Review Action
March 23, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
Review Item
Building Department Review
Height and Area Review
Building Type Compliance
Exiting Review
Complies with approved Site Plan Review
Energy Conservation Compliance Review
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (20B) 359-3020
Fax (208) 359-3022
Actions Required for Approval Approved
Height and area meet the requirements of the
IBC.
Building type is VB.
Occupancy load must be noted in banquet
room and in dining area. Banquet room door to
hallway must open in direction of travel as per
Section 1008.1.2. of the 2003 International
Building Code (IBC). Provide emergency exit
illumination as per IBC Section 1006. Provide
panic hardware as per IBC Section 1008.1.9.
Provide exit signs at exit doors.
The height of floor must be 12" above closest
drainage as per IBC. Please identify on plans.
Provide lighting energy review.
Interior Environment Wall and ceiling finishes must meet the
requirements of Section 803 of the 2003
International Building Code (IBC).
Mechanical Review Provide mechanical design as per ACCA
manual J and D 8th edition.
Structural Review Set up a meeting with special inspection firm
and the City for structural fill inspections, high
strength bolting and any welding prior to start of
construction. The clerestory wall connection
(Detail 5 on Sheet S4.1) to roof identifies a 2x
bottom plate being nailed close to its edge with
16p nails at 6" o.c. The framers ability to make
this connection without splitting the 2x is
questionable to the Building Official. Please
design a framing clip to transfer any loads.
Sheet SO.1 requires a geotechnical report.
Please provide a copy to the Building
Department. Also Sheet S0.1 incorrectly
specifies the building code as the 2000 IBC and
the seismic use group as I. Change these to
03/23/2005
03/23/2005
ow
cm Or
REXBURGUS FAMLY COMMUNITY
Review Action
March 23, 2005
P.O Box 280
19 E Main St.
Rexburg, Maho 83"0
Phone (208) 359-3020
Fax (208) 359-3022
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
Review Item - _ Actions Required for Approval Approved
the 2003 IBC and seismic use group II. Identify
anchor bolt spacing on plans. Provide specs
for steel roof joists.
Plumbing Sewer Drain Review
Sanitary sewer and drain lines are required to
be installed according to the Uniform Plumbing
Code.
If grease interceptor is required a minimum of a
3" vent is required to be installed on the
interceptor.
Water and Sewer Service
Plans do not include kitchen plumbing fixtures.
Pains are required to determine if building is
required to have a grease interceptor. Plans
must be submitted for reveiw before permit will
be issued.
All plumbing services are required to be tested
and inspected before covering.
Plumbing Potable water Review
On water lines indicated on plans. Required to
be sized and installed according to the Uniform
Plumbing Code.
Backflow devices are not shown on plans. All
devices are required to be installed and tested
before Final plumbing inspection.
Miscellaneous
Provide detail showing moisture membrane,
flashing and weepholes for masonry. The
plans do not show kitchen details and dining
area details. Do not perform any construction
activity on either of these two areas without
submitting details and receiving approval from
the Building Department.
Building Code Fire Compliance Review
Section 903.2.1.2 of the 2003 International
Building Code requires a maximum fire area of
5000 sq. ft. Provide details showing separation
for fire areas or provide sprinkler plans.
Accessibility Review
One of the handicapped parking spaces next to
the building must be Van Accessible. Please
identify on site plan. Dining areas were not
shown with aisles and tables. Before an
CITY OI
RRG EXBU4\\1I IUC 4p b\llll cJ\t\IUi\II1'
Review Action
March 23, 2005
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
Review Item Actions Required for Approval Approved
occupancy permit is issued, the tables and
aisles need to be configured and approved by
the City.
Parcel Ws RP06N39E361249
P.O Box 280
Cm or 19 E Main St.
REXBURG Rexburg, Idaho 83440
.nuxxasinacr cawr+unrtr Phone (208) 359-3020
Review Action Fax (208) 359-3022
March 23, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
Review Item _
Actions Required for Approval
Fire Department Review
Fire Access Roads
SEE SITE PLAN REVIEW
Standpipes
SEE SITE PLAN REVIEW
Required Fire Flow
SEE SITE PLAN REVIEW.
Other Comments
SEE SITE PLAN REVIEW
Alarm Systems
SEE SITE PLAN REVIEW
Water Supply
SEE SITE PLAN REVIEW
Fire Extinguishers
SEE SITE PLAN REVIEW
Commercial Cooking
SEE SITE PLAN REVIEW
Automatic Fire Extinguishing Systems
SEE SITE PLAN REVIEW
Parcel#'s RP06N39E361249
Approved
03/22/2005
03/22/2005
+rft1"ee = OF
REXBURG
AJ'9e�aw.o e� M1ERICAS EWLLYC UNITY
Review Action
March 23, 2005
Permit Number: 05 00065
Project Name: Hard Hat Cafe
Project Type: Site Plan Review
RO Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
ffrWJ p rt nt Revie Ii "
Fire Access Roads ESTABLISHED.
