0.027 - 2.11 0.00 70 0 10 0 1470 01 0 196. 0 0 excursion - -14201 Envelope los `gain 753: 23 2673 1332 1 Infiltration b) Room ventilation 904 81 0 0 0 0 13 Intemal gains- Occupants g 230 0 Less exterrial load Appliances (p 1200 0 0 Less transfer 00 0 0 Redisbibution 0 0 0 0 14 Subtotal 81 0 ID18 44 15 Duct Joads1157 % 410 52 % 76% 4595 1 457 _ 1629 110 Total morn load Air req u i r! ( 1 1 1 6224 2559 1 41 124 122 Printout certified by. ACOA to rneet all r ff Right -Suite Residerdial 6.0.02 J4CCXProject2srp Care`mj8 orientation = Urrements of Manual J 8#h Ed. 2005 -May -04 20-5-1-25 Page 4 Mike Wood Heating & m[inq Rightim,, vVrsJob: #1 Entire House. Date: May 04, 2005 M C B y Mike wood 1 Room name it er dinniL all 21.4 ft 15,0 ft Cell -Ing height `0 ft heat/mol 8. 0 ft heat/cool 4. Room dimensions 1.0 x 372.0 ft Room area 372,0 ft21.0 ft 211.0 x 14.0 f# Construction U -value Or HT M Area (f ) Load Area tt Load rimber to /f 2 -QIP) tul or n"m t r () Btuh) or perimeter (ft) (B#u w HiIr Goof Gross N/P/8 Heat col Gross NIPIS Head Cool 1Ebw 0.097Ln 7.57 0.46 0 0 0 0 32 32 242 15 -D 11 F 0 0.2800 n 21.84 5.18 0 0 0 0 0 1 -0 b0.097' rye 7.57. 0.46 34 28 214 13 0 0 0 0 2-A-- 0.550 ne 42.00 44.74 6 0 243 254 0 0 1 13 -Ow 0-097 e T57 0.40 104 75 567 34 0 0 2-A-2ov 0.550 e 42-90164.78 8. 0 343 518 0 0 0 0 11 FO 0.260 21.84 5,181 21 459 100 0 0. 0 0 1 B-0bw 0.037 se 7.57 0.48 34 25 1W 11 0 2A-2o2A-2ov 0,558 se 42.90 5T09 9 0 386 514 0 0 0 0 12B-Obw 0.007 s 7.57 0.46 0 0 0 01 0 0 0 0 2A-ov 0.550 s 42.90 35,14 2A-2L1 8-Obw 0.097 w 7.57 0.46 0 0 0 0 88 88 688 4 t o 0-550 w 42,90 64.78 0 .0 0 0 0 11 I`0 -280 w 21,84 5.18 0 0 0 0 0 0 0 0 P 12C-Osw 0,091 7.10 0.33 144 144 1022 47 0 0 0, 0 10d 0-022 _ 1.72 0.92 372 372 638 E 21A -20t 0.027 2.11 0.00 30 63 0 154, 151 324 6 E D excursion -209 -20 Envelope loss/gain 4125 1545 1 232 34 12 a) I rifi Itrati on b) Room ventilation 804 62 464 4 0 0 0 13 Internal gains, Less extemal load ppl ia r�c� 1200 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 44 1 -1716 -78 15 Duct I d 4 060 1626 0 0 ► 76 1724 1230 5% 76TO 0 0 Total room load 6586 -2856 Air required (cfm) 0 10 °1 0 0 Printout certified k meet all requirements .f nu1 # Ede '' r-1 t Right -Suite Residential 6,0.02 RSR40535 ProjectZrrp Cale = Mig Orientation = W 2005 -May -04 20.51.25 Page 5 Mike Wood Heating Codl N Right-.,., Nre Job: #1 Entire use Date: May 04., 2005 By: Mike Wood 1 Room name family rm. hal) dwn, 2� Exposed wall 39.0 ft 0-0 ft 3' Ceiling height 8-0 ft heatfcool 8. 0 ft 4 Room d)-mensions 16.0 x 24, C) ft heat/cool 5 Rcom area 384. 