I have reviewed the Webb Apartment drawings that you have provided me and
have identified the following discrepancies:
1. Add fire hydrant as per request by Fire Department. They have also requested
that fire lanes be identified on plans, fire extinguishers be installed and alarm
plans submitted. Type A unit should be equipped with horn strobes. I have
attached a copy of the Fire Department review to the back of this document.
2. Move Dumpster so it can be accessed by our side loading garbage trucks.
3. A suitable fence or buffer must be provided between parking areas and other
residential property. Please identify on plans.
4. The handicap parking spaces do not have the minimum 60" wide access aisles
required by ICC/ANSI Al 17.1 —1998. Also, show detail of handicap apron at
curb.
5. Compact stalls must be identified. Show signs at parking lot to identify
compact spaces.
6. Elevations at parking and drives are incomplete.
7. Call out balcony rail height at 42". Stair handrail height called out at 36" but
incorrectly drawn at 42".
8. Dwelling separation is required, not area separation. Change note identifying
area separation on page C-1.
9. As per the 1997 Uniform Building Code (UBC) Section 3.10.3, the minimum
width for a habitable space is 7'. Change the bedroom widths in the smaller
bedrooms. The 7' dimension is a finished requirement. Make sure to take
into account the thickness of the drywall.
10. Locating plumbing so that it will be inside dwelling separation walls requires
additional details to identify fire protection. Plastic pipe may not penetrate the
1 -hr. wall without proper fire -restive application.
11. Provide joist details from manufacturer.
12. Provide truss manufacturer specifications and detail sheets prior to frame
inspection.
Clearance: OK Turn Arounds: YES
Complete Road Acceptable: SEE COMMENTS BELOW
Comments: FIRE APPARATUS ACCESS ON SOUTH SIDE OF BUILDING SHALL BE
SIGNED, HAVE THE CURBS PAINTED RED, AND MAINTAINED. INDICATED IN
RED ON SITE PLAN.
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: MINIMUM OF ONE 2A10BC EXTINGUISHER PER
UNIT
Comments: NONE
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: YES Type Of System Being Installed: FIRE SPRINKLERS
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: YES
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: Both: YES
Type Of System Being Provided: Manual: Automatic: UNKNOWN
Components Of System Shown: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
10) Other Corrections That Are Required By Special Occupancy Or
n
Conditions: PLANS DO NOT SHOW FIRE ALARM SYSTEM. PLEASE SUBMIT
SUBMITTALS OF ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT,
ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS, CONDUCTOR
TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS MODEL
NUMBERS, AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND
MATERIALS AND INTERFACE CONNECTIONS. ADA UNITS HAVE SPECIFIC
REQUIREMENTS, PLEASE ADDRESS.
Plans As Submitted Are Acceptable: NO
Plans Checked By: CHRIS HUSRINSON Date: 6-8-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES