Loading...
HomeMy WebLinkAboutFS APPROVAL - 19-00740 - Thomson Farm Apartments - 2 Story Thomson Farm Apartments – 2 Story – Rexburg 1 of 1 STATE FIRE MARSHAL IDAHO DEPARTMENT OF INSURANCE 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: March 2, 2020 APPROVED: March 4, 2020 REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer PROJECT: Thomson Farm Apartments – 2 Story STREET ADDRESS: 635 Thomson Farm Road CITY: Rexburg AHJ: Madison Fire Department SPRINKLER CONTRACTOR: Automatic Fire Sprinkler Service, Inc. 300 S. Catlin Street, Ste 2 Missoula, MT 59801 IDAHO LICENSE: FPSC-136 CONTACT NAME: John Venche john@afssmt.com PHONE NO: (208) 695-6553 SYSTEM DESIGNED BY: John Venche john@afssmt.com PHONE NO: (208) 695-6553 TYPE OF SYSTEM: NFPA 13R/Wet HEAD COUNT: 188 TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Residential CONSTRUCTION TYPE: VB AREA SQUARE FOOTAGE: 21,249 SCOPE OF WORK: New apartments PLAN REVIEW COMMENTS: Approved with the following comments 1. Fire service mains shall be restrained against movement at changes of direction. (NFPA 13, 10.6) 2. Working Plans per NFPA 13R, 8.1.7(20) 3. Sprinkler protection shall be provided in open–ended corridors and associated exterior stairways and ramps. (2015 IFC 903.3.1.2.2) Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.