HomeMy WebLinkAboutCOMCHECKS - 06-00455 - First American Title Insurance Co0600455
First American Title Insurance CO
Envelope Compliance Certificate Checked By/Date
Standard 90.1-1999
COMcheck-EZ So$ware Version 3.0 Release 2a
Data filename: C:\Progmm Files\Check\COMcheck-EZ\americattitl.cck
Section 1: Project Information
Project Name:
Designer/Contractor:
Document Author:
A New Office Building For:
First American Title Insurance Co.
JRW & Associates
1152 Bond Ave.
Rexburg, Id 83440
Gary Richardson
1152 Bond Ave.
Rexburg, Id. 83440
Section 2: General Information
Building Location (for weather data):
Rexburg, Idaho
Heating Degree Days (base 65 degrees F):
8693
Cooling Degree Days (base 50 degrees F):
1446
Building type for envelope requirements:
Non -Residential
Project Type:
New Construction
Window/ Wall Ratio:
0.17
Office 6800 p C� o
Section 3: Requirements Checklist
SEP 1 4 2006 J
Bldg.
Dept. I REM
�jf
Use I City OF RrE_"f1��.'Pr'7
Insulation
[ ] 1. Open -blown or poured loose -fill insulation has not been used in attic roof spaces with
ceiling slope greater than 3 in 12.
[ ] I 2. Wherever vents occur, they are baffled to deflect incoming air above the insulation.
[ ] I 3. Recessed lights, equipment and ducts are not affecting insulation thickness.
[ ] 4. No roof insulation is installed on a suspended ceiling with removable ceiling panels.
[ ] 5. All exterior insulation is covered with protective material.
[ ] 6. Cargo and loading dock doors are equipped with weather seals.
Fenestration and Doors
[ l I 7. Windows and skylights are labeled and certified by the manufacturer br U-factor and SHGC.
[ l I 8. Fixed windows and skylights unlabeled by the manufacturer have been site labeled using the
default U-factor and SHGC.
.,r *4/
[ ] 9. Other unlabeled vertical fenestration, operable and fixed, that are unlabeled by the
manufacturer have been site labeled using the default U-factor and SHGC.
No credit has been given Ior metal frames with thermal breaks,
low -emissivity coatings, gas fillings, or insulating spacers.
Air Leakage and Component Certification
[ ] I 10. All joints and penetrations are caulked, gasketed, weather-stripped, or otherwise sealed.
[ ] 11. Windows, doors, and skylights certified as meeting leakage requirements.
[ ] 12. Component R-values & U-factors labeled as certified.
[ ] 13. Building entrance doors have a vestibule and equipped with closing devices.
Exceptions:
Buildings less than bur stories above grade, building entrances with revolving doors.
Doors that open directly from a space less than 3000 sq. ft. in area
Climate -Specific Requirements
Gross
Area or Cavity Cont. Proposed Budget
Comoonent Name/Description Perimeter R Value R-ValueU FactorU Factor
Roof 1: Attic Roofwith Wood Joists
6800
38.0 0.0 0.027
0.034
Exterior Wall 1: Wood -Framed, 16" o.c.
6300
19.0 0.0 0.067
0.089
Window 1:
Metal Frame with Thermal Break:Double Pane with Low-E
Tinted, Fixed, SHGC 0.58
899
— — 0.540
0.570
Door I: Glass, Tinted, SHGC 0.49
247
— — 0.920
0.570
Basement Wall 1: Solid Concrete:8" Thickness
Normal Density, Furring: Wood,
Wall Ht 4.0, Depth B.G. 3.5
2148
11.0 0.0 0.098
0.579
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements
Envelope PASSES: Design 18%better than code
Section 4: Compliance Statement
The proposed envelope design represented in this document is consistent with the building plans, specifications and other
calculations submitted with this permit application. The proposed envelope system has been designed to meet the
Standard 90.1-1999 requirements in COMcheck-EZ Version 3.0 Release 2a and to comply with the mandatory
requirements in the Requirements Checklist.