0 ff2 170,0 fF IT 0 x 10- 0 ft TY Construction U- Value Or HTM Area (ft2), Load Area (w) Load number (Btuh/ft22F) (Btuh/ft2) or pen meter (ft) (Btu h) or Pefteter (it) (131uh) Heat Cool Gross N/P/S Heat Cool Grnss NIP/ S Heat cool 6 W. 12B-0-bw 0-097 n 7.57 0,46 192 192 1453 88 0 0 0 1—D 11FO 0,280 n 0: 21.84; 5.18 0 0 0 0 0 0 1213-obw 0.097 ne 7.57' 0A6 0 0 0 0� 01 T 0 2A-2ov 0.550- ne 42.90 44.74 0 0 0 0 0 0 0 0 V IV 12B-Obw 0.097 e 7.57 0-46 0 0 0 0 0 0 0 0 F --G 2A-2ov 0.550 e 42-90 64-78 0, 0 0 0 0 0 0 0 126 , —D 11FO 0.280 e 21.84 5-18 0 0 0 0 0. 0 -Ob0 0 w 0.097 se 7.57 OA6 01 0 0: 0 0 0 0 T__G 2A-2ov 0.550 se 42M 5709 0 0, 0 0 0 0 0 0 �V 0 0 0 0 4V 1213-obw 0.097 s 7.57 0-46 0 01 0 0 1—G 2A-2ov 0,550 S 42.90 35.14 0 0. 0 0 0 0 0 Wt 12B-9bw 9.097 w 7.57 0-46 120 120 908 55 0 0 0 L 0 :G 2A-2ov 0,550 W 42.90 64.78 0 0 0 01 0 0 0 0 D 11 FO 0-280 W 21.84 5A8 0 0 0 0 0 0 0 P 12C-Osw 0.091 - 7.10 0 0-33 0 0 0, 0 0 0 0, 0 C T1613 0.022 - 1.72 0.92 0 0 0 0 0 01 0 F 21A -20t 0.027 - 2.11 0,00 384 39 809 .0 170 00 358 01 T 6 c) AED excursion - - Envelope loss/gain. 3169 89' 358 0 W 12 a) Infiltration 1259 b) Room ventilation 113 0 0i 0 13 Int mal gains.- Occupants 0 230 0 0 Less external load Appliances 0, 1200 0 0 0 Less transfer 0 0 1 01 (). i 0 Q 0 0 Redistri-bution 0 0 14 Subtotal 1547 71 -358 0 15 Duct loads 5975 273 0 0 35% 76% 2118 206 :35% 76% 0 0 Total r load Air required (Cfm) 8093 479 0 162 23 T 0 0 0 - Printout certified by ACCA to meet all r Right -Suite Residentid 6.0-02 RSR40535 Project 2.rrp Calc ;-- MJ8 OAR entation = VV Uirements of Manual J 8th E. 2005 -May -04 20 -SI L25 P2ge 6 ti Mike Wood Heating & Cooling Right-.. Worksheet job: #1 Entire House Date: May 04, 2005 By: f ood 1 Room name master bed Exposed wall 13.0 ft dosetIvanity Ceiling height 8. tt 4 Boom dimensions woI Room � �_ 0 i 1 o ft 182.0 T 88.0 ft2 LArea r (ftp) Loadnumber -"F (Btuh/t2 or rm t r (tuh or pedmeter ft(Btuh) Heat Cool Gross /PIS Heat Cool Gross NIP/S Heat Cool 1213-obw 0.097 n 7.57.0.46 0 01 0 0 - L11 FO 0.2801 n 21.84 5.18 0 0 0 0 0 0 0 t -G 12B-O,bw 0,097 ne 7.57 0.46 0 0 0 0 0 0 01 2A-2ov 0.550 rye 42.90 44.74 0 0 0 0 G 0 0 0 11 W, 1 B -!Ob 0.097 e 7.57 0.46 1 G4 84 636 38 64 56 424 26 E�G 2A-2ov 0.550 e 42.90 64.78 0 858 1296 8 0 343 518 111=0 0.280 e 21.84 5.18 0 0 0 0 w, 1 o bw 0.097 s 7.57 0.46 0 0. a 0 -G 2A-2ov 0550 se 42.90 57.09 W. 1B -Obi 0.097 7.57 0.46 0 0 8 88 666, 40 L -G 2A -2o 0.550 S 42.90 35.14 0 0 0 0 0 12B-obw 0.097 w x.57 0.46 0 .0 0 0 �-0,550 4. 0 64.78 0 0 0 0, 11FO 0.280 w 21-845-18 0 0 0 0 P 1 O a-091 - 7-10 0.33 0 0 1613-44ad 0.022 - 1.7.E 0.92 182 182 31,21 68 88 88 F 1 A- 0t 0.027 .2.11 M 0 0 1 1 1 6 c) AED excursion -150 -82 Envelope lossJgain 1806 1352 1584 584 1Infiltration b Room ventilation 1 On 0 13 Int mal airs: Occmants 0? 23-0 0 .Appliances 9 1200 0 0 0 0 Less este rnal load 0 0 0 Less transfer " 0 0 Redistribution 0 0 14. Subtotal 72 31 0 0 15. Ductloads 2298 1421, .2197 639 %Total room load - -� 814 1075 % 76%779 4 83 Air required 3112 249512976 1122 119 9 53 Printout certified �y.ACCA t meet all r Right -Suite Residential 6.0.02 840535 ACCN PrcjeCt2_rrp Calk = MJS Orientaiion = VV Uirements of Manual J 8th E. 2005 -May -0420:51-25 Page 7 Mike Wccd Heal -Ing & C-Dolirrg Right2m� Norksheet Job: #1 Entire use Date: May 04, 2005 By: Mike Wood I Room name living master bath 2 Exposed wall 15, 0 ft 7. 0 ft 3 Ceilling height 8. 0 ft heaVcool 8,0 ft 4. Room dimensions 15�O X 16. 0 ft heatf000l 5 Room area 8.0 )K 7, 0 ft 240. 0 ft2 56.0 W TY Construction U -value Or HTM Area (ft2) Load Area ftp Load number i (Btuh/ff-OF)l I (Bfuh/fF) i or Perimeter (ft) (Btuh) or perimeter (ft) (Btuh) ft) He.L Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W. 12" bw 0.097 n 7�57 0-46 0 0 0 0 0 0 I—D 11FO 0.280 n 21.84 5�18 0 0 0 01 0 0 0 0 12B-Obw 0.097 ne 7-57 0-46 0 0 0 W 0 0 D 0 T --G 2A-2ov 0-550 ne 42.90 44.74 0 0 0 0 0: 0 0 .0 11 VIV 11213-0bw 0.097 e 7,57 0.46 0 0 G 0 M 0 0 0 —G 2.-2ov 0.550 e 42.90 64,78 0 0 0 0 0 0 0 0 11 FO 0280 e 21.84- 5.18 01 0 0 01. 0 0 0 0 W, 12B-Obw 0.097 se 7.57 0.46 0. 0 G 0 0 0 0 0 L—G 2A-2ov O550 se 42.90, 57.09 0: 0 0 0. 0 0 0 W. 12B-Obw 0.097 s 7,57 0.46. 0 0 0 0 56, 56 424 26 L_G 2Av 0.550 S 42.90 35.14 0 0 0 0 0 0 W. 128-Obw O�097 w 7T57 0.46 120 75 5670 0 34 0 0 0 0 2A-2ov 0-550 w 42.90 6478 24 0 1030 1555 0 01 0 0 D 11 FO 0.280 w 21.84 5-18 21 21 459 109 0 0 0 0 P 12C-O,%w D.091 7.10 0.33 128 128 909 42 0 0 0 01 C 16B-44ad 0.022 - 1.72 0.92 240, 240 412 222 56 56 96 52 F 21 A -20t 0.027 - 2-11 0-00 0 0 0 0 0 0 0 6 c) AED excursion 263 -20 Envelope loss/gain 3376' 2224 520 57 12 a) Infiltration b) R 484 43 Room ventilation 226 2 0 .%_ -01 0 0 0 13 Intemal gains-- Occu p2 ntra 230 0 C) 0 Appliances (p 1200 1 1 1 a 0 Less extemal load 0 0 Less transfer 0 0 0 RedistrTbution 0 0 0 0 14 Subtotai 44 19 15 Duct loads 3905 2286 768 87 ------- 35 0/0 76% 1384 1729 35%' 76% 272 66 Total room load i I Air required (fm ) 5289 4016 1040 153 106 191 21 1 7 Printout cerfified by RCCA to mp.p-t Al r I I N~ff-1!�_j"1L!&4z3jft R ight-Sulte Res id e ntlal. 6,0.0 2 RS 40 535 J4Z'��kProject2srp Ca1C=lVlJ8 Orlantafion=W uirements of Manual J 8th Ed. WhEm 2005 -May -04 20,51:25 Page 8 Mike Wood Heating & Corilirig Right-*. 4Vorksheet Job-. #1 Entire House [aft; May 04,2005 B: Mike Wood 1. Room name 'SII hall bath bed #3 Ceiling height , 0 ft hatic�)ol 4 Room, dimensions .0 ft heat/cool Room area 64.0 ftp :1 12.0 x 12-0 ft Ty Constniction U -value Or HTM Area ftl) Load Area eft Load number B to / F) (B tum or perimeter (ft) (Btuh) or Perimeter (ft) (Btub) Heat cool Gross N/P/S Heat Cool Gross NIP/S HeatNIP/ Cool 8 W. 1 B-8 bw 0.097 n 7.57 0,46 0 0 0 0 0 0 sL—D, 1 1 Fg 0.288 n 21.84 5.18 8 Y__6 12B-obw 0.097 ne 7657 0_46 8 0 8. 0 0 8 8 0 2A-2ov 0,550,ne 4.. 44-74. 0 } 0 0 0 0 0 0. 1112B-obw M97 e 7.57 0.46 0 0 g g 0 0 g 0 2A- ear 0.550 e 42.90 64.78 0 0 0 0 0 01 0 g L 11FO 0.280 21,84 5,18 0 0 0 8 0 8 t—G 12B-Obw 0.097 se 7.57 0_46 0 0 0 0 0 0 2A-2ov 8.550 se 42.90 57.09 0 0 g g g 0 8 0 W. 12B-obw OM7 S 7 57 0.46 64 56 424 26 96 916 726 44 L_G 2A-2ov 0.550 S 42.90 35-14, 0 VV 12B-Obw 0.097 w 7.57 0,46 0 0 0 0 96 80 605 36 L,G 2A- ov 0.550 w 42.98 64-78 0 0 0 0 16 0; 686 1037 11FO 0.280 w 21.841 0 0 0 0 0 g 0 P 12C-Osw 0,091 - 7.10 OMI 0 0 8 0 0 8 0 0 1 f d 0.022 1.72 0.92 64 04 110 59 144 144 247 133 F 21A -20t 0.027 - 2-11 0.00 0 0 : 0 0 8 AEC excursion - 179 Envelope loss/gain 877 357 2265 1428 1 ) Infiltration - b Room ventilation 7 0 1 Internal gains: Occupants Q 230 0 r 0 0 Appliances 1200 8 Less external loaf Less transfer 0 0 0 edi tnbutior 0 0 14 Subtotal 44r 10 22 9 1 Duct loads1179 399 3062 150 768 302 o� °�35 � 7 1 1 40 Total rMM load 1598 8 702 .fir required cfm4148 2648 33. 83 126 Printout certified by AICA to meet all r AAiF. sight -Suite Residential 6.0.02 RSR40535 � Proje t _ rrp Caic = MJS 0.6 15an#ation = VV uirements of Manual J 8th Ed. 2005 -May -04 20-151:25 Page Mike Wood He -sling & Cooling Rwightno Worksheet .yob: #1 Entire House Date: May 04, 2005 By: Mike Wood. I Room name bed #2 2; Exposed ll II 1.0 f00 ft Ceiling height 8.0 ft heat/0001 a.0 ft heat/wol 4 Boom dimension 13-0 X 14 0 ft 1,0 188.D ft Room area 182. 0 ft2 188_0 ft2 Ty Construction U -value Or HTIVI Area (2) Load W ) Load number Btu hI -' F Btu hlft2) or peri meter f B-tu h�o r � meter ft131uh Heat Ecol Gross N/P/S Heat Caul Gross N/P/S Heat Cool 1 B 0.097 n 7.57 0.46 48 48 363 - 11 F0 0.280 n 1 21.8415.18 0 0 0 0 0 0 0 01 T --G 12B-Obw 0.097 n e 7.57 06 0 0 0 0 0 2-A-2ov 0.550 ne 42.90 44.74 0 0 0 0 0 11 VIV 12"bw 12" 0.097 e 7.57 0-46 0 0 [7�G 2A -2o 0.550 a 42M 64.78 0 0 0 0. 010 1 `S FO 0.266 a 21.84 &I B 6 0 0 6 0 t -G 2A-2ov 12B-obw 6.097 se 7.57 0,46 6 D 6 6 0 0 6 0.550 se 42.90 57.69 01 0 0 0 0 6 W. 12B-obw 0.097 s 7.57 O.46 16 11 121 7 0 0 IG 2�c 0-556 s 42.90 35-14 6 0 0 0 0 0 0 0 1' 12B-Obw 0.097 w 7.57 0.46 . 104 66 666 40, 6 0 0 [:�:G -o 0-550 42.90 64.78 16 0 686 1 037 0 0D. 1 � � �1 0_. 80 21.84 5`18 0 0 0 0 0 6 P 12C-Osw 0.091 T-10 0.33 0 0 G 0 01 1 4ad 0,022 - 1.72 0.92 1 162 1 168' �1 1 � 8 F 1,-0t 0.027 y 2-11 O.6 26 3 5.5 0 0 0 ED excursion 175Envelope loss/gain 2204 1449 323 138 12 a) Infiltration 678 - b) Room enWat on 0 0 0 0 0, 13 I temal gains:occupants 9 230 0 Appliances A 1200 0 0 Less tem I load 6 Less transfer � '� 01 0 Redistribution 72 31 6 � 0 0 14 Subtotal -323 -138 1 ��t lis � 1 � ,� � � 1047 �1 +1 % 76% 0 0 Total room load 0 Air requires (f 6� 0 129 0 Printout certified b ACOA to meet all r vvqRight-Suite Residential 6.0.02 RSR40535 Prpj Ct _rrp Caic = mis Orientation vv Uirements of Manual J 8th Ed. 2005-Mav-04 20,51:25 Page 10 Mike Wood Heating BCooling Duct System Summary Entire House Job: #1 Cate: May 04, 2005 BY: Mike Wood For-, Ryan Durfee Rexburg, ID. 83448 Phone'. 313-0228 Eternal static pressure Pressure losses Available static }pressure Supply I return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.00 in H20. 0.00 in H20 0.00 Fn H20 0.00/0-00 in H20 0.000 in/1 QQft 1 095 cfm 630 ft Coling 0.00 in H20 0.00 in HZQ 0.00 in H2O 0.00/0.00 In H2O 0.000 -1 n/1 aoft 1X95 cfm Design Htg CIg Design Diam Rett Dict Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) Size (in) Mat! Ln {ft} Ln (f#) Trunk toy rm. h 173 55 $ 0.000 D ox 0 ShMt 1 1 .D 265. 0 st2 bei #4 C 9 771 54 $4 0.000 0 Ox 0 ShMt 22.0 250_0 Sf.2 ped rm_#,5 h 1 272 95 fip 0.000 Cl OX 0 ShMt 41,0 175.0 st2 bath h 91 31 4 0.0001 p Ox Q ShMt 50_0 23.0 st2 bed rm.#6 h 2559 124 122 0.000 Q Ox (] ShMt 67.0 240.0 std kitchen/dinning C 1428 66 6$ 0.000 0 Ox Q ShMt 11.0 285.0 st'1 kitch enldirinlrlg-A C 1428. ss ss 0.000 0 Ox 0 ShMt 17.0 285.0 stl family rm. it 24a $1 11 0.000D 0x 0 ShMt 43.0 2 55. D st2 family ern. -A F} 240 81 11 0,000 0 Ox 0 ShMt 33.(3 265.0 st2 master bed G 2495 Fit 119 0.0000 Ox 0 ShMt 25.0 275,0 std closet/vanity h 1122 59 53 (}.COQ fl ox 0 ShMt 37,E 25-0.0 Std Irving c 200$ 53 95 0.000 0 ax Q ShMt 32.0 2$5.0 g#1 living -A C 2008 53 95 0.0000 Ox D ShMt 39.0 285.0 SOmaster bath h 153 21 ? 0_000 D Dx D ShMt 44.0 270.0 St1 hall bath c 702 32 33 0.000 0 Ox 0 ShMt 56.0 195.0 5t1 bed #3 c 2648 83 126 0.000 D OX 0 ShMt 69.0 260.0 st1 bed 42 C 2707 84 129 o_ooa 0 Ox 0 ShMt 56.0 285.01 st'f �,.Alt= wrig htsc) 1 Right -Suite Residential 6,0.02 F 2005 -May -04 20:51-35 Page I Grill Htg Cig TEL Design lVeloc IDiam RectSize Stud/Joist Duct Name Size (in) (cfm) (CfM) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb1 Ox 0 136 20 142.0 0.000 0 0 Ox 0 ShMt rb3 0x 0 135 96 156.0 0.000 0 01 Ox 0 ShMt rt2 rb4 0x 0 126 65 208.0 0.00010 0 Ox 0 ShMt 02 rb5 0x 0 724 122 193.0 0.000 0 0 Ox 0 ShMt rt2 rb6 Ox 0 184 231 225.0 0.000 0 0 Ox 0 ShMt rt3 rb7 0x 0 115 1,59 273.0 0.0001 0 0 Ox 0 ShMt R3 rb8 0x 0 136 221 788.0 0.000 0 0 Ox 0 ShMt rt3 rb9 0x 0 139 182 289.0 0.000 0 0 Ox 0 ShMt ria vvr"l9lltSC3 Fight -Suite Residential 6.0.02 RSR40535 - ACCA Proj ct xrp Calc = MJ8rientation = i 2005-a-04 20:51:35