HomeMy WebLinkAboutCOMPLIANCE CERTIFICATES & CALCS - 05-00105 - Mama K's Restaurant - Tenant Finish12./79/2005 09:24 FAX
16 003/005
Lighting Compliance Certificate
2001 IECC
COMcheckEZ Sotware Version 3.0 Release 2
Data filename: Untitledcck
Section 1: Project Information
0500105
Mama K's-Tenant Finish
Project Namer Mamma K's
DesignedContracor. Blane Robbins Electric, Inc.
Document Author. IeffPobbins
Section 2: General Information
Building Use Description by: Whole Building Type
Project Type: New Construction
Section 3: Requirements Checklist
Bldg.
Dept.
Use
Checked By/Due
tit
pC�C�C�a�l
Interior Lighting P,
1. Total actual watts must be less than or equal to total allowed watts DEC 1 9 2605
Allowed Watts Actual Watts Complies(Y/N) t_ _
8500 3103 YES
Ea terior Lighting
2. Efficacy greater than 45 lumens/W
Exceptions:
Specialized lighting highlighting Eatures of historic buildings; signage; safety or security lighting;
low -voltage landscape lighting.
Controls, Switching, and Wiring
3. Independent controls for each space (switch/occupancy sensor),
Evxptlon. Areas that must be continuously illuminated
4. Master switch at entry to hotel/motel guest room.
5. Two switcbes or dimmer in each space to provide uniform light reduction capability.
Eruptions'
Only one luminaim in space; An occupant -sensing device controls the area;
The area is a corridor, storeroom, restroom, or lobby; Ammer that must be continuously illuminated;
Areas greater than 250 sq.L
6. Automatic lighting shutoff control in opera greater than 250 sq.9 in buildings larger than 5,000 sq.8.
7. Photoodl/astronomical time switch on exterior lights.
12/•19/2005 09:23 FAX
la 001/003
vzttc*-r�04 aer'p;-!- #�-
Envelope Compliance Certificate
2001 IECC
COMB EZ Sotwam Version 3.0 Releases 2
Data filename: Untitled. ark
Section 1: Project Information
Project Name: Mamma K's
Designer/Contractor. Blanc Robbins Electric, Inc.
Document Author: JeffRobbins
Section 2: General Information
Building Location (liar weather data):
Rexburg, Idaho
Climate Zone:
16
Heating Degree Days (base 65 degrees F):
8693
Cooling Degren Days (base 65 degrees Fr
143
Project Type:
New Construction
Window / Wall Ratio:
0.00
CV-5V3V
Permit Number
100,
Checked By/D
Building Tvne Floor Area
Restaurant 5000
Section 3: Requirements Checklist
Bldg.
fit• I
Use
Air Leakago, Component CerMeadon, and Vopor RMarder Requirements
[ 1 1. All joints and pwdrafious are caulked, gssketed, weather stripp4 or otherwise sealed.
I 2. Windows, doors, and skylights c attifie d as meeting leaksge requirements,
[ ] l 3. Component R values & U-iic tors labeled as cxrtifie&
e S-373$Mo
121/48/2005 09:23 FAX
@ 002/005
Climn"pecific Requirements
Gmass
Area or Cavity Cont, Proposed Budget
Component NarnefDeapdution dim=. R_ R._ I,L-Fm= IL -Factor
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code mquh=wts.
Eave lope PASSES: Design 0.01/6 better than code
Section 4: Compliance Statement
The proposed envelope design npmented in this document is consistent with the building plans, specifications and other
calcula<ions submitted with this permit application. The pwposed envelope system has been designed to meet the 2001
IECC, Chapter 8, requirements in COMeheck--EZ Version 3.0 Release 2 and to comply with the mandatory requirements
in the Requimneartts Checklist.