Principal Envelope Designer -Name S' Date
0600455
First American Title Insurance CO
COM check Software Version 3.2.1
Isll( In
Mechanical Compliance Certificate
2003 IECC
Report Date: 08/28/06
Data filename: C:\Program Files\Check\COMcheck\Projects\firstamtitle.cck
Section 1: Project Information
Project Title: First American Title
Construction Site: Owner/Agent: Designer/Contractor:
Rexburg, ID 83440 Dwayne Sudweeks
Engineered Systems Assoc., Inc
315 W. Center
Pocatello, ID 83204
208-233-0501
dcs@engsystems.com
Section 2: General Information
Building Location (for weather data): Rexburg, Idaho
Climate Zone: 16
Heating Degree Days (base 65 degrees F): 8693
Cooling Degree Days (base 65 degrees F): 143
Project Type: New Construction
Section 3: Mechanical Systems List
Quantity System Type & Description
3 HVAC System 1: Heating: Central Furnace, Gas / Cooling: Split System, Capacity <65 kBtu/h, Air -Cooled
Condenser / Single Zone
1 Instantaneous Water Heater 1: Service Water Healer
Section 4: Requirements Checklist D 7RE-XB1-JRG
Requirements Specific To: HVAC System 1❑ 1. Newly purchased heating equipment meets the heating efficiency requirements ❑ 2. Equipment minimum efficiency: Split System: 10.0 SEER
Requirements Specific To: Instantaneous Water Heater 1C'I�❑ 1. Heat traps in inleVoutlet fittings
❑ 2. 1/2-in. insulation on 8It of inlet/outlet piping if no integral heat traps
❑ 3. Electric Water Heater efficiency>= 0.92 EF, 130 SL, Btu/h (if > 12 kW)
Generic Requirements: Must be met by all systems to which the requirement is applicable:
❑ 1. Load calculations per 2001 ASHRAE Fundamentals
❑ 2. Plant equipment and system capacity no greater than needed to meet loads
- Exception: Standby equipment automatically off when primary system is operating
- Exception: Multiple units controlled to sequence operation as a function of load
El3. Minimum one temperature control device per system
Page 1 of 4
❑ 4. Minimum one humidity cont- evice per installed humidification/dehumidification syJ,,,.,
❑ 5. Thermostatic controls has 5 degrees F deadband
Exception: Thermostats requiring manual changeover between heating and cooling
❑ 6. Automatic Controls: Setback to 55 degrees F (heat) and 85 degrees F (cool); 7-day clock, 2-hour occupant override, 10-hour
backup
Exception: Continuously operating zones
Exception: 2 kW demand or less, submit calculations
❑ 7. Automatic shut-off dampers on exhaust systems and supply systems with airflow >3,000 cfm
❑ 8. Outside -air source for ventilation; system capable of reducing OSA to required minimum
❑ 9. R-5 supply and return air duct insulation in unconditioned spaces R-8 supply and return air duct insulation outside the
building R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
Exception: Ducts located within equipment
Exception: Ducts with interior and exterior temperature difference not exceeding 15 degrees F.
❑ 10. Ducts sealed - longitudinal seams on rigid ducts; transverse seams on all ducts; UL 181A or 181B tapes and mastics
Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at static
pressures less than 2 inches w.g. pressure classification
❑ 11. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
❑ 12. Hot water pipe insulation: 1 in. for pipes <=1.5 in. and 2 in. for pipes >1.5 in. Chilled water/refrigerant/brine pipe insulation: 1
in. for pipes <=1.5 in. and 1.5 in. for pipes >1.5 in. Steam pipe insulation: 1.5 in. for pipes <=1.5 in. and 3 in. for pipes >1.5
in.
- Exception: Piping within HVAC equipment
- Exception: Fluid temperatures between 55 and 105 degrees F
- Exception: Fluid not heated or cooled
- Exception: Runouts <4 ft in length
❑ 13. Operation and maintenance manual provided to building owner
❑ 14. Balancing devices provided in accordance with IMC 603.15
❑ 15. Newly purchased service water heating equipment meets the efficiency requirements
❑ 16. Water heater temperature controls: 110 degrees F for dwelling units or 90 degrees F for other occupancies
(317. Stair and elevator shaft vents are equipped with motorized dampers
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications and other calculations submitted with this permit application. The proposed mechanical systems have been designed
to meet the 2003 IECC requirements in COMcheckVersion 3.2.1 and to comply with the mandatory requirements in the
Requirements Checklist.
