I have reviewed the plans for the BYU Student Family Housing and have
identified the following discrepancies or questions:
1. The plans show sidewalk located at back of curb. Please include a 7' wide
landscape strip (minimum) between the curb and the sidewalk as per City of
Rexburg Ordinance.
2. Driveway approaches must be constructed to City of Rexburg standards.
Please identify all driveway approaches onto city streets as being constructed
of 6" thick concrete with "4 rebar spaced a minimum of 18" on center in both
directions. The curb at the approach must be constructed with 2 # 4 rebar.
Please make the necessary additions to the plans.
3. Identify a handicapped ramp as per City of Rexburg standard details at the
corner of 7a' South and 2°d West.
4. Please provide us with stone drainage calculations.
5. Section 1 t07.6.2.1 of the 2002 Supplement of the 2000 International Building
Code (IBC) states that "at least 2%" of the dwelling units shall be Type A
units. The plans are for 156 units. Therefore, at least 4 units must be Type A
units. The plans call out only 3 Type A units.
6. The plans make note that in some cases the foundation may be anchored to
bedrock. If this takes place above the frost line, all dirt must be cleaned from
the bedrock prior to the placement of concrete. Please make not of this on the
plans.
7. Identify location of hold-downs, straps, collectorhie and shear walls as per the
tables on page A3.3.
8. Please identify entrance doors to the dwelling units as being 20 -minute rated
assemblies.
9. The bathroom doors on some of the units open into the 30" x 48" minimum
clear space required at the bathtubs. I have attached a copy of bathroom
details from the Fair Housing Act Design Manual. Please make the necessary
changes to the plans.
10. Please provide truss details as soon as you can but prior to frame inspection.
11. I have attached a copy of the Fire Department review to the back of this
document.
Please provide me with 2 new stamped copies of the corrected plans. If you have
any questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
additional inaccessible
receptacle permitted
receptacle required in
an accessible location
lever handles—
not required, but
recommended
0 -
fixed base cabinet
acceptable since parallel
approach centered on
basin is possible
30" X 48" clear floor
space for parallel
approach
7.36
PART TWO: CHAPTER 7
FAIR HOUSING ACT DESIGN MANUAL
reinforced wall areas for
future installation of grab bars
around toilet and bathtub
c.�
O
Example "A" Bathroom
9'- 4" X SF -21'
(See plan page 7.66)
clear floor
space at each
fixture required
30" X 48" min. clear floor
space outside swing of door
required; in this plan the
clear floor space doubles as
the space for access to
bathtub.Toilet beside and
close to bathtub allowed in
"A" bathroom only. Provides
less access to bathtub and
controls.
Notes in italic type are
recommendations only
and are not required by
the Guidelines.
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
2000 INTERNATIONAL FIRE CODE Plan Date: 11-15-02
Plan Review Review Date: 12-17-02
Building Name: BYU-I MARRIED STUDENT HOUSING
Building Address: SECOND WEST AND SEVENTH SOUTH
Stories: 2/3 STORY Type of Construction: VB
Occupancy Classification: R-2 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 9684 SQUARE
FEET/BUILDING
1).Required Fire Flow (Table B105.1): 2750 GPM/TWO HOURS
Comments: REQUIRED FIRE FLOW WILL BE REDUCED TO 1500 GPM/TWO HOURS
WITH THE INSTALLATION OF AN AUTOMATIC FIRE SPRINKLER SYSTEM
INSTALLED.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: EXISTING C-63 9 NEW HYDRANTS PROPOSED
Fire Hydrant Flows: EXISTING OKAY, PROPOSED UNKNOWN
Fire Flow Test Location: C-63
Fire Flow Supplied By: FD
Other Approved Water Source: NONE
Water Supply Acceptable: SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: FLOWS FROM PROPOSED HYDRANTS UNKNOWN. FD
REQUIRES AN ESTIMATED HYDRANT FLOW (FROM AN ENGINEER) OF EACH
HYDRANT TO BE SUBMITTED PRIOR TO CONSTRUCTION.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: X
Length: X
Surface:
X
Turning Radius: X
Grade: X
Vehicle
Vertical: UNKNOWN
Clearance: X
Turn Arounds: X
Complete Road Acceptable: YES, SEE COMMENTS
Comments: DEPENDING UPON FINAL CONFIGURATION, FIRE LANE SIGNAGE AND
PAINTING AND MAINTAINING THE CURBS MAY BE REQUIRED.
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF ACCESS ROADS AND OPERATIONAL FIRE HYDRANTS ARE NOT
INSTALLED PRIOR TO CONSTRUCTION A STOP -WORK WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: MINIMUM SIZE SHALL BE 2A10BC
Comments: PROVIDE AT LEAST ONE FIRE EXTINGUISHER PER UNIT OF THE
REQUIRED SIZE OR LARGER MOUNTED IN A CENTRAL LOCATION.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003)
Required: YES Type Of System Being Installed: WET
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: YES
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required: Comments:
8) Ventilating Hood And Duct. Fire Extinguishing System (Article 10
Section 1006.2) Required: NO Type Being Provided:
Comments: NONE
9) Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: Both: X
Type Of System Being Provided: Manual: Automatic: Both: X
Components Of System Shown: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: .X Visual Devices: X
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO, SEE
COMMENTS
Comments: SMOKE DETECTORS SHALL ALL BE HARDWIRED WITH BATTERY
BACKUP. HANDICAP UNITS REQUIRE SMOKE DETECTORS TO BE HARDWIRED INTO
THE FACP. WITHIN TYPE 3B AND 3C UNITS SMOKE DETECTOR IS MISSING
FROM THE THIRD BEDROOM.
PLANS INDICATE ONLY HORNS IN THE UNITS, PLEASE REPLACE WITH
COMBINATION HORN/STROBE UNITS AS REQUIRED BY ADA. WITHIN TYPE 2T
UNITS PLANS INDICATE ONE HORN IN DOWNSTAIRS PORTION OF UNIT. NFPA
72 REQUIRES HORN/STROBE UNIT TO BE WITHIN 16 FEET OF PILLOWS IN
EACH BEDROOM. PLANS SHOW NO PULL STATIONS, PLEASE EXPLAIN.
FIRE ALARM PLANS NOT COMPLETE. IFC REQUIRES CONSTRUCITON
DOCUMENTS THAT INCLUDE ALARM CONTROL AND TROUBLE SIGNALING
EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS,
CONDUCTOR TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS,
MODELS NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND
MATERIALS, AND THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS.
Plans As Submitted Are Acceptable: NO
Plans Checked By: CHRIS HUSKINSON Date: 12-17-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: X New Plans: X