Standpipes
Required Fire Flow BUILDING REQUIRES 2250 GPM/TWO
HOURS FROM A MINIMUM OF TWO FIRE
HYDRANTS LOCATED WITHIN 450 FEET OF
STRUCTURE.
Fire Extinguishers FIRE EXTINGUISHERS NOT SHOWN ON
DRAWINGS.
Alarm Systems FIRE ALARM SYSTEM REQUIRED. PROVIDE
PLANS AND SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Other Comments LOCK BOX REQUIRED. PICK UP
AUTHORIZATION FORM PRIOR TO BUILDING
PERMIT BEING ISSUED.
Commercial Cooking
COMMERCIAL COOKING REQUIRES
HOODS AND FIRE SUPPRESSION SYSTEM.
PLEASE PROVIDE SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Automatic Fire Extinguishing Systems
OCCUPANCY REQUIRED TO BE FIRE
SPRINKLERED. PLANS AND DRAWINGS
NEED TO BE PROVIDED PRIOR TO
BUILDING PERMIT BEING ISSUED.
Water Supply
FIRE FLOWS NOT ESTABLISHED, PLEASE
PROVIDE FIRE FLOWS PRIOR TO BUILDING
PERMIT ISSUED.
Parcel#'s RP06N39E361249
03/22/2005
03/22/2005
aQ0--N , Cr Y OF
A& T? T_VaT I V i
IMF
•;'� AMERIUT FAM9-Y CQ UNJTY
March 23, 2005
Permit Number: 05 00065
Project Name: Hard Hat Cafe
Project Type: Site Plan Review
Review Item
Building Department Review K' . 1
Fire Separation
Parking Configuration
Parcel Vs RP06N39E361249
Review Action
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Actions Rewired for Approval Approved
Meets the requirements of the 2003 03/23/2005
International Building Code.
One handicapped parking space must be van 03/23/2005
accessible.
*1q
CiY OF
RExBURGAMER SFAML1fOl.N1UNMY
Review Action
March 23, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
RO Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
oved
B it ing Department Rev ew 7
Height and Area Review Height and area meet the requirements of the 03/23/2005
IBC.
Building Type Compliance
Exiting Review
Complies with approved Site Plan Review
Energy Conservation Compliance Review
Building type is VB.
Occupancy load must be noted in banquet
room and in dining area. Banquet room door to
hallway must open in direction of travel as per
Section 1008.1.2. of the 2003 International
Building Code (IBC). Provide emergency exit
illumination as per IBC Section 1006. Provide
panic hardware as per IBC Section 1008.1.9.
Provide exit signs at exit doors.
The height of floor must be 12" above closest
drainage as per IBC. Please identify on plans.
Provide lighting energy review.
Interior Environment Wall and ceiling finishes must meet the
requirements of Section 803 of the 2003
International Building Code (IBC).
Mechanical Review Provide mechanical design as per ACCA
manual J and D 8th edition.
Structural Review Set up a meeting with special inspection firm
and the City for structural fill inspections, high
strength bolting and any welding prior to start of
construction. The clerestory wall connection
(Detail 5 on Sheet S4.1) to roof identifies a 2x
bottom plate being nailed close to its edge with
16p nails at 6" o.c. The framers ability to make
this connection without splitting the 2x is
questionable to the Building Official. Please
design a framing clip to transfer any loads.
Sheet S0.1 requires a geotechnical report.
Please provide a copy to the Building
Department. Also Sheet S0.1 incorrectly
specifies the building code as the 2000 IBC and
the seismic use group as I. Change these to
03/23/2005
C" OF
REXBURG
7°a m If AMERICAS FAMILY Gl. WNUNIiY
Review Action
March 23, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
P.O Box 280
19 E Win St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
Plumbing Sewer Drain Review
Water and Sewer Service
Plumbing Potable Water Review
Miscellaneous
Building Code Fire Compliance Review
the 2003 IBC and seismic use group II. Identify
anchor bolt spacing on plans. Provide specs
for steel roof joists.
Sanitary sewer and drain lines are required to
be installed according to the Uniform Plumbing
Code.
If grease interceptor is required a minimum of a
3" vent is required to be installed on the
interceptor.
Plans do not include kitchen plumbing fixtures.
Pains are required to determine if building is
required to have a grease interceptor. Plans
must be submitted for reveiw before permit will
be issued.
All plumbing services are required to be tested
and inspected before covering.
On water lines indicated on plans. Required to
be sized and installed according to the Uniform
Plumbing Code.
Backflow devices are not shown on plans. All
devices are required to be installed and tested
before Final plumbing inspection.
Provide detail showing moisture membrane,
flashing and weepholes for masonry. The
plans do not show kitchen details and dining
area details. Do not perform any construction
activity on either of these two areas without
submitting details and receiving approval from
the Building Department.
Section 903.2.1.2 of the 2003 International
Building Code requires a maximum fire area of
5000 sq. ft. Provide details showing separation
for fire areas or provide sprinkler plans.
Accessibility Review One of the handicapped parking spaces next to
the building must be Van Accessible. Please
identify on site plan. Dining areas were not
shown with aisles and tables. Before an
CRY OF
REXBURG
'J'+sey�ao9 '4NEWAS F"U COWUNnY
Review Action
March 23, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval _Approved
occupancy permit is issued, the tables and
aisles need to be configured and approved by
the City.
Parcel#'s RP06N39E361249
�E'`a"' CITY OF
REXBURG
AMSUCAS FAMLY COMMUNRY
Review Action
March 23, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
RO Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item
Actions Required for Approval
Approved
Th�x.'3.p.Ntf1T?�:7[V';r e1iL'r •7 y�: 1 ,'''-�:,�''. ^••i-) •7:Tf`f'..;*.,..
Fire-Depariment-Review.-.t-t .�-Y��•.�;r�
.. d.r..:i .. _. ..s,-+.+.:....nw.. ._i.......�..».»-a. c-ci1t.a �i...i Cc �+C:7d•`.�:?ia:":..
Fire Access Roads
SEE SITE PLAN REVIEW
03/22/2005
Standpipes
SEE SITE PLAN REVIEW
03/22/2005
Required Fire Flow
SEE SITE PLAN REVIEW.
Other Comments
SEE SITE PLAN REVIEW
Alarm Systems
SEE SITE PLAN REVIEW
Water Supply
SEE SITE PLAN REVIEW
Fire Extinguishers
SEE SITE PLAN REVIEW
Commercial Cooking
SEE SITE PLAN REVIEW
Automatic Fire Extinguishing Systems
SEE SITE PLAN REVIEW
Parcel #'s RP06N39E361249
CITY OF
. REXBURG
l/
—� Po Box 280
t.
Rexburg, Idaho 3440
A K"SFM YGOMMUNnY
Fhone (208) 359-3020
Review Action
Fax (208) 359-3022
July 28, 2005
Permit Number: 05 00065
Project Name: Hard Hat Cafe
Project Type: Site Plan Review
Review Item Actions Required for Approval Approved
Building Department Review
Fire Separation Meets the requirements of the 2003 03/23/2005
International Building Code.
Parking Configuration One handicapped parking space must be van 03/23/2005
accessible.
Parcel#'s RP06N39E361249
CITY OF
REXBURG
AMeUUS FnnaY COWLINHY
July 28, 2005
Permit Number: 05 00065
Project Name: Hard Hat Cafe
Project Type: Site Plan Review
Review Item
Fire Department Review
Fire Access Roads
Standpipes
Review Action
ESTABLISHED.
Required Fire Flow
BUILDING REQUIRES 2250 GPM/TWO
HOURS FROM A MINIMUM OF TWO FIRE
HYDRANTS LOCATED WITHIN 450 FEET OF
STRUCTURE.
Fire Extinguishers
FIRE EXTINGUISHERS NOT SHOWN ON
DRAWINGS.
Alarm Systems
FIRE ALARM SYSTEM REQUIRED. PROVIDE
PLANS AND SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Other Comments
LOCK BOX REQUIRED. PICK UP
AUTHORIZATION FORM PRIOR TO BUILDING
PERMIT BEING ISSUED.
Commercial Cooking
COMMERCIAL COOKING REQUIRES
HOODS AND FIRE SUPPRESSION SYSTEM.
PLEASE PROVIDE SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Automatic Fire Extinguishing Systems
OCCUPANCY REQUIRED TO BE FIRE
SPRINKLERED. PLANS AND DRAWINGS
NEED TO BE PROVIDED PRIOR TO
BUILDING PERMIT BEING ISSUED.
Water Supply
FIRE FLOWS NOT ESTABLISHED, PLEASE
PROVIDE FIRE FLOWS PRIOR TO BUILDING
PERMIT ISSUED.
Parcel#'s RP06N39E361249
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
03/22/2005
03/22/2005
t CFYOF
REXBURG
Mgr "S FAMCT CC' UNm
Review Action
July 28, 2005
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone(208) 359-3020
Fax (208) 359-3022
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
Review Item Actions Required for Approval Approved
Administrative Review
Test for Admin
Parcel #'s RPRHNRF0010070
CrrY OF
R EXBURG
AMER"$ FAMLY Cawahwn
Review Action
July 28, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Rhone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
Building Department Review
Height and Area Review
Building Type Compliance
Exiting Review
Complies with approved Site Plan Review
Energy Conservation Compliance Review
Height and area meet the requirements of the
IBC.
Building type is VB.
Occupancy load must be noted in banquet
room and in dining area. Banquet room door to
hallway must open in direction of travel as per
Section 1008.1.2. of the 2003 International
Building Code (IBC). Provide emergency exit
illumination as per IBC Section 1006. Provide
panic hardware as per IBC Section 1008.1.9.
Provide exit signs at exit doors.
The height of floor must be 12" above closest
drainage as per IBC. Please identify on plans.
Provide lighting energy review.
Interior Environment Wall and ceiling finishes must meet the
requirements of Section 803 of the 2003
International Building Code (IBC).
Mechanical Review Provide mechanical design as per ACCA
manual J and D 8th edition.
Structural Review Set up a meeting with special inspection firm
and the City for structural fill inspections, high
strength bolting and any welding prior to start of
construction. The clerestory wall connection
(Detail 5 on Sheet S4.1) to roof identifies a 2x
bottom plate being nailed close to its edge with
16p nails at 6" o.c. The framers ability to make
this connection without splitting the 2x is
questionable to the Building Official. Please
design a framing clip to transfer any loads.
Sheet S0.1 requires a geotechnical report.
Please provide a copy to the Building
Department. Also Sheet S0.1 incorrectly
specifies the building code as the 2000 IBC and
the seismic use group as I. Change these to
03/23/2005
03/23/2005
y CrYOF
REXBURG
AMFRI S FAM1Y[DMNllWIY
Review Action
July 28, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone(208) 359-3020
Fax (208) 359-3022
Review Item Actions Requ 0 red for Approval Approved
Plumbing Sewer Drain Review
Water and Sewer Service
Plumbing Potable Water Review
Miscellaneous
Building Code Fire Compliance Review
Accessibility Review
the 2003 IBC and seismic use group II. Identify
anchor bolt spacing on plans. Provide specs
for steel roof joists.
Sanitary sewer and drain lines are required to
be installed according to the Uniform Plumbing
Code.
If grease interceptor is required a minimum of a
3" vent is required to be installed on the
interceptor.
Plans do not include kitchen plumbing fixtures.
Pains are required to determine if building is
required to have a grease interceptor. Plans
must be submitted for reveiw before permit will
be issued.
All plumbing services are required to be tested
and inspected before covering.
On water lines indicated on plans. Required to
be sized and installed according to the Uniform
Plumbing Code.
Backflow devices are not shown on plans. All
devices are required to be installed and tested
before Final plumbing inspection.
Provide detail showing moisture membrane,
flashing and weepholes for masonry. The
plans do not show kitchen details and dining
area details. Do not perform any construction
activity on either of these two areas without
submitting details and receiving approval from
the Building Department.
Section 903.2.1.2 of the 2003 International
Building Code requires a maximum fire area of
5000 sq. ft. Provide details showing separation
for fire areas or provide sprinkler plans.
One of the handicapped parking spaces next to
the building must be Van Accessible. Please
identify on site plan. Dining areas were not
shown with aisles and tables. Before an
J CITY OF
REXBURG
AMFK)M FAMILY COMMUNn
Review Action
July 28, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359.3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
occupancy permit is issued, the tables and
aisles need to be configured and approved by
the City.
The ADA toilets have a dimension of 1'-9" from
the side wall to the centerline of the toilet. ANSI
117 requires this to be 16"-18" for accessibility.
Parcel #'s RPRHNRF0010070
CITY OF
R MURG
AMERCAS FAMLYc L]Nnr
Review Action
July 28, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
Fire Department Review
Fire Access Roads SEE SITE PLAN REVIEW 03/22/2005
Standpipes SEE SITE PLAN REVIEW 03/22/2005
Required Fire Flow
Other Comments
Alarm Systems
Water Supply
Fire Extinguishers
Commercial Cooking
Automatic Fire Extinguishing Systems
Parcel #'s RPRHNRF0010070
SEE SITE PLAN REVIEW.
