March 5, 2007
Permit Number: 06 00372
Project Name:
Project Type:
Rock Creek Hallow - Prelim. Plat
Preliminary Subdivision Pkat
Review Item
Public, Works Review
Public Works Review
Parcel #'s
RPRWSTAT04003A
RPRWSTAT040070
RPRWSTAT040060
A -c -tions Required for A oval
1. The north access road into the S1 is shown
as 24 feet wide. This is too narrow. For the
major access the road needs to be of least 30
feet wide.
2. The front and rear yard setbacks for this
zone have not been met.
3. Where the buildings are set fight an the
corners it will be difficult for fire engines and
moving trucks to make the corners. This needs
to be reviewed closer.
4. The setbacks shown an the buildings needs
to be to the drip line of the roof. It appears that
the measurements are to the foundations.
RO Box 280
1 E Pain St,
Rexburg, Idaho 8340
Phone (20$) 359-3020
fax (208) 359-3022
A mirove d
Y �
I; t
i' Y 0 V
Cleo, ,-------- _--
Aof � Family Community
March 5, 2007
sio
Permit Number: 06 00372
Project game:
Project Type:
Review Item
Review Action
Rack Creek Hollow - Prelim, Pkat
Preliminary Subdivision Plat
Building Department Review
Miscellaneous
Fire Separation
Parcel #'s
RPRWSTAT04003A
RPRWSTAT040070
RPRWSTAT040060
P.0 Box 280
Lint.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Actions Reauired fior-ApproVal _ _ —Approved
The drawing is very small and I can't find a 09/12/2006
scale that works.
Building end'walls that are adjacent to other 09/12/2006
builidings must be one hour rated where they
are closer than 2Q'.
T
CITY OF
--T�—EDWURG
w —
March 5,2007
D
Permit Number: 06 00372
Project Name:
Project Type:
Review Action
Rock Creek Hollow WW Prelim. Play
Preliminary Subdivision Plat
Review1tem
Fire Department Review
Additional Comments
Water Supply
Fire Access Roads
Fire Lane Signage
Parcel #'s
RPRWSTAT04003A
RPRWSTAT040070
RPRWSTAT040060
Actions ReLaed dor Approval
Please provide additional information as noted.
If their are questions please contact Chris at
705-1312.
Plat plan shows one existing fire hydrant.
Depending upon final configuration, occupancy,
building type, etc. additional fire hydrants will be
required. Firs suppression systems may also
be rewired. Please provide more details..
New site plan shows new fire hydrants. If Group
Roccupancy a fire suppression will be required
per Rexburg City Ordinance 933, Section AA,
regarding Section 903.2.7.
Please provide more information on fire access
roads including; width, clear access height, etc.
Fire lane signage will be required. Please
provide additional information.
19 E Main St.
Rexburg, klaho $3440
Phone (208) 359-3020
Fax (208) 359-3022
proved_
08/02/2006
09/13/2006
})
ed,
4F1Ia Y
$V
CITY 0 F
XBURG
Americas Family Community
March 5, 2007
Permit Number: 06 00372
Project Name:
Project Type:
Review item
GAS Review
Review Action
Rock Creek Hollow - Prelim. Plat
Preliminary Subdivision Plat
[description Closes and described the desired
Subdivision is Addressable
Subdivision and Street name are not in
conflict with existing names
Parcel #`s
RPRWSTAT04003A
RPRWSTAT040070
R-PRWSTAT040060
Actions Required for Approval
Without lobated street names it is difficult to
determined how the addressing will be
assigned on this plat. We have the same
potential problems as Parkside here with units
facing a green space rather than a road. The
developer has agreed to Apartment style
addressing. This will require an address index
map displayed at each at the entrances.
The Mame "Pioneer Village' is being used just
across Mariah Ave.
19 E. Main St.
Rexburg, Idaho 83440
Pone (208) 359-3020
Fax (2a8) 359-3022
07/26/2006
CITY F
REX.BLTRG
America' Familyomm unjjj V
March 5, 2007
Review Action
Permit Number: 06 00372
Project Name: Rock Creek Hollow, Prelim. Plat
Project Type: Preliminary Subdivision Plat
Review Item
Planning Staff Review
Development Standards Review
Development Standards Review
Development Standards Review
Parcel #'s
"RWSTAT04003A
R-PRWSTAT040070
RPRWSTAT040060
_ Actions Required for—Ap,proval
Front yard setbacks are requireo be 25 feet.
Parallel parking stalls must be at least 22 feet
long.
Bach yard setbacks are required to be 20 feet.
RO Box 280
19 E. Wn St.
Rexburg, Idaho 83444
Phony {2a8} 359-3020
Fax (20$) 359-3022
Aijp-r—oved
6
09/15/2006
09/15/2006