Loading...
HomeMy WebLinkAboutSTAFF REVIEW - 05-00108 - Walgreens - Site PlanCITY CP REXBURG Arnma'a'f Funnily Gnrmmriry Review Action December 13, 2005 Permit Number: 05 00108 Project Name: Walgreens Site Plan/Design Review Project Type: Site Plan Review P.O Box 280 19 E Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 Review Item Actions Required for Approval Approved Fire Department Review Fire Lane Signage PLEASE PROVIDE CLEAR ACCESS TO FIRE 05/03/2005 DEPARTMENT CONNECTION AT ALL TIMES. Fire Access Roads ACCESS FROM EAST MAIN STREET TO 05/09/2005 WEST SIDE OF BUILDING NOT COMPATIBLE WITH FIRE APPARATUS. WIDTH BETWEEN DRIVE -THROUGH AND CURBING TOO NARROW. PLEASE ADDRESS. PREVIOUS PLAN CORRECTED. Additional Comments PREVIOUS PLANS CORRECTED. 05/09/2005 Water Supply Parcel #'s RPRRXB10370010 PLANS SHOW ONE FIRE HYDRANT. DEPENDING UPON TYPE OF CONSTRUCTION AND IF OCCUPANCY IS SPRINKLERED, BUILDING MAYBE REQUIRED TO HAVE MORE FIRE HYDRANTS, PLEASE ADDRESS. EXISTING HYDRANT NOT SUFFICIENT FOR MINIMUM OF 1500 GPM/TWO HOURS FIRE FLOW REQUIREMENTS. SUGGEST INSTALLING SECOND HYDRANT. CITY OF REXBURG A... Family Cammm�iry, Review Action March 8, 2006 P.O Box 280 19 E Main St. Rexburg, Idaho 83440 Phone(208) 359-3020 Fax (208)359-3022 Permit Number: 05 00108 Project Name: Walgreens Site Plan/Design Review Project Type: Site Plan Review Review Item _ - Actions Required for Approval Approved Building Department Review Plumbing Review 05/09/2005 Snow Storage Snow storage is in parking lot. Remove from 05/09/2005 spaces that will violate the 30' site triangle as required per zoning ordinance. Fire Separation Meets code requirements. 05/09/2005 Parking Configuration Meets the requirements of the zoning ordiance. 05/09/2005 Number of Parking Spaces Not required in Central Business District. 05/09/2005 Setbacks and Propertly Lines Meets zoning and building code requirements. 05/09/2005 Parcel Ws RPRRXB10370010 �*onr P.O Box 280 Aioa °e CITY OF 19 E Main St. REXBURG Rexburg, Idaho 83440 AmerW}Fomiy Cornmunq Rhone (208) 359-3020 Review Action Fax (208) 359-3022 March 8, 2006 Permit Number: 05 00108 Project Name: Walgreens Site Plan/Design Review Project Type: Site Plan Review Review Item _ Actions Required for Approval Approved Fire Department Review Fire Lane Signage PLEASE PROVIDE CLEAR ACCESS TO FIRE 05/03/2005 DEPARTMENT CONNECTION AT ALL TIMES. Fire Access Roads ACCESS FROM EAST MAIN STREET TO 05/09/2005 WEST SIDE OF BUILDING NOT COMPATIBLE WITH FIRE APPARATUS. WIDTH BETWEEN DRIVE -THROUGH AND CURBING TOO NARROW. PLEASE ADDRESS. PREVIOUS PLAN CORRECTED. Additional Comments PREVIOUS PLANS CORRECTED. 05/09/2005 Water Supply PLANS SHOW ONE FIRE HYDRANT. 01/19/2006 DEPENDING UPON TYPE OF CONSTRUCTION AND IF OCCUPANCY IS SPRINKLERED, BUILDING MAY BE REQUIRED TO HAVE MORE FIRE HYDRANTS, PLEASE ADDRESS. EXISTING HYDRANT NOT SUFFICIENT FOR MINIMUM OF 1500 GPM/TWO HOURS FIRE FLOW REQUIREMENTS. SUGGEST INSTALLING SECOND HYDRANT. ADDITIONAL FIRE HYDRANT PROVIDED FOR ON NORTHWEST SIDE OF BUILDING AS OF 01/19/06. Parcel Ws RPRRXB10370010 P.O Box 280 b� yexevt� a 19 E Main St. 7�� �7�.CV�i lT7��Y7O7FT� J c 1tC XB V RG Rexburg, Idaho 83440 nv -- Phone (208) 359-3020 A.edr k Faintly Carnmuniry Review Action Fax (208)359-3022 March 8, 2006 Permit Number: 05 00108 Project Name: Walgreens Site Plan/Design Review Project Type: Site Plan Review Review Item _ Actions Required for Approval Annroved Public Works Review Approved Site Plan Parcel #'s RPRRXB10370010 01 /19/2006 y�4 nExnua�,o CITY OF REXBURG CW AmerkO I;srnih' Community December 13, 2005 Permit Number: 05 00108 Review Action Project Name: Walgreens Site Plan/Design Review Project Type: Site Plan Review P.O Box 280 19 E Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 Review Item Actions Required for Approval Anar„ Dyed Fire Lane Signage PLEASE PROVIDE CLEAR ACCESS TO FIRE 05/03/2005 DEPARTMENT CONNECTION AT ALL TIMES. Fire Access Roads ACCESS FROM EAST MAIN STREET TO 05/09/2005 WEST SIDE OF BUILDING NOT COMPATIBLE WITH FIRE APPARATUS. WIDTH BETWEEN DRIVE -THROUGH AND CURBING TOO NARROW. PLEASE ADDRESS. PREVIOUS PLAN CORRECTED. Additional Comments PREVIOUS PLANS CORRECTED. 05/09/2005 Water Supply PLANS SHOW ONE FIRE HYDRANT. DEPENDING UPON TYPE OF CONSTRUCTION AND IF OCCUPANCY IS SPRINKLERED, BUILDING MAY BE REQUIRED TO HAVE MORE FIRE HYDRANTS, PLEASE ADDRESS. EXISTING HYDRANT NOT SUFFICIENT FOR MINIMUM OF 1500 GPM/TWO HOURS FIRE FLOW REQUIREMENTS. SUGGEST INSTALLING SECOND HYDRANT. Parcel #'s RPRRXB 10370010