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
a CITY OF
R.EXBURG
.I AMFAx SF"ILYCQ UNM
Afa
Review Action
March 22, 2005
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Permit Number: 05 00065
Project Name: Hard Hat Cafe
Project Type: Site Plan Review
Review Item Actions Required for Approval Approved
Fire Department Review
Fire Access Roads ESTABLISHED. 03/22/2005
Standpipes 03/22/2005
Required Fire Flow
BUILDING REQUIRES 2250 GPM/TWO
HOURS FROM A MINIMUM OF TWO FIRE
HYDRANTS LOCATED WITHIN 450 FEET OF
STRUCTURE.
Alarm Systems
FIRE ALARM SYSTEM REQUIRED. PROVIDE
PLANS AND SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Other Comments
LOCK BOX REQUIRED. PICK UP
AUTHORIZATION FORM PRIOR TO BUILDING
PERMIT BEING ISSUED.
Commercial Cooking
COMMERCIAL COOKING REQUIRES
HOODS AND FIRE SUPPRESSION SYSTEM.
PLEASE PROVIDE SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Water Supply
FIRE FLOWS NOT ESTABLISHED, PLEASE
PROVIDE FIRE FLOWS PRIOR TO BUILDING
PERMIT ISSUED.
Fire Extinguishers
FIRE EXTINGUISHERS NOT SHOWN ON
DRAWINGS.
Automatic Fire Extinguishing Systems
OCCUPANCY REQUIRED TO BE FIRE
✓SPRINKLERED. PLANS AND DRAWINGS
NEED TO BE PROVIDED PRIOR TO
BUILDING PERMIT BEING ISSUED.
Parcel#'s RP06N39E361249
da"1ep"v CITY OF
REXBURG
nn MICASFnMaYCOWUNnY
Review Action
March 22, 2005
Permit Number: 05 00065
Project Name: Hard Hat Cafe
Project Type: Site Plan Review
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item _ Actions Required for Approval Approved
Fire Department Review
Fire Access Roads
Standpipes
ESTABLISHED.
Required Fire Flow
BUILDING REQUIRES 2250 GPM/TWO
HOURS FROM A MINIMUM OF TWO FIRE
HYDRANTS LOCATED WITHIN 450 FEET OF
STRUCTURE.
Alarm Systems
FIRE ALARM SYSTEM REQUIRED. PROVIDE
PLANS AND SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Other Comments
LOCK BOX REQUIRED. PICK UP
AUTHORIZATION FORM PRIOR TO BUILDING
PERMIT BEING ISSUED.
Commercial Cooking
COMMERCIAL COOKING REQUIRES
HOODS AND FIRE SUPPRESSION SYSTEM.
PLEASE PROVIDE SUBMITTALS PRIOR TO
BUILDING PERMIT BEING ISSUED.
Water Supply
FIRE FLOWS NOT ESTABLISHED, PLEASE
PROVIDE FIRE FLOWS PRIOR TO BUILDING
PERMIT ISSUED.
Fire Extinguishers
FIRE EXTINGUISHERS NOT SHOWN ON
DRAWINGS.
Automatic Fire Extinguishing Systems
OCCUPANCY REQUIRED TO BE FIRE
SPRINKLERED. PLANS AND DRAWINGS
NEED TO BE PROVIDED PRIOR TO
BUILDING PERMIT BEING ISSUED.
Parcel#'s RP06N39E361249
03/22/2005
03/22/2005
*7q
CITY OF
RExBURcAMCKI $ rAMILY COWUNRY
Review Action
March 22, 2005
P.O Box 280
19 E Main St,
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
Review Item Actions Required for Approval _Approved
Fire Department Review
Fire Access Roads SEE SITE PLAN REVIEW 03/22/2009,
Standpipes
Required Fire Flow
Other Comments
Alarm Systems
Water Supply
Fire Extinguishers
Commercial Cooking
Automatic Fire Extinguishing Systems
Parcel#'s RP06N39E361249
SEE SITE PLAN REVIEW 03/22/2005
SEE SITE PLAN REVIEW.
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
aPAR' . CITY Or
s R.EXBURG
AMEftIUSUMILYCJ%IUL1JIY
Review Action
March 22, 2005
Permit Number: 05 00063
Project Name: Hard Hat Cafe
Project Type: Commercial Tenant Finish
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
Fire Department Review
Fire Access Roads SEE SITE PLAN REVIEW 03/22/2005
Standpipes SEE SITE PLAN REVIEW 03/22/2005
Required Fire Flow
Other Comments
Alarm Systems
Water Supply
Fire Extinguishers
Commercial Cooking
Automatic Fire Extinguishing Systems
Parcel Vs RP06N39E361249
SEE SITE PLAN REVIEW.
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW
SEE SITE PLAN REVIEW