L W. A&A [qg to
Principal Me hanical Designer -Name Signature Date
Page 2 of 4
COMcheck Software Version 3.2.1
Mechanical Requirements
Description
2003 IECC
Report Date:
Data filename: C:\Program Files\Check\COMcheck\Projects\firstamtitle.cck
The following list provides more detailed descriptions of the requirements in Section 4 of the Mechanical Compliance Certificate.
Requirements Specific To: HVAC System 1 :
1. The specified heating equipment is covered by Federal minimum efficiency requirements. New equipment of this type can be
assumed to meet or exceed ASHRAE 90.1 Code requirements for equipment efficiency.
2. The specified heating and/or cooling equipment is covered by ASHRAE 90.1 Code and must meet the following minimum
efficiency: Split System: 10.0 SEER
Requirements Specific To: Instantaneous Water Heater 1 :
Heat traps are required on noncirculating water heating systems on both inlet and outlet connections. Heat traps may be
purchased or field -fabricated by creating a loop or inverted U-shaped arrangement on the inlet and outlet pipes.
Pipe insulation for the specified noncirculating service hot water system is required for all piping in the following calegories:a)
the first 8 tt of outlet piping from any constant -temperature, noncirculating storage systemb) the inlet piping between the
storage tank and a heat trap in a noncirculating storage systemPipe insulation must be at least 1/2 in. and have a conductivity
no >0.28 Btu-in/(h-ft2-degrees F).
Service water healing equipment used solely for heating potable water, pool heaters, and hot water storage tanks must meet
the following miniumum efficiency: Electric Water Heater efficiency >= 0.92 EF, 130 SL, Btu/h (if > 12 kW)
Generic Requirements: Must be met by all systems to which the requirement is applicable:
1. Design heating and cooling loads for the building must be determined using procedures in the ASHRAE Handbook of
Fundamentals or an approved equivalent calculation procedure.
2. All equipment and systems must be sized to be no greater than needed to meet calculated loads. A single piece of equipment
providing both heating and cooling must satisfy this provision for one function with the capacity for the other function as small
as possible, within available equipment options.
- Exception: The equipment and/or system capacity may be greater than calculated loads for standby purposes. Standby
equipment must be automatically controlled to be off when the primary equipment and/or system is operating.
- Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are allowed
if they are provided with controls to sequence operation of the units as the load increases or decreases.
3. Each heating or cooling system serving a single zone must have its own temperature control device.
4. Each humidification system must have its own humidity control device.
5. Thermostats controlling both heating and cooling must be capable of maintaining a 5 degrees F deadband (a range of
temperature where no heating or cooling is provided).
- Exception: Deadband capability is not required if the thermostat does not have automatic changeover capability between
heating and cooling.
6. The system or zone control must be a programmable thermostat or other automatic control meeting the following criteria:a)
capable of setting back temperature to 55 degrees F during heating and setting up to 85 degrees F during coolingb) capable of
automatically setting back or shutting down systems during unoccupied hours using 7 different day schedulesc) have an
accessible 2-hour occupant overrided) have a battery back-up capable of maintaining programmed settings for at least 10
hours without power.
- Exception: A setback or shutoff control is not required on thermostats that control systems serving areas that operate
continuously.
- Exception: A setback or shutoff control is not required on systems with total energy demand of 2 kW (6,826 Btulh) or
less.
7. Outdoor -air supply systems with design airflow rates >3,000 cm of outdoor air and all exhaust systems must have dampers
that are automatically closed while the equipment is not operating.
8. The system must supply outside ventilation air as required by Chapter 4 of the International Mechanical Code. If the ventilation
system is designed to supply outdoor -air quantities exceeding minimum required levels, the system must be capable of
Page 3 of 4
reducing outdoor -air flow to tl�nimum required levels.
9. Air ducts must be insulated to the following levels:a) Supply and return air ducts for condi coned air located in unconditioned
spaces (spaces neither heated nor cooled) must be insulated with a minimum of R-5. Unconditioned spaces include attics,
crawl spaces, unheated basements, and unheated garages.b) Supply and return air ducts and plenums must be insulated to a
minimum of R-8 when located outside the building.c) When ducts are located within exterior components (e.g., floors or roofs),
minimum R-8 insulation is required only between the duct and the building exterior.
Exception: Duct insulation is not required on ducts located within equipment.
Exception: Duct insulation is not required when the design temperature difference between the interior and exterior of the
duct or plenum does not exceed 15 degrees F.
10. All joints, longitudinal and transverse seams, and connections in ductwork must be securely sealed using weldments;
mechanical fasteners with seals, gaskets, or mastics; mesh and mastic sealing systems; or tapes. Tapes and mastics must be
listed and labeled in accordance with UL 181A or UL 181B.
- Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at static pressures
less than 2 inches w.g. pressure classification.
11. Mechanical fasteners and seals, mastics, or gaskets must be used when connecting ducts to fans and other air distribution
equipment, including multiple -zone terminal units.
12. All pipes serving space -conditioning systems must be insulated as follows: Hot water piping for heating systems: 1 in. for pipes
<=1 1/2-in. nominal diameter 2 in. for pipes >1 1/2-in. nominal diameter. Chilled water, refrigerant, and brine piping systems: 1
in. insulation for pipes <=1 1/2-in. nominal diameter 1 1/2 in. insulation for pipes >1 1/2-in. nominal diameter. Steam piping: 1
1/2 in. insulation for pipes <=1 1/2-in. nominal diameter 3 in. insulation for pipes >1 1/2-in. nominal diameter.
- Exception: Pipe insulation is not required for factory -installed piping within HVAC equipment.
- Exception: Pipe insulation is not required for piping that conveys fluids having a design operating temperature range
between 55 degrees F and 105 degrees F.
Exception: Pipe insulation is not required for piping that conveys fluids that have not been heated or cooled through the
use of fossil fuels or electric power.
Exception: Pipe insulation is not required for runout piping not exceeding 4 ft in length and 1 in. in diameter between the
control valve and HVAC coil.
13. Operation and maintenance documentation must be provided to the owner that includes at least the following information:a)
equipment capacity (input and output) and required maintenance actionsb) equipment operation and maintenance manualsc)
HVAC system control maintenance and calibration information, including wiring diagrams, schematics, and control sequence
descriptions; desired or field -determined set points must be permanently recorded on control drawings, at control devices, or,
for digital control systems, in programming commentsd) complete narrative of how each system is intended to operate.
14. Each supply air outlet or diffuser and each zone terminal device (such as VAV or mixing box) must have its own balancing
device. Acceptable balancing devices include adjustable dampers located within the ductwork, terminal devices, and supply air
diffusers.
15. Service water heating equipment must meet minimum Federal efficiency requirements included in the National Appliance
Energy Conservation Act and the Energy Policy Act of 1992, which meet or exceed ASHRAE 90.1 Code. New service water
heating equipment can be assumed to meet these requirements.
16. Water -heating equipment must be provided with controls that allow the user to set the water temperature to 110 degrees F for
dwelling units and 90 degrees F for other occupancies. Controls must limit output temperatures of lavatories in public facility
restrooms to 110 degrees F.
17. Stair and elevator shaft vents must be equipped with motorized dampers capable of being automatically closed during normal
building operation and interlocked to open as required by fire and smoke detection systems. All gravity outdoor air supply and
exhaust hoods, vents, and ventilators must be equipped with motorized dampers that will automatically shut when the spaces
served are not in use. Exceptions: - Gravity (non -motorized) dampers are acceptable in buildings less than three stories in
height above grade. - Ventilation systems serving unconditioned spaces.
Page 4 of 4
A""
2003 IECC
0600455
First American Title Insurance CO
COMcheck Software Version 3.1 Release 1
Lighting Compliance Certificate
Report Date: 08/29/06
Data filename: C:\Program Files\Check\COMcheck\First amedcan.cck
Section 1: Project Information
Project Title: First American Title Insurance Co.