lqpm
Principal Envelope Desigm Name Si Date
12-A19/2005 09:24 FAX
IR005/005
Lighting Application Worksheet
2001 IFCC
COivlcheck-EZ Sotware Version 3.0 Release 2
Section 1: Allowed Ughtlng power Calculation
A B
C
D
Total
Floor
Allowed
Allowed
Area
uu,il ng T= - U
Watts
(watW02)
Watts
ra x 0
RestwMt 5000
1.7
8500
Total Allowed Watts = 8500
Section 2: Actual Lighting power Calculation
A B C D E F
Fixture Fixture Description / Lamps/ # of Fixture
m Natt, tD xE)
1 Drop In's / 48" TS 32W / Electronic 3 54 32 1728
2 Can Lighting / In=desmt dOW 1 20 60 1200
3 Outside Wall Packs / Metal Halide 175W J Electronic 1 1 175 175
Total AMW Watts 3103
Secdon 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is grWa tbn or equal to zero, the braiding complies.
Total Allowed Watts = 8500
Total AOM Watts = 3103
Pmject Compliance 5397
Lighting PASSES: Design 63% better than code
• . 12A19/2005 09:24 FAX
Q 004/005
EwVtiow. Armes requiring lighting during daylight hours
l I 8. Tandem wired one-Iamp and tht+e&-lamp ballasted lumui uim.
I Ftions:
I Mavonia high f+eq=cy ballasts; Luminaires not on some switch
Section 4: Compliance Statement
The proposed lighting design rr9mented in this document is consistent with the building plans, specifications and other
calmilations submitted with this pamit application. The proposed lighting system has been designed to meet the 2001
IECC, Chapter 8, requitement$ in COMdieabEZ Version 3.0 Release 2 and to comply with the mandarory requirements
in the Requimmemts Checklist.
�'J' Ile
Principal Lighting Designer -Name SigndFM Date
rs
C;}e10F Xex&try
Envelope Compliance Certificate
2001 IECC
COMcheck--EZ Software Version 3.0 Release 2
Data filename: Untitled.cck
Section 1: Project Information
Project Name: Mamma Ks
Inside Strip Mall
Designer/Contractor. Blanc Robbins Electric, Inc.
Document Author. Jeff Robbins
Section 2: General Information
Building Location (for weather data):
Rexburg, Idaho
Climate Zone:
16
Heating Degree Days (base 65 degrees F):
8693
Cooling Degree Days (base 65 degrees F):
143
Project Type:
New Construction
Window / Wall Ratio:
0.00
C jr- 83a37 - c9 83�40
Permit Number
Checked By/Datc
Building Type Floor Area
Restaurant 5000
Section 3: Requirements Checklist
Bldg.
Dept.
Use
Air Leakage, Component Certification, and Vapor Retarder Requirements
[ ] 1. All joints and penetrations are caulked, gasketed, weather-stripped, or otherwise sealed.
[ ] 2. Windows, doors, and skylights certified as meeting leakage requirements.
[ ] 3. Component R-values & U-factors labeled as certified.
Climate•Spedfic Requirements
Gross
Area or Cavity Cont. Proposed Budget
Component Name/Descri tp ion Perimeter -V e R Value -Fact U-Factor
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
Envelope PASSES: Design 0.0%better than code
Section 4: Compliance Statement
The proposed envelope design represented in this document is consistent with the building plans, specifications and other
calculations submitted with this permit application. The proposed envelope system has been designed to meet the 2001
IECC, Chapter 8, requirements in COMcheck-EZ Version 3.0 Release 2 and to comply with the mandatory requirements
in the Requirements Checklist.
Principal Envelope Designer -Name -Signature — Date
Lighting Compliance Certificate
2001 IECC
COMcheck-EZ Software Version 3.0 Release 2
Data filename: Untitled.cck
Section 1: Project Information
Project Name: Mamma K's
Inside Strip Mall
Designer/Contractor. Blane Robbins Electric, Inc.
Document Author. Jeff Robbins
Section 2: General Information
Building Use Description by: Whole Building Type
Project Type: New Construction
Permit Number
Checked By/Date
Building Type Floor Area
Restaurant 5000
Section 3: Requirements Checklist
Bldg.
Dept.
Use
Interior Lighting
1. Total actual watts must be less than or equal to total allowed watts
Allowed Watts Actual Watts Complies(Y/1)
8500 6018 YES
Exterior Lighting
2. Efficacy greater than 45 lumens/W
Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or security lighting;
low -voltage landscape lighting.
Controls, Switching, and Wiring
3. Independent controls fDr each space (switch/occupancy sensor).
Fxception: Areas that must be continuously illuminated.
4. Master switch at entry to hotel/motel guest room.
5. Two switches or dimmer in each space to provide uniform light reduction capability.
Exceptions:
Only one luminaire in space; An occupant -sensing device controls the area;
The area is a corridor, storeroom, restroom, or lobby; Areas that must be continuously illuminated;
Areas greater than 250 sq.$.
Lighting Application Worksheet
2001 IECC
COMcheck--EZ Software Version 3.0 Release 2
Section 1: Allowed lighting Power Calculation
A B
C
D
Total
Floor
Allowed
Allowed
Area
Watts
Watts
Building Tyne ML_(watts/#zl
(a x Cl
Restaurant 5000
1.7
8500
Section 2: Actual lighting Power Calculation
A B
Fixture Fixture Description /
TD Lam-2 escription / Wattage Per Lamp / Ballast
1 48" T8 32W / Electronic
2 Incandescent 75W
3 Incandescent 60W
Total Allowed Watts = 8500
C
D
E
F
Lamps/
# of
Fixture
Fixture
Fixtures
Watt.
x E
3
38
96
3648
1
14
75
1050
1
22
60
1320
Total Actual Watts = 6018
Section 3: Compliance Calculation
Ifthe Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 8500
Total Actual Watts = 6018
Project Compliance = 2482
Lighting PASSES: Design 29% better than code
] 6. Automatic lighting shutoffcontrol in spaces greater than 250 sq.t in buildings larger than 5,000 sq.fi.
] 7. Photocell/astronomical time switch on exterior lights.
Exceptions: Areas requiring lighting during daylight hours
] 8. Tandem wired one -lamp and three -lamp ballasted luminaires.
Eueptions:
Electronic high -frequency ballasts; Luminaires not on same switch
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans, specifications and other
calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2001
IECC, Chapter 8, requirements in COMcheck--EZ Version 3.0 Release 2 and to comply with the mandatory requirements
in the Requirements Checklist.
Principal Lighting Designer -Name mgnature Date
o � oo 16�
Page 1 Commercial Heat Loss and Heat Gain Calculation
Report Prepared By:
Mountain West Mechanical Inc.
For: Mama K's
Pioneer Drive
Rexburg, ID 83440
Design Conditions: Rexburg; Latitude: 33; Time 10:00 AM
Indoor:
Summer temperature:
Winter temperature:
Relative humidity:
Building Component
Floors
Walls
Windows
Doors
Door Leakage
Partitions
Ceilings
Skylights
Duct
People
Ventilation
Infiltration
Lights
Miscellaneous
Whole Building - All Components
Outdoor
4/11 /2005
75
Summer temperature:
94
72
Winter temperature:
22
50
Summer grains of moisture:
112
Daily temperature range:
21
Sensible
Latent Total
Total
Gain
Gain Heat Gain
Heat Loss
(BTUH)
(BTUH) (BTUH)
(BTUH)
0
0 0
8,100
2,140
0 2,140
7,864
3,761
0 3,761
5,070
600
0 600
1,200
590
4,374 4,964
13,310
0
0 0
0
2,852
0 2,852
5,821
0
0 0
0
8,359
0 8,359
28,891
34,375
34,375 68,750
0
13,200
97,920 111,120
165,000
0
0 0
0
22,304
0 22,304
0
3,770
230 4,000
0
91,951
136,899 228,850
235,256
( 19 tons )
HVAC-Calc Commercial 4.0 by HVAC Computer Systems Ltd. 888 736-1101
Lead calculations are estimates only, actual loads may vary due to wearer and construction differences.