Construction Site:
Rexburg, ID
Owner/Agent:
Section 2: General Information
Building Use Description by: Activity Type
Project Type: New Construction
Activity Type(s)
Floor Area
Other
459
Office
3498
Corridor, Restroom, Support Area
1087
Storage, Industrial and Commercial
136
Lobby- Other
821
Convention, Conference or Meeting Center
419
Kitchen
280
Section 3: Requirements Checklist
Designer/Contractor:
v u u v Lg
Interior Lighting:
❑ 1. Total actual watts must be less than or equal to total allowed watts. SEP 1 4 j2006
Allowed Watts Actual Watts Complies
7342 6845 YES
rn
El 2. Exit signs 5 Watts or less per side. (h + 9
YOF
Exterior Lighting:
❑ 3. Efficacy greater than 45 lumens/W.
Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or security lighting; low -voltage landscape
lighting.
Controls, Switching, and Wiring:
❑ 4. Independent controls for each space (switch/occupancy sensor).
Exceptions:
Areas that must be continuously illuminated.
❑ 5. Master switch at entry to hotel/motel guest room.
❑ 6. Individual dwelling units separately metered.
❑ 7. Each space provided with a manual control to provide uniform light reduction by at least 50 % .
Exceptions:
Only one luminaire in space;
Page 1 of 3
An occupant -sensing de* -.ontrols the area;
The area is a corridor, st'60q4om, restroom, public lobby or guest room;
Areas that must be continuously illuminated;
Areas that use less than 0.6 Wafts/sq.ft.
❑ 8. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
❑ 9. Photocell/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
❑ 10. Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts).
Exceptions.
Electronic high -frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans,
specifications and other calculations submitted with this permit application. The proposed lighting system has been designed to
meet the 2003 IECC, Chapter 8, requirements in COM check Version 3.1 Release 1 and to comply with the mandatory requirements
in the Requirements Checklist.
Principal Lighting Designer -Name Signature Date
Page 2 of 3
.w
..
Permit #
Permit Date
K I
COMcheck Software Version 3.1 Release 1
Lighting Application Worksheet
2003 IECC
Report Date:
Data filename: C:\Program Files\Check\COMcheck\First american.ock
Section 1: Allowed Lighting Power Calculation
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / 112
D
Allowed Watts
(B x C)
Other
459
1
459
Office
3498
1.1
3848
Corridor, Restroom, Support Area
1087
0.9
978
Storage, Industrial and Commercial
136
0.8
109
Lobby - Other
821
1.3
1067
Convention, Conference or Meeting Center
419
1.3
545
Kitchen
280
1.2
336
Total Allowed Watts =
7342
Section 2: Actual Lighting Power Calculation
A
B
c
D
E
Fixture ID: Description / Lamp / Wattage Per Lamp / Ballast
Lamps/
# of
Fixture
(C X D)
Fixture
Fixtures
Watt.
Compact Fluorescent 1: Triple 4-pin 18W / Electronic
3
4
60
240
Compact Fluorescent 2: Triple 4-pin 18W / Electronic
4
2
80
160
Linear Fluorescent 1: 48' T8 32W / Electronic
2
20
59
1180
Linear Fluorescent 2: 48" T8 32W / Electronic
1
2
32
64
Linear Fluorescent 3: 48" T8 32W ! Electronic
2
4
62
248
Linear Fluorescent 4: 48' T8 32W / Electronic
1
2
32
64
Linear Fluorescent 5: 48" T8 32W / Electronic
2
4
59
236
Linear Fluorescent 6: 48" T8 32W / Electronic
1
1
32
32
Linear Fluorescent 7: 24" T8 17W ! Electronic
1
2
18
36
Linear Fluorescent 8: 24" T8 17W / Electronic
2
9
32
288
Linear Fluorescent 9: 24' T8 17W / Electronic
2
6
32
192
Linear Fluorescent 10: 48" T8 32W / Electronic
4
19
118
2242
Linear Fluorescent 11: 48" T8 32W / Electronic
2
1
64
64
Linear Fluorescent 12: 48' T8 32W / Electronic
2
4
59
236
Linear Fluorescent 13: 48" T8 32W / Electronic
2
3
59
177
Compact Fluorescent 3: Triple 4-pin 32W / Electronic
1
33
36
1188
Incandescent 1: Incandescent 50W
1
2
51
102
Linear Fluorescent 14: 48" T8 32W / Electronic
1
3
32
96
Total Actual Watts = 6845
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 7342
Total Actual Watts = 6845
Project Compliance = 497
DesignUghting PASSES:
Page 3 of 3